make sure that the product supplied is
integral and complete in all its parts. If
this is not the case, please contact the
Dealer who sold the appliance.
– The appliance must be used as intend-
ed by
any damage caused to persons, animals or things, improper installation,
adjustment, maintenance and improper use of the appliance.
– In the event of water leaks, disconnect
the appliance from the mains power supply, close the water mains and
promptl
fied personnel.
– Periodically check that the operating
pressure of the water heating system
when cold is
case, increase the pressure or contact
professionally qualified personnel.
– If the appliance is not used for a long
period of time, at least one of the following operations must be carried out:
-
-
Sime
who is not responsible for
y inform professionally quali-
1-1.2 bar
set the main system switch to "OFF";
close the gas and water valves for the
water heating system.
. If this is not the
m
WARNINGS
–
It is recommended that all operators
read this manual carefully in order to
use the appliance in a safe and rational
manner.
–
This manual
appliance. It must therefore be kept
for future reference and must always
accompany the appliance in the event
the appliance is transferred or sold to
another Owner or User or is installed
on another system.
–
Installation and maintenance
appliance must be carried out by a
qualified company or by a professionally qualified technician, or authorised person, in accordance with the
instructions contained in the manual.
The company or technician will, at the
end of installation operations, issue a
statement of compliance with national and local Technical Standards and
Legislation in force.
is an integral part of the
of this
– In order to ensure optimal appliance
operations
maintenance and checks are carried
out
ONCE A YEAR
Sime
recommends that
.
2
Page 3
RESTRICTIONS
d
IT IS FORBIDDEN
– To allow children under the age of 8 to
use the appliance. The appliance can
be used by children no younger than
8 years old, by people with physical
or cognitive disabilities, and by people
lacking experience or the necessary
knowledge, provided that they are supervised or have been instructed on
how to use the appliance safely and
that they understand the risks associated with it.
– To allow children to play with the ap-
pliance.
–
To allow unsupervised children to per-
form user maintenance and cleaning.
–
Do not use electrical devices or appli-
ances such as switches, electrical appliances etc if you can smell fuel. If this
should happen:
-
open the doors and windows to air the
room;
-
close the gas isolation device;
-
promptly call for professional assistance.
– Do not touch the appliance with bare
feet or with any wet part of the body.
d
IT IS FORBIDDEN
– Do not block the condensate drain (if
present).
– Do not pull, detach or twist the electri-
cal cables coming out of the appliance
ev
en if the appliance is disconnected
from the mains power supply.
– Do not expose the boiler to atmos-
pheric agents. These boilers can also
be ins
as, as per EN 15502, with a maximum
ambient temperature of 60 °C and a
minimum ambient temperature of - 5
°C. It is recommended that the boiler
is installed below weathered roofs, on
the balcony or in a protected niche, to
protect it from exposure to weathering
agents (rain, hail and snow). The boiler
is equipped as standard with an antifreeze function.
– Do not block or reduce the size of the
ventilation openings of the room where
the appliance is installed, if present.
– Remove the mains power and gas sup
ply from the appliance if the external
temper
(risk of freezing).
talled in partially covered are-
-
ature could fall below ZERO
– Do not carry out any technical inter-
vention or cleaning operation before
having disc
from the mains power by setting the
main switch to "OFF", and closing the
gas supply.
– Do not modify the safety or adjustment
devices without authorization and instructions from the manufacturer.
onnected the appliance
– Do not leave containers with flamma-
ble substances in the room where the
appliance is ins
– Do not leave packaging material
around since it could be dangerous.
Therefore dispose of it as prescribed
by legislation in force.
talled.
3
Page 4
RANGE
1312
MODELCODE
UNIQA.REVOLUTION8110438
COMPLIANCE
Our company declares that
with the following directives:
– Gas Appliances EU Regulation 2016/426
– Boiler Efficiency Directive 92/42/EEC
– Low Voltage Directive 2014/35/EU
– Electromagnetic Compatibility Directive 2014/30/EU
– Ecodesign Directive 2009/125/EC
– Regulation (EU) No. 813/2013 - 811/2013
– Energy Labeling Directive 2010/30/CE
Please refer to the technical data plate for the serial number
and year of manufacture.
UNIQA.REVOLUTION
boilers comply
MANUAL STRUCTURE
This manual is organized as follows.
USER INSTRUCTIONS
TABLE OF CONTENTS 5
DESCRIPTION OF THE APPLIANCE
TABLE OF CONTENTS 11
INSTALLATION AND SERVICING
INSTRUCTIONS
TABLE OF CONTENTS 21
SYMBOLS
a
f
d
m
WARNING
To indicate actions which, if not carried out correctly,
can result in injury of a general nature or may damage
or cause the appliance to malfunction; these actions
therefore require particular caution and adequate
preparation.
ELECTRICAL HAZARD
To indicate actions which, if not carried out correctly, could lead to injury of an electrical nature; these
actions theref
quate preparation.
IT IS FORBIDDEN
To indicate actions which MUST NOT BE carried out.
CAUTION
To indicate particularly important and useful information.
ore require particular caution and ade-
CHECKLIST
a
WARNING
Before installing and starting up the boiler, make
sure you have done the following:
– handle the boiler in an upright position (see the
“Handling” section)
– make the holes for the wall fastening using an
assembly template and spirit level to avoid any
inaccuracies (see the section “Boiler installation”)
fix the boiler in place, using the cushioning
–
washers supplied (see the section “Boiler installation”)
install a Y-filter (not supplied) on the system
–
return as shown in Fig. 11 in the section “Main water circuit”
– with separate ducts, use the diaphragm sup
plied in kit 8089932, inserting it on the outlet
al
duct, c
folded upwards, as indicated in Fig. 25 in the
section “Smoke outlet and combustion air inlet”
check the pressure readings at the nozzle and
–
2
the CO
bration procedure” and “Checking the CO
with the chimney sweep function”).
values (see sections “Automatic cali-
culating the number of sections to be
-
-
-
-
2
m
4
CAUTION
Please always adhere to the instructions in the manual, as well as current installation regulations.
Page 5
TABLE OF CONTENTS
USER INSTRUCTIONS
1 USING THE BOILER UNIQA.REVOLUTION 6
1.1 Control panel ...................................6
If pressed once or more than once for at least 1 second
y
during normal operation, this button allows the user to
change the boiler operating mode in a cyclical sequence
(Stand-by – Summer – Winter). If the boiler is experienc
ing a fault which can be reset, it allows boiler operation
to be unbl
During normal operation, pressing the button displays
r
the domestic hot water set point which can be between
10 and 60°C. In "parameter setting", the user can scroll
through the parameter index (decreasing) by pressing
this button.
During normal operation, pressing the button dis-
t
plays the heating set point which can be between 20
and 80°C. In "paramet
through the parameter index (increasing) by pressing
this button.
During normal operation, pressing this button allows the
<
user to reduce the heating or DHW set point on the basis of the selection made previously. If there is a Remote
Contr
button, the user can modify the incline of the climatic
curve (decreasing it) by pressing the button (
rameter setting/display", the user can modify the parameter setting or value (decreasing) by pressing this
butt
During normal operation, pressing this button allows the
>
user to increase the heating or DHW set point on the basis of the selection made previously. If there is a Remote
Contr
button, the user can modify the incline of the climatic
curve (increasing it) by pressing the button (
rameter setting/display", the user can modify the parameter setting or value (increasing) by pressing this
butt
ocked.
ol (Open Therm), aft
on.
ol (Open Therm), aft
on.
er setting", the user can scroll
er having selected the heating
-
). In "pa-
er having selected the heating
+
). In "pa-
Programming connector cover plug.
c
NOTE:
pressing any one of these buttons for more than 30 seconds generates a fault on the display without preventing boiler
operation. The warning disappear
restored.
2
DISPLAY
“SUMMER”
l
erating in "Summer" mode or if only the domestic hot
water mode is enabl
“WINTER”
n
ating in "Winter" mode or if both the domestic hot water
and heating modes are enabl
With the remote control, if no operating modes have
been enabled both symbols
“RESET REQUIRED”
d
having repaired the fault, normal boiler operation can be
restored by pressing the button
“DOMESTIC HOT WATER”
r
DHW request. It flashes during the selection of the domestic hot water set point.
“HEATING”
t
ation. It flashes during the selection of the heating set
point.
-
“BLOCK” DUE TO NO FLAME
f
“FLAME PRESENCE"
F
“POWER LEVEL"
v
the boiler is operating.
“PARAMETER"
p
parameter setting/display, or "info" or "counter", or in
"activated alarms" (history).
“ALARM"
A
number specifies the cause which generated the alarm.
“HEATING SYSTEM PRESSURE"
a
pressure.
“CHIMNEY SWEEP"
z
sweep function" has been activated.
"ECO", ALTERNATIVE ENERGY SOURCES
E
indicates that there is a solar system available.
Flashing
B
On
. Compressor operating.
"MAINTENANCE REQUEST"
c
perform maintenance on the boiler.
. This symbol appears when the boiler is op-
. This symbol appears when the boiler is oper-
. This symbol lights up during heating oper-
. This indicates that a fault has occurred. The
. Waiting time for the compressor to start.
. This indicates the power level at which
. This indicates that the user may be in
s when normal conditions are
ed via the remote control.
ed via the remote control.
and n will be off.
l
. The message indicates that after
.
y
. This symbol is present during a
.
.
. Display of heating system
. This indicates that the "chimney
. Where active, it
. If active, it shows it is time to
Fixed
6
Page 7
1.2 Preliminary checks
1
a
WARNING
– Should it be necessary to access the areas in the
bottom part of the appliance, make sure that the
system components and pipes are not hot (risk of
burning).
– Before replenishing the heating system, put on pro
tective gloves.
– select the "SUMMER" l operating mode by pressing and
holding the
delivery sensor detected at that moment will appear on the
display
-
button for at least 1 second. the value of the
y
Commis
ried out by professionally qualified technicians, after which the
boiler c
for the user to start the appliance autonomously without involv
ing a technician: for example, after a holiday.
First of all check that the gas isolation and water system valves
are open.
sioning of the
an operate automatically. It may, however, be necessary
UNIQA.REVOLUTION
boiler must be car-
1.3 Ignition
After having carried out the preliminary checks, perform the
following to start the boiler:
– set the main system switch to "ON" in order for the display to
show the pressure level in the system during refilling
make sure that the operating mode is set to "Stand-by";
–
not the case, press the button
been selected
ON
– on the display (1), check that the heating system pressure
when cold is
valve (2) and restore the heating system pressure until the
display (1) shows a reading of
– close the filling valve (2)
1-1.2 bar
. If this is not the case, open the filling
until "Stand-by" mode has
y
1-1.2 bar
if this is
Fig. 2
– open one or more than one hot water tap. The boiler will work
at maximum power until the taps are closed.
Once the boiler has been commissioned in "SUMMER mode"l
"WINTER mode"
button
temperature detected at that moment will appear on the display. In this case it is necessary to adjust the air thermostat/s to
the r
stat, check that this is "active" and adjusted.
for at least 1 second. The value of the delivery water
y
equir
ed temperature or if the system has a chrono-thermo-
can be selected by pressing and holding the
n
1.4 Adjusting the heating temperature
If the heating temperature is to be increased or decreased,
press the button
sired temperature is reached. The temperature can be set to
between 20 and 80°C.
followed by the buttons > or < until the de-
t
1.5 Adjusting the domestic hot water temperature
If the domestic hot water temperature is to be increased or decreased, press the button
the desired temperature is reached. The temperature can be set
2
Fig. 3
to between 10 and 60°C.
followed by the buttons > or < until
r
7
Page 8
1.6 Fault / malfunction codes
OFF
OFF
If a fault/malfunction is detected during boiler operation, the
"ALL"
message
code.
If you see alarm
– on the display (1), check that the heating system pressure
when cold is
valve (2) and restore the heating system pressure until the
display (1) shows a reading of
– close the filling valve (2)
1
will appear on the display followed by the fault
“02”
(low water pressure in the system):
1-1.2 bar
. If this is not the case, open the filling
1-1.2 bar
2 SHUTDOWN
2.1 Temporary shutdown
If the user wishes to interrupt boiler operation, press and hold
the button
mode"
n
"- -"
will appear on the display.
for at least one second, once if in "WINTER
y
or twice if in "SUMMER mode" l.
2
If you see alarm
mostat intervention):
press and hold the button
–
check whether normal operating conditions are restored.
If this operation is not successful,
be made, therefore:
– close the gas isolation valve
– set the main system switch to "OFF"
– contact the Qualified Technical Personnel.
“06”
(no flame detected) and
for more than 3 seconds and
y
ONLY ONE MORE ATTEMPT
“07”
(safety ther-
Fig. 4
can
f
If the user is away temporarily, for a weekend, short trip etc and
if the outside temperature is at ZERO:
– press and hold the button
– set the main system switch to "OFF"
– close the gas valve.
m
ELECTRICAL HAZARD
The boiler will still be powered.
once if in "WINTER mode" n
y
or twice if in "SUMMER mode"
by
CAUTION
If the outside temperature might fall below ZERO,
since the appliance is equipped with an "antifreeze
function"
– ONLY PUT THE BOILER INTO STAND-BY
– leave the main system switch set to "ON" (boiler is
powered)
– leave the gas valve open.
to put the boiler into stand-
l
Fig. 6
m
8
Fig. 5
CAUTION
Should you see an alarm not described here, contact a
qualified technical professional
.
Page 9
2.2 Shutting down for long periods
OFF
If the boiler is to be left unused for a long period, the following
operations need to be carried out:
– press and hold the button
"WINTER mode"
the boiler into stand-by
or twice if in "SUMMER mode" l to put
n
for at least 1 second, once if in
y
"- -"
will appear on the display
3 MAINTENANCE
3.1 Adjustments
For the appliance to operate correctly and efficiently it is recommended that the User calls upon the services of a Professionally
Qualified Technician t
o carry out
ANNUAL
maintenance.
– set the main system switch to "OFF"
Fig. 7
– close the gas valve
– close the heating and domestic hot water isolation valves
– drain the heating and domestic hot water system if there is
the risk of freezing.
m
CAUTION
Contact the Qualified Technical Personnel if the procedure described above cannot be easily carried out.
m
CAUTION
Maintenance interventions must ONLY be carried out
by professionally qualified personnel who will follow
the indications provided in the INSTALLATION AND
MAINTENANCE MANUAL.
3.2 External cleaning
a
3.2.1 Cleaning the cladding
When cleaning the cladding, use a cloth dampened with soap
and water or alcohol for stubborn marks.
d
WARNING
– Should it be necessary to access the areas in the
bottom part of the appliance, make sure that the
system components and pipes are not hot (risk of
burning).
– Before performing any maintenance, put on protec
tive gloves.
IT IS FORBIDDEN
to use abrasive products.
4 DISPOSAL
-
4.1 Disposal of the equipment (European Directive 2012/19/EU)
Boilers and electrical and electronic appliances from private households must not be disposed of as unsorted municipal waste at the
e. Ins
tead, they must be taken
d
end of their lif
to specific return and collection facilities, as
per Directive 2012/19/EU and Italian Legisla
tive Decree 49/2014. For more information on
authorised c
your local council or retailer. Individual coun
tries may also define specific rules on how to
handle electrical and electronic waste. Before
disposing of your appliance, please check the
rules in force in your country.
low-NOx, wall-mounted boilers which
heating and domestic hot water production. The main elements
choices made by
– the low NOx burner combined with a copper heat exchanger,
which operates at the same time as the heat pump, for space
heating, and a rapid heat exchanger for domestic hot water
(DHW) production
– a “type C” combustion chamber, sealed off from the environ
ment in which the boiler is installed
– the microprocessor electronic control board, which makes
the heating and domestic hot water production system easier
to manage. The appliance has just one heating request input,
which ambient thermostats or a remote control can be con
nected to. In the latter case, the boiler temperature varies on
the basis of the e
lected optimal climatic curve. This provides significant energy
os
t savings.
and c
Other special features of the
– the anti-freeze function which activates automatically if the
temperature of the water inside the boiler falls below the
threshold of the value set at parameter "PAR 10" and , if there
is an external sensor, if the external temperature falls below
the threshold of the value set at parameter "PAR 11"
– the anti-blocking function of the pump and diverter valve, this
activates automatically every 24 hours if no request for heat
has been made
– domestic hot water comfort function which allows the time
necessary for the hot water to become available to be reduced
and ensures that the temperature is stable
– screen display of the operating and self-diagnostic parame
ters with error code display when the fault occurs. This makes
repair int
erventions easier and allows appliance operation to
be restored correctly.
are high-performing, latest-generation,
Sime
has produced for
Sime
for the
UNIQA.REVOLUTION
xt
ernal temperature, according to the se-
UNIQA.REVOLUTION
boilers are:
boilers are:
5.3 Identification
The
UNIQA.REVOLUTION
1 Packaging label:
ing and provides a code, the serial number of the boiler and
the bar code
2 Energy Efficiency Label:
the packaging to notify the User of the level of energy savings and reduced environmental pollution produced by the
applianc
-
3 Technical Data Plate:
the boiler and provides the technical specification, appliance
performance and any other information required by law.
-
2
III
A
A
A
B
C
D
E
F
G
2015811/2013
-
3
e
++
A
+
B
C
D
E
F
G
kW
dB
boilers can be identified by means of:
this is located on the outside of the packag-
this is positioned on the outside of
this is located inside the front panel of
1
2
5.2 Check and safety devices
The
UNIQA.REVOLUTION
check and safety devices:
– thermal safety sensor 100°C
– 3 bar relief valve
– heating water pressure transducer
– delivery sensor
– DHW sensor
– refrigerant gas high-pressure pressure switch
– air evaporator inlet probe.
d
IT IS FORBIDDEN
to commission the appliance with safety devices which
do not work or which have been tampered with.
a
WARNING
Safety device may only be replaced by professional
qualified personnel using
boilers are equipped with the following
Sime
original spare parts.
3
Fig. 8
12
Page 13
5.3.1 Technical Data Plate
SERIAL NUMBER
YEAR OF MANUFACTURE
MAX HEAT INPUT
MAX USEFUL OUTPUT
MAX OPERATING PRESSURE
NAME
CODE
N° PIN
CE MARKING
WATER CONTENT IN BOILER
MIN HEAT INPUT
MIN USEFUL INPUT
MAX OPERATING TEMPERATURE
D.H.W. CONTENT
MAX HEAT INPUT
MAX OPERATING PRESSURE
FLOW RATE
MAXIMUM ABSORBED POWER
COUNTRY OF INTENDEDINSTALLTION
m
ELECTRICAL SUPPLY
APPLIANCE CATEGORY
GAS CHANGE
BOX TO BE MARKED
IF THE GAS IS CHANGED
CAUTION
Tampering with, removing or failing to display the identification plate or carrying out any other operation which does not
allow safe identification of the product or which may hinder installation and maintenance operations.
MIN HEAT INPUT
MAX D.H.W. TEMPERATURE
ELECTRICAL PROTECTION DEGREE
NOx CLASS
GAS COUNCIL NUMBER CODE (UK)
WRAS CERTIFICATION (UK)
APPLIANCE CLASSIFICATION
TYPE OF GAS
SUPPLY PRESSURE
Fig. 9
13
Page 14
5.4 Structure
262524
1
27
22
2
23
3
21
4
5
6
7
20
19
18
1
Fan
2
Expansion vessel
3
Combustion chamber
4
Dual sensor (thermal safety/
delivery)
5
Compressor
6
Diverter valve
7
System filling unit
8
Domestic hot water sensor
9
Control panel
10
Domestic hot water heat
exchanger
11
Gas valve
12
Domestic water filter and flow
regulator
13
System relief valve
8
17
9
1011
16
14
Boiler drain
15
System pump
16
Water pressure transducer
17
Return probe
18
Automatic bleed valve
19
Water/gas capacitor
20
Burner
21
Ignition/detection electrode
22
Primary heat exchanger
23
Air evaporator
24
Inspection cover
25
Air inlet
26
Smoke outlet
27
Air inlet probe (SIA) housing
13
12
15
14
Fig. 10
14
Page 15
5.5 Technical features
DESCRIPTION
UNIQA.REVOLUTION
CERTIFICATIONS
Country of intended installationIT – EN – ES
FuelG20 - G31
PIN number1312CT6328
CategoryII2H3+
Appliance classificationB32 - C10 - C12 - C12X - C32 - C32X - C42 - C42X - C52 - C52X - C82 - C82X
EFFICIENCY
Max useful efficiency (80-60°C)%93,2
Min useful efficiency (80-60°C)%90,0
Useful efficiency at 30% of load (40-30°C)%108,8
Losses after shutdown at 50°CW111
ENERGY PERFORMANCE
HEATING
Heating seasonal energy efficiency classB
Heating seasonal energy efficiency%86
Sound powerdB(A)54
DOMESTIC HOT WATER
Domestic hot water energy efficiency classA
Domestic hot water energy efficiency%81
Stated domestic hot water profile loadXL
ELECTRICAL SPECIFICATIONS
Power supply voltageV230
FrequencyHz50
Absorbed electrical power in stand-byW3
Electrical protection degreeIPX5D
Maximum absorbed currentA2,0
COMBUSTION DATA
Smoke temperature at Max/Min flow (80-60°C)°C95 / 70
Smoke flow Max/Ming/s29,7 / 15,8
CO
2
at Max/Min (G20) flow rate with separate chimneys%3,5 / 2,5
CO (0% of O
2
)ppm120
NOx measuredmg/kWh26
NOZZLES GAS
Number of nozzlesNo.38
Nozzle diameter (G20)mm0,85
Nozzle diameter (G31)mm0,50
Gas consumption at Max/Min flow rate (G20)m
3
/h2,59 / 1,06
Gas consumption at Max/Min flow rate (G31)kg/h1,90 / 0,78
Gas supply pressure (G20/G31)
kg/h20 / 37
kPa2 / 3,7
TEMPERATURE PRESSURE
Max operating temperature (T max)°C85
Heating adjustment range°C40 ÷ 80
Domestic hot water adjustment range°C10 ÷ 60
Max operating pressure (PMS)
bar3
kPa300
Water content in boilerl3,35
R134a refrigerant gas contentg250
(*) NOx class according to UNI EN 15502-1:2015
(**) Heat input calculated using the lower heat output (Hi)
Lower Heat Output (Hi)
G20 Hi.
9.45 kW/m3 (15°C, 1013 mbar) -
G31 Hi.
12.87 kW/kg (15°C, 1013 mbar)
15
Page 16
5.6 Main water circuit
3
19
1
9
20
4
6
18
7
21
2
10
13
22
11
12
2324
17
16
14
27
15
28
8
5
25
26
MUGERS
KEY:
M System delivery
R System return
U Domestic hot water outlet
E Domesti hot water inlet
S Safety valve outlet
G Gas supply
1
Primary heat exchanger
2
Domestic hot water sensor
3
Boiler fan
4
Dual sensor (thermal safety/delivery)
5
Air inlet probe (SIA)
6
Domestic hot water heat exchanger
7
Diverter valve
8
Expansion valve thermal bulb
9
Refrigerant gas high-pressure pressure switch
10
Gas valve
11
Domestic hot water flow meter
12
Domestic hot water filter
13
System filling
14
Boiler drain
15
System relief valve
16
System pump
17
Air bleed valve
18
Water pressure transducer
19
System expansion vessel
20
Return probe
21
System delivery valve (on request)
22
Gas valve (on request)
23
Domestic hot water inlet valve (on request)
24
System return valve (on request)
25
Air evaporator
26
Thermostatic expansion valve
27
Refrigerant gas/water capacitor
28
ON/OFF compressor (CP)
m
CAUTION
You MUST install a Y filter (not supplied with the appliance) on the heating system return (R).
Fig. 11
16
Page 17
5.7 Sensors
TR
0800 1000 1200 1400 1600600400200
100
200
300
400
500
The sensors installed have the following characteristics:
– Dual sensor (thermal safety/output) NTC R25°C; 10kΩ β25°-
Examples of reading:
TR=75°C → R=1925Ω
TR=80°C → R=1669Ω.
0°C 1°C 2°C 3°C 4°C 5°C 6°C 7°C 8°C 9°C
0°C
27279
26135
25044
24004
23014
22069
21168
20309
19489
18706
17959
17245
16563
15912
15289
14694
14126
13582
13062
8945
6247
4444
3216
2365
1766
1336
1024
12565
8622
6033
4300
3116
2296
1717
1300
998
10°C
20°C
30°C
40°C
50°C
60°C
70°C
80°C
90°C
100°C
12090
8313
5828
4161
3021
2229
1669
1266
973
11634
8016
5630
4026
2928
2164
1622
1232
11199
7731
5440
3897
2839
2101
1577
1199
10781
7458
5258
3773
2753
2040
1534
1168
10382
7196
5082
3653
2669
1982
1491
1137
9999
6944
4913
3538
2589
1925
1451
1108
9633
6702
4751
3426
2512
1870
1411
1079
9281
6470
4595
3319
2437
1817
1373
1051
5.8 Expansion vessel
The expansion vessel installed on the boilers has the following
characteristics:
DescriptionU/M
Total capacityl8,0
Prefilling pressure
Useful capacityl4,0
Maximum system content (*)l109
kPa100
bar1,0
UNIQA.REVOLU-
TION
5.9 Circulation pump
The flow-head performance curve available for the heating system is shown in the graph below.
RESIDUAL HEAD (mbar)
25
0
5.10 Heat recovery system
Resistance R (Ω)
Certain conditions must apply for the heat recovery system to
work. The system return temperature must be below the value
set under
(PAR 46)
between the value set under
these conditions have been met, the
on the display. If the
ery system is in operation; if the symbol is flashing, the boiler is
culating the time required to start up correctly.
cal
. The combustion air temperature must be
(PAR 06)
symbol is on the screen, the heat recov-
>
and
(PAR 07)
symbol shows or flashes
>
FLOW (l/h)
Fig. 12
. Once all of
(*) Conditions of:
Average maximum temperature of the system 85°C
Start temperature at system filling 10°C.
m
CAUTION
– For systems with water content exceeding the max-
imum system content (as indicated in the table) an
additional expansion v
essel must be prearranged.
– The difference in height between the relief valve
and the highest point of the system cannot exceed
6 metres. If the difference is greater than 6 metres,
increase the prefilling pressure of the expansion
vessel and the system when cold by 0.1 bar for each
meter increase.
17
Page 18
5.11 Control panel
21
Fig. 13
1
FUNCTIONAL BUTTONS
If pressed once or more than once for at least 1 second
y
during normal operation, this button allows the user to
change the boiler operating mode in a cyclical sequence
(Stand-by – Summer – Winter). If the boiler is experienc
ing a fault which can be reset, it allows boiler operation
to be unbl
During normal operation, pressing the button displays
r
the domestic hot water set point which can be between
10 and 60°C. In "parameter setting", the user can scroll
through the parameter index (decreasing) by pressing
this button.
During normal operation, pressing the button dis-
t
plays the heating set point which can be between 20
and 80°C. In "paramet
through the parameter index (increasing) by pressing
this button.
During normal operation, pressing this button allows the
<
user to reduce the heating or DHW set point on the basis of the selection made previously. If there is a Remote
Contr
button, the user can modify the incline of the climatic
curve (decreasing it) by pressing the button (
rameter setting/display", the user can modify the parameter setting or value (decreasing) by pressing this
butt
During normal operation, pressing this button allows the
>
user to increase the heating or DHW set point on the basis of the selection made previously. If there is a Remote
Contr
button, the user can modify the incline of the climatic
curve (increasing it) by pressing the button (
rameter setting/display", the user can modify the parameter setting or value (increasing) by pressing this
butt
Programming connector cover plug.
c
ocked.
ol (Open Therm), aft
on.
ol (Open Therm), aft
on.
er setting", the user can scroll
er having selected the heating
-
). In "pa-
er having selected the heating
+
). In "pa-
NOTE:
pressing any one of these buttons for more than 30 seconds generates a fault on the display without preventing boiler
operation. The warning disappear
restored.
2
DISPLAY
“SUMMER”
l
erating in "Summer" mode or if only the domestic hot
water mode is enabl
“WINTER”
n
ating in "Winter" mode or if both the domestic hot water
and heating modes are enabl
With the remote control, if no operating modes have
been enabled both symbols
“RESET REQUIRED”
d
having repaired the fault, normal boiler operation can be
restored by pressing the button
“DOMESTIC HOT WATER”
r
DHW request. It flashes during the selection of the domestic hot water set point.
“HEATING”
t
ation. It flashes during the selection of the heating set
point.
“BLOCK” DUE TO NO FLAME
f
“FLAME PRESENCE"
F
“POWER LEVEL"
v
the boiler is operating.
“PARAMETER"
p
parameter setting/display, or "info" or "counter", or in
"activated alarms" (history).
“ALARM"
A
number specifies the cause which generated the alarm.
“HEATING SYSTEM PRESSURE"
a
pressure.
“CHIMNEY SWEEP"
z
sweep function" has been activated.
"ECO", ALTERNATIVE ENERGY SOURCES
E
indicates that there is a solar system available.
Flashing
B
On
. Compressor operating.
"MAINTENANCE REQUEST"
c
perform maintenance on the boiler.
. This symbol appears when the boiler is op-
. This symbol appears when the boiler is oper-
. This symbol lights up during heating oper-
. This indicates that a fault has occurred. The
. Waiting time for the compressor to start.
. This indicates the power level at which
. This indicates that the user may be in
s when normal conditions are
ed via the remote control.
ed via the remote control.
and n will be off.
l
. The message indicates that after
.
y
. This symbol is present during a
.
.
. Display of heating system
. This indicates that the "chimney
. Where active, it
. If active, it shows it is time to
Fixed
18
Page 19
5.12 Wiring diagram
BLACK
PI
230 V
50 Hz
BLUE
L
N
CN11
V
BROWN
BLUE
BLUE
BROWN
BLUE
BROWN
F1
CR
GREEN
GREEN
SIA
SS
RED
RED
TPA
GND
RED
ARANCIO
OUT
5V
GREEN
FLM
VCC
RED
GND
IN
WHITE
GREEN
BLUE
BROWN
BLACK
BLACK
BLUE
SE
3 2 1456
BLUE
TA
PA
VD
2
3
BLACK
BLACK
BLACK
EV
F3
CN13CN12
CN14
CN15
CN3
CN2
BLACK
BLACK
BLUE
BLUE
RED
RED
GREEN
GREEN
CN5
CN4CN1
SM1
EAR
TRA
CD .6324905
CN17
CN6
F2
BLACK
L
Line
N
Neutral
F1
Fuse (3.15AT)
F2
Fuse (4AR)
F3
Fuse (1AT)
TRA
Ignition transformer
PI
System pump
V
Fan
EAR
Ignition / Detection electrode
EV
Gas solenoid valve
SS
Domestic hot water sensor
SM1-2
Dual sensor (thermal safety/
delivery)
FLM
Flow meter
VD
Diverter valve
TPA
Pressure transducer
TA
Air thermostat
To connect the "Air Thermostat" or, alternatively the "Remote Control", remove the bridge between terminals 5-6.
m
CAUTION
Users must:
m
– Use an omnipolar cut-off switch, disconnect switch
in compliance with EN Standards
complete cut-off in overvoltage category III conditions
(i.e. where there is at least 3 mm between the open
contacts)
.
which ensures
– Respect the connections L (Live) - N (Neutral).
– Ensure that the special power cable is only replaced
d
with a cable ordered as a spare part and connected
by professionally qualified personnel.
C
CP S
R
PA
High pressure switch
SE
External sensor
SR
Return Probe
SIA
Air inlet probe
APS
Air pressure switch
EXP
Expansion card
CP
Compressor
CR
Remote control (instead of air
thermostat)
CAUTION
Users must:
– Connect the earth wire to an effective earthing sys-
tem. The manufacturer is not responsible for any
damage caused by f
ailure to earth the appliance or
failure to observe the information provided in the
wiring diagrams.
IT IS FORBIDDEN
To use water pipes for earthing the appliance.
SM2
EXP
1
3
SR
Fig. 14
19
Page 20
20
Page 21
INSTALLATION AND SERVICING INSTRUCTIONS
TABLE OF CONTENTS
6 INSTALLATION 22
6.1 Receiving the product ...........................22
6.2 Dimensions and weight..........................22
8.7 Malfunction codes and possible solutions ..........46
8.7.1 Maintenance request .................. 47
9 PRODUCT DATA SHEET 48
10 ANNEX AA.1 49
21
Page 22
6 INSTALLATION
H
m
m
CAUTION
External casing seals off the appliance from the environment in which it is installed. Check regularly, and
always aft
front, side and all gaskets have been correctly closed
and are not worn or damaged.
CAUTION
The appliance must only be installed by the
nical Service or by qualified professionals
wear
er performing maintenance work, that the
suitable protective safety equipment.
6.1 Receiving the product
UNIQA.REVOLUTION
tected by cardboard packaging.
appliances are delivered in a single unit pro-
Sime
Tech-
who MUST
6.2 Dimensions and weight
L
Description
W (mm)400
D (mm)345
H (mm)700
Weight (kg)45
UNIQA.REVOLUTION
P
Fig. 16
-
Fig. 15
The plastic bag found inside the packaging contains the following:
Installation, use and maintenance manual
–
– Paper template for boiler installation
– Certificate of warranty
– Hydrostatic test certificate
– System booklet
– Bag with expansion plugs.
m
d
CAUTION
The boiler must ALWAYS travel vertically (see packaging arrow). Failure to observe this precaution may
cause damage t
IT IS FORBIDDEN
Do not leave packaging material around or near children since it could be dangerous. Dispose of it as prescribed by legislation in force.
o the appliance.
22
Page 23
6.3 Handling
NONO
During transportation, the boiler must be kept in a vertical position, and knocks against walls or hard surfaces should be
avoided.
d
IT IS FORBIDDEN
Position the appliance horizontally or on its side.
6.4 Installation room
The room where the appliance is to be installed must comply
with the Technical Regulations and Legislation in force. It must
be equipped with suitably sized ventilation openings when the
installation is a "TYPE B" installation.
The minimum temperature of the installation room must NOT
-5 °C
be lower than
.
YES
Fig. 17
Once the packaging has been removed, the appliance is to be
handled manually, keeping it as vertical as possible, and lifting
by gripping it at the points indicated in the figure.
m
APPROXIMATE MINIMUM DISTANCES
CAUTION
– Before assembling the appliance, the installer
make sure that the wall supports the weight.
– Remember to consider the space needed in order to
access the safety/adjustment devices and to carry
out maintenance interventions (see Fig. 19).
≥ 50 mm
≥ 300 mm
MUST
d
a
NO!
Fig. 18
IT IS FORBIDDEN
To grip the appliance casing. Hold the "solid" parts of
the appliance such as the base and structural frame.
WARNING
Use suitable tools and accident protection when removing the packaging and when handling the appliance. Observe the maximum weight that can be lifted
son.
per per
≥ 900 mm
Fig. 19
23
Page 24
6.5 New installation or installation of a replacement appliance
When
UNIQA.REVOLUTION
or systems requiring updating, it is recommended the installer
checks that:
– the connecting flue pipe is suitable for the combustion tem
perature of the appliance, calculated and manufactured in
complianc
air tight, isolated, with no obstructions or restriction and that
it has appropriate condensate collection and evacuation sys
tems
the electrical system has been manufactured in compliance
–
with specific Standards and by professionally qualified per
sonnel
– the fuel delivery line and the tank (LPG) comply fully with spe-
cific Standards
the expansion vessel ensures total absorption of the fluid di-
–
lation in the system
the pump flow-head performance is sufficient for the system
–
characteristics
– the system is clean, free of any sludge, deposits, de aerated
and air tight. For system cleaning, please refer to the relevant
paragraph.
e with Standards, that it is as straight as possible,
boilers are installed on old systems
If the systems are only low temperature systems, it is recommended that a product is used to prevent the development of
bacteria.
any case, please refer to and comply with Legislation and
In
specific Technical Standards in force.
-
6.8 Boiler installation
UNIQA.REVOLUTION
plate for installation onto a solid wall.
-
-
tallation:
For ins
– position the paper template (1) on the wall (2) where the boiler
is to be mounted
– make the holes and insert the expansion plugs (3)
– tighten the screws with a double thread (4)
– insert the first cushioning washer (5) for each screw
– hook the boiler (6) onto the screws (4)
– insert the second cushioning washer (5) for each screw
– insert the flat washers (7) and fix in place using the nuts (8).
8 735 6 54
boilers leave the factory with a paper tem-
m
CAUTION
The manufacturer declines all liability for any damage
caused by an incorrect implementation of the smoke
outlet or for an excessive use of additives.
6.6 Cleaning the system
Before installing the appliance on a newly constructed system
or replacing a heat generator on an existing system, it is important that the system is thoroughly cleaned to remove sludge,
slag, dirt, r
Before removing an old heat generator from an existing system,
it is recommended that the user:
– puts a descaling additive into the water system
– allows the system to work with the generator active for a few
days
– drains the dirty water from the system and flushes the system
with clean water once or more than once.
If the old generator has already been removed or is not availa
ble, replace it with a pump to circulate water in the system and
then pr
Once cleaning operations have been carried out and before
installing the new appliance, it is recommended that a fluid is
added to the water system to protect it from corrosion and de
posits.
m
esidue et
oc
eed as described above.
CAUTION
– For further information on the type of additive and
usage, please contact the appliance manufacturer.
– Please remember that you
(not supplied with the appliance) on the heating system return (R).
c.
-
-
MUST
install a Y filter
m
2
1
Fig. 20
CAUTION
The height of the boiler is to be such that disassembly
and maintenance interventions are facilitated.
6.7 Water system treatment
When filling and restoring the system it is good practice to use
water with:
– aspect: clear if possible
– pH: 6÷8
– hardness: < 25°f.
If the water characteristics are different from those indicated, it
is recommended that a safety filter is used on the water deliv
ery pipe to retain impurities, and a chemical treatment system
otect against possible deposits and corrosion which could
to pr
affect boiler operation.
24
-
m
CAUTION
The boiler must be perfectly upright. Use a spirit level
or other suitable tool to check that it is perfectly vertical.
Page 25
6.9 Plumbing connections
The plumbing connections have the following characteristics
and dimensions.
21465 65 65 655585
MUGER
L
Fig. 21
Description
M - System deliveryØ 3/4" G
R - System returnØ 3/4" G
U - Domestic hot water outputØ 1/2" G
E - Domestic hot water inletØ 1/2" G
G - Gas supplyØ 3/4" G
W (mm)400
UNIQA.REVOLUTION
-
6.9.1 Plumbing accessories (optional)
To facilitate plumbing and gas connections to the systems, the
accessories as shown in the table below are available and are to
be ordered separately from the boiler.
DESCRIPTIONCODE
Curve kit8075428
Curve and valve kit with connections
from DIN to SIME
Cocks kit8091819
Valve kit with connections from DIN to
kit instructions are supplied with the accessory itself or
are to be found on the packaging.
8075443
8075442
8093900
6.10 Gas supply
UNIQA.REVOLUTION
ranged for G20 gas or G31. The G20 models can be converted to
function with G31 using
vided by
If changing the type of gas to be used, carry out the entire
CONVERSION"
Boiler connection to the gas mains must be carried out in full
compliance with installation Standards in force.
Before connecting the boiler to the gas mains, the user must
ensure that:
– the type of gas is correct for the appliance
– the pipes are clean
– the gas supply pipe is the same dimension as or greater than
a
m
Sime
that of the boiler fitting (G3/4") and with a load loss less than
or equal to that contemplated between the gas mains and the
boiler.
WARNING
Once installation has been completed, check that
the joints are air tight as indicated in the installation
Standards.
CAUTION
It is recommended that the gas line has a suitable filte r.
boilers leave the factory specifically prear-
the "specific nozzle kit" (optional) pro-
on request separately from the boiler.
"GAS
phase of the appliance.
25
Page 26
6.11 Smoke outlet and combustion air inlet
max 0,5 m
UNIQA.REVOLUTION
sidered an integral part of the boiler and are provided by
basis of the type permitted and the system requirements.
Permitted outlets
boilers must be equipped with appropriate smoke flue ducts and combustion air inlet ducts. These ducts are con-
Sime
as an accessory kit, to be ordered separately from the appliance on the
C42
C42X
C52
C52X
C82
C82X
C10
Type C appliance connected, via conduits, to a collective pipe designed for more than one appliance. The
oll
ective pipe is made up of two conduits connected
c
to a terminal which also feeds in air from outside the
burner and evacuates the combustion products exter
nally through concentric orifices or those close enough
esult in the same wind conditions.
to r
NOTE:
the boiler can be type C(10) only with accessory
B32
code 8089560.
C12-C12X
Concentric wall smoke outlet The pipes can start from
the boiler but the outlets must be concentric or close
together (no more than 50 cm) to be subject to similar
wind conditions.
C32-C32X
Concentric roof outlet Outlet as C12X.
C42
C42X
C32
C32X
C10
C42-C42X
Outlet and inlet in shared or separate flue pipes but
subjected to similar wind conditions.
C52-C52X
-
Separate wall or roof inlet and outlet in different pres
sure areas.
NOTE:
the inlet and outlet must never be positioned on
C32
C32X
C12
C12X
C12
C12X
opposing walls.
C82-C82X
Outlet in single or shared flue or with inlet on wall.
P:
smoke outlet system designed to operate with pos-
itive pressure.
X:
appliances and corresponding smoke outlet which
meet German air-tightness requirements.
max 0,5 m
-
m
26
B32
Combustion air inlet into the atmosphere and smoke
outlet into single flue.
NOTE:
opening for combustion air (15 cm2 x kW).
Fig. 22
WARNINGS
– The smoke flue and the connection to the flue pipe must be in compliance with the national and local Standards and Leg-
islation in force.
The use of rigid ducts which are resistant to temperature, condensate, mechanical stress and are air-tight is compulsory.
–
– Outlet ducts which are not isolated are a risk of danger.
Page 27
6.11.1 Coaxial ducts (Ø 60/100mm)
Coaxial accessories
Description
Coaxial duct kit8084813
Extension W. 1000 mm8096103
Extension W. 500 mm8096102
Vertical extension W. 200 mm with
smoke analysis take-off point
Adapter for Ø 80/125 mmAdditional 90° curve8095801
Additional 45° curve8095900
Tile with joint8091300
Roof outlet terminal W. 1284 mm8091200
Vertical condensation recovery W. 200
mm
Load loss - Equivalent lengths
Model
90° curve1
45° curve0,5
Minimum-Maximum Lengths
Duct Length Ø 60/100
Model
UNIQA.REVOLUTION
m
CAUTION
(*) Vertical condensate recovery MUST be introduced
W Horizontal (m)H Vertical (m)
Min.Max.Min.Max.
-2,51,3 (*)5
for vertical ducts (Type C32) or vertical sections of the
duct (Type C42) longer than 1.3m.
Diaphragms for coaxial ducts
Boilers leave the factory equipped with a diaphragm (1) with the
following characteristics:
UNIQA.REVOLUTION
–
: diaphragm Ø 87.5 mm.
Code
Ø 60/100 mm
8086908
8092803
Leq (linear metres)
Ø 60/100 mm
When the outlet is
Type C32
(vertically straight without any
curves), the presence of the diaphragm modifies the maximum
length of the duct as shown below:
ModelDiaphragmMax L (m)
UNIQA.REVOLUTION
UNIQA.REVOLUTION
YES2,5
NO5
6.11.2 Separate ducts (Ø 80mm)
The smoke outlet and combustion air inlet can built with separate ducts, instead of concentric ducts, using the “SEPARATE
DUCTS KIT, c
from the boiler. Connect the other accessories, chosen from
those listed in the table below, to it.
Separate accessories
Description
90° curve M-F (6 pieces)8077410
90° curve M-F (with take-off point)8077407
Extension W. 1000 mm (6 pieces)8077309
Extension W. 500 mm (6 pieces)8077308
Extension W. 135 mm (with take-off
point)
Wall inlet terminal8089550
Wall outlet terminal8089551
Internal and external ring nut kit8091500
Inlet terminal8089500
45° curve M-F (6 pieces)8077411
Condensate recovery W. 135 mm8092800
Manifold8091400
Tile with joint8091300
Roof outlet terminal W. 1390 mm8091201
Condensate recovery Tee8093300
Smoke outlet
The smoke outlet can be constructed by attaching the kit components to the boiler fitting: the Ø125/95 sponge seal (1), the
ollar (2) and the scr
c
ode. 8089932”. This is to be ordered separately
Code
Diameter Ø 80 (mm)
8077304
ews (3) to fix everything in place.
1
When the outlets are
Type C12
or
C42
the diaphragm is to be
removed or kept following the indications below:
ModelDiaphragmfor duct L
UNIQA.REVOLUTION
UNIQA.REVOLUTION
YES
(leave mounted)
NO
(remove it)
< 1 m
> 1 m
4
3
2
1
Fig. 23
Fig. 24
After folding the numbered sections upwards, the diaphragm (4)
must be positioned between the collar (2) and the first part of
the outlet pipe, depending on the desired pipe load loss (inlet +
outlet total length).
(*) The losses of the roof outlet terminal at inlet include the
manifold code 8091400.
m
CAUTION
– The total maximum length is obtained by adding the
length of the inlet and outlet pipes. The total load
loss is determined by the sum of the load losses of
the single accessories that make up the piping. It
2
should not exceed 21,5 mmH
The total extension
–
must not in any case exceed 10 m
O.
(inlet) + 10 m (outlet) for ducts Ø 80 mm.
NOTE:
for the boiler to operate correctly it is necessary that a
minimum distance of 0.50 m of the duct is respected with a 90°
inlet curve.
Example: calculation of the load loss of a
UNIQA.REVOLUTION
boiler.
Accessories Ø 80
mm
Extension W. 1000
mm (horizontal)
Extension W. 1000
mm (horizontal)
90° curve807741011 x 2,3-2,3
90° curve80774101-1 x 2,52,5
Wall terminal8089550/5111,13,64,7
TOTAL14,1
Code
807730922 x 1.0-2,0
80773092-2 x 1,32,6
Quantity
Load loss (mm H2O)
InletOutletTotal
Installation is permitted as the total load loss (14,1 mmH2O) for
2
the required accessories is less than 21,0 mmH
O. With this total load loss, fold sections 1 to 8 (inclusive) on the flue gas outlet
diaphragm (4).
The combustion air inlet, with separate ducts, is assembled as
follows:
– remove the air outlet cap (5); choose your preferred outlet
– cut the bottom of the cap (5) using a suitable tool (a)
– turn over the cap (5) as shown (b) and refit it on the air outlet,
inserting the new seal (6) provided in the kit
– fix everything in place with the screws removed previously.
The overturned cap (5) is now the attachment for the first com
ponent on the air inlet duct
ba
6.12 Electrical connections
The boiler is equipped with a ready wired power cable which is
to be connected to a 230V~50 Hz network.
If this cable needs to be replaced, an original spare must be re
quested from
Therefore only the connections of the original components as
shown in the table are needed. These are to be ordered sepa
rately from the boiler.
-
DESCRIPTIONCODE
External sensor kit (ß=3435, NTC 10KOhm at 25°C)8094101
Power cable (dedicated)6329400
Remote control HOME (open therm)8092280
Remote control HOME PLUS (open therm)8092281
Sime
.
-
-
5
55
Smoke outlet and combustion air inlet fittings
5
6
Fig. 26
m
a
To facilitate introduction of the connection wires of the optional
components into the boiler:
– remove the screws (1), pull the front panel (2) forwards and
CAUTION
The maintenance interventions described must ONLY
be carried out the professionally qualified personnel.
WARNING
Before carrying out any interventions described:
– set the main system switch to "OFF"
– close the gas valve
– make sure that no hot parts inside the appliance are
touched.
Fig. 28
release it from the top by lifting it
D
2
BC
Fig. 27
Description
A (mm)248
B (mm)140
C (mm)175
D (mm)180
E (mm)220
UNIQA.REVOLUTION
1
Fig. 29
29
Page 30
– remove the screws (3) securing the control panel (4)
20151050-10-15-5-20
°C
– move the panel (4) upwards (a) but keeping it in the side
guides (5) to the end of travel
– bring it forwards and down (b) until it is horizontal
4
m
CAUTION
It is compulsory:
– to use an omnipolar cut-off switch, disconnect
switch, in compliance with EN standards (contact
opening of at least 3 mm)
– if the power cable is to be replaced, that ONLY a spe
cial cable is used with a factory produced re-wired
onnect
or, ordered as a spare part and connected by
c
a professionally qualified person
– to connect the earth wire to an effective earthing
system (*)
– that before any intervention on the boiler, the mains
power is disconnected by setting the main system
switch to "OFF".
-
b
3
– insert the connection wires into the cable gland (6) and the
opening (7) on the control panel
6
7
– bring the control panel (4) to the original position and secure
it with the screws (3) which were removed previously
– connect the component wires to the terminal board (8) follow
ing the indications provided on the data plate (9).
a
5
Fig. 30
Fig. 31
(*) The manufacturer is not responsible for any damage
caused by failure to earth the appliance or failure to observe the information provided in the wiring diagrams.
d
IT IS FORBIDDEN
To use water pipes for earthing the appliance.
6.12.1 External sensor
The boiler is prearranged for connection to an external air temperature sensor and can operate with a sliding temperature.
This means that the delivery t
vary on the basis of the external temperature depending on the
climatic curve selected from those shown in the diagram (Fig.
33).
When fitting the sensor on the outside of the building, follow
the instructions provided on the packaging of the product itself.
Climatic curve
Delivery temperature
90
80
70
60
50
40
30
-
20
K=9K=7K=8K=5K=6
emperature sent to the boiler can
External temperature
K=4
K=3
K=2
K=1
°C
4
9
8
TA
SE
SIA
30
6
5
4
3
2
1
3
Fig. 32
m
Fig. 33
CAUTION
If there is an external sensor, in order to select the optimal climatic curve for the system and therefore the
delivery t
ature:
press the button
–
– press buttons
emperature based on the external temper-
for 1 second
t
or < until the required curve K has
been selected (within the range
>
K=0.0 - K=9.0
).
Page 31
6.12.2 Chrono-thermostat or Air Thermostat
CR
SE
SE
The electrical connection of the chrono-thermostat or air thermostat has already been described. When fitting the component
in the room wher
structions provided on the packaging of the product itself.
e the readings are to be taken, follow the in-
6.12.3 EXAMPLE of use of the command/control device on some types of heating systems
KEY
M System delivery
R System return
CR Remote control
SE External sensor
TA Air thermostat for boiler activation
TZ1÷TZ3 Air thermostat for the zone
VZ1-VZ3 Zone valves
RL1-RL3 Zone relays
P1-P3 Zone pump
TSB Low temperature safety thermostat
MULTI ZONE system - with pump, air thermostat and external
sensor.
TA
TZ1
RL1
M
R
SP
TZ2
RL2RL3
TZ3
P2P1
P3
Fig. 36
ONE DIRECT ZONE system , external sensor and air thermostat.
SE
M
R
TA
Fig. 34
MULTI ZONE system - with zone valve, air thermostat and external sensor.
TA
TZ1
M
R
TZ2TZ3
6.13 Refilling or emptying
Before carrying out the operations described below, make sure
that the main system switch is set to "ON" in order for the display to show the pressure level in the system during refilling.
Make sure that the operating mode is set to "Stand-by";
the case, press the button
mode has been selected.
ON
for at least 1 second until this
y
6.13.1 REFILL operations
Remove the front panel:
– remove the two screws (1), pull the front panel (2) forwards
and release it from the top by lifting it.
if this is not
Fig. 37
m
VZ1VZ2VZ3
Fig. 35
CAUTION
Set the parameter "tS 17 = DELAY SYSTEM PUMP ACTIVATION to allow the opening of zone valve Vz.
2
1
Fig. 38
31
Page 32
Domestic hot water circuit:
– open the isolation valves of the domestic hot water circuit (if
present)
– open one or more than one hot water valve to fill and bleed the
domestic hot water circuit
– once bleeding has been completed, close the hot water valves.
Heating circuit:
– open the isolation and air bleeding valves in the highest points
of the system
– loosen the automatic bleed valve (3)
– open the isolation valves of the heating circuit (if present)
– Open the filling valve (4)
– Fill until the water overflows from the air bleeding valves and
shut off the valves again
1-1.2
– Continue filling until the pressure reaches
bar as shown
on the display
– close the filling valve (4)
– check that there is no air in the system by bleeding all the
radiators and the circuit on the high points of the system
6.13.2 EMPTYING operations
Domestic hot water circuit:
– close the domestic hot water circuit isolation valve (prear-
ranged in installation)
open one or more than one hot water valve to fill and bleed the
–
domestic hot water circuit.
Boiler:
– loosen the automatic bleed valve (3)
– close the heating circuit isolation valves (prearranged in in
stallation)
check that the filling valve (4) is shut-off
–
– connect a rubber hose to the boiler drain valve (7) and open it
– when it has fully emptied, close the drain valve (7)
– close the automatic bleed valve (3).
-
3
4
Fig. 39
NOTE:
to completely remove all air from the system, it is recom-
mended that this operation is repeated a number of times.
– check the pressure on the display and if necessary top up until
the correct pressure reading appears
– close the automatic bleed valve (3).
Refit the front panel of the boiler hooking it on at the top, pushing it forwards and securing it with the screw (1) which was removed previously.
7
3
4
Fig. 40
32
Page 33
7 COMMISSIONING
7.1 Preliminary operations
a
Bef
– the type of gas is correct for the appliance
– the gas isolation valves for the heating system and the water
– the pump impeller rotates freely.
WARNING
– Should it be necessary to access the areas in the
bottom part of the appliance, make sure that the
system components and pipes are not hot (risk of
burning).
– Before replenishing the heating system, put on pro
tective gloves.
or
e commissioning the appliance, check that:
system are open
7.2 Before commissioning
After having carried out the preliminary operations, perform the
following to start the boiler:
– set the main system switch to "ON"
ON
– if there is a fault, the message
play, the fault code (eg.
sage
d
-
m
– close the taps opened previously and check that the appliance
shuts down
– press the button
"WINTER mode"
ture detected at that moment will appear on the display
.
CAUTION
To restore the start conditions press and hold the button
y
be carried out no more than 6 times.
"06"
for more than 3 seconds. This operation can
once for at least 1 second to select
Y
. The value of the heating water tempera-
n
"ALL"
will appear on the dis-
- no flame detected) and the mes-
Fig. 41
– the type of gas for which the boiler has been calibrated,
"LG"
(methane) or
After this the correct representation of the symbols will be
checked and finally
– check that the system pressure as shown on the pressure
gauge when the system is cold , is between
– press the button y once for at least 1 second to select
"SUMMER mode"
ed at that moment will appear on the display
(LPG,) will appear followed by the power.
"- -"
will appear on the display
1 and 1.2 bar
. the value of the delivery sensor detect-
l
"nG"
– adjust the air thermostat and check that the boiler starts and
operates correctly.
7.3 Parameter setting and display
To go into the parameter menu:
– from the selected mode (eg. WINTER)
– press the buttons r and t (for approximately 5 seconds) at
the same time until
ue set (0÷4) appears on the display
"PAR 01"
(parameter number) and the val-
– open one or more than one hot water tap. The boiler will work
at maximum power until the taps are closed.
33
Page 34
– press the button t to scroll up the list of parameters and
then
NOTE:
to scroll down the list
r
holding the buttons r or t increases the speed of the
When all the parameter modifications have been made, exit the
parameter menu by pressing and holding down the buttons
all at the same time
and
t
for at least 5 seconds until the initial
screen is displayed.
scrolling movement.
– once the required parameter has been reached, press the
buttons
or <to modify the value within the permitted range.
>
The modifications are stored automatically.
7.4 List of parameters
TypeNo.DescriptionRangeU.M.StepDefault
CONFIGURATION
PAR01Index showing boiler power in kW0 = 25--10
PAR02Hydraulic configuration5 = Low NOx ErP-15
PAR29Anti-legionella function (only hot water tank)
PAR30Maximum domestic hot water temperature35 .. 67°C160
PAR31
PAR32
PAR33
PAR34
PAR35Digital / analogue Pressure switch
PAR36
PAR37
PAR38Compr
PAR39Fan speed in post-ventilation50
PAR40Modulating pump speed-- = No modulation%--PAR41∆T modulating pump delivery/return10 .. 40°C120
PAR42
PAR43
PAR44Minimum time between compressor ignitions
PAR45Minimum time between compressor on-off13
PAR46
PAR47System pump forcing (only in winter mode)
PAR48Reset parameters (to default)0 .. 1----0
Domestic hot water activation delay with
solar power
0 = water pressure switch
1 = water pressure transducer
2 = water pressure transducer (only pressure
Maximum time of consecutive runs for compressor enabled to operate
Rest time for compressor, even where enabled to operate
essor post-operating time (in minutes)7
Return temp. threshold for activating the
compressor (temperature read at heat pump)
RESET
0 .. 300
-- = disabled
50 .. 80
displayed)
------
--11
m
m
0 = Disabled
1 = Enabled
----0
13
15
14
47
Tampering with the default values may cause serious damage to the appliance.
m
In the event of a fault/malfunction the message
pear on the display with the alarm number eg.
"ALL 04"
tic Hot Water Sensor Fault).
"ALL"
will ap-
(Domes-
Repair the fault and start-up the boiler again.
NOTE:
after having repaired the fault, when the alarm number
appears on the display together with the message
(see figure), press the button
to start the appliance up again.
Before repairing the fault:
– disconnect the appliance from the mains power by setting the
main switch to "OFF"
for approximately 3 seconds
y
d
Fig. 42
– as a precautionary measure, close the gas isolation valve.
35
Page 36
7.5 Display of operating data and counters
Once the boiler is operating a qualified technician can view the
operating data and the counters as follows:
– from the operating screen in the mode enabled at that mo
ment (WINTER n or SUMMER l)
– go into
same time
appears
"DISPLAY"
by pressing the buttons r and <
at the
for more than 3 seconds until the following screen
TABLE OF INFORMATION DISPLAYED
TypeNo.Description
PAR00SW version
-
PAR01External sensor
PAR02
PAR03
PAR04
PAR05
PAR06
PAR07Power level
PAR08Flow meter rate
PAR09
PAR10
PAR11
Delivery sensor 1
temperature
Delivery sensor 2
temperature
Domestic hot water
sensor temperature
Air inlet probe (SIA)
display
Actual heating SET
temperature
Water pressure
transducer reading
(if resent)
Return probe
display
Compressor (CP)
status
Range
- 9 ..
99
- 9 ..
99
- 9 ..
99
- 9 ..
99
- 9 ..
99
Pa r.
13 …
Pa r.
14
0 ..
99
0 ..
99
0…99bar0.1
0 ..
99
ON/
OFF
U/MStep
°C1
°C1
°C1
°C1
°C1
°C1
%1
l/min0.1
°C1
From this point, the technician has 2 options:
– scroll through the list of
(PARc)"
by pressing the button t. Scrolling will be in sequence
– display the
the button
“activated alarms”
r
"information (PAR)"
(no more than 10) by pressing
and
"counters
– Once in this section, proceed with button t or r.
When all the values have been displayed, exit the menu by
pressing and holding down the button yfor approximately 5
seconds until the initial screen is displayed.
TABLE OF COUNTER DISPLAYED
TypeNo.Description
PARc0
PARc1
PARc2
PARc3total no. faults
PARc4
PARc5
PARc6
Rc7
PA
total no. of boiler
operating hours
total no. of burner
operating hours
total no. of burner
ignitions
total no. of times
PAR parameters
accessed
total no. of times
OEM parameters
accessed
time unitl next
maintenance inter
vention
total no. of calibra
tions
Range
0 ..
99
0 ..
99
0 ..
99
0 ..
99
0 ..
99
0 ..
99
0 ..
99
-
1 ..
199
TABLE OF ACTIVATED ALARMS/FAULTS
TypeNo.Description
PARA0Last activated alarm/fault
PARA1Last but one activated alarm/fault
PARA2Third from last activated alarm/fault
PARA3Previous activated alarm/fault
PARA4Previous activated alarm/fault
PARA5Previous activated alarm/fault
PARA6Previous activated alarm/fault
PARA7Previous activated alarm/fault
PARA8Previous activated alarm/fault
PARA9Previous activated alarm/fault
U/MStep
0.1; from
h x 1000
h x 1000
h x 1000
x 11
x 11
x 11
months1
x 11
0.0 to 9.9;
1; from 10
to 99
0.1; from
0.0 to 9.9;
1; from 10
to 99
0.1; from
0.0 to 9.9;
1; from 10
to 99
36
Page 37
7.6 Gas conversion
OFF
1
UNIQA.REVOLUTION
with G20 (methane) to G31 (LPG), by installing the “Nozzle kit
for G31” code 8059250, to be ordered separately from the boiler,
, also modifying
models can be transformed from operating
“PAR 03”
.
– remove the screws (3) securing the control panel (4)
– move the panel (4) upwards (a) but keeping it in the side
guides (5) to the end of travel
– bring it forwards and down (b) until it is horizontal
m
a
CAUTION
The maintenance interventions described must ONLY
be carried out the professionally qualified personnel.
WARNING
Before carrying out any interventions described:
– set the main system switch to "OFF"
– close the gas valve
– make sure that no hot parts inside the appliance are
touched.
Fig. 43
7.6.1 Preliminary operations
To carry out the conversion:
– remove the screws (1), pull the front panel (2) forwards and
release it from the top by lifting it
4
b
3
– unscrew the screws (6) and remove the panel (7) carefully
6
a
5
Fig. 45
7
2
Fig. 44
Fig. 46
37
Page 38
– unscrew the swivel joint (8)
X
1
2
7
– remove the clip (9)
– unscrew the two front screws (10)
– replace the nozzle assembly (11) with the one in the kit, fixing
it in place with screws (10)
– replace the 3/4” gasket (12) on the gas valve with the new gas
ket supplied
– refit the components in reverse order and fix in place as ap-
propriate
10
9
12
8
11 10
Fig. 47
7.7 Automatic calibration procedure
This procedure MUST ALWAYS be performed when the appliance is first turned on, when the gas is changed and after replacing:
the nozzles for gas conversion
–
– the gas valve following a fault
– the electronic board following a fault
– electrode
– fan
– burner
and is necessary so that the new components can be identified
and can communicate with those already fitted on the boiler.
m
CAUTION
Considering that:
– the front panel has been removed, the control pan-
el has been brought forward and down and that the
al
points (6) and (7) of the gas v
ed to the pressure gauges
the main system switch must be set to "ON"
–
– the gas supply must be open
– there must be no current requests for heat ("Sum
mer" mode
ter"
n
the adjustments described below must be carried out
–
in sequence.
with hot water valve closed or "Win-
l
with air thermostats open)
ve have been connect-
-
– bring the control panel (4) to the original position and secure
it with the screws (3) which were removed previously.
m
– carry out the "Automatic calibration procedure" and then re-
CAUTION
If the gas supply is changed from G20 to G31, mark the
box on the TECHNICAL DATA PLATE.
G31 - 37 mbar
fit the front panel (2) securing it with the two screws (1).
6
Fig. 49
7.7.1 Setting the type of gas (only after GAS CONVER-
SION)
– go into the parameter section by pressing the buttons r and
(for approximately 5 seconds) at the same time until
t
01"
(parameter number) and the value set (0) appears on the
display
"PAR
NOTE:
holding the buttons r or t increases the speed of the
Fig. 48
38
scrolling movement. Pressing the button
scroll through the previous parameters.
allows the user to
r
Page 39
– keep the button t pressed and scroll through the parameters
until reaching parameter "03"
– press the > button and select “0" (METHANE) or “1” (LPG)
7.7.2 Modifying parameters and adjusting the pressure
Procedure which MUST be carried out after:
the nozzles for gas conversion
–
–
changing the gas valve following a fault
–
changing the the electronic board following a fault
–
electrode
–
fan
–
burner
– go into the parameter section (if not already there) by press-
ing the buttons
same time until
set (0) appears on the display
– keep the button
until reaching parameter
and t (for approximately 5 seconds) at the
r
"PAR 01"
t
(parameter number) and the value
pressed and scroll through the parameters
"PAR 49"
– press the button > to set the value
– the modified value will be stored automatically
– exit the parameter section by pressing and holding down the
and t
buttons
until the delivery temperature is displayed.
m
Adjusting maximum gas pr
– press the button y until "SUMMER" mode lhas been se-
lected
press button
–
maximum using the button
– press and hold down the buttons > and y at the same time
for approximately 6 seconds until the message
on the display alternating with
r
IMPORTANT
To complete this task the user
lowing procedure.
at the same time
essure:
and set the DOMESTIC HOT WATER SET to
r
at "5"
(approximately 5 seconds)
MUST
carry out the fol-
>
"to"
"Au"
appears
– press and hold the button > to set the value
– the modified value will be stored automatically
– keep the button
until reaching parameter
pressed and scroll through the parameters
t
"PAR 70"
at "49"
–
open one or more than one hot water tap
– the boiler will start up and the message
the display (Adjusting maximum gas pressure)
– with a G20 gas supply, press the > or < buttons until the pres-
sure value indicated in the table appears on the pressure
gauge
with a G31 gas supply, press the
–
maximum value
– once the value indicated in the table has been reached, press
the button
value which will then flash once.
“99”
for approximately 2 seconds to confirm the
y
"P01"
will appear on
button until you reach the
>
39
Page 40
Adjusting minimum gas pressure:
7
– press the button
the display
twice, the message
r
"P00"
will appear on
7.8 Checking the CO2 with the chimney sweep
function
This function lasts 15 minutes and is activated by proceeding
as follows:
– press the buttons > or < until the pressure value indicated in
the table appears on the pressure gauge
– once the value indicated in the table has been reached, press
the button
value which will then flash once
– press and hold down the buttons
for approximately 6 seconds until the water delivery temperature appears on the display and the boiler shuts down
– close the valves which were opened previously
– disconnect the pressure gauges, carefully close the pressure
points (6) and (7), put the control panel back to the original
position and refit the front panel (2).
for approximately 2 seconds to confirm the
y
and y at the same time
>
m
– open the gas valve
– power the boiler by setting the main switch to "ON"
– press button y and hold for at least 1 second, until you se-
CAUTION
There must be no heat requests in progress (hot water
valves closed or TA open/not activated).
ON
lect “SUMMER” mode
, where it is not already selected
l
Fig. 51
6
m
Gas supply pressure
Type of gasG20G31
Pressure (mbar)2037
CAUTION
External casing seals off the appliance from the environment in which it is installed. Check regularly, and
always aft
front, side and all gaskets have been correctly closed
and are not worn or damaged.
er performing maintenance work, that the
Fig. 50
– press and hold down the buttons < and > at the same time
for approximately 10 seconds until the message “Hi” appears
on the display together with the flashing symbols
–
open one or more than one hot water tap
– press the > button to run the boiler at maximum power “Hi”
m
– take the CO2 reading using the specific points on the outlet
– press the
CAUTION
Ensure that the front panel on the boiler is closed before
reading the CO
ducts
button to run the boiler at minimum power “Lo”.
The message “Lo” is displayed on the screen and the
n
<
symbols flash
2
value.
l
and
l
n
and
Installations with SPLIT and CONCENTRIC flue gas outlet pipe
systems
ModelHeat Output
UNIQA.REVOLUTION
40
Max13,3 - 13,835,2 - 35,7
min2,9 - 3,26,1 - 6,5
Pressure at nozzles (mbar)
G20G31
Page 41
– press the > button again to run the boiler at maximum power
again
– press the button
dure”. The boiler water delivery temperature will appear on
the display
– close the taps opened previously and check that the appliance
shuts down.
CO2 values
Type of gasG20G31
CO
2
to exit the "Chimney sweeper Proce-
y
max3,0 - 3,53,7 - 4,2
min2,1 - 2,52,8 - 3,2
7.9 Modifying the CO2 values
Should the CO2 values read differ from those in the table, modify
“PAR 73”
– keep the flue gas analyser inserted in the take-off point on
– go into the parameter section by pressing the buttons
– press and hold the
– press and hold the < button to change the value to
– the modified value will be stored automatically
as follows:
the outlet ducts
(for approximately 5 seconds) at the same time until
t
01"
(parameter number) and the value set (0) appears on the
display
button and scroll through the parame-
t
ters until you reach
minimum power)
“PAR 15”
“0”
and
r
"PAR
(force
– press and hold the button > to set the value
– the modified value will be stored automatically
– press and hold the
ters until you reach
– increase or decrease
buttons respectively, checking combustion
or
<
– the modified value will be stored automatically
– after the CO2 values have been modified, set
“100”
– or the most suitable heating power – again
– exit the parameter section by pressing and holding down the
buttons
until the delivery temperature is displayed.
and t
r
button and scroll through the parame-
t
“PAR 73”
at the same time
(default value “20”)
“PAR 73”
one unit at a time using the >
(approximately 5 seconds)
at "49"
“PAR 15”
back to
– keep the button t pressed and scroll through the parameters
until reaching parameter
"PAR 49"
41
Page 42
7.10 Domestic hot water comfort function (preheating)
UNIQA.REVOLUTION
fort" function which ensures the best performance in terms of
domestic hot
ter to become available and ensuring that the temperature is
t
able.
s
To activate the function:
– select parameter
play") and set it to
– exit parameter settings and press button > for approximately
5 seconds until the symbol
gins to flash indicating that the function has been activated.
To deactivate the function:
– press button
symbols
indicating that the function has been deactivated.
r
models have a "domestic hot water com-
water, reducing the time necessary for the hot wa-
"PAR 22"
a 1
again for approximately 5 seconds until the
>
and R appear on the display and begin to flash
(see "Parameter setting and dis-
appears on the display and be-
r
42
Page 43
8 MAINTENANCE
OFF
1
8.1 Adjustments
For the appliance to operate correctly and efficiently it is recommended that the User calls upon the services of a Professionally
Qualified Technician t
m
a
CAUTION
– The maintenance interventions described must
ONLY be carried out the professionally qualified
personnel
equipment.
– Make sure that the system components and pipes
are not hot (risk of burning).
WARNING
Before carrying out any interventions described:
– set the main system switch to "OFF"
– close the gas valve
– make sure that no hot parts inside the appliance are
touched.
o carry out
who MUST wear
ANNUAL
maintenance.
suitable protective safety
8.3 Cleaning the inside of the appliance
m
To clean the inside:
– remove the screws (1), pull the front panel (2) forwards and
CAUTION
External casing seals off the appliance from the environment in which it is installed. Check regularly, and
always aft
front, side and all gaskets have been correctly closed
and are not worn or damaged.
release it from the top by lifting it
er performing maintenance work, that the
2
Fig. 52
8.2 External cleaning
8.2.1 Cleaning the cladding
When cleaning the cladding, use a cloth dampened with soap
and water or alcohol for stubborn marks.
d
IT IS FORBIDDEN
to use abrasive products.
Fig. 53
8.3.1 Cleaning the air evaporator
– unscrew the eight screws (3) and remove the inspection cover
(4)
– use a hoover to remove any dirt.
43
Fig. 54
43
Page 44
8.3.2 Cleaning the heat exchanger
1
– remove the eight screws (5) and remove the front panel (6)
from the combustion chamber (6) working carefully so as not
to damage the gasket or the panel insulation
8.3.4 Checking the ignition/detection electrode
Check the state of the ignition/detection electrode and replace if
necessary. Check the measurements as per the drawing whether the ignition/detection electrode is replaced or not.
0,5
6
5
Fig. 55
– if there is any dirt on the heat exchanger (9) fins, protect the
burner elements (10) covering them with a sheet of newspaper or a cloth and clean the heat exchanger (9) using a soft
brush.
8.3.3 Cleaning the burner
The burner must be cleaned thoroughly. Clean it using suction
once a year, taking special care to clean the back part where
there is a steel and copper blade (7).
7
Boiler
6,5
front
View from the back of the boiler
0,5
3,5
Fig. 57
m
CAUTION
The position of the electrode is essential for the correct
detection of current ionization.
8.3.5 Final operations
After cleaning the inside:
– check that the seals and insulation on the appliance are in-
tact. If they are not, replace them
refit the front panel (2), securing it with the two screws (1).
–
2
Fig. 56
Fig. 58
44
Page 45
8.4 Checks
7
8.4.1 Checking the smoke duct
It is recommended that the user checks that the combustion air
inlet duct and smoke outlet duct are integral and airtight.
8.4.2 Checking the expansion vessel pressure
It is recommended that the expansion vessel on the water side
is drained and that the prefilling pressure is not less than
If this is not the case, pressurize it to the correct value (see sec-
es
tionExpansion v
Once the checks described above have been completed:
– refill the boiler as described in section "REFILL operations"
– start the boiler up and carry out a smoke analysis and/or
measure the combustion efficiency.
– refit the front panel securing it with the two screws which
were removed previously
sel".
1 bar
– close the gas valve
– loosen the "nozzle pressure" point (6) and the screw of the
"supply pressure" point (7) and connect each one to a pres
sure gauge
6
.
-
8.5 Reading the pressure at the nozzles with
the chimney sweep function
Should the pressure at the nozzle need to be checked, a qualified maintenance technician can activate the chimney sweep
function described belo
This function lasts 15 minutes and is activated by proceeding
as follows:
– if the panel (2) has not already been removed, remove the
two screws (1), pull the front panel (2) forwards and release it
from the top by lifting it
2
w.
1
Fig. 59
Fig. 61
m
– open the gas valve
– power the boiler by setting the main switch to "ON"
– press button y and hold for at least 1 second, until you se-
CAUTION
There must be no heat requests in progress (hot water
valves closed or TA open/not activated).
ON
lect “SUMMER” mode
, where it is not already selected
l
Fig. 62
– remove the screws (3) securing the control panel (4)
– move the panel (4) upwards (a) but keeping it in the side
guides (5) to the end of travel
– bring it forwards and down (b) until it is horizontal
4
b
3
a
5
Fig. 60
– press and hold down the buttons < and > at the same time
for approximately 10 seconds until the message “Hi” appears
on the display together with the flashing symbols
l
and
n
45
Page 46
–
open one or more than one hot water tap
– press the button > to make the boiler operate at maximum
"Hi"
power
and check that the gas pressure values on the
pressure gauges correspond to those indicated in the table
below
2
– read the combustion parameters (CO
particularly) and the
combustion performance
– press the button
to make the boiler operate at minimum
<
power "Lo" and check that the gas pressure values on the
pressure gauges correspond to those indicated in the table
below. The message “Lo” will appear on the display together
with the flashing symbols
l
and
n
– press the button > once again to make the boiler operate at
maximum power. If the gas pressure values are correct it is
possible to determine the combustion data and take a reading
of the combustion efficiency as provided for by legislation in
force
– press the button
to exit the "Chimney sweeper Proce-
y
dure”. The boiler water delivery temperature will appear on
the display
– close the taps opened previously and check that the appliance
shuts down
– disconnect the pressure gauges, carefully close the pressure
points (6) and (7), put the control panel back to the original
position and refit the front panel (2).
Gas supply pressure
Type of gasG20G31
Pressure (mbar)2037
Installations with SPLIT and CONCENTRIC flue gas outlet pipe
systems
ModelHeat Output
UNIQA.REVOLUTION
Max13,3 - 13,835,2 - 35,7
min2,9 - 3,26,1 - 6,5
Pressure at nozzles (mbar)
G20G31
8.6 Unscheduled maintenance
If replacing the
ters as indicated in the table and in the sequence shown.
TypeNo.Description
PAR01
PAR02
PAR03
PAR04
To enter "Parameter setting and display"refer to the indications provided in the specific section.
the parameters in the table have been set, you must carry
Once
out the "Automatic calibration procedure".
gas valve
If the
fan
are replaced, the user must still carry out the entire phase
of "Automatic calibration procedure" described in the specific
section.
electronic board
Index showing boiler power in kW
0 = 25
Hydraulic configuration
5 = Low NOx ErP
Gas Type Configuration
0 = G20; 1 = LPG
Combustion configuration
3 = Low NOx ErP APS
and/or the
, the user MUST set the parame-
ignition/detection electrode
Setting for
UNIQA.REVOLU-
TION
-
0
5
0 or 1
3
and/or the
8.7 Malfunction codes and possible solutions
LIST OF MALFUNCTION/FAULT ALARMS
TypeNo. FaultSolution
ALL02
ALL03
ALL04
ALL05Delivery sensor fault
ALL06No flame detection
ALL07
ALL08
ALL09
ALL10Air inlet probe error
Low water pressure in
system
High water pressure in
system
Domestic hot water
sensor fault
Safety thermostat
intervention
Fault in the flame
detection circuit
No water circulating in
the system
- Restore pressure
- Check for any leaks in the
system
- Empty the system via the
drain valve on the hydraulic
assembly and bring the
pressure to approximately
1.2 bar
- Check connections
- Replace the sensor
- Check connections
- Replace the sensor
- Check the integrity of the
electrode and check that it
is not grounded
- Check gas availability and
pressure
- Check the integrity of the
gas valve and the card
- Check the delivery sensor
connections
- Deaerate the system
- Check the bleed valve
- Replace the delivery sensor
- Check that the pump im
peller is not blocked
- Check the integrity of the
electrode and check that it
is not grounded
- Check gas availability and
pressure
- Check the integrity of the
gas valve and the card
- Check the rotation of the
pump rotor
- Check the electrical con
nections
Replace the pump
-
- Check the probe
- Check the electrical connection
-
-
46
Page 47
TypeNo. FaultSolution
ALL11
ALL12
ALL13
ALL14Smoke probe fault
ALL15
ALL18Condensate level fault
ALL28
ALL30
ALL37
ALL40
ALL41
ALL42Button fault
ALL43
ALL44
ALL62
ALL70
ALL72
ALL77
ALL78
ALL79
ALL80
ALL81
ALL82
Gas valve modulator
disconnected
ect configuration
Incorr
of the open /sealed
chamber
Smoke probe intervention
Fan check cable disconnected
Maximum number of
consecutive releases
Return sensor (SR)
fault
Fault due to low net
work voltage
Incorrect network
frequency detected
Flame loss more than 6
consecutive times
Open Therm communi
cation fault
No flame valve opening
time sum anomaly
Self-calibrating proce
dure is required
HP high pr
max. interventions
Incorrect positioning of
the delivery sensor
EV current max/min
absolute limits error
EV current upper limit
error
EV current lower limit
error
Fault on the valve
control logic line
Block due c
during start-up
Block due to numerous
combustion control
failures
sure time
es
ombustion
- Check the electrical connection
- Set the parameter tS 0.4
(Combustion configuration)
to 0
-
Check the sensor is
working
- Replace the smoke probe
- Replace the smoke probe
- Check the electrical connection of the smoke probe
Contact the Technical
Assistance Centre
Check the connection cable
between the fan and the
board
- Check for any clogging in
the pipe which takes the
condensate to the siphon
- Check that the siphon is
not clogged
- Contact the Technical
Assistance Centre
- Replace the return probe
- Check parameters
- Contact the Technical
Assistance Centre
-
Check the voltage
-
- Contact your network
provider
- Contact your network
provider
- Check the detection
electrode
- Check the gas supply (open
valve)
- Check mains gas pressure
- Check that buttons are
working
-
Check the electrical
connection of the remote
control
- Replace the board
Carry out the self-cali
-
brating procedure (see the
specific section)
- Decrease setting PAR 46
- Contact the Technical
Assistance Centre
- Check that the delivery
sensor is attached to the
delivery pipe
- Check gas valve and board
- Check gas valve and board
- Check gas valve and board
- Check/replace the connec
tion cable to the gas valve
- Check for blockage in
chimney or recirculation
- Bleed the air from the gas
circuit
- Check for any dirt on the
air evaporator
- Check electrode
- Check outlets
- Check air diaphragm
- Check gas calibration
- Check for any dirt on the
air evaporator
TypeNo. FaultSolution
ALL83
ALL84
ALL88
ALL89
ALL90
ALL92
ALL93
ALL95
ALL96
ALL98
ALL99General board error
Irregular combustion
(temporary error)
Flow rate reduced for
(presumed) low pressure on mains gas
Internal error (board
component protection)
Unstable combustion
feedback signal error
Combustion set cannot
be reached error
System has reached
maximum air cor
rection error (at the
minimum flow r
Combustion set cannot
be reached error
Flame signal micro
interruptions error
Block due to clogging
in smoke outlet
SW error, board start-up- Contact the Technical
ate)
- Check for blockage in
chimney
- Check for any dirt on the
air evaporator
-
Check gas flow rate
- Replace the board
- Check electrode
- Check outlets
- Check air diaphragm
- Check gas calibration
- Check electrode
- Check outlets
- Check air diaphragm
- Check gas calibration
- Check electrode
-
- Check outlets
- Check air diaphragm
- Check gas calibration
- Check electrode
- Check outlets
- Check air diaphragm
- Check gas calibration
- Check electrode
- Check board
- Check electric power
supply
- Check gas calibration
- Check for blockage in
chimney
Assistance Centre
- Contact the Technical
Assistance Centre
8.7.1 Maintenance request
When it is time to perform maintenance on the boiler, the c
symbol shows on the display.
-
Contact the technical assistance service to organise the necessary work.
-
47
Page 48
9 PRODUCT DATA SHEET
UNIQA REVOLUTION
D.H.W load profile declared
C.H. energy efficiency class
D.H.W. energy efficiency class
Heat output (kW)
C.H. annual energy consumption (GJ)
D.H.W. annual combustible consumption (GJ)
C.H. seasonal energy efficiency (%)
D.HW. energy efficiency (%)
Sound power dB(A)
Specific precautionary measures to be adopted at the time of assembly, installation or maintenance of the equipment
are contained in the boiler instruction manual
Conforming to Annex IV (item 2) of the Delegated Regulations (EU) No. 811/2013 which supplements Directive 2010/30/EU
XL
23
53
18
86
81
54
48
Page 49
10 ANNEX AA.1
Information requirements for boiler space heaters, boiler combination heaters
Model(s):UNIQA REVOLUTION
Condensing boiler:No
Low-temperature boiler:Ye s
B11 boiler:No
Cogeneration space heater:NoEquipped with a supplementary heater:No
Combination heater:Yes
ItemSymbolValueUnitItemSymbolValueUnit
Nominal heat output for space heatingP
n
23kW
For boiler space heaters and boiler combination heaters:
useful heat output
At nominal heat output and hightemperature regime
At 30% of nominal heat output and
low-temperature regime
a
b
P
P
4
1
22,9kW
8kW
Auxiliary electricity consumptionOther items
At full loadel
At part loadel
0,060kWStandby heat lossPstby0,111kW
max
0,289kWIgnition burner power consumptionPign0kW
min
In standby modePSB0,003kWEmissions of nitrogen oxidesNOx38
Contact detailsFonderie Sime S.p.A. Via Garbo 27, 37045 Legnago (VR) ITALIA
a. High-temperature regime means 60°C return temperature at heater inlet and 80°C feed temperature at heater outlet.
b. Low-temperature regime means for condensing boilers 30°C, for low-temperature boilers 37°C and for other heaters 50°C return
temperature.
Seasonal space heating energy efficiency
ηs86%
For boiler space heaters and boiler combination heaters:
useful efficiency
At nominal heat output and hightemperature regime (*)
At 30% of nominal heat output and
low-temperature regime (*)
Water heating energy efficiency
η484,1%
η197,9%
ηwh86%
mg/
kWh
(*) The yield data have been calculated using the higher heating value.