FMI VS1824PM, LVS18-PP, LVS18-VO, LVS24-VO, LVS24-PP Owner's Operation And Installation Manual

UNVENTED (VENT-FREE) GAS LOG HEATER
P F S
®
US
OWNER’S OPERATION AND INSTALLATION MANUAL
VARIABLE MANUALLY CONTROLLED BURNER SYSTEM MODELS
VS1824NM AND VS1824PM
FOR USE WITH THE FOLLOWING LOGS
LVS18-VO, LVS24-VO, LVS18-PP AND LVS24-PP
Also Design-Certied as Vented Decorative Appliance
WARNING: If the information in this manual is not
followed exactly, a re or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
— Installation and service must be performed by a quali-
ed installer, service agency or the gas supplier.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
For more information, visit www.fmiproducts.com
TABLE OF CONTENTS
Safety .................................................................. 2
Product Identication ........................................... 4
Local Codes......................................................... 5
Unpacking............................................................ 5
Product Features ................................................. 5
Air For Combustion and Ventilation ..................... 5
Installation ........................................................... 8
Operation .......................................................... 18
Inspecting Burners............................................. 20
SAFETY
Cleaning and Maintenance ................................ 20
Troubleshooting ................................................. 22
Parts .................................................................. 26
Specications .................................................... 30
Technical Service............................................... 30
Service Hints ..................................................... 30
Replacement Parts ............................................ 30
Accessories ....................................................... 30
Warranty ..............................................Back Cover
WARNING: Improper
installation, adjustment,
alteration, service or main-
tenance can cause injury or property damage. Refer
to this manual for correct
installation and operation­al procedures. For assis-
tance or additional infor-
mation consult a qualied installer, service agency or the gas supplier.
WARNING: This ap-
pliance is for installation only in a solid-fuel burning
masonry or UL127 fac-
tory-built fireplace or in a listed ventless rebox enclosure. It is design-cer­tied for these installations
in accordance with ANSI
Z21.11.2. Exception: Do not install this appliance in a factory-built replace that
includes instructions stat-
ing it has not been tested or should not be used with unvented gas logs.
WARNING: This is an
unvented gas-red heat­er. It uses air (oxygen)
from the room in which
it is installed. Provisions for adequate combustion
and ventilation air must
be provided. Refer to Air for Combustion and Ven­tilation section on page 5
of this manual.
This appliance may be in-
stalled in an aftermarket,*
perma n ently locat e d, manufactured (mobile) home, where not prohib­ited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
www.fmiproducts.com
125500-01A2
SAFETY
Continued
WARNING: This product con-
tains and/or generates chemicals
known to the State of California
to cause cancer or birth defects or other reproductive harm.
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, op­erate or service this replace. Improper use of this replace can cause serious injury or death from burns, re, explo­sion, electrical shock and carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs
of carbon monoxide poisoning resemble the
u, with headaches, dizziness or nausea. If you have these signs, the replace may not be working properly. Get fresh air at once! Have replace serviced. Some people are
more affected by carbon monoxide than oth-
ers. These include pregnant women, people with heart or lung disease or anemia, those under the inuence of alcohol and those at
high altitudes. Natural and Propane/LP Gas: Natural and
propane/LP gases are odorless. An odor-mak­ing agent is added to these gases. The odor
helps you detect a gas leak. However, the odor
added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all
warnings. Keep this manual for reference. It
is your guide to safe and proper operation of
this replace.
WARNING: Any change to
this heater or its controls can
be dangerous.
WARNING: Do not use a
blower insert, heat exchanger insert or other accessory not ap­proved for use with this heater.
WARNING: Do not allow fans
to blow directly into the replace. Avoid any drafts that alter burner ame patterns. Ceiling fans can create drafts that alter burner ame patterns. Altered burner patterns can cause sooting.
Due to high temperatures, the appliance should be located out of trafc and away from furniture and draperies.
Do not place clothing or other ammable material on or near the appliance. Never place any objects on the heater.
Heater base assembly becomes very hot when running heater. Keep children and adults away from hot surface to avoid burns or clothing ignition. Heater
will remain hot for a time after
shutdown. Allow surface to cool before touching.
Carefully supervise young chil-
dren when they are in the room
with heater.
You must operate this heater with a replace screen in place. Make sure replace screen is closed before running heater.
Keep the appliance area clear and free from combustible ma­terials, gasoline and other am­mable vapors and liquids.
1. This appliance is only for use with type of
gas indicated on rating plate. This appli-
ance is not convertible for use with other
gases.
125500-01A 3
www.fmiproducts.com
SAFETY
Continued
2. Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors (propane/LP units only).
3. To prevent performance problems, the
use of a propane/LP tank of less than 100 lbs. capacity is not recommended (propane/LP units only).
4. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor ’s phone. Follow the gas
supplier’s instructions
• if you cannot reach your gas supplier,
call the re department
5. This heater shall not be installed in a bedroom or bathroom unless installed as a vented appliance (see Installing Damper
Clamp Accessory for Vented Operation,
page 11). This gas log set may not be installed as a vented appliance in a bed-
room or bathroom in the Commonwealth
of Massachusetts.
6. Do not burn solid-fuel in a masonry or
UL127 factory-built replace in which a
vent-free room heater is installed.
7. Before installing in a solid fuel burning re­place, the chimney ue and rebox must be cleaned of soot, creosote, ashes and loose paint by a qualied chimney cleaner. Creosote will ignite if highly heated. A dirty chimney ue may create and distribute soot within the house. Inspect chimney ue and rebox for damage. If damaged, repair ue before operating heater.
8.
If replace has glass doors, never operate this heater with glass doors closed. If you operate heater with doors closed, heat buildup inside replace will cause glass to
burst. Make sure there are no obstructions
across openings of replace.
9. This log heater is designed to be smoke-
less. If logs ever appear to smoke, turn off heater and call a qualied service person.
Note: During initial operation, slight smok-
ing could occur due to log curing and heater burning manufacturing residues.
10. To prevent the creation of soot, follow
the instructions in Cleaning and Mainte­nance, page 20.
www.fmiproducts.com
11. Before using furniture polish, wax, carpet cleaner or similar products, turn heater off. If heated, the vapors from these products may create a white powder residue within burner box or on adjacent walls or furniture.
12. This heater needs fresh, outside air ven-
tilation to run properly. This heater has an Oxygen Depletion Sensing (ODS) safety
shutoff system. The ODS shuts down the
heater if not enough fresh air is available. See Air for Combustion and Ventilation,
page 5. If heater keeps shutting off, see
Troubleshooting, page 22.
13. Do not run heater
• where ammable liquids or vapors are
used or stored
• under dusty conditions
14. Do not use this heater to cook food or burn paper or other objects.
15. Do not use heater if any part has been ex-
posed to or under water. Immediately call a qualied service technician to inspect
the room heater and to replace any part of the control system and any gas control
which has been under water.
16. Do not operate heater if any log is broken. Do not operate heater if a log is chipped
(dime-sized or larger).
17. Turn heater off and let cool before servic-
ing. Only a qualied service person should
service and repair heater.
18. Operating heater above elevations of
4,500 feet could cause pilot outage.
19. Provide adequate clearances around air
openings.
PRODUCT
IDENTIFICATION
Grate
Heater Base
Control Knob
Figure 1 - Product Idetication
125500-01A4
LOCAL CODES
Install and use heater with care. Follow all local codes. In the absence of local codes,
use the latest edition of The National Fuel Gas Code ANSI Z223/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
Note: Where listed vented decorative logs are required, thermostat models are not permitted.
UNPACkING
CAUTION: Do not remove the
data plates from the grate as­sembly. The data plates contain important warranty and safety information.
1. Remove log and heater base assembly from cartons.
PRODUCT FEATURES
OPERATION
This heater is clean burning. It requires no
outside venting. There is no heat loss out a vent or up a chimney. Heat is generated by
realistic, dancing yellow ames. This heater is designed for vent-free operation with ue
dampe r clo sed. It has b een tested and approved to ANSI Z21.11.2 standard for unvented heaters. State and local codes in some areas prohibit the use of vent-free
State of Massachusetts: The installa­tion must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts.
Sellers of unvented propane or natural
gas-red supplemental room heaters shall
provide to each purchaser a copy of 527 CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for bedroom and bathroom installation in the
Commonwealth of Massachusetts.
Note: Do not pick up heater base assem-
bly by burners. This could damage heater. Always handle base assembly by grate.
2. Remove all protective packaging applied to log and heater for shipment.
3. Check heater for any shipping damage. If
heater is damaged call FMI PRODUCTS,
LLC at 1-866-328-4537 for replacement parts before returning to dealer.
heaters. Non-thermostat models may also be operated as a vented decorative (ANSI
Z21.60) product by opening ue damper.
SAFETY PILOT
This heater has a pilot with an Oxygen Deple­tion Sensing (ODS) safety shutoff system. The
ODS/pilot is a required feature for vent-free
room heaters. The ODS/pilot shuts off the heater if there is not enough fresh air.
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall
not be installed in a room or space unless the required volume of in­door combustion air is provided by the method described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, the International Fuel Gas Code, or applicable lo-
cal codes. Read the following in­structions to insure proper fresh air for this and other fuel-burning appliances in your home.
125500-01A 5
www.fmiproducts.com
Today’s homes are built more energy efcient than ever. New materials, increased insulation and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. Dur­ing heating months, home owners want their
homes as airtight as possible. While it is good to make your home energy
efcient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning ap­pliances need fresh air for proper combustion and ventilation.
AIR FOR COMBUSTION AND VENTILATION
Continued
Exhaust fans, replaces, clothes dryers and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure
proper venting of vented fuel-burning appli­ances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code. ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space The information on pages 5 through 7 will
help you classify your space and provide
adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion
and ventilation. However, in buildings of un­usually tight construction, you must provide
additional fresh air.
Unusually tight construction is dened as
construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous water vapor retarder with a rating of one perm (6x10 less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window and door frames, between sole plates and oors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines and at other openings.
If your home meets all of the three criteria
above, you must provide additional fresh air.
See Ventilation Air From Outdoors, page 7. If your home does not meet all of the three
criteria above, proceed to Determining Fresh-Air Flow For Heater Location.
Conned Space and Unconned Space
The National Fuel Gas Code ANSI Z223.1/ NFPA 54 denes a conned space as a space
whose volume is less than 50 cubic feet per
-11
kg per pa-sec-m2) or
www.fmiproducts.com
1,000 Btu per hour (4.8 m3 per kw) of the ag­gregate input rating of all appliances installed
in that space and an unconned space as a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 m3 per kw)
of the aggregate input rating of all appliances installed in that space. Rooms communicating
directly with the space in which the appliances are installed*, through openings not furnished with doors, are considered a part of the un­conned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation grills between them.
DETERMINING FRESH-AIR FLOW
FOR FIREPLACE LOCATION
Determining if You Have a Conned or Unconned Space
Use this work sheet to determine if you have a conned or unconned space.
Space: Includes the room in which you will install replace plus any adjoining rooms with door­less passageways or ventilation grills between
the rooms.
1. Determine the volume of the space (length
x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2,560 cu. ft.
(volume of space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 2,560 cu. ft. (volume of space) x
20 = 51,200 (maximum Btu/Hr the space can
support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free replace _________ Btu/Hr Gas water heater* _________ Btu/Hr
Gas furnace _________ Btu/Hr Vented gas heater _________ Btu/Hr Gas replace logs _________ Btu/Hr Other gas appliances* + _________ Btu/Hr Total = _________Btu/Hr * Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.
125500-01A6
Or
Remove Door into Adjoining
Room, Option
3
Ve ntilation Grills
Into Adjoining Room,
Option 2
Ve ntilation
Grills Into
Adjoining
Room,
Option 1
12"
12"
Outlet Air
V e ntilated Attic
Outlet A
ir
Inlet Air
Inlet Air
V e ntilated
Crawl Space
T o
Crawl
Space
T o Attic
AIR FOR COMBUSTION AND VENTILATION
Continued
Example:
Gas water heater _________ Btu/Hr Vent-free replace + _________Btu/Hr
Total = _________Btu/Hr
40,000 31,500 71,500
4. Compare the maximum Btu/Hr the space
can support with the actual amount of Btu/Hr
used.
_______ Btu/Hr (maximum the space can
support)
_______ Btu/Hr (actual amount of Btu/Hr
used)
Example: 51,200 Btu/Hr (maxim um th e
space can support)
71,500 Btu/Hr (actual amount of
Btu/Hr used)
The space in the example is a conned space
because the actual Btu/Hr used is more than the
maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides an
unconned space, remove door to adjoining room or add ventilation grills between rooms.
See Ventilation Air From Inside Building, page 7.
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors, page 7.
C. Install a lower Btu/Hr replace, if lower Btu/Hr
size makes room unconned.
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space is an unconned space. You will need no additional
fresh air ventilation.
WARNING: If the area in which
the heater may be operated does not meet the required volume for indoor combustion air, combus­tion and ventilation air shall be provided by one of the methods described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, the International Fuel Gas Code,
or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconned space. When ventilating to an adjoining unconned space, you must provide two permanent openings: one within 12" of the
125500-01A 7
www.fmiproducts.com
ceiling and one within 12" of the oor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code ANSI
Z223.1/NFPA 54, Air for Combustion and Ventilation for required size of ventilation
grills or ducts.
Figure 2 - Ventilation Air from Inside
Building
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two perma­nent openings: one within 12" of the ceiling and one within 12" of the oor. Connect these
items directly to the outdoors or spaces open to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel Gas Code ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation for required size
of ventilation grills or ducts. IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a thermo-
stat-controlled power vent. Heated air entering the attic will activate the power vent.
Figure 3 - Ventilation Air from Outdoors
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your pri­mary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: A qualied ser­vice person must install heater. Follow all local codes.
NOTICE: State or local codes may
only allow operation of this appli­ance in a vented conguration. Check your state or local codes.
WARNING: Before installing in a solid fuel burning replace, the chimney ue and rebox must be cleaned of soot, creo­sote, ashes and loose paint by a qualied chimney cleaner. Creo­sote will ignite if highly heated. A dirty chimney ue may create and distribute soot within the house. Inspect chimney ue and rebox for damage. If damaged, repair ue before operating heater.
WARNING: Seal any fresh air vents or ash clean-out doors
located on oor or wall of re­place. If not, drafting may cause pilot outage or sooting. Use a heat-resistant sealant. Do not seal chimney ue damper.
WARNING: Never install the
heater
in a bedroom or bathroom un­less installed as a vented appli­ance (see page 11)
• in a recreational vehicle
where curtains, furniture, cloth-
ing or other ammable objects are less than 36" from front and 42" from top of heater; for side clearances see Figure 4, page 9
• in high trafc areas
• in windy or drafty areas
CAUTION: This heater creates
warm air currents. These currents
move heat to wall surfaces next
to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities (such as, but not limited to, to­bacco smoke, aromatic candles, cleaning uids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.
IMPORTANT: Vent-free heaters add moisture
to the air. Although this is benecial, installing heater in rooms without enough ventilation air may cause mildew to form from too much
moisture. See Air for Combustion and Ventila­tion, page 5.
CHECK GAS TYPE
Use only the correct gas type (natural or propane/LP) for your unit. If your gas sup-
ply is not correct, do not install heater. Call dealer where you bought heater for proper
type heater.
WARNING: This appliance is equipped for either natural gas or propane/LP gas but not both. Gas type is indicated on the rat­ing plate. Field conversion is not permitted.
www.fmiproducts.com
125500-01A8
INSTALLATION
Continued
INSTALLATION AND CLEARANCES
(Vent-Free Operation Only)
WARNING: Maintain the
minimum clearances. If you can, provide greater clearances from oor, ceiling and adjoining wall.
Minimum Fireplace Clearance to
Combustible Materials
Side Wall 16", Ceiling 42", Front 36"
Minimum Firebox Size
Height 17", Depth 14", Front Width 24",
Rear Width 20" (measured at 14" depth).
Car efully follow instructions below. This will ensure safe installation into a masonry, UL127-listed manufactured replace or certi­ed vent-free rebox.
Minimum Clearances For Side
Combustible Material, Side Wall and Ceiling
A. Clearances from side of replace cabinet
to any combustible material and wall should follow diagram in Figure 4.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and protrudes 3 1/2" from the wall. This com-
bustible material must be 4" from the side of the replace cabinet (see Figure 4).
Note: When installing your gas logs into
a manufactured rebox, follow rebox
manufacturer’s instructions for minimum clearances to combustible materials.
B. Clearances from the top of the replace
opening to the ceiling should not be less
than 42".
Example
NOTICE: Manual control heaters
may be used as a vented product.
If so, you must always run heater
with chimney ue damper open. If running heater with damper open, noncombustible material above re­place opening is not needed. Go to
Installing Damper Clamp Accessory for Vented Operation, page 11.
Minimum Noncombustible Material
Clearances
If Not Using Mantel
Note: If using a mantel, proceed to If Using Mantel, page 10. If not using a mantel, follow the information below.
You must have noncombustible material(s) above the replace opening. Noncombustible materials (such as slate, marble, tile, etc.)
must be at least 1/2 inch thick. With sheet metal, you must have noncombustible ma­terial behind it. Noncombustible material
must extend at least 8" up (for all models). If noncombustible material is less than 12", you must install the replace hood accessory
(for all models). See Figure 5 on page 10 for minimum clearances.
Noncombustible
Material Distance
(A)
12" or more Noncombustible material
Between 8" and 12"
Less than 8" Noncombustible material
Requirements for Safe
Installation
okay.
Install replace hood
accessory (GA6050 or GA6053 see Accesso-
ries, page 30).
must be extended to at
least 8". See Between 8" and 12", above. If you
cannot extend material,
you must operate heater
with ue damper open.
*
*Minimum 16" from Side Wall
Figure 4 - Minimum Clearance for
Combustible to Wall
125500-01A 9
www.fmiproducts.com
Minimum Noncombustible Material
Minimum Noncombustible Material Height
Distances to Underside of Mantel
Top of Fireplace Opening
Underside of Mantel Shelf
Mantel Shelf
8"
(A)
8" 14" 17" 20"
All minimum distances are in inches
Log Set All Models
2 1/2"
6"
8"
10"
INSTALLATION
Heat Resistant Material
(A)
Continued
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
If Using Mantel
You must have noncombustible material(s) above the replace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2" thick. With sheet metal, you
must have noncombustible material behind it. Noncombustible material must extend at least
8" up. See Figure 5, page 9, and Figure 6 for
minimum clearances. IMPORTANT: If you cannot meet these mini-
mum clearances, you must operate heater with chimney ue damper open. Go to Install-
ing Damper Clamp Accessory for Vented Operation, page 11.
MANTEL CLEARANCES
In addition to meeting noncombustible mate-
rial clearances, you must also meet required clearances between replace opening and
mantel shelf. If you do not meet the clearances
listed below, you will need a hood. You must meet the minimum clearances
between the mantel shelf and the top of the replace opening as shown in Figure 6.
Determining Minimum Mantel Clearance When Using a Hood
If minimum clearances in Figure 6, page 10, are not met, you must have a hood. When
using a hood there are still certain minimum
mantel clearances required. Follow minimum clearances shown in Figure 7 page 11 when
using hood.
NOTICE: Surface temperatures of adjacent walls and mantels be­come hot during operation. Walls and mantels above the rebox may become hot to the touch. If installed properly, these tem­peratures meet the requirement of the national product standard.
Follow all minimum clearances
shown in this manual.
Figure 6 - Minimum Mantel Clearances
Without Using Hood
www.fmiproducts.com
NOTICE: If your installation does not meet the minimum clear­ances shown, you must do one
of the following:
• operate the logs only with the
ue damper open
• raise the mantel to an accept-
able height
• remove the mantel
FLOOR CLEARANCES
A. If installing appliance on oor level, you
must maintain the minimum distance of
14" to combustibles (see Figure 8 page
11).
B. If combustible materials are less than 14"
to replace, you must install appliance at least 5" above combustible ooring (see
Figure 9 page 11).
125500-01A10