FMI VT32EN-A Series, VTC32EN Series, TC32EN Series, VT32EP-A Series, T32EP-A Series Owner's Operation And Instruction Manual

...
DIRECT-VENT FIREPLACE
PFS
USC
OWNER’S OPERATION AND INSTALLATION MANUAL
®
NATURAL GAS “TUDOR” MODELS (V)T32EN-A, (V)TC32EN SERIES
PROPANE/LP GAS “TUDOR” MODELS (V)T32EP-A, (V)TC32EP
SERIES
WARNING: If the information in this manual is not fol-
lowed exactly, a re or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
— Installation and service must be performed by a quali-
ed installer, service agency or the gas supplier.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
For more information, visit www.fmiproducts.com
Safety Information ............................................... 2
TABLE OF CONTENTS
Product Identication ........................................... 5
Local Codes......................................................... 5
Product Features ................................................. 5
Pre-Installation Preparation ................................. 6
Location of Termination Cap ................................ 8
Requirements for the Commonwealth of
Massachusetts..................................................... 9
Venting Installation Instructions ......................... 10
Fireplace Installation.......................................... 19
Wiring Diagram .................................................. 28
SAFETY INFORMATION
WARNING: Improper in­stallation, adjustment, al-
teration, service or main­tenance can cause in-
jury or property damage.
Refer to this manual for correct installation and
operational procedures.
For assistance or addi­tional information con-
sult a qualied installer, service agency or the gas supplier.
This appliance may be in-
stalled in an aftermarket,*
permanently located, manufactured (mobile) home, where not prohib­ited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certied kit is used.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
Operating Fireplace ........................................... 29
Inspecting Burners............................................. 30
Cleaning and Maintenance ................................ 29
Troubleshooting ................................................. 32
Replacement Parts ............................................ 35
Service Hints ..................................................... 35
Technical Service............................................... 35
Specications .................................................... 35
Parts List............................................................ 36
Accessories ....................................................... 40
Warranty Information ...........................Back Cover
State of Massachusetts: The installation must
be made by a licensed plumber or gas tter in
the Commonwealth of
Massachusetts.
WARNING: This product
contains and/or generates
chemicals known to the State of California to cause cancer or
birth defects or other reproduc­tive harm.
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, op­erate or service this replace. Improper use of this replace can cause serious injury or death from burns, re, explosions, electrical shock and carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
This fireplace complies with the National Safety Standards and is listed and tested by PFS Corporation to ANSI Z21.50/CSA 2.22
standard as vented gas replace.
NOTICE: Decorative product not for use as a heating appliance.
www.fmiproducts.com
116647-01H2
SAFETY INFORMATION
Continued
This replace must be installed by a qualied (certied or licensed) service person. It has a sealed gas combustion chamber that uses a coaxial pipe (pipe within a pipe and having the same center) venting system. It brings in fresh air for combustion through the outer pipe
and combustion gases are exhausted through the inner pipe. If the glass door assembly and venting pipe are not properly seated, connected and sealed, carbon monoxide leakage
(spillage) can occur.
Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning resemble the u, with
headaches, dizziness or nausea. If you have these signs, the replace may not be working
properly. Get fresh air at once! Have replace serviced. Some people are more affected by carbon monoxide than others. These include pregnant women, people with heart or lung disease
or anemia, those under the inuence of alcohol and those at high altitudes.
Natural and Propane/LP Gas: Natural and propane/LP gases are odorless. An odor-making agent
is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your
guide to safe and proper operation of this replace.
WARNING: Any change to this replace or its controls can be
dangerous.
WARNING: Do not use a blower insert, heat exchanger insert or
other accessory not approved for use with this replace.
Do not use any solid fuels (wood, coal, paper, cardboard, etc.) in this replace. Use only the gas type indicated on replace name plate.
Carefully supervise young children when they are in the room with replace.
This replace reaches high temperatures. Keep children and adults away from hot surfaces to avoid burns or clothing ignition. Fireplace will remain hot for a time after shutdown. Allow surfaces to cool before touching.
116647-01H 3
www.fmiproducts.com
SAFETY INFORMATION
Continued
Do not operate replace with glass door removed, cracked or broken.
Keep the appliance area clear and free from combustible materials, gasoline and other ammable vapors and liquids.
Do not place clothing or other ammable material on or near re­place. Never place any objects on replace.
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with
other gases unless a certied kit is used.
2. For propane/LP replace, do not place propane/LP supply tank(s) inside any
structure. Locate propane/LP supply
tank(s) outdoors. To prevent performance
problems, do not use propane/LP fuel tank of less than 100 lb. capacity.
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor’s phone. Follow the gas sup­plier’s instructions
• if you cannot reach your gas supplier,
call the re department
4. Never install the replace
• in a recreational vehicle
• in windy or drafty areas where curtains
or other combustible (ammable) objects can make contact with the replace front
• in high trafc areas
5. Do not modify this replace under any
circumstances. Any parts removed for servicing must be replaced prior to operat-
ing replace.
6. Turn fireplace off and let cool before servicing, installing or repairing. Only a
qualied service person should install, service or repair this replace. Have re­place inspected annually by a qualied
service person.
7. You must keep control compartments, burners and circulating air passages clean. More frequent cleaning may be needed due to excessive lint and dust from carpeting, bedding material, etc. Turn off the gas valve and pilot light before
cleaning replace.
8. Have venting system inspected annually
by a qualied service person. If needed,
have venting system cleaned or repaired. See Cleaning and Maintenance, page 30.
9. Do not use this replace to cook food or burn paper or other objects.
10. This appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code,
ANSI/NFPA 70.
11. Do not use replace if any part has been
under water. Immediately call a qualied
service person to arrange for replacement of the unit.
12. Do not operate replace if log is broken.
13. Provide adequate clearances around air openings.
www.fmiproducts.com
116647-01H4
PRODUCT IDENTIFICATION
Upper Louver Panel
Door Screen
(TC32 Series)
Figure 1 - Direct-Vent Fireplace with Electronic Ignition
(T32 Series)
Glowing Embers
Burner Assembly
Electronic Control Valve
LOCAL CODES
Install and use replace with care. Follow all
local codes. In the absence to local codes, use the current National Fuel Gas Code ANSI
Z223.1/NFPA 54*.
Glass Door Assembly
Lower Louver Panel
(T32 Series)
Switch Bracket for Optional Remote and Blower
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
Flue Collar
Nailing Flange
Log Set
Grate Assembly
Lava Rock
PRODUCT FEATURES
These are a few facts that can help you un-
derstand and enjoy your direct-vent replace:
• The venting system may be routed to the
outside of your home in several ways. It
may vent through the roof (vertical) or it may vent to an outside/exterior wall (hori­zontal). The vent pipe installation is very
important to allow for proper operation. You must follow the venting instructions very carefully for either vertical or horizontal applications.
• This replace may be installed in any room
of your house provided all local codes and these installation instructions are followed.
• The blower requires electricity if installed.
If you plan to install the blower at a later date, outlet must be wired at the bottom of
the replace when framing.
116647-01H 5
www.fmiproducts.com
• The electronic ignition creates spark to
ignite the pilot light. It does not require any matches, batteries or any other sources of ignition to light the pilot.
• Each time you turn on your replace, you
may notice some amount of condensation
on the inside of the replace glass. This
is normal and will disappear after 10-20 minutes of operation.
Your direct-vent gas replace system (re­place and venting) is a balanced and sealed
gas operating unit. It requires approximately 10-20 minutes of operating time before the
ame pattern stabilizes.
D
RW
FW
PRE-INSTALLATION PREPARATION
LOCATION AND SPACE REQUIREMENTS
Determine the safest and most efcient loca­tion for your FMI PRODUCTS, LLC direct-vent
replace. Make sure that rafters and wall studs
are not in the way of the venting system. Choose a location where the heat output is not affected by drafts, air conditioning ducts, windows or doors. Figure 2 shows some com­mon locations. Be aware of all restrictions and precautions before deciding the exact location
for your replace and termination cap. When deciding the location of your replace,
follow these rules:
• Do not connect this replace venting to a chimney ue serving a separate solid-fuel burning replace or appliance.
• Due to high temperatures, do not locate this replace in high trafc areas, windy or
drafty areas or near furniture or draperies.
• Proper clearances must be maintained.
• If your replace is to be installed directly on
carpeting, vinyl tile or any combustible ma­terial other than wood, it must be installed on a metal or wood panel extending the full
width and depth of the replace. See Figure
3.
Flush with a wall
Through exterior wall enclosed in a chase
Corner installation
Figure 2 - Common Fireplace Locations
22 1/2"
16 5/8"
34 3/8"
Figure 3 - Fireplace Bottom Dimensions
www.fmiproducts.com
• Your fireplace is designed to be used in
zero clearance installations. Wall or framing material can be placed directly against any exterior surface on the back, sides or top of
your replace, except where standoff spacers
are integrally attached. If standoff spacers
are attached to your replace, these spacers
can be placed directly against wall or framing material. See framing details on page 7.
• If you plan on installing a television or
entertainment center recessed above
your replace, it is recommended that you
maintain a minimum 18" above top of louver opening.
• When locating termination cap, it is impor­tant to observe the minimum clearances shown in Figure 7, page 8.
• If recessing into a wall, you can avoid extra framing by positioning your replace
against an already existing framing mem­ber.
• Do not recess termination cap into a wall
or siding.
• You may paint the termination cap with 450º
F heat-resistant paint to coordinate with the
exterior nish.
• There must not be any obstruction such as
bushes, garden sheds, fences, decks or util­ity buildings within 24" from the front of the termination cap.
• Do not locate termination cap where exces­sive snow or ice build up may occur. Be sure to clear vent termination area after snow falls to prevent accidental blockage of venting system. When using snow blowers, do not direct snow towards vent termination area.
CLEARANCES
Minimum clearances to combustibles for the
replace are as follows:
*Back and sides 0" Perpendicular walls 6" Floor 0" Ceiling to louver opening 42" Front 36" Top 0"
Vent (See venting instructions for specic venting clearances.)
Combustible material with a maximum thick-
ness of 5/8" may be ush with the top front of replace.
* For back and sides of replace, do not pack
with insulation or other materials. 0" clear­ance to combustible materials are for framing purpose only.
116647-01H6
PRE-INSTALLATION PREPARATION
A
B
E
F
G
H
D
C
Nailing Tabs
C
B
A
D
E
F
G
Top of Louver Opening
3
2
1
4
5
6
7
Wall
Continued
NOTICE: This replace is in­tended for use as supplemental heat. Use this replace along with your primary heating sys­tem. Do not install this replace as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using replace. This will help circulate the heat throughout the house. In the event of a power outage, you can use this replace as a heat source.
FRAMING AND FINISHING
Figure 4 shows typical framing of this re­place. Figure 5 shows framing for corner installation. All minimum clearances must be met.
For available accessories for this replace,
see Accessories on page 40. If you are using a separate combustible mantel piece, refer to Figure 6 for proper installation height. You can install noncombustible mantels at any height above the replace. Note: Noncombustible mantels may discolor!
13 5/8"
10 3/8"
39 3/8"
28 1/2"
Nailing
97/8"
343/8"
Tabs
345/8"
541/8"
Figure 5 - Framing Clearances for Corner
Installation
323/8"
Figure 4 - Framing Clearances for
345/8"
17" (Horiz. Vent) 20" (Vert. Vent)
Ref.
Mantel
Depth Ref.
Mantel from Top of
Louver Opening
1 14" A 16" 2 12" B 14" 3 10" C 12" 4 8" D 10" 5 6" E 8" 6 4" F 6" 7 2" G 4"
Figure 6 - Clearances for Combustible
Mantels
Installation Against an Exterior Wall
116647-01H 7
www.fmiproducts.com
LOCATION OF TERMINATION CAP
D
E
V
B
L
A = clearance above grade, veranda, porch, deck, or balcony [*12" (30.5 cm) minimum] B = clearance to window or door that may be opened [6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US if between 10,000 and 50,000, 12" (30 cm) in Canada if between 10,000 and 100,000; 12" (30 cm) in US if greater than 50,000, 36" (91 cm) in Canada if greater than 100,000] C = clearance to permanently closed window [minimum 12" (30.5 cm) recommended to prevent condensation on window] D = vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24" (61 cm) from the center-line of the terminal [18" (45.7 cm) minimum] E = clearance to unventilated soffit [12" (30.5 cm) minimum] F = clearance to outside corner (see below) G = clearance to inside corner (see below) H = *not to be installed above a meter/regulator assembly within 36" (91.4 cm) horizontally from the center line of the regulator
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Inside Corner
† vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves both dwellings* ‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor* * as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A. Note: Local codes or regulations may require different clearances
A
A = 6" (15.2 cm)
V
C
F
V
B
TERMINATION CAP
V
Fixed
Closed
Openable
V
Openable
B
AIR SUPPLY INLET
X
B
V
Fixed
Closed
B
J
V
X
A
I = clearance to service regulator vent outlet [*72" (182.9 cm) minimum] J = clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other fireplace [6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US if between 10,000 and 50,000, 12" (30 cm) in Canada if between 10,000 and 100,000; 12" (30 cm) in US if greater than 50,000, 36" (91 cm) in Canada if greater than 100,000] K = clearance to a mechanical air supply inlet [*In Canada, 6 ft. (1.83m) minimum; In US 3 ft. (91 cm) above if within 10 ft. (3 m) horizontally] L = † clearance above paved side-walk or a paved driveway located on public property [*84" (213.3 cm) minimum] M = clearance under veranda, porch, deck [*12" (30.5 cm) minimum ‡] N = clearance above a roof shall extend a minimum of 24" (61 cm) above the highest point when it passes through the roof surface and any other obstruction within a horizontal distance of 18" (45.7 cm)
Outside Corner Recessed Location
V
B = 6" (15.2 cm)
B
H
I
G
G
GAS METERRESTRICTED AREA
M
(TERMINATION PROHIBITED)
C
N
N
G
V
G
V
K
V
X
A
D
C
E
V
Balcony with No Side Wall
G
V
G = 12" (30.5 cm) minimum clearance
Figure 7 - Minimum Clearances for Termination Cap
Balcony with Perpendicular Side Wall
H
V
J
Combustible & Noncombustible H = 24" (61 cm) J = 20" (50.8 cm)
www.fmiproducts.com
C = Maximum depth of 48" (121.9 cm) for recessed location D = Minimum width for back wall of recessed location ­ Combustible - 38" (965 mm) Noncombustible - 24" (61 cm) E = Clearance from corner in recessed location­ Combustible - 6" (15.2 cm) Noncombustible - 2" (5.1 cm)
116647-01H8
REQUIREMENTS FOR THE COMMONWEALTH OF
MASSACHUSETTS
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall ex-
haust vent termination is less than seven (7) feet above nished grade in the area of the venting,
including but not limited to decks and porches,
the following requirements shall be satised:
INSTALLATION OF CARBON MONOXIDE DETECTORS
At the time of installation of the side wall horizon­tal vented gas fueled equipment, the installing
plumber or gastter shall observe that a hard
wired carbon monoxide detector with an alarm
and battery backup is installed on the oor level
where the gas equipment is to be installed. In
addition, the installing plumber or gastter shall
observe that a battery operated or hard wired car­bon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of
qualied licensed professionals for the installation
of hard wired carbon monoxide detectors. In the event that the side wall horizontally
vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next
adjacent oor level.
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall
have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery
operated carbon monoxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034
listed and IAS certied.
SIGNAGE
A metal or plastic identication plate shall be
permanently mounted to the exterior of the
building at a minimum height of eight (8) feet
above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than 1/2" in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".
116647-01H 9
www.fmiproducts.com
INSPECTION
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a) 1 through 4.
EXEMPTIONS: The following equipment is
exempt from 248 CMR 5.08(2)(a) 1 through 4:
• The equipment listed in Chapter 10 entitled
"Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as
adopted by the Board; and
• Product Approved side wall horizontally
vented gas fueled equipment installed in a room or structure separate from the dwell­ing, building or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
• Detailed instructions for the installation of
the venting system design or the venting
system components; and
• A complete parts list for the venting system
design or venting system.
Gas Equipment Venting System Not
Provided
When the manufacturer of a Product Ap­proved side wall horizontally vented gas fu­eled equipment does not provide the parts for
venting the ue gases, but identies "special
venting systems", the following requirements
shall be satised by the manufacturer:
The referenced "special venting system" in­structions shall be included with the appliance
or equipment installation instructions; and
• The "special venting systems" shall be Prod-
uct Approved by the Board, and the instruc­tions for that system shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting in­structions, all parts lists for venting instruc­tions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
VENTING INSTALLATION INSTRUCTIONS
NOTICE: Read these instruc-
tions completely before at­tempting installation.
These models are tested and approved for
use with FMI PRODUCTS, LLC (direct-vent)
pipe components and terminations. The venting system must terminate on the
outside of the structure and can not be at-
tached to a chimney or ue system serving a
separate solid fuel or gas burning appliance. A direct-vent appliance must have its own venting system. DO NOT common vent this appliance.
These models are approved to be vented either horizontally through an outside wall or vertically through a roof or chase enclosure using the following guidelines:
• When venting system terminates horizon­tally on an outside wall, you may install a standoff if the termination cap is to be
installed directly on a combustible nish
such as vinyl, wood, stucco, etc.
• Never run the vent downward as this may
cause excessive temperatures which
could cause a re.
• Vent pipe air space clearances to com-
bustibles are 1" on all sides except on the horizontal sections, which requires 2" clear­ance from the top of the pipe. Where the termination cap penetrates a combustible wall, 1" air space clearance is required.
• Snorkel terminations are required when
minimum clearance to grade cannot be met
(see Figure 16 on page 14).
• Have replace and selected vent compo-
nents on hand to help determine the exact measurements when elbowing or offsetting.
Always use wall restops when penetrating walls and restops when penetrating ceil-
ings or attic spaces.
• If using a venting conguration of only
horizontal venting with no vertical run, a 1/4" rise for every 12" of run toward the termination is required.
WARNING: Read all instruc-
tions completely and thoroughly before attempting installation.
Failure to do so could result in
serious injury, property damage or loss of life.
NOTICE: Failure to follow these
instructions will void the warranty.
IMPORTANT: Do not seal vent cap to pipe. Cap must be removable for service.
INSTALLATION PRECAUTIONS
• Wear gloves and safety glasses for protection
• Use extreme caution when using ladders or
when on roof tops
• Be aware of electrical wiring locations in
walls and ceilings
The following actions will void the warranty on your venting system:
Installation of any damaged venting component
• Unauthorized modication of the venting system (Do not cut or alter vent compo­nents)
• Installation of any component part not
manufactured or approved by FMI PROD­UCTS, LLC
• Installation other than as instructed by
these instructions
WARNING: This gas replace and vent assembly must be vented directly to the outside. The venting system must NEVER be attached to a chimney serv­ing a separate solid fuel burning appliance. Each direct-vent gas appliance must use a separate vent system. Do not use com­mon vent systems.
WARNING: Vent pipe air space clearances to combustibles are 1" on all sides except on the horizontal sections, which require 2" clearances from the top of the pipe. Where the termination cap penetrates a combustible wall, 1" air space clearance is required.
www.fmiproducts.com
116647-01H10
INSTALLATION PLANNING
(Framing
Detail)
11
1
/2"
11
1
/2" Inside Framing
11
1
/2"
8 1/2"
Vent Opening
Combustible Wall
Vent Opening
Noncombustible Wall
There are two basic types of direct-vent installation:
• Horizontal Termination
• Vertical Termination
Horizontal Termination Installation
IMPORTANT: Horizontal square terminations
require only inner portion of wall restop. Hori­zontal installations using round termination
require exterior portion of wall restop (see Figure 14, page 13).
1. Set the replace in its desired location and
determine the route your horizontal venting
will take. Do not secure the replace until
all venting has been installed. Some instal-
lations require sliding the replace in and out of position to make nal venting con-
nections. Figures 14 through 18 on pages
13 through 15 show different congurations
for venting with horizontal termination that will help you decide which application best suits your installation. Check to see if wall studs or roof rafters are in the path of your desired venting route. If they are, you may
want to adjust the location of the replace.
2. Direct vent pipe sections and components are designed with special twist-lock con­nections.
Twist-Lock Procedure: The female ends
of the pipes have locking lugs (inden­tations). These lugs will slide straight
into matching slots on the male ends
of adjacent pipes. Push pipe sections
together and twist one section clockwise approximately one-quarter turn until the
sections are fully locked (see Figure 8).
Note: Horizontal runs of vent must be supported every three feet. Use wall straps for this purpose.
3. Use a 45° elbow to connect venting
system to replace ue collar. The elbow
is designed to be twist-locked onto the
ue collar as described in step 2. IM­PORTANT: Do not attempt to alter the
configuration of the elbow by cutting, twisting, bending, etc.
4. Assemble the desired combination of pipe
and elbows to the replace ue collar. If
there are long portions of venting run, pre­assembled pipe sections may be installed as subassemblies for convenience.
5. Carefully determine the location where the vent pipe assembly will penetrate the outside wall. The center of the hole should line up with the center-line of the horizontal
116647-01H 11
VENTING INSTALLATION INSTRUCTIONS
Continued
vent pipe. Mark the wall for a 11 1/2" x 11
1
/2" square hole. Cut and frame the square hole in the exterior wall where the vent will be terminated. If the wall being penetrated is constructed of noncombustible material, such as masonry block or concrete, a 8 1/2"
hole with zero clearance is acceptable (see Figure 9).
WARNING: Do not recess
vent termination into any wall. This will cause a re hazard.
Female Locking Lugs
Male Slots
Figure 8 - Vent Pipe Connections
www.fmiproducts.com
Figure 9 - Vent Opening Requirements
Center of Hole
VENTING INSTALLATION INSTRUCTIONS
Continued
6. Noncombustible Exterior Wall: Position the horizontal vent cap in the center of the 8
1
/2" round hole and attach to the exterior wall with four screws. Note: The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete or other types of sidings. Before attaching the vent cap to exterior wall, run
a bead of non-hardening mastic (pliable sealant) around the outside edges to make
a seal between it and the outside wall.
Combustible Exterior Wall: For vinyl siding,
stucco or wood exteriors, a siding standoff may be installed between the vent cap and exterior wall. The siding standoff prevents excessive heat from damag­ing the siding materials. Siding material must be cut to accommodate standoff. Bolt the vent cap to the standoff. Apply non-hardening mastic around outside edge of standoff. Position the standoff/ cap assembly in the center of the 111/2" square hole and attach to exterior wall
with wood screws provided (see Figure
11). The siding standoff must sit ush
against the exterior fascia material.
7. Combustible Exterior Wall Only: Slide the
wall restop over the vent pipe before connecting horizontal run to vent cap (see Figure 12).
8. Carefully move replace, with vent as-
sembly attached, toward wall and insert vent pipe into horizontal termination. The pipe overlap should be a minimum of 11/4"
(see Figure 13, page 13).
9. Combustible Exterior Wall Only: Slide wall
restop against interior wall surface and
attach with screws provided (see Figure
12). See Figure 13, page 13 for horizontal
termination details.
10. Place replace into position and shim with
noncombustible material if needed. Nail or
screw side anges to framing to secure unit in place. IMPORTANT: Make sure re- place is level before securing. If replace
is not level it will not work properly.
Cut Siding Away to Fit Standoff
Standoff
Wood Screw
Vent Cap
Screws
Apply Mastic to All Four Sides
Figure 11 - Installing Siding Standoff
(Combustible Exterior)
Interior Wall Surface
Wall Firestop
Apply Mastic to All Four Sides
Vent Cap
Wood Screw
Figure 10 - Installing Horizontal Vent Cap
(Noncombustible Exterior)
www.fmiproducts.com
Vent Cap
(Horizontal Termination)
Screw
Horizontal Vent Pipe
Figure 12 - Connecting Vent Cap with
Horizontal Vent Pipe
116647-01H12
VENTING INSTALLATION INSTRUCTIONS
Minimum Pipe Overlap 11/4"
Wall Firestop
Siding Standoff
Screws
Continued
GROUND FLOOR INSTALLATION Recommended Applications:
• Installation using cabinet surrounds
• Through the wall using round or square termination (up to 12" horizontal pipe)
• NOT FOR CORNER INSTALLATION
45° Elbow Horizontal High Wind Square Termination
Direct Vent Pipe
Maintain 1" Minimum Air Space Around Outer Pipe When Penetrating a Wall
Figure 13 - Typical Horizontal Termination Cap Mounting with Additional Siding
Horizontal Termination Congurations
Figures 14 through 18 show different con-
gurations and alternatives for venting with horizontal termination. Each gure includes
a chart with critical minimum and maximum dimensions which MUST be met. IMPOR-
TAN T: If using a venting conguration of only
horizontal venting with no vertical run, a 1/4" rise for every 12" of run toward the termina­tion is required.
10 3/4" x 10 3/4" Framed Opening
Standoff Installed
High Wind Termination
Apply Mastic to Outside Edge of Standoff
Exterior Wall with Vinyl Siding
WARNING: Never run vent
downward as this may cause
excessive temperatures which could cause a re. Operation of improperly installed and main­tained venting system could result in serious injury, property damage or loss of life.
Adjustable
Pipe 12" Max.
Wall Firestop
Square Termination
Vertical (V) Horizontal (H)
29 3/4" 17" max.
45° Elbow
Wall Firestop
Figure 14 - Horizontal Termination
Conguration for Square or Round
Termination
Exterior Portion of Wall
Firestop (Round Termination Only)
Horizontal Round Termination
116647-01H 13
www.fmiproducts.com
VENTING INSTALLATION INSTRUCTIONS
Continued
CORNER INSTALLATION Recommended Applications:
• Corner ground oor installation
• Ground oor installation where pipe vents horizontally through wall (over 12" horizontal pipe)
• Basement installation where one foot clearance from ground to termination is possible
Not to Exceed
Square Termination
Wall Firestop
Figure 15 - Horizontal Termination Conguration for Corner Installation Using One
SNORKEL TERMINATION INSTALLATION Recommended Applications:
• Installations requiring a vertical rise on
building exterior
• Any installation using snorkel termination
to achieve one foot above ground
(H) Limits
45° Elbow
Vertical (V) Required
Vertical (V) Vertical Pipe Horizontal (H)
*43 3/4" min. None 30" max. 53 3/4" min. 1 ft. 48" max. 65 3/4" min. 2 ft. 60" max. 77 3/4" min. 3 ft. 84" max.
89 3/4" min. 4 ft. 20' max.
* Ground Floor Corner Venting
Snorkel Termination
90° Elbow
As Required
for (V), See
Chart for Pipe Section Required
90° Elbow
Not to Exceed
(H) Limits
90° Elbow
Wall Firestop
45° Elbow
Snorkel terminations are available for instal­lations requiring a vertical rise on the exterior of the building. If installing snorkel termination below grade, you must provide proper drain­age to prevent water from entering snorkel
termination (see Figure 16). Do not back ll
around snorkel termination.
Snorkel
Termination
90° Elbow
12" Min.
Wall
Firestop
Square Termination
12" Min.
Snorkel
Termination
12" Min.
12" Min.
Adequate
Drainage
Figure 16 - Snorkel Termination Congurations for Below Ground Installation
www.fmiproducts.com
116647-01H14
Loading...
+ 30 hidden pages