Fonderie SIME FORMAT TECHNYL Series, FORMAT 25 OF, FORMAT 30 BF, FORMAT 30 OF, FORMAT 25 BF Installer's Instructions

Page 1
CONTENTS
1 DESCRIPTION OF THE BOILER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 73
2 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 76
3 CHARACTERISTICS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 84
4 USE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . pag. 88
INSTALLER INSTRUCTIONS
IMPORTANT
good earthing system. – Open the gas tap and check the soundness of the connections, including that of the burner. – Make sure that the boiler is set for operation for the type of gas supplied. – Check that the flue pipe for the outlet of the products of the combustion is unobstructed and has been pro-
perly installed. – Make sure that any shutoff valves are open. – Make sure that the system is charged with water and is thoroughly vented. –
Check that the circulating pump is not locked (CAUTION: Remember to release the pump coupled with the control
panel, if necessary, to protect the electronic control card). – Purge the system, bleeding off the air present in the gas pipe by operating the pressure relief valve on the gas
valve inlet.
FORMAT TECHNYL - ENGLISH
FONDERIE SIME S.p.A. of Via Garbo 27 - Legnago (VR) - Italy declares that its hot water boilers, which bear the CE mark under
Gas Directive 90/396/CEE and are fitted with a safety thermostat calibrated to a maximum of 110°C, are not subject to appli­cation of PED Directive 97/23/CEE as they meet the requirements of article 1 paragraph 3.6 of the Directive.
Page 2
1.1 INTRODUCTION
“FORMAT” boilers are gas-fired thermal
appliances for central heating and domestic hot water production, designed and manu­factured to satisfy the needs of multiple dwelling and modern plant requirements. They comply with the european directives 90/396/CEE, 89/336/CEE, 73/23/CEE,
92/42/CEE and with the european specifi­cations EN 297 - EN 483. These appliances can be fired by natural gas (methane) and butane gas (G30) or propane gas (G31). This booklet provides the instructions for the following boiler models: – “FORMAT 25 OF - 30 OF”
with electronic ignition and modulation,
natural draught.
– “FORMAT 25 BF - 30 BF”
with electronic ignition and modulation, room sealed forced-draught.
The instructions given in this manual are provided to ensure proper installation and perfect operation of the appliance
73
1 DESCRIPTION OF THE BOILER
1.2 DIMENSIONS
1.2.1 “FORMAT 25 OF - 30 OF”
1.2.2 “FORMAT 25 BF - 30 BF”
L
865
D
205
47,5
47,5
31
110
370
=
=
70
70
70
70
R
M
G
E
U
732,5
80
Fig. 1
370
110
205
47,5
47,5
ø 100/60
86,5
865
L
732,5
=
=
70
707070
R
MGE
U
31
80
Fig. 1/a
R C.H. return 3/4” M C.H. flow 3/4” G Gas connection 3/4” E D.H.W. inlet 1/2” U D.H.W. outlet 1/2”
25 30
L mm 450 500 D mm 130 150
R C.H. return 3/4” M C.H. flow 3/4” G Gas connection 3/4” E D.H.W. inlet 1/2” U D.H.W. outlet 1/2”
25 30
L mm 450 500
Page 3
74
1.3 TECHNICAL FEATURES
* The gas consumptions refer to the calorific value at standard conditions at 15°C - 1013 mbar. ** Differential measure between the pressure upstream of the gas valve and the depression in the room sealed
25 OF 30 OF 25 BF 30 BF
Heat output
Nominal kW 23.3 28.6 23.3 29.0
kcal/h 20,000 24,600 20,000 24,900
Minimum kW 9.3 11.7 9.3 11.5
kcal/h 8,000 10,100 8,000 9,900
D.H.W. heat output
Nominal kW 23.3 28.6 23.3 29.0
Heat input
Nominal kW 25.8 31.6 25.8 31.6
Minimum kW 10.8 13.5 10.8 13.5
Water content l 2.4 2.4 3.4 3.4
Adsorbed power consumption W 105 110 150 160
Electrical protection grade
IP 44 44 44 44
Maximum water head bar 3333
Maximum temperature °C 95 95 95 95
Expansion vessel
Water content l 7 10 7 10
Preloading pressure bar 1111
CH. setting range °C 40÷80 40÷80 40÷80 40÷80
D.H.W. setting range °C 40÷60 40÷60 40÷60 40÷60
D.H.W. flow rate (EN 625) l/min 10.5 12.7 10.5 12.7
Continuous D.H.W. flow rate ∆t 30°C l/min 11.1 13.6 11.1 13.8
Minimum D.H.W. flow rate l/min 2222
D.H.W pressure
Minimum bar 0.5 0.5 0.5 0.5
Maximum bar 7777
Smokes temperature °C 119 120 135 150
Smokes flow gr/s 21.0 22.5 19.0 20.3
Category II2H3+ II2H3+ II2H3+ II2H3+
Type B11BS B11BS
B22-C12-C32-C42-C52 C12-C32-C42-C52
Weight kg 35 41 43 49
Main burner nozzle
Quantity n° 13 15 13 15
Methane ø mm 1.30 1.30 1.30 1.30
G30 - G31 ø mm 0.75 0.77 0.75 0.76
Gas consumption *
Methane m3st/h 2.72 3.34 2.72 3.34
Butane (G30) kg/h 2.02 2.48 2.02 2.48
Propane (G31) kg/h 1.99 2.40 1.99 2.40
Burner gas pressure
Methane mbar 2÷9 2÷10.5 2÷9.6 2.3÷11.1**
Butane (G30) mbar 5÷27 5.2÷27.9 5÷27 5.5÷26.8**
Propane (G31) mbar 5÷35 6.9÷35.5 5÷35 6.9÷34.9**
Gas supply pressure
Methane mbar 20 20 20 20
Butane (G30) mbar 30 30 30 30
Propane (G31) mbar 37 37 37 37
Page 4
7
3 2
1
13
10
11
12
6
5
14
4
15
8
7
5
4
6
3
2
1
10
9
11
12
15
FORMAT OF
FORMAT BF
“30” model
75
2
3
4
22
U
21
17
19 18
13
15
12
16
6
5
14
10
9
11
8
7
1
20
EG MR
23
1.4 FUNCTIONAL DIAGRAM
Fig. 2
KEY
1 Fan (vers. “BF”) 2 Water-gas exchanger 3 Combustion chamber 4 Gas valve 5 D.H.W. exchanger 6 Divertor valve with charging 7 NTC sensor 8 100°C safety stat
9 Air relief valve 10 Circulation pump 11 Expansion vessel 12 Safety valve 13 Boiler discharge 14 Flowmeter 15 Thermomanometer 16 Automatic by-pass 17 D.H.W.filter 18 C.H. return cock (optional) 19 C.H. flow cock (optional) 20 D.H.W. cock (optional) 21 Gas cock (optional) 22 Fixing jig 23 C.H. water filter
1.5 MAIN COMPONENTS
Fig. 3
KEY
1 Control panel 2 Divertor valve 3 Flowmeter 4
100°C safety stat 5 Water-gas exchager 6 C.H. sensor (SM) 7 Combustion chamber
8 Fan (vers. “BF”) 9 Smoke pressure switch (vers. “BF”)
10 Gas valve 11 D.H.W. exchager 12 Circulating pump 13 Smoke chamber (vers. “OF”) 14 Smoke stat (vers. “OF”)
15 C.H. water filter
Page 5
The boiler must be installed in a fixed loca­tion and only by specialized and qualified firms in compliance with all instructions contained in this manual. Furthermore, the installation must be in accordance with current standards and regulations.
2.1 VENTILATION OF BOILER ROOM
The “25 OF - 30 OF”
version boilers must be installed in adequately ventilated dome­stic rooms. It is essential that in rooms where the boiler are installed at least as much air can arrive as required by normal combustion of the gas consumed by the various appliances. Consequently, it is necessary to make ope­nings in the walls for the air inlet into the rooms. These openings must meet the fol­lowing requirements: – have a total free section of at least 6
cm2for every kW of heat input, with a minimum of 100 cm2;
– They must be located as close as possi-
ble to floor level, not prone to obstruc­tion and protected by a grid which does not reduce the effective section required for the passage of air.
The “25 BF - 30 BF” version boilers may instead be installed, without any con­straints regarding location or supply of air for combustion, in any domestic rooms.
2.2 INSTALLATION PLATE
To mount the installation plate supplied as an optional extra (kit code 8075407), follow the instructions written below (fig. 4): – Fix the connecting sheet to plate (A) and
lower plate (B).
– With the template complete, fix plate (A)
to the wall using the two boiler support screws.
– Check that plate (B) is perfectly horizon-
tal using a spirit level.
– Connect the bends or connecting valves
supplied in the optional kit to the system pipes.
2.2.1 Fitting the pipe elbows (optional)
To fit the connecting elbows supplied in kit code 8075418, follow the instructions reported in fig. 5.
2.2.2 Fitting isolating valves (optional)
To fit the isolating valves, supplied in kit code 8091806, follow the instructions mentio­ned in fig. 6.
2.2.3 Replacement wall kit for other makes (optional)
The kit code 8093900 is supplied comple­te with mounting instructions.
2.3 CONNECTING UP SYSTEM
Before proceeding to connect up the boiler, you are recommended to make the air cir­culating in the piping in order to eliminate any foreign bodies that might be detrimen­tal to the operating efficiency of the appliance.
The discharge pipe of the safety valve must be connected to a collector funnel for channelling away any discharge if the safety valve goes into action. If the heating system is on a higher floor than the boiler, install the on/off taps sup­plied in kit code 8091806 on the heating system delivery/return pipes.
The gas connection must be made using seamless steel pipe (Mannesmann type), galvanized and with threaded joints provi­ded with gaskets, excluding three-piece con­nections, except for initial and end connec­tions. Where the piping has to pass through walls, a suitable insulating sleeve must be provided. When sizing gas piping, from the meter to the boiler, take into account both the volume flow rates (consumption) in m
3
/h and the relative density of the gas in question. The sections of the piping making up the system must be such as to guarantee a supply of gas sufficient to cover the maxi­mum demand, limiting pressure loss between the gas meter and any apparatus being used to not greater than: –
1.0 mbar for family II gases (natural gas);
– 2.0 mbar for family III gases (butane or
propane).
An adhesive data plate is sticked inside the front panel; it contains all the technical data identifying the boiler and the type of gas for which the boiler is arranged.
76
2 INSTALLATION
Fig. 4
KEY 1 Fixing jig 2 Elbow 1/2”x14 3 Gasket ø 18.5/11.5 4 Elbow 3/4” x 18 5 Gasket ø 24/17 6 Copper pipe 3/4”x18 7 Gas cock 3/4” MF 8 Copper isolation valve 9 Isolation valve 1/2” MF
Fig. 5
KEY
1 Fixing jig 2 Straight coupling 1/2”x14 3 Gasket ø 18.5/11.5 4 Elbow 1/2”x14 5 Copper pipe 1/2”x14 6 Isolation valve 1/2” MF 7 Isolation valve 3/4” MF 8 Gasket ø 24/17 9 Gas cock 3/4” MF
10 Straight coupling
3/4”x18 11 Copper pipe 3/4”x18 12 Straight coupling
3/4”x18 with olive
Fig. 6
Page 6
2.3.1 Filter on the gas pipe
The gas valve is supplied ex factory with an inlet filter, which, however, is not adequate to entrap all the impurities in the gas or in gas main pipes. To prevent malfunctioning of the valve, or in certain cases even to cut out the safety device with which the valve is equipped, install an adequate filter on the gas pipe.
2.4 CHARACTERISTICS OF FEEDWATER
To prevent lime scale and damage to the tap water exchanger, the water supplied should have a hardness of no more than 20°F. In all cases the water used should be tested and adequate treatment devices should be installed. To prevent lime scale or deposits on the primary exchanger, the water used to supply the heating circuit should must be treated in accordance with UNI-CTI 8065 standards. It is absolutely essential that the water is to be treated in the following cases: – very extensive system (with high con-
tents of feedwater);
– frequent addition of makeup water into
the system;
– should it be necessary to empty the
system either partially or totally.
2.5 SYSTEM FILLING
Filling of the boiler and the system is done by the charge cock (2 fig. 7). The charge pressure, with the system cold, must be between 1 and 1.2 bar. During system filling you are recommended to keep the main switch turned OFF. Filling must be done slowly so as to allow any air bubbles to be bled off through the air valves.
Should the pressure have risen well above the limit expected, discharge the over pressure by opening the pressure-relief valve.
2.6 FLUE
The flue for the atmospherical expulsion of the combustion products from natural draught appliances must meet the following requirements: –
Be gas-tight to the combustion products, waterproof and thermally insulated.
–
Be built of materials suitable for keep resisting to normal mechanical stresses, heat, and the action of combustion pro­ducts and their possible condensates.
– Follow a vertical path and not present
any throttling throughout its entire length.
– Be adequately insulated to prevent phe-
nomena of condensation or smokes coo­ling, in particular if located outside the building or in unheated ambiences.
– Be set at an adequate distance from
combustible or easily inflammable mate­rial by means of an air gap or suitable insulating material.
– Have beneath the mouth of the first
smoke duct a chamber for collecting solid material and any condensate; the height of the chamber must be at least 500 mm. Access to the chamber must be guaran­teed by means of an opening provided with an air-tight metal door.
– Have a circular, square, or rectangular
internal cross section; in the case of square or rectangular sections, the cor­ners must be rounded off with a radius of not less than 20 mm. However, hydraulically equivalent cross sections are allowed.
– Be equipped with a chimney-pot at the
top, which must be outside the so-called back-flow zone, so as to prevent the for­mation of back-flow, which prevents free discharge of the products of combustion into the atmosphere.
– Be devoid of mechanical means of suc-
tion located at the top of the pipe.
– No overpressure should be present in a
chimney that passes within or close up to inhabited rooms.
2.6.1 Connecting up flue
Fig. 8 refers to the connection of the boiler “25 OF - 30 OF” to the flue or chimney through smoke ducts. When making the connection, in addition to respecting the dimensions given, you are recommended to use gas-tight materials capable of resi­sting over time mechanical stresses and the smokes heat. At any point along the smoke duct, the tem­perature of the combustion products must be higher than the dew point. More than a total of three changes of direction must not be made, including the inlet connection to the chimney/flue. For any changes of direction use only cur­ved pipe lengths.
Fig. 8/a shows some applications of drau­ght terminals that ensure proper expulsion of the combustion products, in case of discharge through the wall.
2.7 “25 BF - 30 BF” COAXIAL DUCT
The air inlet-smoke outlet assembly ø 60/100 is supplied in a kit code 8084805 complete with mounting instructions.
77
KEY
1 D.H.W. inlet/outlet
manifold 2 Filling cock 3 D.H.W. filter 4 Manifold by-pass 5 Water rate adjuster 6 D.H.W. exchanger 7 Microswitches 8 Flowmeter 9 Boiler discharge
Fig. 7
Fig. 8
Fig. 8/a
6
7
8
5
2
3
1
9
4
Page 7
2.7.1 Installation of diaphragm
The diaphragm is normally supplied together with boiler version “30 BF”. See fig. 9 for positioning.
ATTENTION: Install the diaphragm only when the length of the ø 60/100 coaxial pipe is less than 1 m.
2.7.2 Coaxial duct accessories
The accessories to be used for this type of installation and some of the connecting systems that may be adopted are illustra­ted in fig. 10.
With the pipe bend included in the kit, the maximum length of the piping should not exceed 3 m.
When the vertical extension code 8086900 is used, the terminal part of the pipe must always come out horizontally.
2.7.3 Positioning the outlet terminals
The outlet terminals for forced-draught appliances may be located in the external perimeter walls of the building. To provide some indications of possible solu­tions, Table 1 gives the minimum distances to be observed, with reference to the type of building shown in fig. 10/a.
2.7.4 Coaxial duct outlet on the roof
The roof discharge terminal L. 1284 cannot be shortened and when positioning the tile, the minimum distance from the discharge head terminal must not be less than 600 mm (fig. 11). The accessories to be used for this type of installation and some of the connecting systems that may be adopted are illustra­ted in fig. 12.
It is possible to insert up to a maximum of three extensions and reach a maximum rectilinear distance of 3.7 m. Should it be necessary to make two chan-
78
KEY
1a-b Coaxial duct kit code 8084805
2a Extension L. 1000 code 8096100 2b Extension L. 500 code 8096101
3 Vertical extension L. 200
with take-off point code 8086908
4 Supplementaty 90° elbow code 8095800
TABLE 1
Siting of terminal Appliances from 7 to 35 kW
(distances in mm) A - below openable window 600 B - below ventilation opening 600 C - below eaves 300 D - below balcony (1) 300 E - from adjacent window 400 F - from adjacent ventilation opening 600 G - from horizontal or vertical soil or drain pipes (2) 300 H - from corner of building 300 I - from recess in building 300 L - from ground level or other treadable surface 2500 M - between two terminals set vertically 1500 N - between two terminals set horizontally 1000 O - from a surface facing without openings or terminals 2000 P - as above but with openings and terminals 3000
Fig. 10/a
Fig. 10
1)
Terminals below a practicable balcony must be located in such a way that the total path of the smoke from its outlet point from the terminal to its outlet point from the external perimeter of the balcony, including the height of possible railings, is not less than 2000 mm.
2) When siting terminals, where materials that may be subject to the action of the combu-
stion products are present in the vicinity, e.g., eaves, gutters and downspouts painted or made of plastic material, projecting timberwork, etc., distances of not less than 1500 mm must be adopted, unless adequate shielding is provided to guard these materials.
Fig. 9
IMPORTANT: – Each additional 90° curve installed reduces the
available length by 0.90 metres.
– Each additional 45° curve installed reduces the
available length by 0.45 metres.
Page 8
ges of direction in the pipe development, the maximum length of the pipe must not exceed 2 m.
2.8
“25 BF - 30 BF” SEPARATE PIPES
When installing the pipes, follow closely the requirements of the current stan­dards, as well as the following practical pointers: – With direct intake from outside, when
the pipe is longer than 1 m, you are recommended to insulate the piping so as to prevent formation of dew on the outside of the piping during particularly hard periods of the year.
– With the outlet pipe outside the building
or in cold indoor environments, insulation is necessary to prevent burner failure in starting. In such cases, provide for a condensate­collector system on the piping.
– With the outlet pipe outside the building
or in cold indoor environments, insulation is necessary to prevent burner failure in starting. In such cases, provide for a condensate­collector system on the piping.
The maximum overall length of the intake and exhaust ducts depends on the head losses of the single fittings installed (excluding the doublers) and must not be greater than 7.00 mm H
2
O (vers. “25”)
and 11.00 mm H2O (vers. “30”).
For head losses in the fittings, refer to Table 2.
79
TABLE 2
Accessories ø 80 Head loss (
mm H2O)
“25” version “30” version
Inlet Outlet Roof outlet Inlet Outlet Roof outlet
90° elbow MF 0,30 0,40 – 0,30 0,50 – 45° elbow MF 0,20 0,30 – 0,20 0,40 – Extension L. 1000 (horizontal) 0,20 0,30 – 0,20 0,40 – Extension L. 1000 (vertical) 0,30 0,20 – 0,30 0,30 – Outlet terminal – 0,30 – – 0,40 – Intake terminal 0,10 – – 0,10 – – Doubler fitting 0,20 – – 0,30 – – Roof outlet terminal L.1390 – – 0,50 – – 0,60 Tee condensation outlet – 0,90 – – 1,10 –
Example of allowable installation calculation (“25” version) in that the sum of the head los­ses of the single fittings is less than 7.00 mm H
2
O:
Intake Outlet
7 meter horizontal pipe ø 80 x 0.20 1.40 – 7 meter vertical pipe ø 80 x 0.30 – 2.10 n° 2 90° elbows ø 80 x 0.30 0.60 – n° 2 90° elbows ø 80 x 0.40 – 0.80 N° 1 terminal ø 80 0.10 0.30
Total head loss 2.10 + 3.20 = 5.3
mm H2O
With this total head loss, remove the ø 38 baffle from the intake pipe.
KEY 1 Tile with articulated joint 2 Lead panel 3 Collar 4 Locking screw
Fig. 11
Fig. 12
KEY 1 Vertical extension L. 200 with take-off point code 8086908 2a Extension L. 1000 code 8096100 2b Extension L. 500 code 8096101 3 Tile with articulation joint code 8091300 4 Roof outlet terminal L. 1284 code 8091200 5 Supplementaty 90° elbow code 8095800 6 Supplementaty 45° elbow code 8095900
Page 9
2.8.1 Separate pipe accessories
Kit code 8093000 is supplied for this pur­pose (fig. 13). The sectored diaphragm is to be used according to the maximum head loss allowed in both pipes, as given in fig. 14. The complete range of accessories neces­sary for satisfying all installation require-
ments is reported in fig. 15.
2.8.2 Separate-pipes roof outlet
The roof outlet terminal L. 1390 cannot be shortened and when positioning the tile, the minimum distance from the discharge head terminal must not be less than 700 mm (fig. 16). The accessories to be used for this type of installation and some of the connecting systems that may be adopted are illustra­ted in fig. 17. There is the possibility of doubling the air­intake and smoke-outlet pipes and then brin-
ging them back together again so as to obtain a concentric discharge by using the doubler fitting (7 fig. 17). In these cases, when assembling, recover the silicone gasket used on the terminal adapter (5 fig. 16), which is to be replaced by the doubler, and insert it into the seat made in the doubler.
For this type of discharge the sum of the maximum rectilinear development allowed for the pipes must not exceed 7.00 mm H2O (“25” vers.) and 11.00 mm H2O (“30” vers.). When calculating the lengths of pipe,
take into account the parameters given in the Table 2.
80
Fig. 13
12 0
=
=
ø 80
16 0
KEY 1 Sponge-rubber gasket ø125/95 2 Fixing screw 3 Air-smokes flow splitting unit
with take-off point
4 Sectors of diaphragm ø 38
Fig. 14
Fig. 15
KEY 1 Air-smokes flow plitting unit
with take-off point code 8093000 2a 90° elbow MF (n° 6) code 8077410 2b Isolated 90° elbow MF code 8077408 3a Extension L. 1000 (n° 6) code 8096003 3b Isolated extension L. 1000 code 8077306 3c Extension L. 500 (n° 6) code 8096002 4 Outlet terminal code 8089501 5 Int.-est. ring kit code 8091500 6 Intake terminal code 8089500 7 45° elbow MF (n° 6) code 8077411 8 Condensation outlet L. 135 code 8092800 9 Locking junction (n° 5) code 8092700
SECTOR OF DIAPHRAGM
Sectors of diaphragm Total head loss
to remove mm H
2OPa
1 0 ÷ 2 0 ÷ 19,6 2 2 ÷ 3 19,6 ÷ 29,4 4 3 ÷ 4 29,4 ÷ 39,2 6 4 ÷ 5 39,2 ÷ 49,0
Remove diaphragm 5 ÷ 7 49,0 ÷ 68,6
“25 BF” version
Sectors of diaphragm Total head loss
to remove mm H
2OPa
1 0 ÷ 1 0 ÷ 9,8 2 1 ÷ 2 9,8 ÷ 19,6 3 2 ÷ 4 19,6 ÷ 39,2 4 4 ÷ 5 39,2 ÷ 49,0 5 5 ÷ 6 49,0 ÷ 58,8 6 6 ÷ 7 58,8 ÷ 68,6
Remove diaphragm 7 ÷ 8 68,6 ÷ 78,4
“25 BF” version B22 type
Sectors of diaphragm Total head loss
to remove mm H
2OPa
1 0 ÷ 2 0 ÷ 19,6 2 2 ÷ 3 19,6 ÷ 29,4 3 3 ÷ 4 29,4 ÷ 39,2 4 4 ÷ 5 39,2 ÷ 49,0 5 5 ÷ 6 49,0 ÷ 58,8 6 6 ÷ 7 58,8 ÷ 68,6
Remove diaphragm 7 ÷ 11 68,6 ÷ 107,8
“30 BF” version
Page 10
2.9 FORCED OUTLET
The “25 BF” version can also be installed as a B22 type apparatus by assembling the stub pipe inlet/outlet kit cod. 8089950. The kit comes with a sector diaphgram, instruction sheet and a label with the room aeration warnings to be attached to the boi­ler casing. The sector diaphram must be used according to the maximum load loss allowed by the duct, as indicated in fig. 14. The complete range of fittings required to carry out the installation is given in fig. 18.
The maximum length of the duct is deter­mined by the load losses of the single atta­ched fittings (excluding the inlet/outlet stub pipe) and should not be greater than
8.00 mm H2O.
To calculate the load loss of the individual fit­tings attached see Table 2.
2.10 ELECTRICAL CONNECTION
The boiler is supplied with an electric cable. Should this require replacement, it must be purchased exclusively from SIME. The electric power supply to the boiler must be 230V~50Hz single-phase through a fused main switch, with at least 3 mm spa­cing between contacts.
NOTE: Device must be connected to an efficient earthing system. SIME declines all responsibility for injury or damage to persons, animals or things, resulting from the failure to provide for proper earthing of the appliance.
2.10.1 Electric switchboard
To access the electrical panel, turn off the power supply and then remove the front panel and the two screws that anchor the control panel to the sides(see point 4.7).
The panel will tilt forward at a sufficient angle to allow access to the components. To remove the protection, unscrew the fixing screws and use a screwdriver to release the upper tabs and free it from the control panel (fig. 19).
81
Fig. 17
KEY
1 Air-smokes flow splitting unit
with take-off point code 8093000
2 a 90° elbow MF (n° 6)
code 8077410
2 b Isolated 90° elbows MF
code 8077408
3 a Extension L. 1000 (n° 6)
code 8096003
3 b Isolated extension L. 1000
code 8077306
3 c Extension L. 500 (n° 6)
code 8096002 4 Int.-est. ring kit code 8091500 5 Intake terminal code 8089500 6 Locking junction (n° 5)
code 8092700 7 Doubler fitting code 8091400 8 Tile with articulated joint
code 8091300 9 Roof outlet terminal L. 1390
code 8091201
10 45° elbow MF (n° 6) code 8077411 11 Condensation outlet L. 135
code 8092800
12 Tee condensation outlet
code 8093300
Fig. 16
Fig. 18
KEY
1 Inlet/outlet terminal 2 Sectors diaphragm 3 90° elbow MF with point
cod. 8077407
4a Extension L. 1000 (n° 6)
cod. 8096003
4b Isolated extension L. 1000
cod. 8077306
4c Extension L. 500 (n° 6)
cod. 8096002
5 Locking junction (n° 5)
cod. 8092700
6 90° elbow MF (n° 6) cod. 8077410 7 Extension L. 135 with point
cod. 8077304 8 45° elbow MF (n° 6) cod. 8077411 9 Condensation outlet L. 135
cod. 8092800
10 Tile with articulated joint
cod. 8091300
11 Roof outlet terminal L. 1390
cod. 8091201
12 Tee condensation outlet
cod. 8093300
KEY 1 Tile with articulated joint 2 Lead panel 3 Collar 4 Locking screw 5 Reducing fitting
with gasket
Page 11
2.10.2 Room stat connection
To gain access to connector TA, remove the control panel cover (7 fig. 9) and con-
nect the room stat to the terminals 22-23 after having removed the jumper.
The thermostat or timer-thermostat,
recommended for better room tempe­rature control, must be class II as spe­cified by standard EN 60730.1 (clean contact).
82
2.10.3 “25 OF - 30 OF” wiring diagram with SIT control box
Fig. 20
KEY EV1 Gas valve coil EV2 Gas valve coil EA Ignition electrode ER Sensing electrode A SIT 503 control box TS 100°C safety stat TF Smoke stat FL Flowmeter P Circulation pump VP Divertor valve TAG Antifreeze stat (optional) C Rotary switch TA Room stat M Modulator SM C.H. sensor
Note: The room stat (TA) must be connected to the terminals 22-23
12
6
7
58
3
4
KEY
1 Thermomanometer 2 Timer-programmer housing 3 Rotary switch 4 Electronic board 5 Earth faston 6 Instrument protection 7 Room stat cover 8 Room stat connector
Fig. 19
CONNECTOR SPARE PART CODES:
J1 code 6260966 J2 code 6260962 J3 code 6260968 J5 code 6260957
Page 12
83
2.10.4 “25 BF - 30 BF” wiring diagram with SIT control box
Fig. 20/a
KEY EV1 Gas valve coil EV2 Gas valve coil EA Ignition electrode ER Sensing electrode A SIT 503 control box TS 100°C safety stat PF Smoke pressure switch VFan FL Flowmeter P Circulation pump VP Diverto valve TAG Antifreeze stat (optional) C Rotary switch TA Room stat M Modulator SM C.H. sensor
Note: The room stat (TA) must be connected to the terminals 22-23
2.10.5 “25 OF - 30 OF” wiring diagram with HONEYWELL control box
Fig. 20/b
KEY EV1 Gas valve coil EV2 Gas valve coil EA Ignition electrode ER Sensing electrode A HONEYWELL S4565CF control box TS 100°C safety stat TF Smoke stat FL Flowmeter P Circulation pump VP Divertor valve TAG Antifreeze stat (optional) C Rotary switch TA Room stat M Modulator SM C.H. sensor
Note: The room stat (TA) must be connected to the terminals 22-23
CONNECTOR SPARE PART CODES:
J1 code 6260956 J2 code 6260961 J3 code 6260968 J5 code 6260964
CONNECTOR SPARE PART CODES:
J1 code 6260966 J2 code 6260960 J3 code 6260968 J5 code 6260957
Page 13
3.1 ELECTRONIC BOARD
The electronic boards are manufactured in compliance with the EEC 73/23 low-voltage directives. They are supplied with 230V and, through a built-in transformer, send a volta­ge of 24V to the following components: modulator, C.H. sensor and time program­mer. An automatic and continuous modula­tion system enables the boiler to adjust the heat output to the various system require­ments or the User’s needs. The electronic components are guaranteed against a tem­perature range of –10 to +60°C.
3.1.1 Central heating operation
Upon demand for heating from the room temperature stat, the circulation pump is activated, and approximately 90 seconds must elapse for the burner to start opera­ting. This will happen only if the temperature is set above the value detected by the hea­ting sensor. The setting range is between 40 and 80°C. The heat output can be varied according to the system needs by adjusting
the trimmer (1 fig. 21). At start-up of each working cycle, af ter the period of slow igni­tion having a duration of approx. 5 sec, the boiler will set itself at the heat output set on the “Minimum heating pressure” trimmer.
3.1.2 D.H.W. operation
Upon demand for hot water, the boiler starts instantaneously when the microswit­ch on the pressure switch valve trips. The required power output is regulated, via flame modulation, by the hot water sensor, which will compare the temperature read with the temperature set on the potentio­meter. The adjustment range is between 40 and 60°C. When the heating flow sensor is at 75°C the electronic limiter will trip and switch-off the burner. The burner will re-igni­te when the temperature falls below 2 °C.
3.1.3 Control leds
The electronic board is equipped with control leds which show some of the possible failures
that can cause an irregular and/or improper operation of the appliance. The leds are loca­ted on the card as indicated in fig. 21 and marked with the following wording: – “LD1 BLOCCO”
Red led on when control box, safety stat and/or smoke stat trips.
– “LD2 LINEA”
Green led off when there is no tension present.
3.1.4 Devices available on the electronic board
The electronic board is equipped with the following devices:
– “POT. RISC.” trimmer (1 fig. 21)
Sets the maximum heating power value. To increase the value turn the trimmer clockwise; to reduce the value turn the trimmer anticlockwise.
– “POT. ACC.” trimmer (6 fig. 21)
Trimmer to vary the pressure level upon ignition (STEP), of the gas valve.
84
3 CHARACTERISTICS
2.10.6 “25 BF - 30 BF” wiring diagram with HONEYWELL control box
Fig. 20/c
KEY EV1 Gas valve coil EV2 Gas valve coil EA Ignition electrode ER Sensing electrode A HONEYWELL S4565CF control box TS 100°C safety stat PF Smoke pressure switch VFan FL Flowmeter P Circulation pump VP Divertor valve TAG Antifreeze stat (optional) C Rotary switch TA Room stat M Modulator SM S.H. sensor
Note: The room stat (TA) must be connected to the terminals 22-23
CONNECTOR SPARE PART CODES:
J1 code 6260956 J2 code 6260959 J3 code 6260968 J5 code 6260964
Page 14
85
According to the type of gas for which the boiler is equipped, the trimmer must be regulated so as to obtain a pressure of approx. 3 mbar at the burner for metha­ne gas and 7 mbar for butane gas (G30) and propane gas (G31). To increase pres­sure, turn the trimmer clockwise; to redu­ce pressure, turn the trimmer counter­clockwise. The slow ignition pressure level can be set during the first 5 seconds fol­lowing burner ignition. After setting the
pressure level upon ignition (STEP) according to the type of gas, check that the pressure for heating is still at the value previously set.
– “GPL-MET” connector (4 fig. 21)
The connector link must be inserted on the type of gas for which the boiler is equipped.
– “ANN. RIT.” connector (5 fig. 21)
In the heating phase, the electronic board is programmed to include a bur­ner technical delay interval of approx. 2 minutes, which occurs both at system cold starting and at subsequent re-igni­tions. The aim is to overcome the pro­blem of repeated ignitions and turning off with very short time intervals between. This could occur in particular in systems presenting high head losses. At each restart after the period of slow ignition, the boiler will set itself for about 1 minute at the minimum modulation pressure, and will then move to the heating pressu­re value set. When the connecting link is inserted, both the programmed technical pause and the period of operation at
minimum pressure in the startup phase will be cancelled. In this case, the times elapsing between turning off and subse­quent re-ignition will depend on a tempe­rature difference of 3°C detected by the SM sensor (heating flow sensor).
ATTENTION: It is essential that the opera­tions described above be carried out by authorized technical staff.
3.2 TEMPERATURE SENSOR
The “FORMAT” boilers are equipped with sensor for detecting temperature: The probe acts as a limit thermostat, swit­ching-off the burner when the temperatu­re measured is higher than 90°C; the reset temperature is set at 80°C.
When probe (SM) has tripped, the boiler will not function for either service. Table 3 shows the resistance values (Ω) that
are obtained on the sensor as the tempe­rature varies.
In case of replacement, the thermistor will have to be fitted onto the relevant clew, located on the flow pipe (fig. 22).
3.3 CONTROL BOX
The boilers are equipped with HONEYWELL S4565CF and/or SIT 503 electronic con­trol and protection.
Ignition and flame detec­tion is controlled by two electrodes located on the burner. These guarantee maximum safety with intervention times, for accidental switching off or gas failure, of within one second.
3.3.1 Operating cycle
Before igniting the boiler, use a voltmeter to make sure that the electrical connection to the terminal block has been made properly, respecting the position of line and neutral,
TABLE 3
Temperature (° C) Resistance (Ω)
20 12.764 30 8.579 35 7.102 40 5.915 45 4.955 50 4.173 55 3.533 60 3.006 70 2.208 80 1.650
Fig. 22
CLEW
Fig. 21
KEY
1 “Heating output” trimmer 2 Fuse (1.6 AT) 3 D.H.W. potentiometer 4 “GPL-MET” bridge
5 “Cancel delay” bridge 6 “Ignition pressure” trimmer 7 “LD1 Block” led 8 Heating potentiometer
9 “LD2 Line” led
NOTE: To gain access to trimmers (1) and (6), unscrew the central heating potentiometer knob.
21
6
9
8
7
6
5
3
4
C
1
Page 15
as shown in the diagram. Rotate the selector to summer or winter, the red led should light up. The boiler is now ready to start working upon demand for heating or drawing off of D.H.W.; a discharge current is sent to the ignition electrode through the programmer, and the gas valve opens at the same time. Burner ignition normally takes place within 2 or 3 seconds. However, it is possible for ignition failures to occur, with consequent activation of signal indicating that the control box has “locked out”.
– Gas failure
The control box runs through the cycle normally sending electric power to the ignition electrode. The electrode continues spark discharge for a maximum of 10 sec. If the burner does not ignite, the control box “locks out”.
This may occur upon first ignition or after long periods of boiler lay-of f when there is air in the pipes. It may be caused by the gas cock being closed or by one of the valve coils having a break in the winding, so that the valve cannot open. The HONEYWELL valve connector is defective.
– Ignition electrode fails to spark
In the boiler, only the gas to the burner is seen to open. After 10 sec. the control box “locks out”.
This may be due to a break in the wire of the electrode or to the wire not properly fastened to the electric terminal of the control box; or else, the transformer has burnt out.
– No detection of flame
The continuous spark discharge of the electrode is noted starting from ignition even though the burner is lit. After 10 seconds have elapsed, the sparks cease, the burner goes out, and the warning light indicating equipment “lock-out” lights up.
This occurs when the position of phase and neutral has not been respected on the terminal block. There could have a break in the wire of the sensing electrode or the electrode itself is touching earth: the electrode is worn out and needs replacing. The con­trol box is defective.
When there is a sudden voltage failure, the burner shuts out immediately; when power supply returns, the boiler will start up again automatically.
3.3.2 Operating cycle
At each start-up the programmers perform
a self-check which, if there is a malfunction or parasite flame signal, disables the pro­gram start. The programmer will not start when the air pressure switch is not in the non-venting position.
3.4 “25 OF - 30 OF” SMOKE SAFETY DEVICE
This is a safety device against possible smoke emission into the ambience (14 fig.
3). The safety device goes into action by
blocking operation of the gas valve when the return of the smoke into the ambience is continuous and in quantities that might con­stitute a danger. The intervention of the device locks out the appliance because the burner has not igni­ted. In this case, place the rotary switch to the
( ) position
must be pressed for the boiler to restart automatically. Should the boiler continue to “lock out”, it will be necessary to make a careful check on the flue pipe, making all the necessary modi­fications and amendments so that it can work properly.
3.5 “25 BF - 30 BF” SMOKE
PRESSURE SWITCH
The pressure switch is factory set at the optimal values of 4.5 - 6 mm H
2
O (“25”
vers.) and 10-13 mm H2O (“30” vers.). This enables the boilers operation even with air intake and smoke outlet pipes at the maximum limit of the length allowed (9 fig. 3). Impurities and possible formations of condensate, which are more likely in cold periods of the year, could lead the pres­sure switch not to work and the boiler fail to start.
3.6
NO WATER FLOW SAFETY DEVICE
The boiler has a flow switch (8 fig. 7) which is tripped when it does not detect water flow in the primary circuit (>400 l/h), pre­venting the burner from functioning. To start the burner again, check the pres­sure in the system and make sure that the pump and the flow switch are working properly.
3.7 SYSTEM AVAILABLE HEAD
The head available for the heating plant is shown as a function of the flow in graph in fig. 24.
3.8 TIME PROGRAMMER (optional)
The control panel is designed to allocate a timer-programmer, code 8092203, which can be supplied upon request. To fit the timer, remove the housing blanking piece from the control panel and, with the panel open, fit the timer to the panel using the screws supplied therein. Remove the faston that links the terminal 3 of the rotary switch and connect it to the terminal 3 of the time-clock. Connect the unit as shown in the wiring dia­gram (fig. 25).
3.9 MAINS ELECTRICITY CONNECTION
Use a separate electricity supply to con­nect the room stats and relative zone val­ves or pumps. The micro or relay contact connection is made to terminals 22-23 (TA) of the cir­cuit board af ter having removed the jum­per (fig. 26).
86
Fig. 24
FLOW RATE (l/h)
RESIDUAL HEAD (mbar)
30
600
25
500
25
400
30
300
200
PREVALENZA RESIDUA (mbar)
con by-pass senza by-pass
Format - Planet - Open
10 0
0
200
140012001000800600400
PORTATA (l/h)
1600
Page 16
87
KEY OP Time programmer C Rotary switch
Fig. 25
L
N
TA
TA
1
VZ
R
VZ1
R1
NOTA: I relé vengono impiegati solo nel caso le valvole di zona siano prive di micro.
CR1
CR
Connettore "TA"
22 23
L
N
TA
TA1
P
R
P1
R1
CIRCUITO CON VALVOLE DI ZONA
CIRCUITO CON POMPE DI ZONA
Fig. 26
KEY TA-TA1 Zone room stat VZ-VZ1 Zone gas valve R-R1 Zone relay CR-CR1 Zone microvalve or relay contact P-P1 Zone pump
REMOVE
“TA” connector
NOTE: The relays are only used where the zone valves are not fitted with micros.
1. CIRCUIT WITH ZONE VALVES
2. CIRCUIT WITH ZONE PUMPS
Page 17
4.1 TEMPERATURE ADJUSTMENT OF D.H.W.
The sistem with a potentiometer for adju­sting the temperature of D.H.W. with a set­ting range from 40° to 60°C offers a dou­ble advantage:
1) The boiler adapts perfectly to any type of
D.H.W. system, whether the mixing system is a mechanical or a thermostat­controlled type.
2) The thermal output is dosed according
to the temperature required, which means a considerable saving in fuel.
NOTE: In order to avoid any misunder­standing please remember that the value obtained by the product of temperature difference (in °C) between D.H.W. output and input into the boiler by the hourly flow rate measured on the tap, where hot water is drawn off (l/h), cannot be higher than the useful output developed by the boiler. For measurements and checks on flow rate and temperature of D.H.W., use suitable instruments, taking into consideration any heat dispersion along the stretch of piping between the boiler and the measuring point.
4.2 ADJUSTMENT OF D.H.W. FLOW RATE
To adjust the hot water flow rate, use the flow-rate regulator on the pressure switch valve (5 fig. 7). Remember that the flow rates and corresponding temperatures of use of hot water, given in section 1.3, have been obtained by positioning the selector of the circulation pump on the maximum value.
Should there be any reduction in the D.H.W. flow rate, the filter installed on the inlet to the pressure switch valve (3 fig. 7) will need cleaning.
4.3 GAS VALVE
The “FORMAT” boilers, are equipped stan­dard with the SIT 837 TANDEM gas valve (fig.
27) and with HONEYWELL VK 4105M gas
valve (fig. 27/a). The gas valve is set at two pressure values: maximum and minimum. According to the type of gas burnt, these cor­respond to the values given in Table 4. The gas pressures at the maximum and mini­mum values, are factory set. Consequently they must not be altered. Only when you switch the appliance from one type of gas supply (methane) to another (butane or propane), it is permitted to alter the operating pressure. It is essential that
this operation is carried out exclusively by authorized technical staff. When the working pressures have been adjusted, reseal the regulators.
When the gas pressures are to be reset, this must be done following a set order
first setting the MAXIMUM and then the MINI­MUM.
4.3.1 Maximum pressure adjustment valve SIT (fig. 28)
To set the maximum pressure, proceed as follows: – Connect the pressure column or a pres-
sure gauge to the pressure inlet down­stream of the gas valve. In the “30 BF” versions, instead, connect the manome-
ter as shown in fig. 27/b. – Remove the plastic cap (1). – Set the knob of the D.H.W. potentiome-
ter to the maximum value. – Ignite the boiler by operating the switch
and open the hot water tap. –
Using a ø 10 spanner, turn the nut (3) to
arrive at the maximum pressure value
given in Table 4: to reduce the pressure, turn the nut counterclockwise; to increa­se the pressure, turn it clockwise.
–
Operate the main switch a number of times, keeping the hot water tap open all the time, and check that the pressure cor­responds to the values given in
Table 4
.
4.3.2 Minimum pressure adjustment valve SIT (fig. 28)
After having adjusted the maximum pressu­re, calibrate the minimum pressure as fol­lows: – Disconnect the electric power to the
modulator.
88
KEY 1 Modulator 2 EV1 - EV2 coils 3 Pressure inlet upstream 4 Pressure inlet downstream 5 VENT pressure test point
Fig. 27/a
TABLE 4
Burner max. Modulator Burner min. Modulator
Type of gas pressure current pressure current
mbar mA mbar mA Methane - G20 9 - 11 130 2 0 Butane - G30 27 - 28 165 5 0 Propane - G31 35 165 5 - 7 0
Fig. 27/b
4 USE AND MAINTENANCE
Fig. 27
KEY 1 Modulator 2 EV1 - EV2 coils 3 Pressure inlet downstream 4 Pressure inlet upstream 5 VENT pressure test point
1
4 35
2
Page 18
89
– With the domestic hot water potentio-
meter knob on maximum, the domestic hot water tap open and the burner igni­ted, turn the screw (2) keeping locked the nut (3) to achieve the minimum pres­sure value given in
Table 4
: to reduce the pressure, turn the screw counter­clockwise; to increase the pressure, turn it clockwise.
–
Operate the main switch a number of times, keeping the D.H.W. tap open all the time, and check that the pressure corre­sponds to the values given in Table 4.
– Restore electric power to the modulator. – Replace the plastic cap (1) in position.
4.3.3 Maximum pressure adjustment valve HONEYWELL (fig. 28/a)
To set the maximum pressure, proceed as follows : –
Connect the pressure column to the pres­sure inlet downstream of the gas valve.
– For the “BF” models connect the pressu-
re column as shown in fig. 27/b.
– Remove the plastic cap on the modula-
tor (1).
– Set the knob of the D.H.W. potentiome-
ter to the maximum value. – Ignite the boiler and open the D.H.W. cock. – Using a ø 9 spanner, turn the nut (3) to
achieve the maximum pressure value
given in
Table 4
: to reduce the pressure, turn the nut counterclockwise; to increa­se the pressure, turn it clockwise.
–
Operate the main switch a number of times, keeping the D.H.W. cock open all the time, and check that the pressure corre­sponds to the values given in Table 4.
4.3.4 Minimum pressure adjustment valve HONEYWELL (fig. 28/a)
After adjusting maximum pressure, pro­ceed to calibrate minimum pressure:
–
Disconnect the electric power supply from the modulator.
–
With the hot water potentiometer knob set to the maximum, the hot water tap turned on and the burner lit, hold nut (3) locked in place and simulta-
neously turn nut (2) using a fixed ø 7 wrench to identify the minimum pres­sure value shown in Table 4: turn the nut anti-clockwise to reduce pressure or clockwise to increase it.
– Turn the boiler on and off repeatedly
while keeping the hot water tap turned on, checking that pressure corresponds to the values shown in Table 4.
– Connect up the power supply to the
modulator again.
– Replace the plastic cap (1).
4.4 ADJUSTMENT OF HEAT OUTPUT FOR HEATING
To adjust boiler heat output for heating pur­poses, i.e., modifying the setting made at the factory which is approximately 16 kW, use a screwdriver to adjust the heating heat output trimmer (1 fig. 21). To increase working pres­sure, turn the trimmer clockwise; to reduce pressure, turn the trimmer counterclockwise. To facilitate the operations of adjusting heat output, see the pressure/heat output dia­grams for natural gas (methane) and butane or propane gas (figg. 29 - 29/a - 29/b).
KEY 1 Plastic cap 2 Minimum pressure adjusting screw 3 Maximum pressure adjusting nut
Fig. 28
Fig. 28/a
KEY 1 Plastic cap 2 Minimum pressure adjusting nut 3 Maximum pressure adjusting nut
11
10
9
8
7
6
5
4
3
2
1
8,1 (7.000) 11,6 (10.000) 17,4 (15.000) 23,2 (20.000)
POTENZA TERMICA kW (kcal/h)
PRESSIONE UGELLO mbar
29,0 (25.000)
25
30
Fig. 29
Pressure/heat output diagram for natural gas (methane)
25
20
15
10
8,1 (7.000) 11,6 (10.000) 17,4 (15.000) 23,2 (20.000)
POTENZA TERMICA kW (kcal/h)
PRESSIONE UGELLO mbar
30
5
29,0 (25.000)
25 30
Fig. 29/a
Pressure/heat output diagram for butane gas (G30)
HEAT OUTPUT kW (kcal/h)
NOZZLE PRESSURE mbar
HEAT OUTPUT kW (kcal/h)
NOZZLE PRESSURE mbar
Page 19
4.5 GAS CONVERSION
A kit is supplied complete with the necessary change-over materials for operation with butane gas (G30) or propane gas (G31). Operate in the following manner for changing over from one gas to another (fig. 30): – Close the gas cock. – Slide out the burner unit. – Replace the main nozzles supplied in a kit
(6), inserting the copper washer (4). Use a ø 7 spanner to perform this ope­ration.
– Remove the “GPL-MET” connector link on
the card and set it on “GPL”(4 fig. 21).
– To set the values of maximum and mini-
mum gas pressure, follow the instruc­tions given in section 4.3, according to the type of gas valve used.
When the working pressures have been adjusted, reseal the regulators.
– The gas feed pressure must, under no
circumstances, exceed 50 mbar.
– After have ultimated the conversion of
the boiler, please stick onto the casing panel the plate showing the relevant fee­ding gas which is included into the kit.
NOTE: After assembling all the gas connec­tions, a test for gas tightness must be car­ried out using soapy water or special pro­ducts. Do not use naked flames. The conver­sion to different gas must be carried out exclusively by authorized technical personnel.
4.6 DISASSEMBLY OF EXPANSION VESSEL
To disassemble the expansion vessel, pro­ceed as follows (fig. 31): – Make sure that the water has been emp-
tied out of the boiler.
– Unscrew the connection (1) and the lock-
nut (5).
– Remove the bracket and the expansion
vessel (4).
NOTE: Before refilling the system, using a pressure gauge attached to the valve (3) make sure that the expansion vessel is preloaded at a pressure of 0.8 to 1 bar.
4.7 REMOVAL OF OUTER CASING
It is possible to completely disassemble the shell for an easy maintenance of the boiler following these simple instructions (fig. 32): – Remove the two screws and bracket (6)
locking the front panel to the sides.
– Pull the front panel forwards so as to
release it from the slot-in pins located on the sides.
– Unscrew the two screws fixing the instru-
ment panel to the sides.
– Unscrew the four screws fixing the sides
to the instrument panel support.
– Push the sides (3) and (4) upwards, sli-
ding them out of their slots.
90
Fig. 32
KEY 1 Self-tapping screw 2 Rear panel 3 L.H. side panel 4 R.H. side panel 5 Front panel 6 Fixing bracket
Fig. 31
KEY 1 Connection 3/4” 2 Expansion vessel 3 Preloaded valve 4 Fixin bracket 5 Locknut 1/2”
Fig. 30
KEY
1 Swivel connection 2 Locknut 1/2” 3 Burner manifold
4 Washer ø 6.1 5 Burners 6 Nozzle M6 7 Screw
25
20
15
10
8,1 (7.000) 11,6 (10.000) 17,4 (15.000) 23,2 (20.000)
POTENZA TERMICA kW (kcal/h)
PRESSIONE UGELLO mbar
30
35
5
29,0 (25.000)
25 30
Fig. 29/b
Pressure/heat output diagram for propane gas (G31)
HEAT OUTPUT kW (kcal/h)
NOZZLE PRESSURE mbar
WARNING: To ensure a perfect seal, always use the washer (4) supplied in the kit when replacing nozzles, even in bur­ner units for which it is not specified.
Page 20
4.8 CLEANING AND MAINTENANCE
At the end of each heating season, it is essential to have the boiler thoroughly checked and cleaned out. Proceed as follows: – Turn the main switch off to stop electric
power reaching the boiler and close the gas feed cock.
– Remove the outer casing as described in
section 4.7.
– Remove the gas burner manifold unit
(fig. 30).
– To clean the burner, blow in a jet of air, so
as to remove any dust particles that may have accumulated.
– Clean the heat exchanger, removing any
dust or residue from combustion.
– When cleaning the heat exchanger or
the burners, chemical products or steel brushes MUST NOT BE USED.
–
Make sure that the tops of the burners with the holes are free from encrusta­tions.
– Reassemble the items removed from
the boiler, making sure to follow the cor­rect sequence.
– Check the chimney to make sure that
the flue is clean.
– Check operation of the equipment and
the main burner.
– After assembly of all the gas connec-
tions, these must be tested for sound­ness, using soapy water or appropriate products. DO NOT USE NAKED FLAMES.
– Do not use calcium chloride to treat the
plastic component during generator maintenance.
Preventive maintenance and checking of efficient operation of equipment and safety devices must be carried out exclu­sively by authorized technical personnel.
4.8.1 Cleaning the C.H.
water filter (fig. 33)
To clean the filter, close the delivery/return on/off taps, turn off the power to the con­trol panel, remove the casing and empty the boiler using the drain provided (9 fig. 7) until the hydrometer shows “zero”. Place a con­tainer for collection underneath the filter, unscrew the cap and proceed to clean the filter, removing impurities and limestone deposits. Check the seal o-ring before reas­sembling the cap with the filter
4.9 FAULT FINDING
The burner does not ignite and the circu­lator is working.
– Check that the water pressure reads 1 -
1.2 bar. – The flowmeter is faulty, replace it. – The flow switch has been tripped becau-
se the heating circuit filter is obstructed with impurities; it needs cleaning.
Main burner does not start either to draw off D.H.W. or for heating.
– Check flowmeter; if necessary, replace it. – The smoke stat has tripped; reset it. – Check whether electric power is rea-
ching the gas valve actuator; check its operation and, if necessary, replace it.
– Check operation of the smoke pressure
switch (“BF” vers.).
– The fan is operating but at low rpm, so
failing to activate the smoke pressure switch (“BF” vers.); replace the fan.
– Replace the electronic card.
Boiler turns on, but after 10 seconds “locks out”.
– Check that during electric wiring the
position of line and neutral have not been
inverted. – The sensing electrode is faulty; replace it. – The control box is faulty; replace it.
Gas valve fails to modulate in D.H.W. and C.H. modes.
– The sensor is interrupted; replace it. – The modulator has a break in winding;
replace it. – Check that the current to the modulator
complies with the specifications – The electronic card is faulty; replace it.
Main burner fails to start in D.H.W. pro­duction mode.
– Unscrew completely the screw of the
pressure switch valve (5 fig. 7) – Check that the filter on the pressure
switch valve inlet is clean (3 fig. 7). – Mains water charge pressure is too low;
install water-lift system. – The microswitch of the pressure switch
valve is faulty; replace it.
D.H.W. is very hot but at low flow rate.
– Exchanger or D.H.W. outlet pipe obstruc-
ted by lime deposits; remove encrusta-
tions.
D.H.W. potentiometer and heating poten­tiometer fails to regulate properly.
– Check that the sensor in question is in
contact with the pipe; use silicone paste
to improve sensitivity. – The sensor in question is faulty; replace.
Boiler is noisy or heat exchanger makes a sizzling sound.
– Check whether circulation pump P is
obstructed; if necessary clear it out. – Unclog impeller of circulation pump, clea-
ring away any impurities or sediments.
– Circulation pump is burnt out or has a
lower rpm than required; replace it.
– Check boiler output is adequate for
actual needs of heating system.
Boiler safety valve keeps tripping.
– Check charge cock is closed. If it doesn’t
close properly, replace it.
–
Check system cold charge pressure is not too high; keep to recommended values.
– Check whether safety valve is out of cali-
bration; if necessary, replace it.
– Check whether the vessel is sufficiently
capacious to contain the water for the system.
– Check preloading pressure of expansion
vessel.
– Replace expansion vessel if faulty.
Radiators fail to heat up in winter.
– The rotary switch is on “Summer”; swit-
ch to “Winter”.
– The room stat is set too low or needs
replacing because faulty.
– The electrical connections of the room
stat are wrong.
– The microswitch of divertor valve is
faulty; replace it.
Main burner burns badly: flames too high, deep yellow.
– Check that pressure of burner gas is
regular. – Check burners are clean. – Check coaxial assembly has been instal-
led correctly (“BF” vers.).
Smell of unburnt gases.
– Check boiler is properly clean. – Check draught is sufficient. – Check gas consumption is not too high.
Boiler operates but does not increase temperature.
– Check gas consumption is not lower
than it should be. – Check boiler is clean. – Check boiler is sized in proportion to
system.
In the “FORMAT” boilers, upon demand for D.H.W. or heating, fan fails to turn at max speed.
– Make sure that the smoke pressure
switch is working and that the relative
contact is in the rest position. – Check whether connection tubes of
smoke pressure switch are obstructed
and, if necessary, clean away impurities
or condensate. – The smoke pressure switch needs repla-
cing. – Replace electronic board.
91
Fig. 33
Page 21
92
USER INSTRUCTIONS
WARNINGS
– In case of fault and/or incorrect equipment operation, deactivate it, without making any repairs or taking any direct
action. Contact the nearest Authorised Technical Service Centre.
– The installation of the boiler and any servicing or maintenance job must be carried out by qualified personnel. Under
no circumstances, the devices sealed by the manufacturer can be tampered with.
– It is absolutely prohibited to block the intake grilles and the aeration opening of the room where the equipment is
installed.
LIGHTING AND OPERATION
BOILER IGNITION
Open the gas valve and light the appliance by turning the rotary switch to summer position
(fig. 1). The green led indicates that electricity is being supplied to the appliance. – With the rotary switch in the summer
position , the boiler will start-up upon demand for domestic hot water, and run at full power to reach the selected tem­perature.
The gas feeding pressure will then auto­matically vary to ensure that the requi­red temperature is kept constant.
– With the rotary switch in the winter
position , once the boiler has reached the value set on the heating potentiome­ter, it will star t to modulate in automati­cally in order to supply the required power output to the system. The operation of the boiler will be stop­ped through the intervention of the ther­mostat or timer.
TEMPERATURES ADJUSTMENT
– The D.H.W. temperature can be adju-
sted by turning the knob of the D.H.W. potentiometer which has a range of between 40 to 60°C (fig. 2).
– The C.H. temperature can be adjusted by
turning the knob of the C.H. potentiome­ter which has a range of between 40 to 80°C. To ensure optimal boiler efficiency at all times, we recommend not to drop below a minimum working temperature of 50°C (fig. 2).
LOCK OUT RESET OF THE CONTROL BOX
If the burner does not ignite, the red lock out indicator will light up (fig. 3). In order to re-attempt boiler ignition, place the rotary switch to the position and release it immediately, then turn it back to the summer or winter .
Should the appliance again “lock out”, please approach the authorized technical staff.
Fig. 1
Fig. 2
OPEN
306090
0
°C
120
bar
034
1
APRE
Page 22
TURNING OFF BOILER
To turn off the boiler set the switch to “OFF” and close the gas-feeding pipe tap if the boi­ler remains inoperative for a long period (fig. 1).
SYSTEM FILLING (
fig. 4)
Check periodically that the thermomanome­ter shows a reading of between 1 - 1.2 bar (1), with the system cold.
If the pressure drops below the blue scale (1), the boiler will not operate. To re-set the pressure, rotate the char­ging valve to the anticlockwise direction until the thermomanometer reading re­enters the blue scale (1).
Once this operation is completed, make sure the tap is closed. In case the pressure goes above the limit, empty the exceeding pressure by opening the pressure relief valve on any radiator. The blue part of the scale (2) indicates the
working pressure range with the heating in operation. Should the pressure exceed the values of the blue scale (2), causing the safety valve intervention, call the authorized technical staff.
"25 OF - 30 OF" SMOKE SAFETY DEVICE
This is a safety device against possible smoke emission into the ambience. The safety device switches off the gas valve when the return of the smokes into the ambience is continuous and then dange­rous. The intervention of this device locks out the appliance because the burner is not ignited. In this case, turn the rotary switch to the
position
(fig. 3)
nd release it imme-
diately, then turn it back to the summer or winter .
Should the boiler “lock out” again, you must call the authorized technical staff.
GAS CONVERSION
Should it be necessary to convert the appliance to a dif ferent gas from the one for which the boiler has been equipped, approach the technical staff.
CLEANING AND MAINTENANCE
At the end of each heating season, it is essential to have the boiler thoroughly checked and cleaned out.
Preventive maintenance and checking of the efficient operation of the equipment and safety devices must be carried out exclusively by the authorized technical staff.
The boiler is supplied with an electric cable. Should this require replacement, contact exclusively with the authorized technical staff.
TIME PROGRAMMER (optional)
With the selector in the “AUTO” position, the boiler operation is regulated according to the temperatures set for the program­med time periods. During star t-up, the second selector must be in the “RUN” position. Programming:
– Setting the time (fig. 5)
Move the selector to “”. To change the hour on the display, press the “h” button, to change the minutes, press the “m” button. To set the day, press button “1...7” until the arrow points to the correct day (1 =
Monday ....... 7 = Sunday).
– Setting the programme (fig. 6)
The programmer has 8 start-up pro­grammes and 8 shutdown options. To make programming easier, 3 star t-up and 3 shutdown programmes have already been set up for each day of the week, as follows:
NOTE:Programmes from 7 to 16 are not pre-set.
To select programmes other than those pre-set, move the selector to the “P” position: “0:00 1” will appear on the display: the first three figures indicate the hour and minutes, the fourth figure is the number of the programme. Programmes with odd numbers are swit­ch-on times (daytime temperature) and are indicated on the display by a light bulb symbol. Programmes with even numbers indicate the temperature reduction (night). Use button “1...7” to select the day of the week (from 1 to 7), or the period (1 ÷ 5, 6 - 7; 1 ÷ 6; or every day if the program­me has to be repeated every day of the week). Set the hour and minutes using buttons “h” and “m”. The operation in memorized by pressing button “P”
93
Fig. 3
Fig. 4
Programa Hora de Hora de
encendido apagado 1 06.00 ­2 - 09.00 3 12.00 ­4 - 14.00 5 18.00 ­6 - 22.00
Fig. 5
BLUE SCALE (1)
BLUE SCALE (2)
OPEN
SCALA COLORE AZZURRO
60
30
90
120
0
°C
bar
0
4
1
3
60
30
90
0
120
°C
bar
0
4
1
3
SCALA COLORE BLU
APRE
Page 23
The display then changes to the further programme. Repeat the same opera­tions to set the successive programmes. At the end of the programming. Move the selector to the “RUN” position.
– Cancelling one or more
programmes (fig. 7) The programmed switch-on time and switch-off time must be cancelled for each individual programme by moving selector (2) to the “P” position. Select the required programme with but­ton (3), press button (4) to cancel the settings for that day (the triangular day indicator should disappear). If a par t of the programme is cancelled, when selector (2) is returned to the “RUN” position, an error message will appear on the clock display together with an indication of the incorrect program­me. To cancel all the programmes, move
the selector to the “P” position and press buttons (3) and (5) simultaneously.
– Setting the “SKIP” function (fig 7)
The SKIP function defused the program­mes when going out for the day, during which no heating is required. To start this function, press button (7);
the button is only active when selector (2) is in the “RUN” position.
Once selected, the SKIP function beco­mes active at 0:00 of the following day and lasts for 24 hours. Once activated, it cannot be defused. Consequently the normal programme will only be resumed after 24 hours.
94
KEY 1 Manual/automatic operation selector 2 Programmer/timer setting selector 3 Programme button 4 Day button 5 Hour button 6 Minute button 7 SKIP function button 8 Reset button
Fig. 6
Fig. 7
Loading...