If this replace is not properly installed, a
house re may result. For your safety, follow
the installation instructions. Contact local
building or re ofcials about restrictions
and installation inspection requirements in
your area.
SERIAL #
INSTALLATION
AND OPERATING
TESTED and LISTED to CAN/ULC
S610-M87 AND UL 127
Meets the Environmental Protection
Agency's July 1990 Particulate Emission
Standards
NOTE:
WE STRONGLY
RECOMMEND THAT
SMOKE DETECTORS BE
INSTALLED.
If smoke detectors have been previously installed, you may notice that
they are operating more frequently.
This may be due to curing of replace
paint or fumes caused by accidentally
leaving the re door open. Do not
disconnect the detectors. If necessary, relocate them to reduce their
sensitivity.
SAFETY NOTICE:
If this replace is not
properly installed, a
house re may result.
For your safety, follow the installation
instructions. Contact
local building or re
ofcials about restrictions and installation
inspection requirements in your area.
Please read this entire manual before
you install and use your new room
heater. Failure to follow instructions
may result in property damage, bodily
injury, or even death.
Contents
Safety and Maintenance.............................................................. 3
WARNING: DO NOT SUBSTITUTE GLASS WITH ANY
OTHER TYPE MATERIAL OTHER THAN CERAMIC
GLASS
Maintenance
1. Burn only, dry and well seasoned cord wood. The
denser or heavier the wood when dry, the greater its heat
value. This is why hardwoods are generally preferred.
Green or wet wood should not be used, it will reduce heat
output, as well as, contribute signicantly to creosote
buildup.
WARNING: NEVER USE CHEMICALS OR ANY OTHER
VOLATILE LIQUID TO START A FIRE. DO NOT BURN
GARBAGE OR FLAMMABLE FLUIDS SUCH AS
GASOLINE, NAPHTHA, OR ENGINE OIL. WE STRONGLY
RECOMMEND THAT SMOKE DETECTORS BE
INSTALLED.
2. Maintain a 1"(25mm) minimum ash base for best results.
The area where boost combustion air enters the rebox
must be kept clear of excessive ash buildup which will
block air ow. This area is at the front of the rebox.
Remove ashes if excess buildup occurs. Embers may roll
out of the rebox door opening and create a re hazard.
3. If glass becomes darkened through slow burning or poor
wood, it can be cleaned with replace glass cleaner
when the replace is cold. Never scrape with an object
that might scratch the glass. The type and amount of
deposit on the glass is a good indication of the ue pipe
and chimney buildup. A light brown dusty deposit that is
easily wiped off usually indicates good combustion and
dry, well-seasoned wood and therefore relatively clean
pipes and chimney. On the other hand, a black greasy
deposit that is difcult to remove is a result of wet and
green wood and too slow a burning rate. This heavy
deposit is building up as quickly in the chimney.
4. Establish a routine for the fuel, wood burning and
ring technique. Check daily for creosote buildup until
experience shows how often you need to clean to be safe.
WARNING: ONLY USE MATERIALS AND COMPONENTS
SUPPLIED OR SPECIFIED BY MANUFACTURER WHEN
DOING MAINTENANCE OR REPLACEMENTS. DO NOT
USE A FIREPLACE INSERT OR OTHER PRODUCTS NOT
SPECIFIED FOR USE WITH THIS FIREPLACE.
5. DOOR GASKETS - The gasket used by Pacic Energy
(3/4"(19mm) round high density breglass rope) requires
only light pressure to seal. This will prolong seal life. It
is important that the door seal be maintained in good
condition. Periodically inspect seals and replace if
necessary with WODC.NEODGKIT.
6. DOOR GLASS - Replacement glass can be obtained
from your dealer. Use 18”(457mm) x 10-1/4”(260mm) x
5 mm ceramic glass only.
WARNING: DO NOT SLAM LOADING DOOR OR
OTHERWISE IMPACT GLASS. WHEN CLOSING DOOR,
MAKE SURE THAT NO LOGS PROTRUDE TO IMPACT
THE GLASS. IF THE GLASS GETS CRACKED OR
BROKEN, IT MUST BE REPLACED BEFORE USING
THE FIREPLACE.
WARNING: OVER FIRING THE APPLIANCE WILL
SHORTEN THE LIFE OF THE PRODUCT. FAILURE
TO RECTIFY AN OVER FIRING CONDITION CAN BE
HAZARDOUS AND MAY VOID THE MANUFACTURER'S
WARRANTY.
To remove broken glass,remove the door gasket and clean out
the screw heads. Remove the screws that hold the retainers
and remove the retainers, noting position for re-assembly.
Remove all particles of glass . Be careful as they are very
sharp. Install new glass complete with gasket. Replace
retainers, screws and gasket.
CAUTION:
- DO NOT OVERTIGHTEN - TIGHTEN SCREWS HAND
TIGHT
- DO NOT CLEAN GLASS WHEN HOT
- DO NOT USE ABRASIVE CLEANERS ON GLASS
7. Do not store wood within heater installation clearances, or
within the space required for fuel loading and ash removal.
Keep the area around the heater clean and free of loose
combustibles, furniture, newspapers, etc.
8. Be aware that the hotter the re, the less creosote is
deposited. Weekly cleaning may be necessary in mild
weather, even though monthly cleaning is usually enough
in the coldest months when burning rates are higher.
9. Instruct all members of your family on the safe operation
of the heater. Ensure they have enough knowledge of the
entire system if they are expected to operate it. Stress the
section on chimney res and the importance of following
the steps outlined "In Case of Chimney Fire".
10. Inspect and clean your chimney system at the beginning
of the burning season before your rst re and at least
every two months during the burning season. Inspect
the interior and exterior of the pipe for defects and/or
damage. Remove and inspect the rain cap. Refer to the
chimney system manufacturer's installation instructions
for the procedure to remove and or replace any necessary
components to the chimney system.
11. Maintain a distance of 48"(1.22m) to all combustible
materials in the room unless otherwise specidifed.
(see Floor Protector section on page 19 for Floor Protection
Check the following parts for damage such as cracks, excessive corrosion, burned out sections and excessive warping:
(See website for descriptions and more detail)
Weekly:
- Firebrick - Visual, for cracking.
- Door Gasket - sagging, displacement, damage.
Monthly
- Brick rail tabs and brick rails.
- Air riser tube in the back of the rebox.
- Back side of airwash chamber.
- Bafe locking pin.
- Boost tube cover.
When Cleaning the
Chimney System:
- Top bafe board/blanket.
- Bafe.
- Top heat shield and mounting bolt.
- Bafe Gasket.
- Brick Rails.
- Manifold.
Blowers:
- The blowers should be cleaned out a annually or more often if required by using a vacumn on the intakes on the side of
the blower to remove any dust and debris. The blower is accessed by removing both the outer and inner surrounds.
Bafe:
- Some warping of the bafe is normal(up to 1/4” or .65cm).
- Replace if the bafe has permanent warping greater than this or has cracking or breakage.
- Please contact your Dealer if you experience any of the damage listed above. Continuing to operate your replace with
broken parts may accelerate damage to other parts and may void your warranty
When wood is burned slowly, it produces tar and other organic
vapours, which combine with expelled moisture to form
creosote. The creosote vapours condense in the relatively
cool chimney ue of a slow burning re. As a result, creosote
residue accumulates on the ue lining. When ignited, this
creosote makes an extremely hot re. The chimney connector
and chimney should be inspected periodically (at least once
every two months) during the heating season to determine if
a creosote buildup has occurred. If creosote has accumulated
(3 mm. or more), it should be removed to reduce the risk of
a chimney re.
1. The highest smoke densities occur when a large amount
of wood is added to a bed of hot coals and the air inlet is
closed. The heated wood generates smoke, but without
ample air, the smoke cannot burn. Smoke-free, clean
burning requires smaller fuel loads, two or three logs at
a time or 1/4 to 1/2 of fuel load and leaving the air inlet
relatively wide open, especially during the rst 10 to 30
minutes after each loading, when most of the smoke
generating reactions are occurring. After 30 minutes or
so, the air inlet can be turned down substantially without
excessive smoke generation. Wood coals create very
little creosote-producing smoke.
2. The cooler the surface over which the wood smoke is
passing, the more creosote will be condensed. Wet
or green wood contributes signicantly to creosote
formation as the excess moisture that is boiled off cools
the re, making it difcult for the tars and gases to ignite,
thus creating dense smoke and poor combustion. This
moisture-laden smoke cools the chimney, compounding
the problem by offering the smoke the ideal place to
condense.
In summary, a certain amount of creosote is inevitable
and must be lived with. Regular inspection and cleaning
is the solution. The use of dry, seasoned wood and ample
combustion air will help to minimize the buildup.
Chimney Fires
The result of excessive creosote buildup is a chimney re.
Chimney res are dangerous. Temperatures inside the
chimney can exceed 2000° F(1093˚C). This causes much
higher than normal temperatures on its exterior surfaces.
Thus ignition of nearby or touching combustible material is
more likely during a chimney re. Proper clearances are
critical during such a re.
Chimney res are easy to detect; they usually involve one
or more of the following:
-Flames and sparks shooting out of the top of the chimney
-A roaring sound
-Vibration of the chimney
In the event of a Chimney Fire
1. Prepare to evacuate to ensure everyone's safety. Have
a well understood plan of action for evacuation. Have a
place outside where everyone is to meet.
2. Close air inlet on replace.
3. Call local re department. Have a re extinguisher handy.
Contact your local municipal or provincial re authority
for further information on how to handle a chimney re.
It is most important that you have a clearly understood
plan on how to handle a chimney re.
4. After the chimney re is out, the chimney system must be
cleaned and checked for damage before starting another
re. Have the system inspected by a certied installer or chimney sweep. Also check combustibles around the
chimney and the roof.
Preventing a Chimney Fire
There are three things you can do to prevent chimney res:
1. Do not let creosote build up to a point where a chimney
re is possible.
2. Do not have res in the heater that may ignite chimney
res. These are very hot res, such as when burning
household trash, cardboard, Christmas tree limbs, or
even ordinary fuel wood; (e.g.. with a full load on a hot
bed of coals and with the air control open for long period
of time.)
3 Regular inspections and cleaning.
- The services of a competent or certied installer, (certied
by the Wood Energy Technical Training program (WETT) - in
Canada, Hearth Education Foundation (HEARTH) - in U.S.A.,)
are strongly recommended.
Wood Selection
This heater is designed to burn natural wood only. Higher
efciency and lower emissions generally result when burning
air-dried seasoned hardwoods, as compared to softwoods
or to green or freshly cut hardwoods.
Wood should be properly air dried (seasoned) for six months
or more. Wet or undried wood will cause the re to smoulder
and produce large amounts of creosote. Wet wood also
produces very little heat and tends to go out often.
Do not burn anything but wood. Other fuels, eg. charcoal,
can produce large amounts of carbon monoxide, a tasteless,
odourless gas that can kill. Under no circumstances should
you attempt to barbecue in this heater.
How to Test Your Wood
Add a large piece of wood to the replace when it has a large
hot bed of coals. It is dry if it is burning on more than one
side within one minute. It is damp if it turns black and lights
within three minutes. If it sizzles, hisses and blackens without
igniting in ve minutes it is soaked and should not be burnt.
CAUTION: HOT WHILE IN OPERATION. KEEP CHILDREN,
CLOTHING AND FURNITURE AWAY. CONTACT WILL
CAUSE SKIN BURNS.
WARNING: OVER FIRING THE APPLIANCE WILL
SHORTEN THE LIFE OF THE PRODUCT. FAILURE
TO RECTIFY AN OVER FIRING CONDITION CAN BE
HAZARDOUS AND MAY VOID THE MANUFACTURER'S
WARRANTY.
DO NOT OVER FIRE THIS HEATER: ATTEMPTS TO
ACHIEVE HEAT OUTPUT RATES THAT EXCEED HEATER
DESIGN SPECIFICATIONS CAN RESULT IN PERMANENT
DAMAGE TO THE HEATER AND CHIMNEY AND MAY VOID
MANUFACTURERS WARRANTY.
CAUTION: Never use gasoline, gasoline type lantern fuel,
kerosene, charcoal lighter uid or similar liquids to start or
"freshen up" a re in this heater. Keep all such liquids well
away from the heater while it is in use.
DO NOT BURN :
-Salt water wood * -Treated wood
-Wet or green wood -Coal charcoal
-Garbage/Plastic * -Solvents
* These materials contain chlorides which will rapidly
destroy metal surfaces and void warranty.
Your PACIFIC ENERGY heater is designed for maximum
overall efciency at a moderate ring rate. Over ring is
hazardous and a waste of fuel. Too slow a burn contributes
to creosote buildup and lowers combustion efciency.
NOTE: Left and Right as referred to in this manual are
considered your left and right when facing the front of the
replace.
Lighting for the First Time
Curing of the Paint Finish/Insulation
To achieve the best nish, the paint on your replace must
be baked on. When burning your replace for the rst 2-3
times it is very important that the room be well ventilated.
Open all windows and doors. Smoke and fumes caused by
the curing process may cause discomfort to some individuals.
Lighting a Fire
WARNING: Never use chemicals or any other volatile
liquid to start a re.
1. Adjust the air control located under the ashshelf to
"High"(Full Left) position and open door.
2. Place crumpled newspaper in the centre of the heater
and crisscross with several pieces of dry kindling. Add
a few small pieces of dry wood on top.
3. Ignite the paper and close the door. (Depending on length
of chimney installation, you may need to leave door open
approximately 1/2"(13mm) until kindling is fully ignited.)
DO NOT LEAVE FIREPLACE UNATTENDED WHILE
DOOR IS OPEN.
4. After the re has established itself, open the door and
add a few small logs. Close door.
5. Begin normal operation after a good coal base exists and
wood has charred.
1. Set the air control to a desired setting. If smoke pours
down across the glass (waterfall effect) this indicates you
have shut the control down too soon or you are using too
low a setting. The wide range control makes nding the
desired setting easy. As every home's heating needs vary,
(ie. insulation, windows, climate, etc.) the proper setting
can only be found by trial and error and should be noted
for future burns.
2. To refuel, adjust air control to "High"(Full Left) position,
and give the re time to brighten. Open the door slowly,
this will prevent back pufng.
3. Use wood of different shape, diameter and length
(recommended 18”(457mm)). Load your wood and try
to place the logs so that the air can ow between them.
Always use dry wood.
4. Do not load fuel to a height or in such a manner that would
be hazardous when opening the door.
5. For extended or overnight burns, unsplit logs are preferred.
Remember to char the wood completely on maximum
setting before adjusting the air control for an overnight
burn.
WARNING: Always keep the loading door closed when
burning. This heater is not designed for open door
burning. If unit is operated with the door open, gases
and ame may be drawn out of the replace opening
creating risks of both re and smoke.
WARNING: No alteration or modification of the
combustion air control assembly is permitted. Any
tampering will void warranty and could be very hazardous.
WARNING: Do not use grates or andirons to elevate the
fuel. Burn directly on the re bricks. Replace broken or
missing bricks. Failure to do so may create a hazardous
condition.
Restarting After Extended or Overnight
Burns
1. Open door and rake any hot embers towards the front of
the heater. Add a couple of dry, split logs on top of the
embers, close the door.
2. Adjust the air control to the "High" position (all the way
to the left) and in just a few minutes, logs should begin
burning.
3. After the wood has charred, reset the air control to the
desired setting.
4. To achieve the maximum ring rate, set the air control
to high. Do not use this setting other than for starting or
preheating fresh fuel loads.
Over ring can be caused by the following; operating the
unit with the door open, damage to door gaskets allowing
excess air to enter the rebox, the use of kiln dried lumber,
mill ends or paper waste and prolonged or continual use on
a high burn setting.
Bafe Removal
DO NOT OPERATE WITH BAFFLE ASSEMBLY OR
INSULATION REMOVED.
Average Heat Output Calculation
Seasoned wood has approximately 7500 BTU's per pound.
The calculation is as follows:
Amount of wood in lbs. X 7500BTU’s
Burn rate in Hrs.
Experience will give you the right settings for proper
combustion and efcient burning. Remember the correct air
inlet setting is affected by variables such as type of wood,
outside temperature, chimney size and weather conditions.
With practice, you will become procient in operating your
heater and will obtain the performance for which it was
designed.
X .8(80% Avg. Eciency)
Proper Draft
• Draft is the force which moves air from the appliance up
through the chimney. The amount of draft in your chimney
depends on the length of the chimney, local geography,
nearby obstructions and other factors.
• Too much draft may cause excessive temperatures in
the appliance. An uncontrollable burn or a glowing red
replace part or chimney indicates excessive draft.
• Inadequate draft may cause back pufng into the room
and plugging of the chimney. Smoke leaking into the
room through appliance and chimney connector joints
indicates inadequate draft.
Ash Removal
Caution: Ashes are to be removed only when the heater
is cold. Whenever ashes get 3(76mm) to 4(102mm) inches
deep in your rebox, remove excess ashes. Leave an ash
bed approximately 1" (25 mm) deep on the rebox bottom
to help maintain a hot charcoal bed.
Disposal of Ashes
Ashes should be placed in a metal container with a tight tting
lid. The closed container of ashes should be placed outside
on a non-combustible oor or on the ground, well away from
all combustible materials, pending nal disposal. If the ashes
are disposed of by burial in soil or otherwise locally dispersed,
they should be retained in closed container until all cinders
have thoroughly cooled. Other waste should not be placed
in this container.
WARNING: AFTER YOU REMOVE THE BAFFLE,
ALWAYS COVER THE TOP OF THE BAFFLE AIR
TUBE LOCATED IN THE REAR OF THE FIREBOX.
THIS PREVENTS DEBRIS FALLING DOWN THE
TUBE. FAILURE TO DO SO WILL RESULT IN POOR
OPERATION AND POSSIBLE DAMAGE TO FIREPLACE
COMPONENTS.
BAFFLE
TUBE
Remove retaining pin located just beneath the bafe at the
rear inside top of the rebox. Lift bafe up and pull forward
to disconnect from the supply tube. Slide the bale to one
side and then tilt bafe sideways to drop down and remove
from rebox. To re-install the bafe, perform the removal
steps in the reverse order. Ensure that the two side pieces
of insulation are set tight against the bafe. If the insulation
is damaged during removal, it should be replaced.
Secondary Air Box Cleaning
1. The secondary air box access is located on the bottom
rear of the replace and can be accessed for cleaning by
removing the two bottom center bricks inside the replace
Fig. #1. This will expose the access cover.
2. Remove the screws securing the access cover to the
rebox bottom. Inspect airbox for debris. If debris is
present, carefully use a vacum to suck debris through
the hole in the rebox bottom.
3. Replace the cover plate and the bricks.
FIG. # 1
Blower Operation
The blowers are wired with a thermo switch that will turn on
the blower automatically once the replace has reached an
appropriate operating temperature.
The blowers must be wired to a wall switch or fan speed
controller for manual control(not included). If a blower should
ever need to be replaced, power to the blowers can be shut
off at the switch during replacement.
If glass becomes darkened due to poor burning conditions,
it can be cleaned with replace/ceramic glass cleaner when
the replace is cold. Never scrape with an object that might
scratch the glass. The type and amount of deposit on the
glass is a good indication of ue pipe and chimney buildup.
A light brown dusty deposit that is easily wiped off usually
indicates good combustion and dry, well-seasoned wood and
therefore relatively clean pipes and chimney. On the other
hand, a black greasy deposit that is difcult to remove is a
result of green wood or poor draft. NOTE: This heavy deposit
is building up just as quickly in the chimney.
Blower Replacement
1. Remove the surround front by lifting and pulling away
from the unit. Remove the four screws securing the back
surround to the brackets and set the surround aside carefully to avoid damage.
FIG. # 3
FIG. # 2
BOLTS
2. With a 3/8” wrench, loosen the two bolts securing the
blower mounting bracket to the unit. Fig. #2
3. Disconnect the two wires leading to the blower motor.
4. Lift the blower mounting bracket up and pull the top out
rst and then lift the blower up and out to remove from the
bolts.If replacing the right side blower, then disconnect
the two wires leading to the thermo-switch at this time as
well.
BOLTS
FIG. # 4
Thermo
Switch
Electrical Rating : 115 V, 60 Hz, 1.1A
Blowers
5. Remove the three bolts securing the blower to the mounting bracket and replace the blower. Fig. #3
6. Reverse all previous steps to reinstall the new blower.
This package contains 18 full-size rebricks, as well as 5 various cut-size bricks.
With the heater in the upright position, install rebricks as follows:
- Place 6 full-size rebricks and bricks C & D on the bottom of the heater rst in the pattern shown below.
- Next, install the rear rebricks, 4 full-size, two on each side of the bafe tube.
- Then place 1 brick C in the back left corner as shown below.
- Lastly, install 4 full-size rebricks and brick B as shown on each side of the rebox.
B
C
D
A
B
ITEM DIMENSIONS PART NUMBER
A 9” X 4 1/2” X 1 1/4” (230 mm x 115 mm x 32 mm) 5096.99
B 4 1/2” X 4 1/2” X 1 1/4” (115 mm x 115 mm x 32 mm) 7847
C 2 1/4” X 9” X 1 1/4” (57 mm x 230 mm x 32 mm) 7847.3
D 2 1/4” X 4 1/2” X 1 1/4” (57 mm x 115mm x 32 mm) 7847.1
2) Remove the screws securing the replace to the pallet(4).
3) Remove from pallet bottom.
Warning: Under no circumstances is this heater to be installed
in a makeshift or "temporary" manner. It may be red only
after the following conditions have been met.
- DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE
SERVING ANOTHER APPLIANCE.
- WARNING:DO NOT INSTALL IN A SLEEPING ROOM.
(MANUFACTURED OR MOBILE HOME ONLY)
- The services of a competent or certied installer, (certied
by the Wood Energy Technical Training program (WETT)
- in Canada, Hearth Education Foundation (HEARTH) - in
U.S.A.,) are strongly recommended.
Locating The FP25 Fireplace
The best location to install your replace is determined by
considering the location of windows, doors, and the trafc
ow in the room where the FP25 Fireplace is located,
allowing space in front of the unit for the hearth extension
and the mantel, and taking into consideration the location
of the chimney. Ideally, you should choose a location
where the chimney will pass through the house without
cutting oor or roof joists.
Clearances
Clearances to combustible surfaces and materials are shown
on pages 11 & 16.
Clearances may be reduced with various heat insulating
materials. Consult local, National re codes and authorities
for approval.
Procedure:
Note: See "Combustion Air" section on page 17.
MAINTAIN CLEARANCES TO COMBUSTIBLES AS
SPECIFIED IN THE INSTALLATION INSTRUCTIONS
CAUTION: THE STRUCTURAL INTEGRITY OF THE
FLOOR, WALL AND CEILING/ROOF MUST BE
MAINTAINED.
THE SPACE HEATER MUST BE CONNECTED TO A
FACTORY-BUILT CHIMNEY CONFORMING TO CAN/
ULC-S629 OR UL 103HT STANDARDS FOR 650C
FACTORY-BUILT CHIMNEYS.
1. Position replace and oor protection in accordance
with the clearances as stated on the label and in these
installation instructions.
2. Mark the position for the hole for the chimney in the
ceiling and roof by using a string and plumb-bob.
Check the adequacy of the oor by rst estimating the
weight of the replace system(approx. 500lbs(227Kg)).
Next measure the area the replace will occupy. Note the
oor construction and consult your local building code to
determine if any additional support is needed. In most
cases, no additional oor support is needed for the FP25
replace.
The FP25 replace may be installed directly on a
combustible oor or on a raised base. A minimum of
84"(2.13m) measured from the base of the appliance or
38 3/4"(984mm) from the top of the unit to the ceiling is
required.
The FP25 replace may not be installed in a factory built
replace unless tested with the replace.
Wind direction and magnitude can play a factor in the
chimney performance. Therefore the chimney outlet
position is important when locating the replace
We recommend, whenever possible, that the chimney
should:
• Penetrate the highest part of the roof.
• Be installed as far as possible from roof offsets,
trees or any other obstructions that may cause wind
turbulence or back drafts in the chimney.
• Contain the fewest number of offsets (elbows)
possible.
3. Check that the intended location will not interfere with
oor joists, ceiling joists or rafters before proceeding
further.
NOTE: FRAMING
DIMENSIONS AROUND THE
FIREPLACE ARE THE
MINIMUMS. FRAMING
DIMENSIONS WILL NEED TO
BE ADJUSTED ACCORDINGLY TO ACCEPT DRYWALL IF
USED INSIDE ENCLOSURE.
The chimney may incorporate
an offset. To do this safely, all
sections of listed connector,
offset elbows and chimney
section must be screwed
together by at least three
sheet metal screws per joint.
The chimney must be suitably
supported by the chimney
manufacturer's listed offset
support. NOTE: Maximum
unsupported chimney height
is 20 feet(6.1m)
Spark arrestor
rain cap
Storm collar
Roof ashing
Radiation shield
Chimney Support
Minimum 7' (2.13m)
Ceiling Height from
base of unit
Chimney
Non-combustible
oor protector
38 3/4" (984mm)
Minimum distance
from top of unit to
ceiling
* 4"(102mm) diameter combustion outside air inlet. One
on either side of unit.
WARNING: Combustible materials cannot be used in the
space directly above the replace. Do not ll the space
above the replace with any material. (except the wood
framing)
WARNING: The replace must not be in contact with any
insulation or loose lling material. Cover the insulation
with drywall panels around the replace. Maintain proper
clearances as per Fig. #7.
WARNING: Drywall materials are considered combustible
and theIr thickness must be accounted for in your framing
dimensions.
If the chimney runs up the outside of the residence, we
recommend it be enclosed in a chase structure. The chase
should be constructed in such a way that it is an extension of
the home. It should be well insulated between the footings and
the oor of the home to prevent heat loss. We also recommend
to insulate the ceiling of the chase just as if it were in the attic
space. This will prevent cold air from dropping down through
the chase and into the room where the replace is installed.
Some local codes require that the walls be insulated, vapor
sealed and sheathed with a re rated gypsum board. We
strongly recommend this procedure for all installations to
prevent cold drafts from originating in the replace enclosure.
If you follow this procedure, do not insulate the wall directly
above the front of the replace.
NOTE: Check local codes concerning installation requirements
and restrictions in your area.
Mobile Home Installation:
- In the USA: the unit must be installed in accoradance with
the requirements of the Department of Housing and Urban
Development(HUD)"Manufactured Home Construction
and Safety)
- In Canada: the unit must be installed with access openings
into the built in enclosure for inspection purposes that
must require a household tool to open.
FP25 160415-28 15
Chimney
Installation
Listed Chimney and Chimney Connector
This appliance must be installed with a 6"(150mm) chimney
system approved under the following standards: CAN-ULC S629(IN
CANADA) OR UL 103HT(IN U.S.).
YOU MUST FOLLOW THE CHIMNEY MANUFACTURER'S
INSTALLATION INSTRUCTIONS FOR INSTALLATION OF
ALL CHIMNEY COMPONENTS.
MAINTAIN CLEARANCES TO COMBUSTIBLES AS
SPECIFIED IN THE CHIMNEY MANUFACTURERS
INSTALLATION INSTRUCTIONS
USE APPROPRIATE SUPPORTS, CAPS, FLASHING
AND SHIELDS IN ACCORDANCE WITH THE CHIMNEY
MANUFACTURERS INSTALLATION INSTRUCTIONS.
THE FOLLOWING INSTRUCTIONS ARE GENERAL
GUIDELINES ONLY.
CAUTION: THE STRUCTURAL INTEGRITY OF THE FLOOR,
WALL AND CEILING/ROOF MUST BE MAINTAINED.
NOTE: FOR ALL CHIMNEYS, YOU MUST USE THE
MANUFACTURER'S FIREPLACE ANCHOR PLATE. (If
using ICC chimney pipe and anchor plate, you will need
to install an Anchor Plate spacer. Part #FP30.7757)
NOTE: The FP25 must be installed so the outlet of the chimney
system is a minimum 15ft(4.6m) in height as measured from
the base of the unit up to a maximum height of 35'(10.7m).
The chimney must be supported on lengths over 20'(6.1m).
NOTE: Longer chimney lengths and different pitch ashings
may be used. Install all components to the chimney
manufacturer's installation requirements. Consult your
chimney supplier for installation advice.
1. After locating the desired location and framing in the
replace, cut and frame square holes in all oors, ceilings,
and roof that the chimney will pass through. Use a plumb
bob to line up the holes. The chimney support is mounted
to the framing.
2. Maintain a minimum 2"(51mm) clearance between the
chimney and any combustible materials. Do not ll the
space with insulation or any other combustible material.
3. Install the pipe manufacturer's, replace anchor plate
by inserting it into the ue collar on the replace. We
recommend sealing the joint with stove cement. Secure
the anchor plate with stainless steel screws.
4. Assemble the chimney sections so the nished length
is resting on the manufacturer's adapter and protruding
through the roof. Avoid having joints between the ceiling
and the roof. It is required that the chimney connections
be secured with three (3)-#8x½"(12 mm) metal screws.
5. Install the radiation shields, restops and all pieces
necessary to prevent contact with combustible materials
whenever passing through oors, ceilings or attic spaces.
6. Install the roof support then assemble the ashing and
the storm collar. Be sure to maintain the vapour barrier
at this point. (Seal securely.)
7. Attach the rain cap and check the ashing for leaks.
8. If the chimney extends more than 5'(1.5m) above the
point of contact with the roof, then it must be secured
using roof braces.
Minimum width of oor protection from side of door opening(in U.S.A.) and
from side of unit(in Canada).
Fireplace Clearances and Dimensions
22” (560mm)
35’ (10.7m)
Recommended maximum chimney height (at sea level) from top of replace
to rain cap.
Minimum distance of adjacent wall to side of replace door.
Distance of combustible material from side, back standos and framing kit.
Ceiling clearance: from the base of the replace to the
ceiling.
Minimum chimney height: minimum total chimney height from replace
bottom to below the chimney rain cap.
Maximum unsupported chimney height.
Minimum depth of non-combustible ember protector: from the front of the
replace.
Minimum distance to side facing from replace door opening.
11 1/2” (292mm)
The chimney for the FP25 can be installed with a maximum
of four 45° elbows(in Canada) and four 30° elbows(in
U.S.A.) as shown in Fig. #10.
Installation:
1. NOTE: Install the rst elbow and turn it in the required
direction.
2. Install the necessary chimney lengths to achieve the
required offset. Lock the chimney lengths together
according to the chimney manufacturer’s instructions.
If the offset length is made of two (2) chimney lengths
or more, many chimney manufacturers may require that
you use an offset or roof support halfway up the offset. If
penetrating a wall, install a wall radiation shield supplied
by the chimney manufacturer and install according to the
manufacturer's instructions.
3. Use another elbow to turn the chimney vertically and
secure the elbow.
4. Use a plumb bob to line up the centre of the hole with the
center of the ue collar on the replace. Cut a hole for the
chimney in the ceiling/oor. Frame the hole as described
on page 15.
NOTE: IT IS REQUIRED THAT ALL
CHIMNEY SYSTEM CONNECTIONS BE
SECURED WITH (3)-#8 X ½"(12 MM)
METAL SCREWS.
FIG. #10
30° or 45°
ELBOWS
5. Install a restop following the chimney manufacturer's
directions.
6. Follow the chimney manufacturer's guidelines for
supporting the offsets. Reminder - The chimney must be
supported after the rst 20'(6.1m).
In U.S.A: 18" (457 mm) to the front and 8"(203mm) to the
sides of the fuel loading door opening. See Figure #16, below.
Combustion Air
Intake or combustion air can be supplied to the replace
in one of two ways. Consult your local building code or
CAN/CSA-B365, Installation Code for Solid-Fuel-Burning
Appliances and Equipment before proceeding.
1. Outside air supply - Outside air may be drawn through
either side of the unit by connecting 4"(102mm) rigid or
ex pipe onto the outside aur adapter provided on the
right side of the combustion air box. The replace comes
with the outside air adapter factory installed on the right
side. You are able to switch this with the cover plate on
the left side if you so desire. (Fig. #11).
Installation:
Use an approved 4"(102mm) inlet vent cap. Cut or drill a
corresponding hole in the closest exterior wall or in the
oor anywhere inside the chase. Cover the hole with a
20GA wire mesh minimum, rodent screen and staple/
nail in place. Provide water protection as required. Attach
4"(102mm) venting (not supplied).
A typical outside air connection is shown in Fig. #12.
FIG. #11
WARNING: This hole must get its air from the outdoors
and be nished with an approved vent cap. The use of
outside combustion air for residential installations requires
that the replace be secured to the structure to prevent
dislodging of the air duct. Check local building codes for
instructions on sealing the vent cap at the penetration
point of the building. The combustion air inlet ducts can
not terminate in an attic space or garage.
WARNING: This unit is not designed to be operated with
the ring door open. In addition to the obvious hazard of
sparks landing on combustibles, an open re door will
cause the heater to draw excess air from the living space
and possibly cause suffocation.
CAUTION: The living space around the heater must be
well ventilated with good air circulation. Anything that
may cause a negative pressure can cause gases or
fumes to be pulled into the living area. During extremely
cold weather, and especially when burning at very slow
rates, the upper parts of the exposed chimney may ice
up, partially blocking the ue gases. If blockage occurs,
ue gases may enter living space.
Outside Air opening.
1 in each side,
FIG. #12
WARNING: THE COMBUSTION AIR INLET
MUST BE AT LEAST 5ft(1.5m) BELOW CHIMNEY FLUE AND MUST NEVER TERMINATE IN
ATTIC SPACES.
DECORATIVE
NON-COMBUSTIBLE
FACING MAXIMUM
4”(102mm) THICK
MIN
1.42m
NON-COMBUSTIBLE CEMENT BOARD
REQUIRED IN THESE AREAS.
30in (194cm)
CHASE AIR INLET
56”
MIN
ALTERNATE LOCATION
FOR CHASE AIR INLET CAN ALSO
BE ON OTHER SIDE OF CHASE
1 1/2”(38mm)
MINIMUM HEIGHT FROM FLOOR
18”(457mm)
MAXIMUM HEIGHT FROM FLOOR
Page 19
18" [457mm]
8" [203mm]
8" [203mm]
35" [889mm]
18" [457mm]
8" [203mm]8" [203mm]
57 5/8" [1.46m]
Ember
Protection
The stove may be installed on a combustible oor provided
ember protection made from a non-combustible material with
a minimum K value of 23.7 btu/ft h ˚F is used. Equivalent to
20GA steel.
This protection must extend as follows:
FIG. #15
Minimum Width - 57 5/8"(1.46m)"
Minimum Overall Depth - 18"(457mm)
Canada Only
Safety Strip
The oor between the replace and the hearth extension/
ember protection must be protected with a 2"(51mm) deep
safety metal strip equal to the width of the unit.
One half of the metal strip must be under the replace front
and the other half must extend onto the oor and under the
hearth extension/ember protection as shown in Fig. #17.
FIG. #17
Fireplace front
Safety metal strip
Hearth extension
non-combustible
finish material
Floor
51mm
The space between
the fireplace and the
hearth extension must
be sealed with a
non-combustible
material such as
sand-cement grout.
2”
Non-combustible
oor protector
In Canada: 18" (457 mm) on the ring side and 8"(203mm)
to the sides. See Figure #15, below.
The FP25 blowers must be connected to 120 VAC house
hold electrical system.
It is recommended to also connect the circuit to a wall switch
or fan speed controller.(not supplied)
Insert the Romex 14/2 wire, or equivalent, into the unit through
the strain relief located in the junction box on the right hand
side of the support base Fig. #20.
Connect the wiring as shown in the wiring diagram below to
the wires located in the junction box. See section (Blower
Replacement) on Page 8. All electrical connections should
be performed by a certied/licensed electrician.
NOTE: THE CHASE ENCLOSURE MUST HAVE A 30in²
(194 cm²) AIR INLET. (IN U.S.A. AND CANADA) FOR
EVERY REMOTE HEAT KIT INSTALLED WITH THE UNIT.
NO CHASE AIR INLET IS REQUIRED IF NOT INSTALLING
A REMOTE HEAT KIT.
CONTENTS:
1 - OUTLET ADAPTER
1 - HEAT DUCT ADAPTER
1 - 14"(356mm) X 10"(254mm) OUTLET GRILL
1 - 8"(203mm) X 8"(203mm) INLET GRILL
1 - 6"(150mm) ROUND TO 6"(150mm) SQUARE INLET BOOT
1 - 5ft(1.5m) LONG, 6"(150mm) DIAMETER TYPE "B"
FLEX VENT
1 - INSTRUCTIONS PACK WITH SCREWS
If passing through a wall to an another room or space you
will need a restop (not included with the WODC.RHKA).
Part #5095.75
If you require more than 5ft(1.5m) of the Type ”B” exible
venting order Part #5095.7.
INSTALLATION:
1. Using a pair of tin snips, cut away the square section
blocking the heat duct openings and cut out and remove
insulation(Fig.#22).
FIG. #22
Heat Duct
Adapters
Heat Duct
openings
2. Insert a remote heat ap box in the opening/s that you
are attaching a kit to. Attach the heat duct adapter/s with
the screws provided in the WODC.RHKA (Fig. #22).
3. Locate the Remote Blower Assembly in the desired wall
or ceiling location, maximum 20’(6.1m) away from the
unit, and secure to the framing.
NOTE: THE REMOTE HEAT KIT BLOWER/S CAN BE
INSTALLED SO THAT ANY EDGE OF THE GRILL IS A
MINIMUM 12"(305mm) FROM THE CEILING OR WALLS
AND 36"(914mm) FROM THE FLOOR.
4. Attach the 10”(254) X 3 1/4”(83mm) Transition Boot to
the Remote Blower Assembly and seal with aluminium
duct tape. Run a 6”(150mm) diameter approved Type “B”
venting between the blower and the replace. Fasten in
place with screws and seal with aluminium DUCT tape.
5. Locate the make-up air inlet in a desired location in the
chase wall.
6. Attach nishing grills over both inlet and outlet using the
screws provided.
Electrical Wiring
NOTE: ALL ELECTRICAL WIRING MUST BE DONE BY
A QUALIFIED ELECTRICIAN.
FIG. #24
BLOWER ASSEMBLY
Consult local codes or, in the absence of local codes,
with the current CSA C22.1 Canadian Electrical Code
and in the USA with the National Electrical Code, ANSI/
NFPA 70 (Latest Edition).
The Optional Remote Heat blower electrical rating: 120V,
60HZ, 80 watts. For your protection against shock hazard,
use only a properly grounded power supply.
This kit includes a junction box, rheostat and cover plate.
The junction box should be mounted in a convenient location
away from the replace.
NOTE: THE REMOTE HEAT KIT BLOWER/S SHOULD BE
WIRED TO A SEPARATE SWITH OR SPEED CONTROLLER THAN THE CONVECTION BLOWERS ON THE UNIT.
Understanding & Operating Your Pacic Energy Fireplace
The Pacic Energy line of replaces is a culmination of years
of research and development. Designed to be efcient, cleanburning and user-friendly, this heater will give you years of
warm service. However, a knowledgeable operator is still
the most important factor for maximum performance and part
of this is understanding the basic functions of this design.
Traditional replaces had a basic combustion system which
allowed a considerable amount of heat energy to escape up
the chimney as unburned gases and particulates (smoke).
Pacic Energy has designed a system that solves the problem by burning the smoke and releasing the additional heat
to the room.
This system has two critical design features:
1. Above re secondary air injection:
The hollow "air bafe" injects super-heated secondary air just
above the load. With the replace at the proper operating
temperature, this will create a secondary ame that will be
evident for approximately 1/3 of the total burn time.
2. High mass and thermal insulation:
The high mass (weight) acts as a heat storage and the
thermal insulation keeps the combustion zone hot. Active
aming takes place during the rst part of the burn. During
this stage, heat is stored in the mass of the unit and is later
released slowly and evenly. As wood chars, active aming
will diminish. This clean charcoal burning stage will last for a
considerable length of time and refuelling should be avoided
until the charcoal base has become quite small.
OPERATING TIPS
1. Always use dry, seasoned rewood, up to 18"(457mm)
long. Load wood endwise, a mixture of large and small
pieces, on top of a good ash base (1"(25mm) minimum)).
2. Operate on a medium to high setting, for up to 1 hour from
cold start. After the initial warm up period, refuel and leave
the air control on a medium setting for 5 to 10 minutes more
and then set the air control to the desired position.
3. If a slow burn is desired, set the air control to low. Active
secondary burning should be present above the wood load.
If it is not present or goes out shortly after, proper operating
temperature has not been reached and the replace needs
LE SYSTÈME DE CHEMINÉE DOIT ÊTRE HOMOLOGUÉ COMME SUIT : AU CANADA - CHEMINÉE HOMOLOGUÉE ULC-S-629, AUX ÉTATS-UNIS - CHEMINÉ
HOMOLOGUÉE UL-103 HT.
• INSTALLEZ ET UTILISEZ SELON LES INSTRUCTIONS D’INSTALLATION ET D’UTILISATION FOURNIES AVEC LE FOYER.
• LES PARTIES DU FOYER INCORPORANT DES CONDUITS CHAUDS OU FROIDS DOIVENT ÊTRE ENCHÂSSÉES, CONFORMÉMENT AUX INSTRUCTIONS
D’INSTALLATION ET D’UTILISATION FOURNIES AVEC LE FOYER.
• CONTACTEZ LES AGENTS LOCAUX DU CODE DU BÂTIMENT OU DU SERVICE-INCENDIE POUR LES RESTRICTIONS, PERMIS D’INSTALLATION ET
EXIGENCES D’INSPECTION DANS VOTRE RÉGION.
• NE RACCORDEZ PAS CE FOYER À UN CONDUIT DE CHEMINÉE DESSERVANT UN AUTRE APPAREIL
• NE PAS OBSTRUER PAS LES OUVERTURES DEVANT LE FOYER, NI RESTREINDRE L’ALIMENTATION D’AIR NÉCESSAIRE POUR LE FONCTIONNEMENT
NORMAL DU FOYER, TEL QUE SPÉCIFIÉ DANS LES INSTRUCTIONS D’INSTALLATION ET D’UTILISATION FOURNIES AVEC L’APPAREIL. LA PROVISION
INADEQUATE D’AIR POUR COMBUSTION, MAI DE VENTILATION ET DILUTION A POUR RESULTAT L’OPERATION DANGEREUSE DE CECI ET AUTRES
APPAREILS.• VOIR LE CODE DU BÂTIMENT LOCAL ET LES INSTRUCTIONS DU FABRICANT, POUR LES PRÉCAUTIONS EXIGÉES LORSQU’UNE
CHEMINÉE TRAVERSE UN MUR OU PLAFOND EN MATÉRIAUX COMBUSTIBLES.• COMPOSANTS OPTIONNELS: KIT DE CONDUITS DE DISTRIBUTION DE
CHALEUR (PIÈCE no WODC.RHKA).• UTILISEZ LES COMPOSANTS SPÉCIFIÉS DANS LES INSTRUCTIONS D’INSTALLATION DE PACIFIC ENERGY.• UTI
LISEZ SEULEMENT AVEC LA PORTE DE CHARGEMENT FERMÉE. NE L’OUVREZ QUE POUR ALIMENTER LE FEU.
• POUR COMBUSTIBLE SOLIDE SEULEMENT.• REMPLACEZ LA VITRE SEULEMENT PAR UNE VITRE EN CÉRAMIQUE.• LA SOUFFLERIE CLASSEMENT
ELECTRIQUE 115V, 60 Hz, 1.1AMP• CETTE CHEMINEE n’A pas ETE ESSAYEE AVEC UN UNVENTED JOURNAL DE GAZ A REGLE. POUR REDUIRE LE
RISQUE DE FEU OU BLESSURE, LE PAS INSTALLE UN UNVENTED JOURNAL DE GAZ A REGLE DANS CHEMINEE. • CE FOYER PEUT ÊTRE INSTALLÉ
DANS UNE MAISON PRÉFABRIQUÉE. UTILISER DU BOIS SOLIDE SEULEMENT.
CERTIFIED FOR CANADA AND U.S.A./LISTED FACTORY BUILT
FIREPLACE.CERTIFIED TO ULC S610-M87 AND CONFORMS TO UL 127-2011
FOYER PRÉFABRIQUÉ HOMOLOGUÉ / CERTIFIÉ POUR UTILISATION AU CANADA ET AUX É.-U.TESTÉ
SELON ULC S610-M87 ET UL 127-2011.
SERIES/SÉRIE:
A
MODEL/ MODÈLE:
FP25 FP25AR
• INSTALL AND USE IN ACCORDANCE WITH THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THE APPLIANCE. • AREAS OF
THE FIREPLACE INCORPORATING WARM OR COLD AIR DUCTS SHALL BE ENCLOSED IN ACCORDANCE WITH THE INSTALLATION AND OPERATING
INSTRUCTIONS SUPPLIED WITH THE APPLIANCE. SEE MANUFACTURER’S INSTALLATION AND OPERATING INSTRUCTIONS FOR THIS MODEL.
• CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS, INSTALLATION PERMIT AND INSPECTION IN YOUR AREA. • DO NOT CONNECT
THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE
• DO NOT OBSTRUCT THE OPENINGS IN FRONT OF THE FIREPLACE OR OTHERWISE RESTRICT SUPPLY AIR NECESSARY FOR NORMAL FIREPLACE
OPERATION AS SPECIFIED IN INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THE APPLIANCE. INADEQUATE AIR SUPPLY FOR
• COMBUSTION, VENTILATION AND DILUTION MAY RESULT IN DANGEROUS OPERATION OF THIS AND OTHER APPLIANCES.
• SEE LOCAL BUILDING CODE AND MANUFACTURER'S INSTRUCTIONS FOR PRECAUTIONS REQUIRED WHEN PASSING A CHIMNEY THROUGH A COM-
BUSTIBLE WALL OR CEILING. CHIMNEY SYSTEM MUST BE LISTED TO:
IN CANADA - USE CHIMNEY LISTED TO ULC-S-629, IN USA - UL-103 HT LISTED
• OPERATE ONLY WITH FEED DOOR CLOSED. OPEN TO FEED FIRE ONLY.
• USE SOLID WOOD FUEL ONLY. • BLOWER ELECTRICAL RATING 115V, 60HZ, 1.1AMP • REPLACE GLASS ONLY WITH 5mm CERAMIC GLASS.
• DO NOT USE OR INSTALL COMPONENTS OR PRODUCTS NOT SPECIFIED IN PACIFIC ENERGY INSTALLATION INSTRUCTIONS. DO NOT USE A
FIREPLACE INSERT OR OTHER PRODUCTS NOT SPECIFIED FOR USE WITH THIS PRODUCT. • THIS FIREPLACE HAS NOT BEEN TESTED WITH AN
UNVENTED GAS LOG SET. TO REDUCE RISK OF FIRE OR INJURY, DO NOT INSTALL AN UNVENTED GAS LOG SET INTO FIREPLACE.
• FIREPLACE, ALSO FOR USE IN MANUFACTURED HOMES WITH SOLID WOOD FUEL ONLY.
CLEARANCES TO SIDE AND BACK STANDOFFS/ DÉGAGEMENTS 0 in. / 0 mm
C. CORNER TO SIDEWALL/ COIN AU MUR LAT. 3.1 in. / 79mm
D. FRAMING OPENING/ OVERTURE DE CADRAGE 56 in./1.42m
E. CEILING TO UNIT/ DU PLAFOND AU FOYER 38-3/4 in. / 986mm
NON-COMBUSTIBLES ONLY IN THE SPACE ABOVE UNIT TO CEILING, NOT INCLUDING
APPROVED FRAMING / NON-COMBUSTIBLES SEULEMENT AU-DESSUS FOYER À PLAFOND
F. BASE OF UNIT TO MANTEL/ BASE DE L’UNITÉ AU MANTEAU
G. EMBER PROTECTION FROM FRONT OF UNIT/ PROTECTEUR de PLANCHER À
L’AVANT DU FOYER 18 in. / 457 mm
H. EMBER PROTECTION TO SIDE OF UNIT/ PROTECTEUR de PLANCHER AU CÔTÉ
DU FOYER 8 in./203 mm
IN USA: (Type 1 oor protector - approved to UL1618)Minimum 20GA steel
DO NOT REMOVE THIS LABEL/ NE RETIREZ PAS CETTE IQUETTE
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS/ DÉGAGEMENTS MINIMUMS AUX MATÉRIAUX COMBUSTIBLES
SN-
C
D
E
G
F
CAN.
U.S.A.
H
H
ETL#4001507
MANUFACTURED BY/ FABRIQUÉ PAR :
PACIFIC ENERGY FIREPLACE PRODUCTS LTD.
2975 ALLENBY RD., DUNCAN, BC V9L 6V8
CAUTION
MADE IN CANADA/ FABRIQUÉ AU CANADA
2015 2016 2017 2018 2019 2020
J F M A M J J A S O N D
DATE OF MANUFACTURE/ DATE DE FABRICATION
FP25-1
HOT WHILE IN OPERATION. DO NOT TOUCH. KEEP CHILDREN, CLOTHING
AND FURNITURE AWAY. CONTACT MAY CAUSE SKIN BURNS. SEE NAMEPLATE AND
INSTRUCTIONS./ DEVIENT TRÈS CHAUD. NE TOUCHEZ PAS. ÉLOIGNEZ LES ENFANTS, LES
VÊTEMENTS ET LES MEUBLES. UN CONTACT PEUT CAUSER DES BRÛLURES. VOIR LA PLAQUE
SIGNALÉTIQUE ET LES INSTRUCTIONS.
U.S. ENVIRONMENTAL PROTECTION AGENCY CERTIFIED TO COMPLY WITH
JULY, 1990, PARTICULATE EMISSION STANDARDS/ CERTIFIÉ CONFORME AUX
NORMESSUR LES ÉMISSIONS DE PARTICULES (JUILLET 1990).
1112145050.7618
MANTEL HEIGHT MUST BE MEASURED FROM THE BASE OF THE UNIT AS FOLLOWS: 48 1/8 in.(1.22m) FOR ALL MANTEL DEPTHS FROM 2”(51mm)
TO 12”(305mm)./// LA HAUTEUR DU MANTEAU, MESURÉE DE LA BASE DE L’APPAREIL, DOIT ÊTRE DE 48-1/8po (1,22 m) POUR LES MANTEAUX AYANT
UNE PROFONDEUR DE 2 po (51 mm) À 12 po (305 mm).
***
***
505
Label Location
The rating label is located on the rating label plate which can be accessed
by removing the inner and outer surrounds. The plate is attached to the
front face of the combustion air box by
a wire and rests beneath the replace.
Pull on the wire and lift the label plate
out to view the label.