Follett equipment may be returned for credit under the following conditions:
1. The equipment is new and unused.
2. A return authorization number has been issued by customer service within 30 days after shipment.
3. Follett receives the equipment at the factory in Easton, PA within 30 days after issuance of the return authorization number.
4. The equipment must be returned in Follett packaging. If the packaging has been damaged or discarded, Follett will forward, at the customer’s expense,
new packaging.
Note: Return freight charges are the responsibility of the customer. If equipment is returned and is damaged because of improper packaging,
Follett Corporation will not be held responsible.
Credit will be issued when:
The equipment has been inspected by Follett and deemed suitable to be returned to stock.
Note: A 15% restocking charge will be deducted from the credit. If the cost to return the product to stock exceeds 15%, the actual cost will be deducted.
3
Welcome to Follett
Follett ice dispensers enjoy a well-deserved reputation for excellent performance, long-term reliability and
outstanding after-the-sale support. To ensure that this dispenser delivers that same degree of service, we ask that
you take a moment to review this manual before beginning the installation of the dispenser. Should you have any
questions or require technical help at any point, please call our technical service group, (800) 523-9361 or
(610) 252-7301.
Before you begin
After uncrating and removing all packing material, inspect the equipment for concealed shipping damage. If
damage is found, notify the shipper immediately and contact Follett Corporation so that we can help in the filing of
a claim, if necessary.
Check your paperwork to determine which model you have. Follett model numbers are designed to provide
information about the type and capacity of Follett ice dispensing equipment. Following is an explanation of the
different model numbers in the VU300 series.
VU300B8LP
Ice and valve actuation
Model series
Tower side (facing unit)
L – Left hand side
R – Right hand side
D – Dual-sided
Beverage cooling
B – Integral beverage cooling
K – Integral beverage cooling with cold carbonation
M – No beverage cooling
P – Pushbutton
L – Lever
Number of valves
8, 10 or 20
Important cautions
!
Storage area of dispenser contains mechanical, moving parts. Keep hands and arms clear of
this area at all times. If access to this area is required, power to unit must be
disconnected first.
Ice is slippery. Maintain counters and floors around dispenser in a clean and ice-free condition.
Ice is food. Follow recommended cleaning instructions to maintain cleanliness of delivered ice.
Always disconnect power before cleaning or servicing the dispenser.
Failure to remove all sanitizer may result in health hazard.
Follett manual load dispensers can accommodate most cube/cubelet ices up to 1" square, or Follett
compressed nugget ice. Crushed, flake, bagged, nugget or congealed ice cannot be used. Use of
these ices can jam dispenser and void warranty. Separate any “waffle-like” sections of cubes before
adding to dispenser. For ice compatibility questions, please call Follett customer service at
(800) 523-9361 or (610) 252-7301.
4
Specifications
Electrical
Each dispenser requires a separate circuit with electrical disconnect within 10 ft (6m). Equipment ground required.
Standard electrical – 115V, 60Hz, 1 phase. Maximum dispenser fuse – 20 amps, maximum icemaker fuse – 20
amps each. Cord and plug provided with each dispenser.
Model Icemaker Dispenser
number amperage amperage
Single-sided models
VU300M series 11.0 amps ea (2) 6.0 amps
VU300B series 11.0 amps ea (2) 7.0 amps
Dual-sided models
VU30020MD series 11.0 amps ea (2) 8.0 amps
Plumbing
Dispenser 3/4" PVC pipe nipple for bin drain
3/4" PVC pipe nipple for drain pan drain
1" ID hose for beverage bath drain
Beverage connections
1/4" ID syrup beverage hose
3/8" ID carbonated water beverage hose
3/8" ID plain water beverage hose
Note: Drains should be hard piped and insulated. Maintain at least 1/4" per foot (6mm per 304mm run)
slope on drain line run.
Water disconnect within 10 feet (3m) of dispenser is suggested for automatic load units.
Follett recommends use of a Follett water filter (part# 00130229) on icemakers connected to automatic fill dispensers.
IcemakerRefer to detailed specifications in icemaker installation manual
packed with icemaker
5
Dimensions and clearances
Single-sided dispensers
Required clearances
60" (1524mm) minimum above counter for installation if dispenser will be dropped into counter
49" (1245mm) minimum above counter for auger removal
12" (305mm) minimum on ice chute side for service
12" (305mm) minimum on side opposite ice chute if ice transport tube enters this side
12" (305mm) minimum between dispenser side(s) and optional icemaker(s)
40.875
(1039mm)
Front View
(shown with two Chewblet
MC400A auto-fill icemaker kits)
ice transport
tube
17"
(432 mm)
18.875"
(479mm)
®
counter top
6"
min
Side View
electrical
conn.
disp.
drains
18.875"
(479mm)
Dispenser with 1 optional auto-fill icemaker kit(s)
Dispenser with 2 optional auto-fill icemaker kit(s)
12"
min
24.62"
(626mm)
25.25"
(642mm)
54.875"
(1394mm)
29.625"
(753mm)
Manual load unit
32.375"
(823mm)
ice waterbath
(VU300B only)
beverage
lines
1/2" ID drain tube
bin signal
power
10"
(254mm)
ice transport
tube entry
8.5"
(216mm)
27.5"
(699mm)
3/4" FPT
drain
30"
(762mm)
15"
(381mm)
2"
(51mm)
3/4" drain
nipple
6
Dual-sided dispensers
Required clearances
60" (1524mm) above counter for installation if dispenser will be dropped into counter
49" (1245mm) above counter for all units after installation for auger cleaning and servicing
12" (305mm) on dispense chute side of all models for connections
12" (305mm) on side opposite dispense chute if ice transport tube enters side opposite chute
12" (305mm) on side opposite dispense chute on all dual-sided dispensers for connections
ice
transport
tube
17"
(432 mm)
Front View
6"
min
®
18.875"
(479mm)
(shown with two Chewblet
MC400A auto-fill icemaker kits)
18.875"
(479mm)
43.875
(1115mm)
counter top
beverage lines
exit through
bottom of chase
electrical
connections
12"
min
Manual load unit
Dispenser with 1 optional auto-fill icemaker kit(s)
Dispenser with 2 optional auto-fill icemaker kit(s)
12" min.
(305mm)
25.25"
(642mm)
54.875"
(1394mm)
29.625"
(753mm)
Ice dispense chute side viewIce dispense chute opposite side view
32.375"
(823mm)
16.875"
(429mm)
beverage
lines exit
through bottom
of chase
bin signal
power
10"
(254mm)
7
13.25"
(337mm)
alt. ice
transport
tube
entry
13.25"
(337mm)
27.5"
(699mm)
3/4"
drain
nipple
3/4" FPT
drain
30"
(762mm)
ice tube
entry
27.5"
(699mm)
15"
(318mm)
Installation
Installing dispenser in counter
Note: All dispensers must be supported from below with supplied 4" – 6" (102 – 153mm) adjustable leg accessory,
or equivalent. Do not hang dispenser on flange.
All dispensers must be installed level in both directions to ensure proper operation.
1. Check that dispenser location meets all requirements in this manual and cut counter as shown.
Plan View
Single-sided dispensers
counter cut-out
Shaded area is additional cut-out required for
slide-in installations only
30.375"
(772mm)
38.5"
(978mm)
Min.
33"
(839mm)
flat
surface
Dual-sided dispensers
Dual-sided dispensers cannot be slid into counter unless
raised above counter. Call factory for details.
30.375"
(772mm)
Plan View
counter cut-out
42.5"
(1080mm)
38.5"
(978mm)
11.625"
(296mm)
7.125"
(181mm)
11.625"
(296mm)
Min.
33"
(839mm)
flat
surface
2. Place support blocks in cabinet to raise dispenser to a height of 12" (305mm).
3. Place dispenser in counter onto support blocks.
4. Attach adjustable legs to dispenser.
5. Remove support blocks and lower dispenser feet to floor.
6. Adjust legs for 1/8" (4mm) clearance between dispenser lip and countertop to verify there is no load on flange.
7. Apply a bead approximately 1/4" (6mm) in diameter of NSF-listed silicone sealant (Dow Corning RTV-732 or
equivalent) around perimeter of dispenser where it meets counter. Smooth sealant to a 1/8" (4mm) radius.
8. Install a PVC drain line with at least a 1/4" per foot (20mm per 1m) slope. Insulate drain line to prevent
condensation.
Note:Do not apply excessive heat if any sweating of fittings is necessary. Heat conduction through metal may melt threads in plastic drain.
Do not reduce drain line size or tie drains together.
9. Make electrical connections in accordance with applicable wiring diagrams provided. Provide disconnects within
10 ft (3m) of dispenser and icemaker for servicing.
8