Fresh-Aire MINI UV Installation Instructions Manual

Direct exposure t o UV light is harmf ul to bare skin
and eyes
This unit is equipped with a U V light disinfect ion system
To prevent exposure to UV light, dis connect power befo re servicing
Indirect exposure (blue g low) is not harmful
Caution
UV Light
Germicidal UV Light Installation Instructions
Fresh-Aire Mini UV improves indoor air quality and ghts biological contamination inside the air handling system. It extends the life of the air system and reduces maintenance costs.
Installation Notes
Mini UV is typically used for mini split systems and other limited space applications. Because space is tight the best place for mounting the UV lights is usually inside the supply vent with the light shining onto the blower wheel (which is prone to the worst mold growth).
3. Drill holes to pass lamp
cables through to back of unit as needed.
1. Determine the best location for the UV lamp clips
and clean that area with the alcohol wipe. Slide the mounting brackets onto the ends of the UV lamps.
1. Remove cover.
2. Detach drain pan to
access the area behind it.
Parts Included
A
UV Lamps
B
Lamp Clips
C
Power Supply
C
Self-tapping Screws
D
Power Harness
E
Zip Ties
F
Zip Tie Base
G
Ring Connectors
H
Alcohol Wipe
I
Adhesive Tape
J
UV Warning Sticker
IMPORTANT!
• Only qualified technicians should install this product
• Install in accordance with relevant building codes
• Read instructions carefully including safety warnings
IMPORTANT!
Rotate the lamp so the warning sticker is visible and the UV light shines on blower wheel and mold prone areas, NOT INTO THE ROOM.
IMPORTANT!
Orient the UV lamps so that the light shines into the air system, not into the room
A
B
C
C
D
E
G
H
F
I
J
WARNING
PROTECT EYES FROM UV LIGHT
TURN OFF UNIT OR DISCONNECT
BEFORE SERVICING
Air System Preparation
UV Lamp Mounting
2. Peel o paper from the adhesive
backing on the mounting brackets. Press the lamp with lamp clips rmly in place about 2” from blower wheel.
3. Pass the UV lamp cables
through to the back of the AC system.
TUV-MINI-MAN 04.30.12© 2012 Fresh-Aire UV
120 or 230 VAC
POWER SUPPLY
UV LAMP
UV LAMP
BLACK
WHITE
GREEN
1. Remove the control box cover and
connect the wiring harness as shown.
For 120 VAC wiring
•Blacktohotterminal
•Whitetoneutral
•Greentoground
For 208 - 230 VAC wiring
•Blacktoline1
•Whitetoline2
•Greentoground
3. Insert the UV lamp cable connectors and wiring
harness connector into the power supply.
4. Tuck the power supply into the
line chase on the back of the ac unit or place it in or under the control box or other secure location.
5. Return power to the system and
conrm that Mini UV is working.
6. Apply the UV warning sticker in
an appropriate location.
Note: It can take up to 10 minutes for the UV lamp to warm up and fully illuminate.
2. Wiring Diagram
Note: Some indoor systems
may require additional wiring to provide line voltage to the Mini UV™ power supply.
LAMP CABLES
POWER LEAD
The germicidal UV lamp in Fresh-Aire Mini UV® needs to be replaced yearly.
GermicidaleectivenessfallsoovertimesoUVlampreplacementisnecessary
even if the lamps continue to emit visible light after one year.
Power Supply Installation Lamp Replacement
Limited Warranty:
This warranty supersedes and replaces any warranty statements orally made by the Sales Person, Distributor or Dealer or contained in the written instructions or other Brochures or informational documents in relation to this product. This warranty gives you specic legal rights, and you may also have other rights which vary from State to State.
Manufacturer warrants the Mini UV to be free from defects in material and workmanship under the normal use and service when operated and maintained in strict accordance with manufacturer’s instructions for one (1) year from the date of purchase of equipment, including the Ultraviolet Lamp (Part# TUVL-MINI), which is warranted for UV germicidal output for one (1) year. The UV lamp warranty does not cover cracked or broken lamps due to mishandling or improper application.
Manufacturer’s obligation under this warranty is being limited to repairing or replacing any part found to its satisfaction to be so defective. This warranty does not cover parts damaged resulting from misuse, abuse, or any other than its intended use, accident, neglect, or from improper operation, maintenance, installation, modication or adjustments. Triatomic Environmental, Inc. shall have no responsibility for charges incurred by the customer for installation or removal of warranted items.
This warranty does not cover parts or equipment used with the Mini UV that are not made by the Manufacturer, since these items are covered by warranties of the respective manufacturer. This warranty shall be void if UV lamps from manufacturer’s other than Triatomic Environmental, Inc. are used with this equipment.
Manufacturer assumes no liability for any harm, which may occur as a result of the use of the equipment herein and shall not be liable for consequential or any other damages whether or not caused by manufacturer’s negligence or resulting from any express or implied warranty or breach thereof. Consequential damages for the purpose of this warranty shall include, but not be limited to, loss of use, income or prot, or loss of or damages to property or injury or death to persons or animals occasioned by or arising out of operation, use, the operation, installation, repair or replacement of the equipment or otherwise.
THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF
Replace lamp only with part #TUVL-MINI
Note: Use of replacement UV lamps other than Fresh-Aire UV® voids warranty.