2. Installation instructions
2.1. Warning to the user
All the local and national regulations, and in
particular those relating to national and European
standards, must be observed when installing the
appliance.
An incorrectly installed heating appliance can
cause serious accidents (chimney fires, burning of
plastic insulation materials, in partition walls, etc.).
The insulation of both the appliance and the
exhaust gas pipe has to be reinforced and done
according to the Standards and the Building
Regulations for safety reasons.
Failure to respect the mounting instructions leads to
engage the responsibility of the one doing the
installation.
The manufacturer’s responsibility shall be limited to the
supply of the equipment.
2.2. Location of the unit
Ventilation :
For satisfactory appliance operation with a natural
draught, check that sufficient air for combustion is
available in the room.
Position of the unit :
For new installations, select a central position within the
house, to provide a good heat distribution around the
building.
The heat distribution towards the other rooms will be
made through the communicating doors.
These rooms must be in negative pressure or must
include ventilation gratings.
Floor and walls :
Make sure they are not combustible or covered with
combustible material (as per the Building regulations).
Otherwise it must necessary to install a
non-combustible protection.
There must be a clearance of at least 150 mm at each
side of the appliance and at the back of the appliance
from a non-combustible wall.
This distance must be
extended to a minimum
clearance of 350 mm from any
combustible materials.
This measurement may be
reduced to a minimum gap of
50 mm when the
non-combustible wall is at
least 200 mm thick.
When using a single wall flue
pipe, there must be a
clearance (A) of at least three
times its diameter (B) from
any combustible materials.
If the appliance has to be
located in an opening, this
distance must be extended to
a minimum clearance (A) of
375 mm from the pipe or the
stove body to any combustible
materials.
Hearth :
The appliance must stand on a fireproof hearth.
It is possible to provide a hearth made of non
combusible board/sheet material or tiles at least 12 mm
thick.
Constructional hearths should be constructed of solid
non combustible material at least 125 mm thick
(including the thickness of any non combustible floor
under the hearth).
The hearth must protrude at least 225 mm in front of the
stove and 150 mm each side.
If the hearth is constructed on timber, there must be a
clearance of at least 250 mm from the timber to the top
surface of the hearth.
See section J of the Building regulations.
2.3. Chimney
The chimney must comply with Current Building
Regulations. If in doubt, consult your Dealer or local
Building Inspector.
Existing flue :
-
The flue must be suitable for the installation of fuel
burning appliances, otherwise it must necessary to
install a tubing
-
The flue must be in good condition and must provide
sufficient draught (refer to technical details p. 3 ).
-
The flue must be clean. It should be swept to remove
soot and dislodge tar deposits.
-
The flue must be well insulated. If the flue inner wall
surfaces are cold, a good thermal draw is impossible
causing condensation problems (tar formation etc.) to
occur.
-
The flue must be watertight.
-
The chimney must have a constant cross section.
-
The flue must not be shared with other appliances.
-
The chimney must be at least 4.5 m (15 ft high).
-
In case of a flat roof or when the roof gradient is lower
than 15°, the stack must be 1,2 m (4 feet) high at least.
-
The capping must not restrain the draught.
4 Technical manual “986”
“Savoy” - ref. 134 08 05 Installation instructions
1 5 0
1 5 0
1 5 0
3 0 0
1 5 0
B
A
A
C
1 5 0
Figure 2 - Clearances