Introduction
This instruction sheet includes installation, operation, and maintenance procedures for 2-piece threaded
and solder end brass or bronze ball valves.
Installation
Warning:
To avoid personal injury to yourself and fellow workers, or to avoid property damage due to accidental
release of fluid from the system, before installation please utilize the following procedure:
a] Shut off all operating lines to the valve site
b] Isolate the valve site from the line fluid
c] Relieve the pressure of the fluid in the system
d] Drain the fluid in the system around the valve site.
1] Prior to installation the valve should be inspected for any exterior deformations, and the interior or
porting area inspected for any foreign matter or damage to the treads or soldering cups.
2] Prior to installation, inspect the pipeline and the mating pipe making sure both are free of foreign
material. In addition, inspect these piping components ensuring they are clean, and there are zero burrs
or pits that could cause leakage.
3] Make sure it piping system is tension free before and after installation.
4] The valve should be manually cycled a couple of times prior to installation
5] Make sure the valve is installed in the OPEN position.
6] Brass ball valves are NOT to be installed at or BELOW GROUND LEVEL.
7] Bronze ball valves can be installed at or below ground level, but NOT BURIED.
THREADED ENDS
1] Unless otherwise specified, ball valve pipe threads are American National Standard Taper Pipe Threads
[NPT] to ANSI/ASME B1.20.1. Use pipe sealants in accordance with the manufacturer’s instructions and in
keeping with good piping
2] To prevent distortion or damage to the brass or bronze ball valve do not apply torque directly to the
valve. When tightening the valve always use a wrench on the end nearest the pipe being tightened. It is
preferred that the pipe be screwed into the valve, holding the valve stationary at the end being connected.