Foster HR120, LR120, HRB120, LRB120, HR140 Service Manual

...
Page 1
Undercounter &
Slimline Cabinet Range
HR/LR 120 HRB/LRB120
HR/LR 140 HR/LR 150 HR/LR 200 HR/LR 240
HR/LR 360
HR/LR 410
Page 2
Introduction 1 to 2
2. Controller and operation 3 to 4
3. Controller settings 4 to 5
4. Electrical connections 5 to 6
5. Technical data 7
6. Wiring Diagrams 8 to 9
PAGE
INTRODUCTION
CABINET DESCRIPTION
The cabinets are manufactured as a one piece foamed shell.
The condensing unit is located on the base of the cabinet.
The cabinets conform to ISO Climate Class 4. (320c with 40% RH)
Temperature is controlled by a LAE microprocessor control with digital temperature display.
The HR 120, LR 120, HRB 120, LRB 120, HR 200, LR 200, HR 240, LR 240, HR 360 and LR 360 refrigeration system is integral with an air-cooled condensing unit with the refrigerant distribution into the evaporator controlled by capillary.
The HR 140, LR140, HR 150, LR 150, HR 410 and LR 410 refrigeration system is integral with an air-cooled compressor and static condenser with the refrigerant distribution into the evaporator controlled by capillary.
The HR 120, LR 120, HRB 120, LRB 120, HR 200, LR 200, HR 240, LR 240, HR 360 and LR 360 are forced air cooling. The air is circulated through the evaporator, via the fan/s into the storage area.
The HR 140, HR 150 and HR 410 are forced air cooling. The air is drawn over the evaporator and through the fan/s blowing into the storage area. The LR 140, LR 150 and LR 410 have static freezer shelves with circulation in the storage compartment by natural convection. The HR 120, LR 120, HRB 120, LRB 120, HR 200, LR 200, HR 240, LR 240, HR 360 and LR 360 have a plastic vaporiser tray with the hot gas line inserted into it to attain vaporisation.
The HR 140, HR 150, HR 200, LR 200 and HR 410 condensate vaporisation is provided by a self contained condensate vaporiser tray attached to the top of the compressor.
The HR 120, HRB 120, HR 140, HR 150, HR 200, HR 240 and HR 360 are timed off cycle defrost.
The LR 120, LRB 120, LR 200, LR 240 and LR 360 have electric defrost set at 4 times per 24 hours.
The LR 140, LR 150 and LR 410 refrigeration is provided by static freezer shelves requiring manual defrost.
The doors are fitted with pivot hinges, stainless steel door handle and magnetic door gasket.
All models are fitted with roller castors to the rear and M8 adjustable levelling bolts to front.
On glass door models the interior light is fitted to the top of the storage area at the front. The on/off switch is incorporated in the light.
Nomenclature based on –
H = High Temperature. L = Low Temperature.
R = Refrigerator.
120/ 140/ 150/ 200/ 240/ 360/ 410 = Net Capacity (litres). F = Forced Air. S = Static Shelf. U = Undermount. G = Glass Door
1
Page 3
Model Ref HR 120 LR 120 HRB 120 LRB 120 HR 140 LR 140
Temperature
range
Capacity -
litres
Shelves
Internal
fittings
Refrigerant
External
Dimensions
Model Ref HR 150 LR 150 HR 200 LR 200 HR 240 LR 240
Temperature
range
Capacity -
litres
Shelves
Internal
fittings
Refrigerant
0
+1
c to + 40c
120 120
2 x nylon
coated
shelves
Fixed shelf
supports
300gms
R134a
H 896mm x W 441mm x
D 762mm
0
+3
c to + 50c
150 150 200 200 240 240
2 x nylon
coated
shelves
Fixed shelf
supports.
120 gms
R134a
-180c to -210c
2 x nylon
coated
shelves
Fixed shelf
supports
160gms
R404A
H 896mm x W 441mm x
D 762mm
-180c to -210c +30c to + 50c -180c to -210c
3
(fixed freezer
shelves)
Static
refrigerated
shelves
115 gms
R134a
0
+1
c to + 40c
120
2 x nylon
coated
shelves
Fixed shelf
supports
160gms
R134a
H 896mm x W 646mm x
D 562mm
2 x nylon
coated
shelves
Fixed shelf
supports.
190 gms
R134a
-180c to -210c
120 140 140
2 x nylon
coated
shelves
Fixed shelf
supports
300gms
R404A
H 896mm x W 646mm x
D 562mm
2 x nylon
coated
shelves
Fixed shelf
supports.
235 gms
R404A
0
+3
c to + 50c
2 x nylon
coated
shelves
Fixed shelf
supports.
115gms
R134a
H 830mm x W 605mm x
D 630mm
0
+1
c to + 40c
4 x nylon
coated
shelves
Fixed shelf
supports.
220 gms
R134a
-180c to -210c
2 x nylon
coated
shelves
Static
refrigerated
shelves
115gms
R134a
H 830mm x W 605mm x
D 630mm
-180c to -210c
4 x nylon
coated
shelves
Fixed shelf
supports.
320 gms
R404A
External
Dimensions
Model Ref HR 360 LR360 HR 410 LR 410
Temperature
range
Capacity -
litres
Shelves
Internal
fittings
Refrigerant
External
Dimensions
H 830mm x W 600mm x
D 652mm
+30c to + 50c -180c to -210c
360 360 410 410
4 x nylon
coated
shelves
Fixed shelf
supports.
360 gms
R134a
H 828mm x
W 1210mm x
D 750mm
H 830mm x W 600mm x
D 652mm
4 x nylon
coated
shelves
Fixed shelf
supports.
260 GMS
R404A
H 828mm x
W 1210mm x
D 750mm
H 828mm x W 681mm x
D 750mm
0
+3
c to + 50c
4 x nylon
coated
shelves
Fixed shelf
supports.
180 gms
R134a
H 1875mm x
W 600mm x
D 652mm
H 828mm x W 681mm x
D 750mm
-180c to -210c
6
(fixed freezer
shelves)
Static
refrigerated
shelves
200 gms
R134a
H 1875mm x
W 600mm x
D 652mm
H 896mm x W 868mm x
D 762mm
H 896mm x W 868mm x
D 762mm
2
Page 4
2. Controller and Operation.
BIT 20B11E and BIT 20B22E used upto 00-00-2005
The BIT 20B11E is fitted to the HR150, LR150, HR200, HR360, HR410 and LR410 (Foster part No. 00-554860). The BIT 20B22E is fitted to the LR200 and LR360 (Foster part No. 00-554166). The LAE BIT 12 RU front display fitted to both controllers (Foster part No. 00-554167).
They are a two piece controller, the Control Unit is fitted at the rear of the cabinet with the Display Unit fitted into the front top right hand side of the cabinet, interconnected by a ribbon cable. Defrost type for HR models is a timed off cycle. Defrost on the LR120, LRB120, LR 200, LR240 and LR360 is electric. To defrost the LR150 and LR410 switch the machine off and allow the ice to melt, once it is clear of ice dry the cabinet thoroughly before switching the machine back on. A manual defrost, for the HR models and the LR120, LRB120, LR 200, LR240 and LR360, can be initiated by pressing the red button on the control unit or by pressing the upward and downward arrows on the display simultaneously. During defrost the air temperature is displayed. One probe is fitted measuring air temperature and is used to control cabinet temperature. In the event of probe failure “E1” will be displayed. In the event of air probe failure on HR models the refrigeration system will be controlled by a timed sequence. The controller parameter setting cF is set at 00 which allows for the compressor to be on for 3 minute and off for 4 minutes. In the event of air probe failure on LR models the compressor will run continuously, the controller parameter setting cF is set at 1. On the LR120, LRB120, LR 200, LR240 and LR 360 an evaporator probe is fitted, in the event of probe failure “E2” will be displayed. If the evaporator probe fails defrost will be controlled on a timed basis.
Control Unit
Button 1
Button 3
Button 2
Display Unit
3
Page 5
2. Controller Operation
2.1 Check set point 1.
Press button 1

2.2 Increase set point

Press and hold button 1

Press button 2 until required temperature is displayed.

2.3 Decrease set point

Press and hold button 1
Press button 3 until required temperature is displayed.
2.4 Controller set up
Access to the controller is achieved by pressing in sequence: –
+ + And holding the keys in for a period of 4 seconds.
It is possible to scroll through the parameters by pressing or .
The value of a selected parameter is checked by pressing and may be
Altered by pressing or whilst still pressing .
Exit from set up occurs after 15 seconds if no button is pressed.
3. Controller Settings

3.1. BIT 20B 11E Controller settings for models below

HR120,140, 150,200,
Parameter Nmenonic Std. Setting

Temperature Set Point

Min. Set Point SL -3 0 -23
Max. Set Point Sh 12 10 -15
Hysteresis Hy 3 3 3
Compressor Min. Pause cr 3 4 4
Operation with T1 Fail cF 0 0 1
Defrost Frequency dF 6 4 0
Max. Defrost duration dt 20 10 1
Defrost Limit Temp dL 10 10 10
Defrost Mode dm 1 1 1
Drain Time dr 3 3 0
Display During Defrost th 10 0 0
Display Offset to 0 0 0
Display Slow Down
SP 3 3 -21
tS 3 0 0
4
360 & HR 410
Settings
LR140, 150 & LR410
Settings
Page 6
3.2. BIT 20 b22e Controller settings for models below.
Parameter Nmenonic

Temperature Set Point SP 3 -21

Min. Set Point SL -3 -23
Max. Set Point Sh 12 -15
Hysteresis Hy 3 3
Compressor Min. Pause cr 3 1
Operation with T1 Fail cF 0 1
Defrost Frequency dF 6 4
Max. Defrost duration dt 20 10
Defrost Limit Temp dL 10 10
Defrost Mode dm 1 1
Drain Time dr 3 3
Display During Defrost th 10 0
Display Offset to 0 0
Display Slow Down tS 3 0
4. Electrical connections
Std.
Setting
LR120, LRB120,
LR 200, LR240
and LR360
4.1 .BIT 20 B11E Controller. (Foster part No. 00-554860)
}
N3
OO
N2
OO
N1
POWER N L L
1
[ [
OL OL
O2 O3
O O O
Power Supply N = Neutral Power Supply L = Live L - Power in plus evaporator fan and light (if fitted) live feed. N – Neutral in. L1 - Compressor feed. L2 and L3 not used. N1- Compressor, evaporator fan and light (if fitted) neutral.
5
Page 7
N2 and N3 not used.
}
4.2 BIT 20B22E Controller. (Foster part No. 00-554166)
[ [ [
N3
N2
POWER
N1
Power Supply N = Neutral Power Supply L = Live L1 - Compressor feed. L2 – Evaporator fans and mullion heater/s. L3 – Defrost heater N1- Compressor. N2 - Evaporator fans and mullion heater.
N3 –Defrost heater.
N L L L L 1 2 3
6
Page 8
5. Technical Specification
Model Gas
HR120 R134a 300 grms GD40MBD 3mts x 042 Timed Off Cycle 357w 192w 230/50/01 165w 1.3 10
LR 120 R404A 160 grms ML90FB 3mts x 042 Electric 585w 241w 230/50/01 344w 2.4 10
HRB 120 R134a 300 grms GD40MBD 3mts x 042 Timed Off Cycle 357w 192w 230/50/01 165w 1.3 10
LRB 120 R404A 160grms ML90FB 3mts x 042 Electric 585w 241w 230/50/01 344w 2.4 10
HR 140 R134a 180 grms GD30MBa
HR140G R134a 200grms GD40MBa
LR140 R134a 200 grms GL50AA
HR 150 R134a 120 grms GD30Mba
HR 150G R134a 115 grms GD40MB
LR 150 R134a 115 grms GL 50AA
HR 200 R134a 190 grms GD40MBD 3mts x 042 Timed Off Cycle 399w 192w 230/50/1 207w 1.4 10
Gas
Charge
Compressor
Capillary Defrost Type
Part of evaporator
assembly
Part of evaporator
assembly
Part of evaporator
assembly
Part of evaporator
assembly
Part of evaporator
assembly
Part of evaporator
assembly
Timed Off Cycle 265w 116w 230/50/1 137w 0.9 10
Timed Off Cycle 355w 153w 230/50/1 202w 1.3 10
Manual Defrost 197w 63w 230/50/1 134w 0.9 10
Timed Off Cycle 265w 116w 230/50/1 137w 0.9 10
Timed Off Cycle 355w 153w 230/50/1 202w 1.3 10
Manual Defrost 197w 63w 230/50/1 134w 0.9 10
Heat
Output
Extraction
Rate
Voltage
Power Consumption
Watts Amps
Fuse
Rating
Amps
HR 200G R134a 190 grms GD40MBD 3mts x 042 Timed Off Cycle 399w 192w 230/50/1 207w 1.4 10
LR 200 R404A 235 grms ML90FB 3mts x 042 Electric 638w 241w 230/50/1 397w 2.6 10
HR 240 R134a 220 grms GL60TB 3mts x 042 Timed Off Cycle 514w 310w 230/50/1 204w 1.5 10
LR 240 R404a 320 grms ML90FB 3mts x 042 Electric 613.5w 241w 230/50/1 372.5w 2.6 10
HR 360 R134a 360 grms AEZ4425Y 3mts x 042 Timed Off Cycle 603 324w 230/50/1 279w 1.9 10
HR 360G R134a 360 grms AEZ4425Y 3mts x 042 Timed Off Cycle 603 324w 230/50/1 279w 1.9 10
LR360 R404a 260 grms CAE2417Z 3mts x 042 Electric 685 243w 230/50/1 442w 2.5 10
HR 410 R 134A 180grms GL60TB
HR 410G R134A 200grms GL80AA
LR 410 R 134A 200 grms GL 90AA
Part of evaporator
assembly
Part of evaporator
assembly
Part of evaporator
assembly
Timed Off Cycle 451w 233w 230/50/1 218 1.3 10
Timed Off Cycle 546w 285w 230/50/1 261 1.5 10
Manual Defrost 575w 206w 230/50/1 369 2.8 10
7
Page 9
6. High Temperature Controller Wiring Diagram
8
Page 10
6. Low Temperature Controller Wiring Diagram
9
Page 11
10
Page 12
Foster Refrigerator Oldmedow Road Kings Lynn Norfolk PE30 4JU
Tel: 01553 691122 Fax: 01553 691447 Website: www.fosterrefrigerator.co.uk Email: sales@foster-uk.com
a Division of ‘ITW (UK) Ltd’
UNDCOUNT/CAB/SM 05/06
11