tenance can cause injury
or property damage. Refer
to this manual for correct
installation and operational procedures. For assis-
tance or additional infor-
mation consult a qualied
installer, service agency
or the gas supplier.
WARNING: This is an
unvented gas-red heater. It uses air (oxygen)
from the room in which
it is installed. Provisions
for adequate combustion
and ventilation air must
be provided. Refer to Air
for Combustion and Ventilation section on page 5
of this manual.
This appliance is only for
use with the type of gas
indicated on the rating
plate. This appliance is
not convertible for use
with other gases.
www.fmiproducts.com
This appliance may be installed in an aftermarket,*
perma n ently locat e d,
manufactured (mobile)
home, where not prohibited by local codes.
* Aftermarket: Completion of sale, not for
purpose of resale, from the manufacturer
WARNING: This product con-
tains and/or generates chemicals
known to the State of California
to cause cancer or birth defects
or other reproductive harm.
IMPORTANT: Read this owner’s
manual carefully and completely
be for e t rying to assemble,
operate or service this heater.
Improper use of this heater can
cause serious injury or death
from burns, fire, explosion,
electrical shock and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs
of carbon monoxide poisoning resemble the
u, with headaches, dizziness or nausea. If
you have these signs, the heater may not be
working properly. Get fresh air at once! Have
heater serviced. Some people are more affected by carbon monoxide than others. These
include pregnant women, people with heart or
lung disease or anemia, those under the inuence of alcohol and those at high altitudes.
125325-01A2
SAFETY
Continued
Natural and Propane/LP Gas: Natural and
propane/LP gases are odorless. An odormaking agent is added to these gases. The
odor helps you detect a gas leak. However, the
odor added to the gas can fade. Gas may be
present even though no odor exists.
Make certain you read and understand all
warnings. Keep this manual for reference. It
is your guide to safe and proper operation of
this heater.
WARNING: Any change to
this heater or its controls can
be dangerous.
WARNING: Do not use a
blower insert, heat exchanger
insert or other accessory not approved for use with this heater.
Due to high temperatures, the
appliance should be located out
of trafc and away from furniture
and draperies.
Do not place clothing or other
ammable material on or near
the appliance. Never place any
objects on the heater.
Surface of heater becomes very
hot when running heater. Keep
children and adults away from
hot surface to avoid burns or
clothing ignition. Heater will
remain hot for a time after shut-
down. Allow surface to cool
before touching.
Carefully supervise young chil-
dren when they are in the room
with heater.
Make sure grill guard is in place
before running heater.
125325-01A3
www.fmiproducts.com
Keep the appliance area clear
and free from combustible materials, gasoline and other ammable vapors and liquids.
1. This appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convertible for use with
other gases.
2. Do not place propane/LP supply tank(s)
inside any structure. Locate propane/LP
supply tank(s) outdoors.
3. This heater shall not be installed in a
bedroom or bathroom.
4. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor’s phone. Follow the gas supplier’s instructions
• if you cannot reach your gas supplier,
call the re department
5. This heater needs fresh, outside air ventilation to run properly. This heater has an Oxygen Depletion Sensing (ODS) safety shutoff
system. The ODS shuts down the heater if
not enough fresh air is available. See Air for Combustion and Ventilation, page 5.
6. Keep all air openings in front and bottom
of heater clear and free of debris. This will
insure enough air for proper combustion.
7. If heater shuts off, do not relight until you
provide fresh, outside air. If heater keeps
shutting off, have it serviced.
8. Do not run heater
• where ammable liquids or vapors are
used or stored
• under dusty conditions
9. Before using furniture polish, wax, carpet
cleaner or similar products, turn heater off.
If heated, the vapors from these products
may create a white powder residue within
burner box or on adjacent walls or furniture.
10. Do not use heater if any part has been
under water. Immediately call a qualied
service technician to inspect the room
heater and to replace any part of the
control system and any gas control which
has been under water.
SAFETY
Ignitor Button
Control Knob
Heater
Cabinet
Front Panel
Glass Panel
Grill Guard
Continued
11. Turn off and let cool before servicing. Only
a qualied service person should service
and repair heater.
12. Operating heater above elevations of
4,500 feet (1,371 m) could cause pilot
outage.
13. To prevent performance problems, do not
use propane/LP fuel tank of less than 100
lbs. (45 kg) capacity.
LOCAL CODES
Install and use heater with care. Follow all
local codes. In the absence of local codes,
use the latest edition of The National Fuel
Gas Code ANSI Z223/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
14. Provide adequate clearances around air
openings.
State of Massachusetts: The installation must be made by a licensed plumber
or gas fitter in the Commonwealth of
Massachusetts.
Sellers of unvented propane or natural
gas-red supplemental room heaters shall
provide to each purchaser a copy of 527
CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for
bedroom and bathroom installation in the
Commonwealth of Massachusetts.
PRODUCT
IDENTIFICATION
Figure 1 - Vent-Free Gas Heater
(actual heater may vary from illustration
UNPACkING
1. Remove heater from carton.
2. Remove all protective packaging applied
to heater for shipment.
3. Check heater for any shipping damage. If
heater is damaged call FMI PRODUCTS,
LLC at 1-866-328-4537 for replacement
parts before returning to dealer.
PRODUCT FEATURES
SAFETY DEVICE
This heater has a pilot with an Oxygen Depletion Sensing (ODS) safety shutoff system. The
ODS/pilot is a required feature for vent-free
room heaters. The ODS/pilot shuts off the
heater if there is not enough fresh air.
IGNITION SYSTEM
Some models are equipped with a piezo
ignitor that requires no matches, batteries or
other sources to light heater.
Other heaters are equipped with an electronic
ignitor to light heater fuel supply.
THERMOSTATIC HEAT CONTROL
Thermostat models have a thermostat sensing bulb and a control valve. This results in the
greatest heater comfort. This can also result
in lower gas bills.
www.fmiproducts.com
125325-01A4
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall
not be installed in a room or space
unless the required volume of indoor combustion air is provided
by the method described in the
National Fuel Gas Code, ANSI
Z223.1/NFPA 54, the International
Fuel Gas Code, or applicable lo-
cal codes. Read the following instructions to insure proper fresh
air for this and other fuel-burning
appliances in your home.
Today’s homes are built more energy efcient
than ever. New materials, increased insulation
and new construction methods help reduce
heat loss in homes. Home owners weather
strip and caulk around windows and doors to
keep the cold air out and the warm air in. During heating months, home owners want their
homes as airtight as possible.
While it is good to make your home energy
efcient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning appliances need fresh air for proper combustion
and ventilation.
Exhaust fans, heaters, clothes dryers and fuel
burning appliances draw air from the house to
operate. You must provide adequate fresh air
for these appliances. This will insure proper
venting of vented fuel-burning appliances.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel
Gas Code. ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 5 through 7 will
help you classify your space and provide
adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion
and ventilation. However, in buildings of unusually tight construction, you must provide
additional fresh air.
Unusually tight construction is dened as
construction where:
a. walls and ceilings exposed to the outside
atmosphere have a continuous water
vapor retarder with a rating of one perm
-11
(6x10
kg per pa-sec-m2) or less with
openings gasketed or sealed and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to areas
such as joints around window and door
frames, between sole plates and oors,
between wall-ceiling joints, between wall
panels, at penetrations for plumbing,
electrical and gas lines and at other open-
ings.
If your home meets all of the three criteria above,
you must provide additional fresh air. See Ven-tilation Air From Outdoors, page 7.
If your home does not meet all of the three
criteria above, proceed to Determining Fresh-Air Flow For Heater Location.
Conned Space and Unconned Space
The National Fuel Gas Code ANSI Z223.1/
NFPA 54 denes a conned space as a space
whose volume is less than 50 cubic feet per
1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed
in that space and an unconned space as a
space whose volume is not less than 50 cubic
feet per 1,000 Btu per hour (4.8 m3 per kw)
of the aggregate input rating of all appliances
installed in that space. Rooms communicating
directly with the space in which the appliances
are installed*, through openings not furnished
with doors, are considered a part of the unconned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation
grills between them.
125325-01A5
www.fmiproducts.com
AIR FOR COMBUSTION AND VENTILATION
Continued
DETERMINING FRESH-AIR FLOW
FOR HEATER LOCATION
Determining if You Have a Conned or
Unconned Space
Use this work sheet to determine if you have
a conned or unconned space.
Space: Includes the room in which you will install
heater plus any adjoining rooms with doorless
passageways or ventilation grills between the
rooms.
1. Determine the volume of the space (length
x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (6.1m) (length) x
16 ft. (4.88m) (width) x 8 ft. (2.44 m) (ceiling
height) = 2,560 cu. ft. (72.49 m2)(volume of
space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume
of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2,560 cu. ft. (72.49 m2) (volume of
space) x 20 = 51,200 (maximum Btu/Hr the
space can support)
3. Add the Btu/Hr of all fuel burning appliances
in the space.
Vent-free heater _________ Btu/Hr
Gas water heater* _________ Btu/Hr
Gas furnace _________ Btu/Hr
Vented gas heater _________ Btu/Hr
Gas heater logs _________ Btu/Hr
Other gas appliances* + _________ Btu/Hr
Total = _________Btu/Hr* Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.
Example:
Gas water heater _________ Btu/Hr
Vent-free heater + _________Btu/HrTotal = _________Btu/Hr
40,000
20,000
60,000
4. Compare the maximum Btu/Hr the space
can support with the actual amount of Btu/
Hr used.
_______ Btu/Hr (maximum can support) _______ Btu/Hr (actual amount used)Example: 51,200 Btu/ Hr (ma ximum the
space can support)
60,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the example is a conned space
because the actual Btu/Hr used is more than the
maximum Btu/Hr the space can support. You
must provide additional fresh air. Your options
are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides an
unconned space, remove door to adjoining
room or add ventilation grills between rooms.
See Ventilation Air From Inside Building.
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors, page 7.
C. Install a lower Btu/Hr heater, if lower Btu/Hr
size makes room unconned.
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is
an unconned space. You will need no additional
fresh air ventilation.
WARNING: If the area in which
the heater may be operated does
not meet the required volume for
indoor combustion air, combustion and ventilation air shall be
provided by one of the methods
described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54,
the International Fuel Gas Code,
or applicable local codes.
www.fmiproducts.com
125325-01A6
AIR FOR COMBUSTION AND VENTILATION
Or
Remove
Door into
Adjoining
Room,
Option 3
Ventilation Grills
Into Adjoining Room,
Option 2
12"
12"
Ventilation
Grills into
Adjoining
Room,
Option 1
Outlet
Air
Ventilated
Attic
Outlet
Air
Inlet
Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconned space. When ventilating to an
adjoining unconned space, you must provide
two permanent openings: one within 12" (30.5
cm) of the ceiling and one within 12" (30.5 cm)
of the oor on the wall connecting the two
spaces (see options 1 and 2, Figure 2, page
7). You can also remove door into adjoining
room (see option 3, Figure 2, page 7). Follow
the National Fuel Gas Code, ANSI Z223.1/
NFPA 54, Air for Combustion and Ventilation
for required size of ventilation grills or ducts.
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills
or ducts. You must provide two permanent
openings: one within 12" (30.5 cm) of the ceiling and one within 12" (30.5 cm) of the oor.
Connect these items directly to the outdoors
or spaces open to the outdoors. These spaces
include attics and crawl spaces. Follow the Na-
tional Fuel Gas Code, ANSI Z223.1/NFPA 54,
Air for Combustion and Ventilation for required
size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for inlet
or outlet air into attic if attic has a thermostatcontrolled power vent. Heated air entering the
attic will activate the power vent.
Figure 2 - Ventilation Air from Inside
Building
Figure 3 - Ventilation Air from Outdoors
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat.
Use this heater along with your
primary heating system. Do not
install this heater as your primary heat source. If you have a
central heating system, you may
run system’s circulating blower
while using heater. This will help
circulate the heat throughout the
house. In the event of a power
outage, you can use this heater
as your primary heat source.
125325-01A7
www.fmiproducts.com
WARNING: A qualied service person must install heater.
Follow all local codes.
CHECK GAS TYPE
Use only the correct gas type (natural
or propane/LP) for your unit. If your gas
supply is not correct, do not install heater.
Call dealer where you bought heater for
proper type heater.
WARNING: This appliance is
equipped for either natural gas or
propane/LP gas but not both. Gas
type is indicated on the rating plate.
Field conversion is not permitted.
INSTALLATION
Continued
INSTALLATION ITEMS
Before installing heater, make sure you have
the items listed below.
• for propane/LP gas, external regulator
(supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• ground joint union
• sediment trap
• tee joint
• pipe wrench
• for natural gas, test gauge connection*
• hardware packet (included)
- wall anchor (4) 095112-02
- red key (1) 095116-01
- pan head screw, black (4) 097403-02
- nylon spacer (2) 099064-02
- clip (1) 099123-01
- Phillips head screw, silver (4) 100159-02
* An equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge
connection. The optional equipment shutoff
valve can be purchased from your dealer.
LOCATING HEATER
This heater is designed to be mounted on a wall.
WARNING: Maintain the
minimum clearances shown
in Figure 4. If you can, provide
greater clearances from oor,
ceiling and joining wall.
You can locate heater on oor, away from
a wall. An optional oor mounting stand is
needed. Purchase the oor mounting stand
from your dealer. See Accessories, page 26,
if stand is not included with your heater.
WARNING: Never install the
heater
• in a bedroom or bathroom
• in a recreational vehicle
• where curtains, furniture, clothing or other ammable objects
are less than 36" (91.5 cm)
from the front, top or sides of
the heater
• as a replace insert
• in high trafc areas
• in windy or drafty areas
www.fmiproducts.com
CAUTION: This heater creates
warm air currents. These currents
move heat to wall surfaces next
to heater. Installing heater next
to vinyl or cloth wall coverings or
operating heater where impurities
(such as, but not limited to, tobacco smoke, aromatic candles,
cleaning uids, oil or kerosene
lamps, etc.) in the air exist, may
discolor walls or cause odors.
IMPORTANT: Vent-free heaters add moisture to the air. Although this is benecial,
installing heater in rooms without enough
ventilation air may cause mildew to form
from too much moisture. See Air for Com-bustion and Ventilation, page 5. If high
humidity is experienced, a dehumidier
may be used to help lower the water vapor
content in the air.
CAUTION: If you install the
heater in a home garage
• heater pilot and burner must be at
least 18" (45.7 cm) above oor
• locate heater where moving
vehicle will not hit it
For convenience and efciency, install heater
• where there is easy access for operation,
inspection and service
• in coldest part of room
If not included with your heater, an optional fan
kit is available from your dealer. See Acces-sories, page 26. If planning to use fan, locate
heater near an electrical outlet (see page 16).
125325-01A8
INSTALLATION
Minimum
From
Sides Of
Heater
2" (5.1 cm)
FLOOR
CEILING
36"
(91.5 cm)
Minimum
Minimum To
Top Surface
Of Carpeting,
Tile Or Other
Combustible
Material
Left
Side
Right
Side
10" (25.4 cm)
36"
(91.5 cm)
Screw
Front Panel
Continued
Figure 4 - Mounting Clearances As
Viewed From Front of Heater
THERMOSTAT SENSING BULB
(Thermostat Models Only)
The thermostat sensing bulb is located below
the heater. Do not move this bulb during installation or operation of the heater.
INSTALLING HEATER TO WALL
Mounting Bracket
Locate mounting bracket in heater carton. Remove mounting bracket from heater carton.
Figure 5 - Mounting Bracket
Removing Front Panel Of Heater
1. Remove the four painted screws, two on
each side of front panel.
2. Pull bottom of front panel forward, then
out.
3. Remove any remaining packaging materials.
Figure 6 - Removing Front Panel of
Heater (actual heater may vary from
Illustration)
Methods For Attaching Mounting Bracket
To Wall
Only use last hole on each end of mounting
bracket to attach bracket to wall. These two
holes are 14" (35.6 cm) apart from their centers. Attach mounting bracket to wall in one
of two ways:
1. Attaching to wall stud
2. Attaching to wall anchor
Attaching to Wall Stud: This method provides the strongest hold. Insert mounting
screws through mounting bracket and into
wall studs.
Attaching to Wall Anchor: This method allows you to attach mounting bracket to hollow
walls (wall areas between studs) or to solid
walls (concrete or masonry).
Decide which method better suits your needs.
Either method will provide a secure hold for
the mounting bracket.
Marking Screw Locations
1. Tape mounting bracket to wall where
heater will be located. Make sure mounting bracket is level.
WARNING: Maintain minimum
clearances shown in Figure
8, page 10. If you can, provide
greater clearances from oor and
joining wall.
www.fmiproducts.com
125325-01A9