The cabinets are manufactured as a one piece foamed shell.
The condensing unit is located on the base of the cabinet.
The cabinets conform to ISO Climate Class 4. (320c with 40% RH)
Temperature is controlled by a LAE microprocessor control with digital temperature display.
The HR 120, LR 120, HRB 120, LRB 120, HR 200, LR 200, HR 240, LR 240, HR 360 and LR 360 refrigeration system is
integral with an air-cooled condensing unit with the refrigerant distribution into the evaporator controlled by capillary.
The HR 140, LR140, HR 150, LR 150, HR 410 and LR 410 refrigeration system is integral with an air-cooled
compressor and static condenser with the refrigerant distribution into the evaporator controlled by capillary.
The HR 120, LR 120, HRB 120, LRB 120, HR 200, LR 200, HR 240, LR 240, HR 360 and LR 360 are forced air cooling.
The air is circulated through the evaporator, via the fan/s into the storage area.
The HR 140, HR 150 and HR 410 are forced air cooling. The air is drawn over the evaporator and through the fan/s
blowing into the storage area.
The LR 140, LR 150 and LR 410 have static freezer shelves with circulation in the storage compartment by natural
convection.
The HR 120, LR 120, HRB 120, LRB 120, HR 200, LR 200, HR 240, LR 240, HR 360 and LR 360 have a plastic
vaporiser tray with the hot gas line inserted into it to attain vaporisation.
The HR 140, HR 150, HR 200, LR 200 and HR 410 condensate vaporisation is provided by a self contained condensate
vaporiser tray attached to the top of the compressor.
The HR 120, HRB 120,HR 140, HR 150,HR 200, HR 240 and HR 360 are timed off cycle defrost.
The LR 120, LRB 120, LR 200, LR 240 and LR 360 have electric defrost set at 4 times per 24 hours.
The LR 140, LR 150 and LR 410 refrigeration is provided by static freezer shelves requiring manual defrost.
The doors are fitted with pivot hinges, stainless steel door handle and magnetic door gasket.
All models are fitted with roller castors to the rear and M8 adjustable levelling bolts to front.
On glass door models the interior light is fitted to the top of the storage area at the front. The on/off switch is
incorporated in the light.
Nomenclature based on –
H = High Temperature.
L = Low Temperature.
R = Refrigerator.
120/ 140/ 150/ 200/ 240/ 360/ 410 = Net Capacity (litres).
F = Forced Air.
S = Static Shelf.
U = Undermount.
G = Glass Door
1
Page 3
Model RefHR 120LR 120HRB 120LRB 120HR 140LR 140
Temperature
range
Capacity -
litres
Shelves
Internal
fittings
Refrigerant
External
Dimensions
Model RefHR 150LR 150HR 200LR 200HR 240LR 240
Temperature
range
Capacity -
litres
Shelves
Internal
fittings
Refrigerant
0
+1
c to + 40c
120 120
2 x nylon
coated
shelves
Fixed shelf
supports
300gms
R134a
H 896mm x
W 441mm x
D 762mm
0
+3
c to + 50c
150150200200240240
2 x nylon
coated
shelves
Fixed shelf
supports.
120 gms
R134a
-180c to -210c
2 x nylon
coated
shelves
Fixed shelf
supports
160gms
R404A
H 896mm x
W 441mm x
D 762mm
-180c to -210c+30c to + 50c-180c to -210c
3
(fixed freezer
shelves)
Static
refrigerated
shelves
115 gms
R134a
0
+1
c to + 40c
120
2 x nylon
coated
shelves
Fixed shelf
supports
160gms
R134a
H 896mm x
W 646mm x
D 562mm
2 x nylon
coated
shelves
Fixed shelf
supports.
190 gms
R134a
-180c to -210c
120140140
2 x nylon
coated
shelves
Fixed shelf
supports
300gms
R404A
H 896mm x
W 646mm x
D 562mm
2 x nylon
coated
shelves
Fixed shelf
supports.
235 gms
R404A
0
+3
c to + 50c
2 x nylon
coated
shelves
Fixed shelf
supports.
115gms
R134a
H 830mm x
W 605mm x
D 630mm
0
+1
c to + 40c
4 x nylon
coated
shelves
Fixed shelf
supports.
220 gms
R134a
-180c to -210c
2 x nylon
coated
shelves
Static
refrigerated
shelves
115gms
R134a
H 830mm x
W 605mm x
D 630mm
-180c to -210c
4 x nylon
coated
shelves
Fixed shelf
supports.
320 gms
R404A
External
Dimensions
Model RefHR 360LR360HR 410LR 410
Temperature
range
Capacity -
litres
Shelves
Internal
fittings
Refrigerant
External
Dimensions
H 830mm x
W 600mm x
D 652mm
+30c to + 50c-180c to -210c
360360410410
4 x nylon
coated
shelves
Fixed shelf
supports.
360 gms
R134a
H 828mm x
W 1210mm x
D 750mm
H 830mm x
W 600mm x
D 652mm
4 x nylon
coated
shelves
Fixed shelf
supports.
260 GMS
R404A
H 828mm x
W 1210mm x
D 750mm
H 828mm x
W 681mm x
D 750mm
0
+3
c to + 50c
4 x nylon
coated
shelves
Fixed shelf
supports.
180 gms
R134a
H 1875mm x
W 600mm x
D 652mm
H 828mm x
W 681mm x
D 750mm
-180c to -210c
6
(fixed freezer
shelves)
Static
refrigerated
shelves
200 gms
R134a
H 1875mm x
W 600mm x
D 652mm
H 896mm x
W 868mm x
D 762mm
H 896mm x
W 868mm x
D 762mm
2
Page 4
2. Controller and Operation.
BIT 20B11E and BIT 20B22E used upto 00-00-2005
The BIT 20B11E is fitted to the HR150, LR150, HR200, HR360, HR410 and LR410 (Foster part No. 00-554860).
The BIT 20B22E is fitted to the LR200 and LR360 (Foster part No. 00-554166).
The LAE BIT 12 RU front display fitted to both controllers (Foster part No. 00-554167).
They are a two piece controller, the Control Unit is fitted at the rear of the cabinet with the Display Unit fitted into
the front top right hand side of the cabinet, interconnected by a ribbon cable.
Defrost type for HR models is a timed off cycle.
Defrost on the LR120, LRB120, LR 200, LR240 and LR360 is electric.
To defrost the LR150 and LR410 switch the machine off and allow the ice to melt, once it is clear of ice dry the
cabinet thoroughly before switching the machine back on.
A manual defrost, for the HR models and the LR120, LRB120, LR 200, LR240 and LR360, can be initiated by
pressing the red button on the control unit or by pressing the upward and downward arrows on the display
simultaneously. During defrost the air temperature is displayed.
One probe is fitted measuring air temperature and is used to control cabinet temperature.
In the event of probe failure “E1” will be displayed.
In the event of air probe failure on HR models the refrigeration system will be controlled by a timed sequence. The
controller parameter setting cF is set at 00 which allows for the compressor to be on for 3 minute and off for 4
minutes.
In the event of air probe failure on LR models the compressor will run continuously, the controller parameter setting
cF is set at 1.
On the LR120, LRB120, LR 200, LR240 and LR 360 an evaporator probe is fitted, in the event of probe failure “E2”
will be displayed. If the evaporator probe fails defrost will be controlled on a timed basis.
Control Unit
Button 1
Button 3
Button 2
Display Unit
3
Page 5
2. Controller Operation
2.1 Check set point 1.
Press button 1
2.2 Increase set point
Press and hold button 1
Press button 2until required temperature is displayed.
2.3 Decrease set point
Press and hold button 1
Press button 3 until required temperature is displayed.
2.4 Controller set up
Access to the controller is achieved by pressing in sequence: –
+ + And holding the keys in for a period of 4 seconds.
It is possible to scroll through the parameters by pressing or.
The value of a selected parameter is checked by pressingand may be
Altered by pressingorwhilst still pressing.
Exit from set up occurs after 15 seconds if no button is pressed.
3. Controller Settings
3.1. BIT 20B 11E Controller settings for models below
HR120,140, 150,200,
ParameterNmenonicStd. Setting
Temperature Set Point
Min. Set PointSL-30-23
Max. Set PointSh1210-15
HysteresisHy333
Compressor Min. Pausecr344
Operation with T1 FailcF001
Defrost FrequencydF640
Max. Defrost durationdt20101
Defrost Limit TempdL101010
Defrost Modedm111
Drain Timedr330
Display During Defrostth1000
Display Offsetto000
Display Slow Down
SP33-21
tS300
4
360 & HR 410
Settings
LR140, 150 & LR410
Settings
Page 6
3.2. BIT 20 b22e Controller settings for models below.
ParameterNmenonic
Temperature Set PointSP3-21
Min. Set PointSL-3-23
Max. Set PointSh12-15
HysteresisHy33
Compressor Min. Pausecr31
Operation with T1 FailcF01
Defrost FrequencydF64
Max. Defrost durationdt2010
Defrost Limit TempdL1010
Defrost Modedm11
Drain Timedr33
Display During Defrostth100
Display Offsetto00
Display Slow DowntS30
4. Electrical connections
Std.
Setting
LR120, LRB120,
LR 200, LR240
and LR360
4.1 .BIT 20 B11E Controller. (Foster part No. 00-554860)
}
N3
OO
N2
OO
N1
POWER
N L L
1
[[
OL OL
O2 O3
O
O
O
Power Supply N = Neutral
Power Supply L = Live
L - Power in plus evaporator fan and light (if fitted) live feed.
N – Neutral in.
L1 - Compressor feed.
L2 and L3 not used.
N1- Compressor, evaporator fan and light (if fitted) neutral.
5
Page 7
N2 and N3 not used.
}
4.2 BIT 20B22E Controller. (Foster part No. 00-554166)
[[[
N3
N2
POWER
N1
Power Supply N = Neutral
Power Supply L = Live
L1 - Compressor feed.
L2 – Evaporator fans and mullion heater/s.
L3 – Defrost heater
N1- Compressor.
N2 - Evaporator fans and mullion heater.
N3 –Defrost heater.
N L L L L
1 2 3
6
Page 8
5. Technical Specification
ModelGas
HR120R134a300 grmsGD40MBD3mts x 042Timed Off Cycle357w192w230/50/01165w1.310
LR 120R404A160 grmsML90FB3mts x 042Electric585w241w230/50/01344w2.410
HRB 120R134a300 grmsGD40MBD3mts x 042Timed Off Cycle357w192w230/50/01165w1.310
LRB 120R404A160grmsML90FB3mts x 042Electric585w241w230/50/01344w2.410
HR 140R134a180 grmsGD30MBa
HR140GR134a200grmsGD40MBa
LR140R134a200 grmsGL50AA
HR 150R134a120 grmsGD30Mba
HR 150GR134a115 grmsGD40MB
LR 150R134a115 grmsGL 50AA
HR 200R134a190 grmsGD40MBD3mts x 042Timed Off Cycle399w192w230/50/1207w1.410
Gas
Charge
Compressor
CapillaryDefrost Type
Part of evaporator
assembly
Part of evaporator
assembly
Part of evaporator
assembly
Part of evaporator
assembly
Part of evaporator
assembly
Part of evaporator
assembly
Timed Off Cycle265w116w230/50/1137w0.910
Timed Off Cycle355w153w230/50/1202w1.310
Manual Defrost197w63w230/50/1134w0.910
Timed Off Cycle265w116w230/50/1137w0.910
Timed Off Cycle355w153w230/50/1202w1.310
Manual Defrost197w63w230/50/1134w0.910
Heat
Output
Extraction
Rate
Voltage
Power Consumption
WattsAmps
Fuse
Rating
Amps
HR 200GR134a190 grmsGD40MBD3mts x 042Timed Off Cycle399w192w230/50/1207w1.410
LR 200R404A235 grmsML90FB3mts x 042Electric638w241w230/50/1397w2.610
HR 240R134a 220 grmsGL60TB3mts x 042Timed Off Cycle514w310w230/50/1204w1.510
LR 240R404a 320 grmsML90FB3mts x 042Electric613.5w241w230/50/1372.5w2.610
HR 360R134a 360 grmsAEZ4425Y3mts x 042Timed Off Cycle603324w230/50/1279w1.910
HR 360GR134a 360 grmsAEZ4425Y3mts x 042Timed Off Cycle603324w230/50/1279w1.910
LR360R404a 260 grmsCAE2417Z3mts x 042Electric685243w230/50/1442w2.510