Follet 1034727 Quick Start Manual

Page 1
Horizon™ Ice Machine Installation Instructions
HCD700R HCD/HMD/HCF/HMF1000R _ _ HCD/HMD/HCF/HMF1400R _ _ HCD/HMD/HCF/HMF1650R _ _
(See model number congurator on page 2 for details.)
Order parts online www.follettice.com
for Remote Condensing Unit
n Pennsylvania to
T NO
Eas
PAR
SINGLE PHASE
OZ
HZ
G PSI
SERIAL NO
GE
CORPORATION
AR
CH
VOLTS
IN
Y PROTECTED
ADE M SA
W SIDE
MALL
THE U
EL
LO
THER
MOD
NSF
ESSOR
U LL
R
COMPR
C
U
MOTOR
FULL LOAD AMPS
R
S P M A
IDE S
AMPS
REFRIGERANT
TY I
N PRESSURE HIGH
C
IG
MPA A
DES
RCUIT
ZE SI
H CI
E ANC R . B IRCUIT FUS MIN C NCH BRA . X MA
208264
Stock Module Identification Plate Module No. Product
Service No.
O N T R
LE A P
SING
E
S
A
H
P
Z
O
HZ
IG
S
P
E G R HA C
IN
E
E
A
SID
MAD
S
U
E
W
H
L
O
T
E
L
F
MOD
NS
U L
R
C
U
L
R
S P M A
S MP A
208264
Stock Module Identification Plate Module No. Product
Service No.
Drop-in Remote Condensing
RIDE® remote ice delivery equipment
ania v l y s
n n e
NO
on P st
RT
E
a E
PA
NGL
SI
SE A
H P
Z
OZ
H
L NO ION T IA R
PSIG
SE
ORA
E
RP
D
G
E
O
R
T
C
S
C
LT
HA C
OTE
VO
N
R
I
E
P
D
A
IDE
A
S
M
S
LLY
U
A
W
HE
L
O
T
RM
L
E H
ODE
T
M
R
NSF
O SS E
S
R P
MP
U L
A
R
D
COM R
OA L L
C
U L
UL
MOTO
F
R
PS M
E
A
NT
ID
A
H S
PS
RIGER
M
HIG
F
A
E
RE
R
U SS E R
Y
P
PACIT
IGN S
M IT A
DE
CU
E
R
Z I
CI
S E S
CH
U
F
AN R
IT
B .
CU
N I M
CIR CH N A R B . X A M
208264
Stock Module Identification Plate Module No. Product
Vision™ Remote Condensing
RIDE remote ice delivery equipment
Harmony Remote Condensing
Top Mount
O N RT
E
PA
GL N SI SE HA P
Z O
HZ
G I S P
GE AR H C
N I
E D
ADE A M US E H
L
T
E
LOW SI
MOD
NSF
U LL
R
C
U
R
AMPS
S AMP
208264
Stock Module Identification Plate Module No. Product
Service No.
Harmony™ Remote Condensing
RIDE remote ice delivery equipment
Bin Remote Condensing
Top Mount
Bin Remote Condensing
RIDE remote ice delivery equipment
801 Church Lane • Easton, PA 18040, USA Toll free (877) 612-5086 • +1 (610) 252-7301 www.follettice.com
01034727R03
Page 2
Read and complete the following 8 installation steps
Unpack
1
Site preparation
2
Condenser installation
3
Pressure adjustment
5
Hail hood
6
Startup and test
7
Refrigeration line assembly
4
Chewblet® Ice Machine Model Number Configurations
R B SD 1650HC
Icemaker Voltage Series Condenser
MC Maestro™ Chewblet (400 Series) HC Horizon™ Chewblet (1000, 1400, 1650 Series) HM Horizon Micro Chewblet
C 208-230/60/1 (icemaking head)
Self-contained only.
D 115/60/1 (icemaking head)
Self-contained and remote.
If remote unit, high side is 208-230/60/1.
E 230/50/1 (icemaking head)
Self-contained only.
F 115/60/1 (icemaking head)
Remote only. High side is
208-230/60/3.
400 up to 454 lb (206 kg) 1000 up to 1036 lb (471 kg)
1400 up to 1450 lb (658 kg) 1650 up to 1580 lb (717 kg)
A Air-cooled, self-contained W Water-cooled, self-contained R Air-cooled, remote condensing unit N Air-cooled, no condensing unit for
connection to parallel rack system
Application Configuration
V Vision™ H Harmony™ B Ice storage bin J Drop-in M Ice Manager™ diverter valve system
S RIDE
(RIDE remote
ice delivery equipment)
T Top-mount
®
Condensing Unit Shipping Weight
Model Horizon 1000 Horizon 1400 Horizon 1650
Single-phase 265 lb (102 kg) 330 lb (150 kg) 390 lb (177 kg) 3-phase 320 (145 kg) 320 (145 kg) 340 lb (154 kg)
2
REMOTE CONDENSING UNIT
Page 3
Carefully unpack and inspect the contents of your condensing unit
Site preparation
To ensure proper performance, ease of service and warranty coverage, it is critical that you follow the requirements detailed in this manual. If you cannot meet these requirements or have questions, call our technical service group at 877.612.5086 for installation support.
Unpack
1
2
2.1
2.1
Condenser Unit Clearances
min. 24" (61 cm)
min. 48" (122 cm)
23.50" (59.70 cm)
AIR FLOW
35.38" (89.86 cm)
min. 48" (122 cm)
min. 24" (61 cm)
• Position condenser unit as shown above, with clearances noted above
REMOTE CONDENSING UNIT
3
Page 4
2.1
2.2
Condenser installation specications
S-trap
required
P-trap
required if
rise is
greater than
3' (0.9 m)
Easton Pennsylvania
CORPORATION
SERIAL NO
MODEL
PART NO
SINGLE
HZ
VOLTS
FULL LOAD AMPS
PHASE
MOTOR COMPRESSOR THERMALLY PROTECTED
OZ
CHARGE
REFRIGERANT
LOW SIDE
PSIG
DESIGN PRESSURE HIGH SIDE
208264
MIN. BRANCH CIRCUIT AMPACITY
AMPS
Stock Module Identification Plate
MADE IN
ULU
NSF
THE USA
L
RR
Module No.
MAX. BRANCH CIRCUIT FUSE SIZE
AMPS
C
Product
Service No.
EVAPORATOR
UNIT
➊
100' max.
(30.5 m)
➍
EVAPORATOR UNIT LEVEL
CONDENSER UNIT
maximum
line rise
CONDENSER UNIT
CONDENSER UNIT
maximum
line drop
➋
+35'
(+10.7 m)
+20'
(+6.1 m)
+3'
(+0.9 m)
–15'
(–4.6 m)
100' max.
(30.5 m)
➌
➍
Site layout:
• Outdoor ambient temperature range: –20 F to 120 F (–29 C to 49 C)
• Installation with condenser unit elevations above 20' (6.1 m) require an S-trap at the midpoint of the rise
➊
• Maximum line rise must not exceed 35' (10.7 m) ➋
• Maximum line set length must not exceed 100' (30.5 m) ➌
• Maximum line drop must not exceed 15' (4.6 m) ➍ Note: The service loop is not included when calculating the length, rise or drop of the tubing run.
Note: 1400/1650 units only:
HCD1400/1650 condensing units contain a liquid to suction line heat exchanger. To maintain
optimum liquid refrigerant sub-cooling from the heat exchanger, the entire liquid line should be insulated separately from the suction line.
4
REMOTE CONDENSING UNIT
Page 5
Condenser installation
3
3.1
• Level unit
• Securely attach base of unit using holes
Install condensing unit
found in base plate
3.2
Horizon Remote Single-Phase
• 208-230/60/1
Horizon Remote 3-Phase
• 208-230/60/3
• Refer to wiring schematic located in
Electrical connections
700 - 15A circuit 1000 - 15A circuit 1400 - 30A circuit 1650 - 50A circuit
1000 - 15A circuit 1400 - 25A circuit 1650 - 35A circuit
condenser unit electrical box
CAUTION
• Electrical disconnects required within 10' (3 m) for all hard wired connections
• Install in accordance with NEC and local electrical codes
3.3
Condensing unit refrigeration line-set connection point
REMOTE CONDENSING UNIT
700/1000/1400:
5/8" suction 3/8" liquid
1650:
7/8" suction 3/8" liquid
5
Page 6
Refrigeration line installation
4
4.1
Refrigeration line installation: 7/8" suction / 3/8" liquid line (1650)
5/8" suction / 3/8" liquid line (700, 1000, 1400)
CAUTION
• The installer of the refrigeration line set must be USA Government Environmental Protection Agency (EPA) certied in proper refrigeration handling and service procedures
• A qualied person must perform all roof or wall penetration
• Do not form unwanted traps in refrigeration lines. A service loop is not considered an oil trap.
• Never coil excess refrigeration tubing
• The compressor oil rapidly absorbs moisture. Minimize the exposure of the refrigeration system by not releasing the condenser unit or evaporator unit holding charge until all line connections are nished and the system is ready for evacuation.
• HCD1400/1650 condensing units contain a liquid to suction line heat exchanger. To maintain optimum liquid refrigerant sub-cooling from the heat exchanger, the entire liquid line should be insulated separately from the suction line..
WARNING
• This unit contains an R404A holding charge
1. Make and connect line set run from the condensing unit to the evaporator unit with all specications found in the installation specications section. Do not overheat shut off valves on the condenser unit or evaporator unit.
2. Leak check eld joints via the evaporator unit service valves.
3. Evacuate line set via the evaporator unit service valves.
4. Determine required charge size based on the model and line length.
R404A Ice Machine Charge Specications
Line Run Charge 700R Charge 1000R Charge 1400R Charge 1650R
0 - 50' (0 - 15.2 m) 8 lb (4.9 kg) 8 lb (4.9 kg) 11 lb (4.9 kg) 11 lb (4.9 kg)
50 - 75’ (15.2 - 22.9 m) 9 lb (5.4 kg) 9 lb (5.4 kg) 12 lb (5.4 kg) 12 lb (5.4 kg)
75 - 100’ (22.9 - 30.5 m) 10 lb (5.9 kg) 10 lb (5.9 kg) 13 lb (5.9 kg) 13 lb (5.9 kg)
100’ + (30.5 m+) not recommended – consult factory
5. Open the liquid line service valve and suction line service valve on the evaporator unit and
condenser unit.
6. Open the liquid line valve on the receiver, then the suction line valve on the compressor unit.
7. Liquid charge unit through liquid line shut off valve on the evaporator unit or receiver valve on
the condensing unit.
8. Isolate the refrigerant tank from high pressure side on the system.
9. Turn on power to condensing unit and evaporator unit.
10. Complete system charge through low pressure side.
11. Insulate entire suction line including shut off valves to prevent condensation.
6
REMOTE CONDENSING UNIT
Page 7
Pressure adjustment
5
5.1
1. The pressure control is located in the electrical box on the top of the condensing unit.
2. Gauges must be used to verify proper pressure control settings of 5 psig cut-out and
3. If adjustment is needed always adjust the cut in rst.
Check pressure adjustment
45psig cut-in.
Hail hood
6.1
Install hail hood
6
Please remove the condenser enclosure top to access the following parts:
• Left and right brackets (not interchangeable)
• Hail hood
• 1/4 x 20 x 1/2 hex head screw (10)
1. Locate the left bracket (1)
and install using two supplied screws (2).
2. Locate the right bracket (3)
and install using two supplied screws (4).
1
2
2
3
4
4
REMOTE CONDENSING UNIT
7
Page 8
3. Install hail hood (5) to brackets using the remaining six screws (6).
Note: The bottom hole in the bracket is not
used when mounting the hail hood (7).
6
7
NOT USED
Start up and test
NOTICE
Ice machine MUST be cleaned and sanitized prior to operation!
Consult Operation and Service Manual provided with ice machine for cleaning and sanitizing instructions.
6.1
Verify operation
5
7
• Turn dispenser power ON if applicable
• Check current draw of compressor to verify correct electrical operation
• Put a piece of ice on bin thermostat or hold a cup under the shuttle actuator on the bin/ dispenser to verify that the evaporator unit shuts OFF; condensing unit pumps down and shuts off.
• After shut off, restart the ice machine
Harmony, Horizon, Ice Manager, and Vision are trademarks of Follett Corporation. Chewblet, RIDE and Follett are registered trademarks of Follett Corporation, registered in US.
Horizon Condenser Unit Compressor Amperage
Single-Phase
Model Number Condensing Unit Running amps (+/- 10%)
700R AKA9462ZXD 6.8
1000R
00168054
1400R
00178640
1650R
00973925
3-Phase
Model Number Condensing Unit Running amps (+/- 10%)
1000R
00990200
1400R
00990218
1650R
00990226
AJA7490ZXDHN 7. 4
AWA9517ZXNHN 14.7
AVA9522ZXNHN 22.6
AWA9490ZXTHN 4.7
AWA9517ZXTHN 7. 3
AVA9522ZXTHN 10.3
801 Church Lane • Easton, PA 18040, USA Toll free (877) 612-5086 • +1 (610) 252-7301 www.follettice.com
01034727R03
© Follett Corporation 11/13