Figure 17. Typical System Conguration WLA3XXX............................................ 38
Figure 18. Typical System Conguration WLA4XXX............................................ 39
Figure 19. Clean and Inspect Pressure/Vacuum Foam Tank Vent ........................... 40
Figure 20. WLA300 Parts List ................................................................................. 41
Figure 21. WLA400 Parts List ................................................................................. 42
3
WLA300 Rev170606
INTRODUCTION
Overview
The FRC TankVisionPro indicator shows the actual volume of liquid in a tank. The
liquid in the tank exerts a pressure that is measured by a sensor. As the amount of liquid
changes, the pressure it exerts on the sensor changes proportionally. The pressure change
is used to calculate the exact volume of liquid in the tank. The TankVisionPro can be
calibration to accurately display the volume of liquid in tanks of all shapes and sizes.
The display module is able to communicate with other display modules over the
FRC datalink. This allows for one master display module to control multiple displays.
The module also provides an output for cab miniature displays, remote light drivers,
and a low level warning buzzer.
The TankVisionPro indicator is a unique design made up of an extended wide view
lens with 9 or 10 super bright LEDs (depending on the chosen conguration) mounted
behind it. This allows the display to be visible and clearly read from all line-of-sight
angles for a full 180 degrees.
The pressure/vacuum foam tank vent is supplied for use on foam concentrate storage
tanks. These tanks should remain closed to the atmosphere. The FRC vent enables
the tank to compensate for changes in pressure or vacuum due to thermal expansion,
lling, or when withdrawing foam concentrate from the tank.
The MaxVision LED tank display provides a remote, wide angle view of how much
water or foam concentrate is left in the tank in fractional 1/8 tank eight level increments.
The remote light driver provides the option to have four 60 watt remote lights
controlled by the TankVisionPro to show full, 3/4, 1/2, and 1/4 tank.
Features
Self-Calibrating for Any Shape or Size Tank
Visual Warnings At 1/4 and Almost Empty Tank Conditions
Multiple Remote Displays
Pressure/Vacuum Foam Tank Vent for Sealed Foam Tanks
Color Coded for Water, Class A, or Class B Foam
Self-Diagnostic Capabilities
Cab Miniature Display (Optional)
MaxVision LED Tank Display (Optional)
Remote Light Driver (Optional)
Low Level Warning Buzzer (Optional)
Tank Thin Wall Adapter Kit (Optional)
Output for Foam Fill and Auto Tank Systems (Factory Programmed)
4
WLA300 Rev170606
Adjustable/Programmable Brightness Levels—10 adjustable brightness control levels
Tri-Color LEDs (Red, Green and Blue)—Programmable in various light patterns.
(See pages 27-28 for more detailed information.)
Magnet activated switch for calibration and settings
Option for 12 pin connector with additional features:
Visual warning output
Silence button input to disable audio warning only
Valve control output
Frame attachment is provided for a more secure mounting
Waterproof Polycarbonate Housing and lens enclosure provided to
protect electronics.
5
WLA300 Rev170606
Specications
Display Module
Supply Voltage: 9 - 30 VDC
Supply Current: 0.25 Amp Maximum
Dimensions: 4 3/8 by 3 Inches
Housing: Waterproof Polycarbonate with plastic lens and enclosure
to protect electronics
Indicators: Tri-Color of Bright LEDs (9/10 Rows)
Viewing Angle: 180°
Cab Miniature Display
Supply Voltage: 9 - 30 VDC
Supply Current: 0.5 Amp Maximum
Dimensions: 2 1/4 by 1 1/2 Inches
MaxVision LED Tank Display
Supply Voltage: 12/24 VDC
Supply Current: 1 Amp Maximum at 12 VDC
Dimensions: 14 3/8 by 1 7/8 Inches
Indicators: 96 Super Bright LEDs
Remote Light Driver
Supply Voltage: 9 - 30 VDC
Supply Current: 0.1 Amp Maximum
Switch: Solid State
Switching Voltage: 9 - 30 VDC
Switching Current: 20 AMPS Maximum @ 12 VDC
10 AMPS Maximum @ 24 VDC
Pressure Sensor
Housing: Stainless Steel with 1/4-18 NPT for Mounting
Maximum Flow Rate: Compensates 100% for Concentrate Flow Rates
Below 60 GPM
6
GENERAL DESCRIPTION
Components
The TankVisionPro consists of the following components:
Display Module
Cab Miniature Display (Optional)
Pressure Sensor
Pressure/Vacuum Relief Vent (Foam Tanks)
MaxVision LED Tank Display (Optional)
Remote Light Driver (Optional)
Buzzer (Optional)
Cables
WLA300 Rev170606
Display Module
The tank display module is waterproof and has dimensions of 4.4 inches high by
3 inches wide. An output signal from a pressure sensor mounted on the tank is input
to the primary display module. It is processed and the volume of liquid in the tank is
shown on the 9 LED display as a fractional amount on the overlay (or available as
a percentage value for a 10 LED display). Outputs from the primary display module
provide tank volume information to other displays and remote devices.
WLA400 Series primary displays are used for Auto Tank ATA400 systems.
WLA300 Series primary displays can be programmed to use pin #5 for Auto Tank
ATA400 systems.
Cab Miniature Display (Optional)
The cab miniature display has dimensions of 2.75 inches high by 1.5 inches wide.
It provides the option of mounting a remote display in the cab that uses a minimum
of panel space. An output signal from the primary display module is input to the cab
miniature display and the volume of liquid in the tank is shown on the 5-LED display.
Pressure Sensor
The pressure sensor is mounted on a side of the tank near the bottom. It provides a
signal that is proportional to the volume of liquid in the tank to the input of the primary
display module. The electrical connector is waterproof and molded into the pressure
sensor housing.
The standard pressure sensor is used on tanks between 1 and 10 feet in vertical
height. For tanks taller than 10 feet contact FRC for options.
7
WLA300 Rev170606
Pressure/Vacuum Foam Tank Vent
The pressure/vacuum foam tank vent is supplied for use on sealed foam tanks.
The vent compensates for changes in tank pressure due to thermal expansion or when
withdrawing foam concentrate from the tank. Internal passageways provide a path
for air to move between the tank and a center cavity in the vent. These passageways
are self-draining and designed to prevent splashing foam from entering the center
cavity and clogging the pressure and vacuum valves. The pressure and vacuum valves
are easily accessed and disassembled for periodic cleaning or inspections. (Refer to
Maintenance section.)
Note: The vent can compensate for a maximum foam concentrate ow rate
of 60 GPM. If the ow rate of foam concentrate from the tank will exceed
60 GPM, two (2) vents will be required.
MaxVision LED Tank Display (Optional)
The LED display is waterproof and has dimensions of 14 3/8 inches high by 1 7/8
inches wide by 7/8 inch deep. It has 96 RGB LEDs and built in LED drivers. A signal
from the primary display module is output on a two wire datalink and input to the LED
light to show the volume of liquid in the tank.
The display shows the level in 1/8 tank increments. It has a photo sensor that adjusts
brightness for day or night operations. The LEDs are programmable for various display
modes and multiple brightness levels:
Note: The MaxVision LED tank display shows how much water or foam
concentrate is left in the tank in fractional 1/8 tank eight level increments.
Remote Light Driver (Optional)
The remote light driver is waterproof and has dimensions of 4 inches high by 2.75
inches wide by 1 inch deep. An output signal from the primary display module is input
to the remote light driver. This provides the option to power four (4) 60 watt remote
lights that show the volume of liquid in the tank. The lights will show full, 3/4, 1/2,
and 1/4 tank levels.
Buzzer (Optional)
The buzzer provides an audio alarm when the tank volume drops to 25%.
The buzzer resets when the tank volume goes above 25%.
Note: When the TankVisionPro WLA300 primary display is used to control
an Auto Tank ATA400 system, pin 5 does not provide a ground for the
buzzer. WLA400 Series primary displays are used for Auto Tank ATA400
systems. WLA300 Series primary displays can be programmed to use pin
#5 for Auto Tank ATA400 systems.
8
WLA300 Rev170606
INSTALLATION
The TankVisionPro primary display module is connected to the pressure sensor
and is the only module that needs to be calibrated.
Note: The calibration procedure needs to be performed every time a primary
display module is installed.
Install Display Module
The full size display modules all have the same mounting dimensions. Standard
display modules are interchangeable.
Note 1: It is recommended to mount the display at eye level.
Note 2: Do not use Loctite on any screws near the Lexan lens. Lexan lenses
can become brittle and prone to cracking when exposed to Loctite compounds.
1. Measure and mark mounting location for display module panel cutout and
mounting screw holes. Make sure there is clearance behind the panel for
the display and cables before cutting holes. Refer to Figure 1 for layout and
dimensions.
2. Cut out a 4 by 2 1/8-inch hole and drill four (4) holes (clearance or tapped) for
#10 mounting screws.
3. Place display module in position and secure with four (4) screws.
4. Connect the display module cables and wires. (Refer to Wiring Section.)
Install Cab Miniature Display
1. Measure and mark mounting location for cab miniature display mounting hole.
Make sure there is clearance behind the panel before drilling hole. Refer to
Figure 2 for layout and dimensions.
2. Drill a clearance hole for 3/8" threads.
3. Place cab miniature display in position and secure with nut.
4. Connect the cab miniature display wires. (Refer to Wiring Section.)
The pressure sensor is mounted on one of the tank sides approximately 2 inches
from the bottom. If the tank has a vertical height greater than 10 feet contact FRC, a
different sensor may be required.
Pressure sensors are interchangeable. It is recommended that the calibration
procedure be performed if the pressure sensor is changed.
Note: When mounting the pressure sensor on a tank with thin walls, less
than 3/8", it is recommended that the tank wall be reinforced at the sensor
mounting location.
Pressure Sensor Installation
Note: Do not mount the sensor in the bottom of the tank. Sediment may collect in the port
and cause sensor failure.
1. Measure and mark mounting location for sensor. (Mounting hole should be
approximately 2" from bottom of tank.) Make sure there is clearance for sensor
and cable before drilling hole. Refer to Figure 3 for dimensions.
2. Drill and tap a 1/4 NPT hole.
3. Apply sealant around base and threads of pressure sensor.
4. Screw sensor into hole.
5. Connect sensor cable. (Refer to Wiring Section.)
Thin Wall Adapter Installation
The thin wall adapter kit includes the adapter, two 10-24 x 5/8" screws, 5 minute
epoxy, and a mixing stick.
1. Measure and mark mounting location for adapter. Make sure there is clearance for
adapter, sensor, and cable before drilling hole. Refer to Figure 3 for dimensions.
2. Drill and tap a 1/2 NPS hole.
3. Screw the adapter into the hole.
4. Use the adapter as a template and drill and tap two 10-24 holes for two screws.
5. Back adapter out of hole and apply 5 minute epoxy to back of ange, on threads,
and in two 10-32 through holes.
6. Screw adapter into hole and secure with two screws.
7. Allow the epoxy time to set.
8. Apply sealant around base and threads of pressure sensor and screw into adapter.
9. Connect sensor cable. (Refer to Wiring Section.)
11
WLA300 Rev170606
Mount sensor approximately
2" from bottom of tank.
7/8"
Across Flats
2.8"
(max)
1.1"
0.6"
Apply sealant around
base and threads.
3-Pin
Packard Plug
0.87"
1/4 NPT
Typical
Tank
Typical Pressure
Sensor Location
Note: Do not mount the sensor in the
bottom of the tank. Sediment may collect
in the port and cause sensor failure.
Note: The sensor can be mounted
vertically on a 90° tting in cold areas to
help prevent water freezing in the sensor.
Thin Wall Adapter
2"
Apply sealant
around base and
threads of sensor.
1/2 NPS
Apply epoxy around
ange, threads, and
screws.
Figure 3. Pressure Sensor
12
WLA300 Rev170606
Install Pressure/Vacuum Foam Tank Vent
A pressure/vacuum foam tank vent is supplied for use on sealed foam tanks. The
recommended location to mount the vent is in the cover of the foam tank ll tower. If
there is no ll tower, mount the vent at the highest point of the tank top so that it is not
immersed in foam. For installations where clearance above the ll tower is limited, a
90° mounted vent is available.
Note: The vent can compensate for a maximum foam concentrate ow rate
of 60 GPM. If the ow rate of foam concentrate from the tank will exceed
60 GPM, two (2) vents will be required.
Install Top Mounted Tank Vent
The top mounted tank vent is mounted in a vertical position through a 1 1/8-inch
hole on the lid of the ll tower and is secured by a hand tightened nut.
Note: The tank vent must be in a vertical position and can not be immersed
in foam.
1. Measure and mark mounting location for vent. Make sure there is clearance
for the valve before drilling hole. Refer to Figure 4 for dimensions.
2. Drill 1 1/8-inch diameter hole.
3. Insert vent into the hole with the gasket in place.
4. Screw on nut and hand tighten.
Install 90° Mounted Tank Vent
The 90° mounted tank vent is mounted on a vertical side of the ll tower. It must
be located as close to the top of the ll tower as possible. The vent is held in place with
two (2) 1/4-20 x 3-inch bolts, washers, and locknuts.
Note: The tank vent must be in a vertical position and can not be immersed
in foam.
1. Measure and mark mounting location for vent. Make sure there is clearance
for the valve before drilling holes. Refer to Figure 4 for dimensions.
2. Drill 3/4-inch diameter hole and two through holes for 1/4-20 bolts.
3. Apply sealant to mounting surfaces and bolt holes.
4. Secure vent in place with two bolts, washers, and locknuts.
13
WLA300 Rev170606
90° Mounted Tank Vent
3/4" Diameter Hole with
ll tower, mount the vent at the highest
Top Mounted Tank Vent
2 1/2"
Top Mounted Tank Vent
1 1/8" Diameter Hole
Two 1/4" Bolt Holes
Note: The tank vent must be mounted
in a vertical position. The vent can not
be immersed in foam. (If there is no
point of the tank top so that it is not
immersed in foam.)
Typical
Foam Tank
Fill Tower
1 3/4"
5/8"
Maximum Mounting
Surface Thickness
90° Mounted Tank Vent
2 5/8"
2 5/8"
3 7/8"
Gasket (Between Mounting
Surface and Tank Vent)
Nut (1 1/8" - 12 TPI)
3/4" Dia.
1/4" Dia.
(Thru holes for two
1/4-20 x 3" bolts.)
Figure 4. Pressure/Vacuum Foam Tank Vent
1 1/2"
14
WLA300 Rev170606
Install MaxVision LED Tank Display
The LED display is waterproof to allow for exibility in the mounting location.
Ensure that the light is mounted with the rear against a at surface.
Mount the display so that the raised MaxVision logo on the lens and the drain notch
on the rubber gasket are at the bottom and is mounted with the rear against a at surface.
The wires can be run through any one of the three holes in the rubber gasket.
Note: Before drilling holes place the light in position to check for t. Ensure
that the display clears all obstructions.
1. Measure and mark the mounting hole locations and through hole for the wiring.
2. Drill the two (2) mounting holes for #10 screws and a wire feed thru hole. Any
of the three locations (holes) in the rubber boot can be used for the wires.
Note: Ensure that the terminating resistor is installed on the datalink wires
when required.
3. Connect the wiring and secure the light with two (2) screws. (Refer to Wiring Section.)
Terminating Resistor Notes
The datalink requires two terminating resistors.
1. One TankVisionPro with one or two LED displays: Install one resistor
close to the primary display; install the other resistor farthest away from the
primary display, but closer to the remote display.
2. Two TankVisionPro displays: Install terminating resistor at both ends.
3. If the TankVisionPro is used with a TurboFoam system: Do not install
terminating resistor.
Program MaxVision LED Tank Display
The MaxVision acts as a remote, and the color pattern will mirror the pattern
chosen for the primary display. (See page 29 for detailed information about synching primary and remote displays.)
Code Entry:
1. Hold a magnet over the calibration point for ve seconds. Two middle rows
of LEDs come on.
2. Swipe the magnet to select the program to be changed; a row of LEDs come
on with each swipe.
Brightness Adjustment:
1. Top 2 rows on - set daytime brightness.
2. Top 3 rows on - set nighttime brightness.
15
WLA300 Rev170606
3. Wait 5 seconds to enter the program.
4. Each swipe changes the LEDs brightness—ten levels that are stepped through
and then repeated.
5. Hold the magnet over the calibration point for ve seconds to load the new
setting. The display blinks three times to conrm setting is loaded.
Programming the MaxVision to Display Foam A, Foam B or Water:
Code Entry:
●Hold a magnet over the calibration point for ve seconds. Two middle rows
of LEDs come on.
Swipe 4 times to set the display for one of the following options:
●Water (Default option)—displays alternate Blue LEDs
●Foam A—displays alternate Green LEDs
●Foam B—displays alternate Yellow LEDs
1. Wait 5 seconds to enter the program.
2. Each swipe changes the choice from Water, to Foam A, to Foam B—the three
options are stepped through and then repeated.
3. Hold the magnet over the calibration point for ve seconds to load and save the
new setting. The display ashes or blinks three times to conrm setting is saved
and updated.
Programming the Color Pattern for the MaxVision:
The default setting for the color pattern is to have this synchronized with the primary
display (as described on page 29, Fig. 10). If it is required to have the MaxVision synchronize
with the primary display, activate the "Code Entry" (as mentioned on page 15), select Pattern
#10, wait for 5 seconds and swipe the magnet once. Save the setting by holding the magnet
for 5 seconds at the calibration point.
However, these same six color patterns from Fig. 10 (shown in Fig. 5) can be "locked
in" for the MaxVision only, separately from the color pattern shown on the primary display.
Additionally, there are three color patterns to display the status level of either Foam A
(all Green LEDs) , Foam B (all Yellow LEDs) or Water (all Blue LEDs). This allows for
customizing of up to nine different "locked-in" color patterns on the MaxVision display
(separate from the primary display).
Perform the following steps to select the locked in color pattern for the MaxVision:
1. Start the "Code Entry" by holding the magnet the calibration point for ve seconds.
Two middle rows of LEDs come on.
2. Swipe the magnet to select the program to be changed; a row of LEDs come on
with each swipe.
16
WLA300 Rev170606
3. Swipe the magnet once and in ve seconds the previously saved color pattern will
be displayed. The Red LEDs will all light up and scroll upward (as shown in Pattern
10). The Red LEDs scrolling upward means the MaxVision display is synchronized
with the primary display. The color pattern on the MaxVision will be identical to
the one on the primary display. (This is the default setting).
Each swipe changes the choice from each of the nine color patterns—the nine
options are stepped through and then repeated.
4. Hold the magnet over the calibration point for ve seconds to save the new color
pattern setting. The display ashes or blinks three times to conrm setting is saved
Note: Do not use Loctite on any screws near the Lexan lens.
Lexan lenses can become brittle and prone to cracking when
exposed to Loctite compounds.
Mounting holes are
clearance or tapped
for #10 screws.
14 3/8"
13 1/4"
Front
View
Side
View
Three locations are
available for the wires to
exit the rubber gasket.
Rear
View
7/8"
6 5/8"
5 3/4"
11 1/2"
1 7/8"
Figure 6. MaxVision LED Display Mounting Dimensions
Calibration
Point
(behind "R")
Photo
Sensor
7/8"
5 3/4"
6 5/8"
7/8"
Drain
Notch
18
WLA300 Rev170606
Install Remote Light Driver
The remote light driver is water proof to allow for exibility in the mounting location.
1. Measure and mark mounting location for light driver. Make sure there is clearance
for driver and cable before drilling holes. Refer to Figure 5 for dimensions.
2. Drill and tap two 10-32 holes.
3. Secure remote light driver with two screws.
4. Connect cable and wires. (Refer to Wiring section.)
1 3/8"
2 3/4"
3 1/2"
4"
1"
Install Buzzer
Install the buzzer close to the TankVisionPro so the audible warning is easily
associated with the TankVisionPro. A cutout hole diameter of 1-1/4" is required.
(Refer to the wiring section.)
Figure 7. Remote Light Driver
19
WLA300 Rev170606
OPERATION
No operator input is required for the TankVisionPro to be operational. When power
is on, the display is operating. The signal from the pressure sensor is processed and
the volume of liquid in the tank shows on the display.
Note: Calibrating the TankVisionPro display to the tank is required before
operations. (Refer to Calibration section.)
Primary Display Module
All LEDs are on when the tank is full. Each LED goes off starting at the top and
working down as the liquid in the tank decreases.
The bottom 3 LEDs flash when the tank is less than 1/4 full.
(For the WLA400 Series, the visual warning indicator signal is synchronized
with the ashing LED on the display.)
All LEDs rapidly down-chase when the tank is almost empty.
Options
Programmable LED Display
LED Indicator lights can be programmed to be Red for all 9/10 rows, or one of
the patterns shown on pages 27-29.
12 Pin Connector with Additional Features:
Visual warning output. (Active ground; Maximum 150mA)
Silence button input for audio warning only. (Active ground)
Separate Valve control output. (Active ground; Maximum 150mA)
Separate ground connection for the level sensor
Remote Display Module
The remote display repeats exactly what is shown on the master display.
Cab Miniature Display
All 5 LEDs is on when the tank is full. The LEDs will show full, 3/4, 1/2, 1/4,
and empty tank.
MaxVision LED Display
The LED display repeats exactly what is shown on the master display.
20
WLA300 Rev170606
Remote Light Driver
When power is applied, the remote light driver runs a lamp test function. The lamp
test starts at the 1/4 light and cycles each remote light on and off. At the completion
of the lamp test, the remote light driver turns on the correct light(s) to show the tank
water or foam volume.
All four lights are on when the tank is full. The top light goes off as the tank starts
to empty (at 7/8 full the light is off). The three bottom lights are on to show that the
tank is between less than full (approx. 7/8 tank) and 1/2 tank. The bottom two lights
show 1/2 and 1/4 tank. The bottom light blinks when the tank volume goes less than
1/4 tank.
Buzzer
The buzzer sounds when the tank volume drops to 1/4 tank. (This is programmable.
Review the Warning and Control Level Adjustment section on page 28 for
detailed information.)
21
WLA300 Rev170606
CALIBRATION
The TankVisionPro has unique calibration programs that enable it to be used on
tanks of all shapes and sizes.
Note: The standard pressure sensor is limited to a maximum tank height of
ten feet.
Overview
Magnet Sensor
The calibration programs are accessed by activating the C 1 and C 2 magnet
sensors that are located on the front of the display module. The sensor is activated by
placing the north or south pole of a small magnet in close proximity of the sensor. The
magnet is then moved about 1-inch away, this will produce an electronic signal that is
similar to a button being released. If the LEDs in the display do not change try moving
the magnet further away from the sensor.
In these procedures the term ‘swipe’ will mean to move the magnet up to and then
away from the magnetic sensor.
Non-Linear Calibration
The rst program is a non-linear calibration procedure that can be used for any shape
or size tank. This procedure must to be used for irregular shape tanks (e.g.: T-shape,
oval, elliptical, tank with through hole, etc.). The program compares the pressure in the
tank, as the tank lls at a steady rate, to time. This provides for very accurate displays.
Linear Calibration
The second program is a linear calibration procedure that can only be used when
the tank volume is proportional to the height. This would include square or rectangular
shape tanks with no irregularities. It is quick way of calibrating a tank but not as accurate
as the non-linear procedure. The program compares a full tank to an empty tank, takes
the difference and divides it into eight equal volume displays.
Full Tank Correction
This program is for use to ne tune the tank display after a non-linear or linear
calibration procedure has been completed. It would only be needed in cases where
one type of liquid is used for calibration when a different liquid would normally be in
the tank. For example this would allow the basic calibration of a foam tank to be done
using water and then the calibration would be ne tuned when the tank is lled with
foam concentrate.
22
WLA300 Rev170606
PROGRAMMING CODES
Code Entry
1. Swipe the magnet at C1. Each of the bottom row of LEDs turns on one at a time.
2. Swipe the magnet at C2. Each of the top row of LEDs turns on one at a time.
For example:
A. To enter Code 32, swipe the magnet at C1 three times, and then swipe the
magnet at C2 twice.
B. If the code is accepted, the display will ash with the corresponding
number of top and bottom LEDs as the entered count. For example—three
bottom row and two top row LEDs will ash alternately between the top and
bottom rows.
3. The process times out after 10 seconds of inactivity, or if no additional codes
are entered (except for the non linear calibration).
4. Save the new setting or enable new data entry by holding the magnet at C2 for
5 seconds.
Calibration and Tank Level Correction
Linear Tank Calibration
1. Start this process with a full tank.
2. Enter Code 44 to activate the Linear tank calibration. (See page 23 for detailed step-by-step instructions.)
Nonlinear Tank Calibration
1. Start this process with an empty tank.
2. Enter Code 33 to activate the Nonlinear tank calibration. (See page 22 for detailed step-by-step instructions.)
Level Correction and Warning
Enter Code 55 to start full level correction. Make sure the tank is almost full, or
at greater than 90%.
Enter Code 66 to activate the warning, if the signal is 0.5V higher than the full level.
Note: See page 27 for complete Diagnostics & Warnings information.
23
WLA300 Rev170606
Non-Linear Calibration
This non-linear calibration procedure can be used for any shape or size tank. The
calibration process requires that the tank be empty at the start of the procedure and
then lled at a steady rate of ow.
The term ‘swipe’ means to move the magnet up to and then away from the C 1
and C 2 sensors on front of the display.
Note: To exit the calibration mode without saving any new calibration, reset
the power to the display.
1. Empty the tank.
2. Apply power to the display module.
3. Swipe the magnet three times at C 1 and three times at C 2 to enter the calibration
mode. Hold the magnet at C 2 for ve seconds to activate the calibration.
Result: Top three display LEDs and bottom three LEDs ash on and off.
Note: Once the calibration process is activated the ow rate of liquid into the
tank must remain constant for the procedure to be accurate.
4. Fill the tank at a steady rate of ow.
Note: As the tank is lling up, the display will simulate a visual "ll-up"
light pattern.
5. When the tank is full stop the ow.
6. Hold the magnet at C 2 for ve seconds to set the calibration into memory.
7. After six seconds the calibration process terminates and all the LEDs are on
to show that the tank is full.
24
WLA300 Rev170606
Linear Calibration
This linear calibration procedure can only be used for square or rectangular shape
tanks with no irregularities. The calibration process requires that the tank be full at the
start of the procedure.
The term ‘swipe’ means to move the magnet up to and then away from the
C 1 or C 2 sensors on front of the display.
Note: To exit the calibration mode without saving any new calibration, reset
the power to the display.
1. Fill the tank. (Do not ll up into the ll tower.)
2. Apply power to the display module.
Note: Once the calibration program is activated there is a six second time out.
Do not wait more than six seconds to move from step 3 to step 4.
3. Swipe the magnet four times at C 1 and four times at C 2 to enter the
calibration mode. (Do not wait more than six seconds in between swipes or
the session will time out.)
Wait until the top four and bottom four display LEDs alternatively ash on
and off. (See the diagram below.)
4. While the LEDs are still ashing, hold the magnet at C 2 for ve seconds to set
the calibration into memory.
5. After a few seconds the calibration process will terminate and all the LEDs
will go on to show that the tank is full.
C2
At Step 4 - Top four and bottom
four LEDs will ash alternatively
on and off
C1
25
WLA300 Rev170606
Full Tank Correction (Code 55)
This ne calibration procedure is used to ne tune the tank display after a
non-linear or linear calibration has been completed. The calibration process requires
that the tank be full at the start of the procedure and the display shows 75% or more.
The term ‘swipe’ means to move the magnet up to and then away from the
C 1 or C 2 sensors on front of the display.
Note: To exit the calibration mode without saving any new calibration, reset
the power to the display.
1. Fill the tank. (Do not ll up into the ll tower.)
2. Apply power to the display module.
Note: Once the calibration program is activated there is a six second time
out. Do not wait more than six seconds to move from step 3 to step 4.
3. Swipe the magnet ve times at C 1 and ve times at C 2 to enter the
calibration mode.
Result: Top and bottom ve display LEDs ash on and off.
4. After three seconds hold the magnet at C 2 for ve seconds to set the calibration
into memory.
5. After six seconds the calibration process will terminate and all the LEDs will
go on to show that the tank is full.
26
WLA300 Rev170606
DIAGNOSTICS
There are diagnostic codes built into the TankVisionPro. These diagnostic codes
can help in the troubleshooting process.
If there is no input on pin 2 of the remote light driver, the remote lights remain off.
The following FAULTS are displayed as long as the fault exists.
Display
Top 2 and Bottom 2
LEDs Alternately Flash.
Top 4 and Bottom 4
LEDs Alternately Flash.
Problem
Pressure Sensor not
detected at Primary
Display
(voltage < 0.3V)
Datalink not detected at
Remote Display
Pressure Sensor high
output voltage.
(voltage > 4.6V)
Probable Cause
Sensor cable not connected
Broken wire / bad connector on
sensor cable
Defective sensor
Datalink cable not connected
Broken wire / bad connector on
datalink cable
Shorted wire on sensor cable
Pressure Sensor or Primary
Display Failure
The display cycles between normal and the following WARNINGS when a warning
condition exists.
Display
Top and Bottom LEDs
Blink ON and OFF
Problem
The difference in voltage
from the Pressure Sensor
between tank empty and
tank full is too small.
(non-linear 3-swipes volt
change less than 0.16V)
Illegal calibration procedure.
Sensor cable not connected.
Broken wire / bad connector on
sensor cable.
Tank height less then 6”.
Defective sensor.
(linear 4-swipes volt
change less than 0.66V)
Figure 8. Diagnostics - Faults
27
Probable Cause
WLA300 Rev170606
The display cycles between normal and the following WARNINGS when a warning
condition exists.
Display
Problem
Probable Cause
CODE 66
Top 2 and Bottom 2 LEDs
Blink ON and OFF
If the voltage from the
Pressure Sensor is more
than 4.6 volts, then it is
above normal range.
Apparatus at incline
(parked on a hill).
Not calibrated correctly.
Shorted wire / bad connector
on sensor cable.
This high voltage warning can be enabled or disabled by swiping the C 1 and C 2
sensors six times. (Factory default setting: disabled.)
When ENABLEDTop 2 and Bottom 2 LEDs Blink
When DISABLEDTop 6 LEDs Blink
To change the setting swipe the C 1 and C 2 sensors six times again. Then hold the
magnet at C 2 for ve seconds to set the calibration into memory.
To leave the setting as it is, let the processor time out and go back to normal display.
Figure 9. Diagnostics - Warnings
28
WLA300 Rev170606
COLOR PATTERN SELECTION
Code 11 Pattern 1 - One solid color. 4-green\3-blue\2-orange\1-red (Default)
Code 12 Pattern 2 - All red (same as WLA-2XX Series)
Code 13 Pattern 3 - Top 1/8 level is green and all others are red.
Code 14 Pattern 4 - Three colors: blue\orange\red.
Code 15 Pattern 5 - All green, and turns red when the WARNING is active
(when the tank level is at or below 25%, or 1/4 full).
Code 16Pattern 6 - Four fixed colors for each 1/4 or 25% level:
green\blue\orange\red.
Wait 5 seconds.
Save the new setting by holding the magnet at C 2 for 5 seconds.
Note: The above is an example of a programmed LED Color Pattern.
Figure 10. Color Pattern Selection
29
WLA300 Rev170606
Warning and Control Level Adjustment
Code 21 To set the Audio warning level. Default—1/4 (25%)
Code 22 To set the Visual warning level. Default—1/4 (25%)
Code 23 To set the "Tank Full" audio signal level.
Default—disabled.
Code 24To set the Valve control signal "Low" activation level. Default— 1/2 (50%)
Code 25To set the Valve control signal "Full" deactivation level. Default —7/8 (95%)
Code 26To set the level for Audio warning to be turned off (or disabled). Default —1/4 (25%)
Code 27To set the level for Visual warning to be turned off. Default —1/4 (25%)
Code 28To set the delay time in seconds before the Audio warning is activated. Default —1 second (NOTE: each LED delays the Audio warning
activation by 1 second. This is adjustable from 1 to 7 seconds. )
1. Enable the data entry by holding the magnet at C 2 for 5 seconds. This sets the
desired level for either Warnings or Valve Control setting activation.
2. Wait ve seconds.
3. Save the new setting by holding the magnet at C 2 for 5 seconds.
Note: If the WL300 is set with code 24 and 25, the buzzer output will work
as a valve controller.
Figure 11. Diagnostics - Warnings
30
Level Adjustment Setting Pattern
1. Every magnet swipe at C 1 will incrementally increase/decrease the
activation value by 1/16 (5% for % scale).
2. Every Green LED is 1/8 level (10% for % scale).
3. Every blue LED is 1/16 level (5% for % scale).
4. LEDs are all red when activated, and show the default or previously set value.
WLA300 Rev170606
Fractional Scale
Percentage (%) Scale
at 11/16
at 65%
31
WLA300 Rev170606
Brightness Adjustment
Code 31 Day time brightness. Default—Brightness Level - 8
Code 32 Night time brightness. Default—Brightness Level - 2
1. Every magnet swipe at C 1 will incrementally increase/decrease the
brightness for 10 various levels.
2. Starting from the lowest level, repeat the process from number 1.
3. Enable the data entry by holding the magnet at C 2 for 5 seconds.
4. Adjust the brightness to the desired level.
5. Save the new setting by holding the magnet at C 2 for 5 seconds.
Primary and Remote Synchronization
If the level pressure sensor is detected, (0.3V or more) the unit will work as a
Primary display. Any remote unit including Water, Foam A, or Foam B, and MaxVision,
that is connected via CAN bus will be synchronized with following settings:
• Tank level calibration
• Display Pattern
• Warning and control activation levels
NOTE: Brightness will remain as adjusted locally in the remote display unit.
32
WIRING
Primary Display (WLA3XX/WLA4XX)
WLA3XX Primary Display
Connector
Pin Description
1 Power 9-30 VDC
45
1
8
2 Ground (Sensor Ground)
3 Sensor 5 VDC
4 Sensor Signal
5 Buzzer Ground (150mA)
6 Display Signal Out
7 Datalink (+)
8 Datalink (–)
WLA300 Rev170606
6
112
7
WLA4XX Primary Display
Connector
Pin Description
1 Power 9-30 VDC
2 Ground
3 Sensor 5 VDC
4 Sensor Signal
5 Buzzer Ground (150mA)
6 Display Signal Out
7 Datalink (+)
8 Datalink (–)
9 Silence Button Input
10 Sensor Ground
11 Valve Control Output (150 mA)
12 Visual Warning Ground (150 mA)
Figure 12. Primary Display Wiring
33
WLA300 Rev170606
WIRING
Primary Display Rear View (WLA3XX/WLA4XX)
Pressure Sensor Connector
WLA3XX
Primary Display
Module
Deutsch Plug
DT06-8S
Standard Harness
Primary Display
Module
Output
Signal
Supply
Voltage
5 VDC
Ground
Power
To
Pressure
Sensor
WLA4XX
Primary Display
Module
Deutsch Plug
DT06-12S
Standard Harness
Primary Display
Module
Pressure Sensor Connector
Output
Signal
Supply
Voltage
5 VDC
Power
To
Pressure
Sensor
Ground
Figure 13. Primary Display Wiring (Rear View)
34
Remote Displays (WLA3XX/WLA4XX)
WLA3XX Remote Display
Pin Description
1 Power 9-30 VDC
2 Ground
3 N/A
4 N/A
5 Buzzer Ground (150mA)
6 Display Signal Out
7 Datalink (+)
8 Datalink (–)
Remote Display
Module
Deutsch Plug
DT06-8S
Standard Harness
Remote Display
Module
WLA300 Rev170606
Connector
Datalink
Remote Display
Module
Deutsch Plug
DT06-12S
Standard Harness
Remote Display
Module
Power
WLA4XX Remote Display
Connector
Pin Description
1 Power 9-30 VDC
2 Ground
3 N/A
4 N/A
5 Buzzer Ground (150mA)
6 Display Signal Out
7 Datalink (+)
8 Datalink (–)
9 Silence Button Input
10 N/A
11 Valve Control Output
12 Visual Warning Output
Datalink
Figure 14. Remote Display Wiring (WLA3XX/WLA4XX)
Power
35
WLA300 Rev170606
Cab Miniature and MaxVision LED Displays
Note: A white wire with a Deutsch contact
on one end (to plug into the standard harness
connector) and a butt connector on the other
(to connect to customer provided wire) is
provided with the Cab Miniature Display.
Cab Miniature
Display
MaxVision LED Display
Wires can be routed
from top, middle, or
bottom feed through.
Power
TankVisionPro
Pin
Yellow 7
Green 8
Butt
Connectors
White Wire
Cab Miniature Display
Wiring
Wire Description
Red Power 9-30 VDC
Black Ground
White Display Signal
LED Display Wiring
Wire Description
Red Power 9-30 VDC
Black Ground
Yellow Datalink (+)
Green Datalink (–)
Note: See Terminating Resistor Notes
for the MaxVision on page 15.
Note: A terminating resistor kit is
included with the MaxVision
LED display.
Figure 15. Cab Miniature and LED Display Wiring
36
WLA300 Rev170606
Remote Light Driver
Notes:
Connect a wire from the primary or a remote display module pin 6 to the remote
light driver pin 2 (this is the input signal to the remote driver). If there is no signal on
pin 2 the lights remain off.
Connect power to pin 3 and to pin 8, this is power for the remote driver and the
remote lights. It is recommended that pin 3 and pin 8 be tied together. The maximum
current is 20 AMPS @ 12VDC (10 AMPS @ 24 VDC).
Light Driver Connector
Pin Signal Description
1 Ground
45
1
8
2 Signal Input
3* Remote Light Power
4 1/4 Tank Output
5 1/2 Tank Output
6 3/4 Tank Output
7 Full Tank Output
8* Remote Light Power
Full Tank
Typical Remote
Light Stack
(four 60 watt lights)
GND
Input From
Display Module Pin 6
Ground
Note: If there is no signal on pin 2
(input from a display module) the
lights remain off.
3/4 Tank
1/2 Tank
1/4 Tank
Remote Light
Driver
*Light Power
(12 VDC 20 A)
(24 VDC 10 A)
Use 16 AWG Wire
Figure 16. Remote Light Driver Wiring
37
WLA300 Rev170606
Typical System Conguration WLA3XX
Note: Multiple number of remote displays can be
connected to the primary display. Any remote display can
become a primary by disconnecting the sensor from the
primary and connecting it to the remote.
MaxVision
Cab
Miniature
Display
LED
Display
Datalink Daisy
Chain To Other
Devices
Terminating
Resistor
Warning
Buzzer
12/24 VDC
Primary
Display
9-30VDC
To Other
Miniature
Displays
To Remote
Light Driver
White
Wire
Pin 6
Terminating
Resistor
Remote
Display
Power
9-30VDC
FRC Datalink
9-30VDC
Pressure Sensor
Figure 17. Typical System Conguration WLA3XXX
Note: See Pin Description/
Location on pages 32 and 34.
38
Typical System Conguration WLA4XX
Note: Multiple number of remote displays
can be connected to the primary display. Any
remote display can become a primary by
disconnecting the sensor from the primary
and connecting it to the remote.
WLA300 Rev170606
Datalink Daisy
Chain To Other
Devices
Cab
Miniature
Display
Warning
Buzzer
12 or 24 VDC
To Remote
Light Driver
To Other
Miniature
Displays
9-30VDC
White
Wire
MaxVision
LED
Display
Remote
Display
Terminating
Resistor
Power
9-30VDC
Primary
Pin 6
Display
9-30VDC
Pressure Sensor
Note: See Pin Description/
Location on pages 32 and 34.
Terminating
Resistor
Visual Warning
Indicator
12 or
24 VDC
FRC Datalink
Silence Button
To Valve
Controller
NOTE: For Valve
Controller Activation:
Max 150 mA
to ground supply to
activate the signal or an
external relay.
Figure 18. Typical System Conguration WLA4XXX
39
WLA300 Rev170606
CLEAN/INSPECT PRESSURE/VACUUM FOAM TANK VENT
The pressure/vacuum foam tank valve is supplied for use on sealed foam tanks.
There are internal passageways that provide a path for air to move between the
tank and a center cavity in the vent. These passageways are self-draining and designed
to prevent splashing foam from entering the center cavity and clogging the pressure
and vacuum valves.
The pressure and vacuum valves are easily accessed and disassembled for periodic
cleaning or inspections. Unscrew the cap from the main body and lift the valves out
of the center cavity. Clean all parts with warm water.
Note: The internal pressure and vacuum valves are different sizes. Make sure
to reassemble these valves correctly.
Note: It is extremely
important that the pressure
and vacuum valves are
assembled correctly.
Vent Cutaway
Diagram
Main
Body
Nipple
Cap
Vacuum
Valve
Pressure Valve
Vacuum Valve
Pressure
Valve
Center
Cavity
Atmosphere
Vent
Tank
Top
Figure 19. Clean and Inspect Pressure/Vacuum Foam Tank Vent
Tank
Vent
40
WLA300 Rev170606
WLA300 Standard Parts List
INDEXPART NO.DESCRIPTION
-WLA300TankVisionPro Kit, Water
-WLA360TankVisionPro Kit, Class A Foam
-WLA370TankVisionPro Kit, Class B Foam
1XE-WL300-DDisplay Module, Water
XE-WL360-DDisplay Module, Class A Foam
XE-WL370-DDisplay Module, Class B Foam
2XE-WL200S-CXXAPrimary Display Cable, XX=Length
3XE-WL200R-CXXARemote Display Cable, XX=Length
4XE-WLPT4-SPressure Sensor
5XE-WL20A-AThin Wall Adapter Kit
6XE-WL400-AFoam Vent, Vertical Mount
7XE-WL400H-AFoam Vent, 90 Degree Mount
8WLA205Cab Miniature, Water
8WLA265Cab Miniature, Class A Foam
8WLA275Cab Miniature, Class B Foam
9WLA290Remote Light Driver
-XE-WLE08-AWhite Wire w/Deutsch Pin and Butt Connector
10WLA280MaxVision LED Tank Display
11XE-XXDLTERMW-A0AAccessory Kit TV Data-Link 2 Term. Resistors w/Wires
PARTS LIST
1
3
2
4
6
7
5
8
9
10
Figure 20. WLA300 Parts List
41
11
WLA300 Rev170606
WLA400 Standard Parts List
INDEXPART NO.DESCRIPTION
-WLA400TankVisionPro Kit, Water
-WLA460TankVisionPro Kit, Class A Foam
-WLA470TankVisionPro Kit, Class B Foam
1XE-WL400-DDisplay Module, Water
1XE-WL460-DDisplay Module, Class A Foam
1XE-WL470-DDisplay Module, Class B Foam
2XE-WL400S-CXXAPrimary Display Cable, XX=Length
3XE-WL400R-CXXARemote Display Cable, XX=Length
4XE-WLPT4-SPressure Sensor
5XE-WL20A-AThin Wall Adapter Kit
6XE-WL400-AFoam Vent, Vertical Mount
7XE-WL400H-AFoam Vent, 90 Degree Mount
8WLA205Cab Miniature, Water
8WLA265Cab Miniature, Class A Foam
8 WLA275Cab Miniature, Class B Foam
9WLA290Remote Light Driver
-XE-WLE08-AWhite Wire w/Deutsch Pin and Butt Connector
10WLA280MaxVision LED Tank Display
11XE-XXDLTERMW-A0AAccessory Kit TV Data-Link 2 Term. Resistors w/Wires
1
3
2
4
6
7
5
8
9
Figure 21. WLA400 Parts List
42
10
11
NOTES
WLA300 Rev170606
43
WLA300 Rev170606
44
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.