FMI MF42INE, MF42IPE, VFGT24NE, VFGT24PE, VFGT30NE Owner's Operation And Installation Manual

...
UNVENTED (VENT-FREE) GAS LOG HEATER
PFS
US
OWNER’S OPERATION AND INSTALLATION MANUAL
REMOTE CONTROL LOG SET AND BURNER SYSTEM MODELS
MF42INE, MF42IPE, MF48INE, MF48IPE, VFGT24NE, VFGT24PE,
VFGT30NE, VFGT30PE, VFGT36NE AND VFGT36PE
MF42 MODELS MAY BE USED WITH LMF36-SC AND LMF42-SC LOGS ONLY
MF48 MODELS MAY BE USED WITH LMF48-SC LOGS ONLY
VFGT24 MODELS MAY BE USED WITH GT24 LOGS ONLY VFGT30 MODELS MAY BE USED WITH GT30 LOGS ONLY VFGT36 MODELS MAY BE USED WITH GT36 LOGS ONLY
®
WARNING: If the information in this manual is not
followed exactly, a re or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
— Installation and service must be performed by a quali-
ed installer, service agency or the gas supplier.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
For more information, visit www.fmiproducts.com
TABLE OF CONTENTS
Safety .................................................................. 2
Product Identication ........................................... 5
Local Codes......................................................... 5
Unpacking............................................................ 5
Product Features ................................................. 6
Air For Combustion and Ventilation ..................... 6
Installation ........................................................... 8
Operation ........................................................... 23
Inspecting Burners............................................. 29
SAFETY
WARNING: Improper
installation, adjustment,
alteration, service or main-
tenance can cause injury or property damage. Refer
to this manual for correct
installation and operation­al procedures. For assis-
tance or additional infor-
mation consult a qualied installer, service agency or the gas supplier.
WARNING: This ap­pliance is for installation only in a solid-fuel burn­ing masonry or UL127 factory-built replace or in a listed ventless rebox enclosure. It is design-cer­tied for these installations
in accordance with ANSI
Z21.11.2. Exception: Do not install this appliance in a factory-built replace that
includes instructions stat-
ing it has not been tested or should not be used with unvented gas logs.
Cleaning and Maintenance ................................ 29
Specications .................................................... 30
Wiring Diagram .................................................. 31
Troubleshooting ................................................. 32
Accessories ....................................................... 39
Parts .................................................................. 40
Replacement Parts ............................................ 43
Service Hints ..................................................... 43
Technical Service............................................... 43
Warranty ..............................................Back Cover
WARNING: This is an
unvented gas-red heat­er. It uses air (oxygen)
from the room in which
it is installed. Provisions for adequate combustion
and ventilation air must
be provided. Refer to Air for Combustion and Ven­tilation section on page 6
of this manual.
This appliance may be in-
stalled in an aftermarket,*
permanently located, manufactured (mobile) home, where not prohib­ited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
www.fmiproducts.com
125795-01B2
SAFETY
Continued
WARNING: This product con-
tains and/or generates chemicals
known to the state of California
to cause cancer or birth defects or other reproductive harm.
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, op­erate or service this replace. Improper use of this replace can cause serious injury or death from burns, re, explo­sion, electrical shock and carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning resemble the u, with headaches, dizziness or nausea. If you have these signs, the replace may not be
working properly. Get fresh air at once! Have replace serviced. Some people are more af­fected by carbon monoxide than others. These
include pregnant women, people with heart or lung disease or anemia, those under the inu-
ence of alcohol and those at high altitudes. Natural and Propane/LP
odor-making agent is added to these gases. The odor helps you detect a gas leak. How-
ever, the odor added to the gas can fade. Gas
may be present even though no odor exists. Make certain you read and understand all
warnings. Keep this manual for reference. It is your guide to safe and proper operation of
this replace.
gases are odorless. An
WARNING: Any change to
this heater or its controls can
be dangerous.
WARNING: Do not allow fans
to blow directly into the replace. Avoid any drafts that alter burner ame patterns. Ceiling fans can create drafts that alter burner ame patterns. Altered burner patterns can cause sooting.
Due to high temperatures, the appliance should be located out of trafc and away from furniture and draperies.
Do not place clothing or other ammable material on or near the appliance. Never place any objects on the heater.
Heater base assembly becomes very hot when running heater. Keep children and adults away from hot surface to avoid burns or clothing ignition. Heater
will remain hot for a time after
shutdown. Allow surface to cool before touching.
Carefully supervise young chil-
dren when they are in the room
with heater. When using the hand­held remote accessory, keep se­lector switch in the OFF position to prevent children from turning on burners with remote.
You must operate this heater with the replace screen and hood in place. Make sure re­place screen and hood are in place before running heater.
WARNING: Do not use a
blower insert, heat exchanger insert or other accessory not ap­proved for use with this heater.
125795-01B 3
www.fmiproducts.com
Keep the appliance area clear and free from combustible ma­terials, gasoline and other am­mable vapors and liquids.
SAFETY
Continued
1. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases.
2. Do not place propane/LP supply tank(s) inside any structure. Locate propane/LP supply tank(s) outdoors (propane/LP units only).
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor’s phone. Follow the gas sup­plier’s instructions
• if you cannot reach your gas supplier,
call the re department
4. This heater shall not be installed in a bedroom or bathroom.
5. Before installing in a solid fuel burning re­place, the chimney ue and rebox must be cleaned of soot, creosote, ashes and loose paint by a qualied chimney cleaner.
Creosote will ignite if highly heated. A dirty
chimney ue may create and distribute
soot within the house. Inspect chimney
ue for damage. If damaged, repair ue and rebox before operating heater.
6. Do not burn solid-fuel in a masonry or
UL127 factory-built replace in which a
vent-free room heater is installed.
7. If replace has glass doors, never operate
this heater with glass doors closed. If you
operate heater with doors closed, heat buildup inside replace will cause glass to
burst. Make sure there are no obstructions
across openings of replace.
8. To prevent the creation of soot, follow the
instructions in Cleaning and Maintenance, page 29.
9. Before using furniture polish, wax, carpet cleaner or similar products, turn heater off. If heated, the vapors from these products may
create a white powder residue within burner box or on adjacent walls and furniture.
10. This heater needs fresh, outside air ven­tilation to run properly. This heater has an Oxygen Depletion Sensing (ODS) safety shutoff system. The ODS shuts down the heater if enough fresh air is not available. See Air for Combustion and Ventilation,
page 6. If heater keeps shutting off, see Troubleshooting, page 32.
11. Do not run heater
• where ammable liquids or vapors are
used or stored
• under dusty conditions
12. Do not use this heater to cook food or burn paper or other objects.
13. Do not use heater if any part has been ex­posed to or under water. Immediately call
a qualied service technician to inspect
the room heater and to replace any part of the control system and any gas control which has been under water.
14. Do not operate heater if any log is broken. Do not operate heater if a log is chipped
(dime-sized or larger).
15. Turn heater off and let cool before servic-
ing, installing or repairing. Only a qualied service person should install, service or
repair heater.
16. Make sure the remote is set to the OFF position when you are away from home for long periods of time.
17. Remote heaters must not be connected to any external electrical source.
18. Operating heater above elevations of
4,500 feet may cause pilot outage.
19. To prevent performance problems, do
not use propane/LP fuel tank of less than 100 lb. capacity (propane/LP units only).
20. Provide adequate clearances around air openings.
www.fmiproducts.com
125795-01B4
Chassis
Glowing
Embers
PRODUCT IDENTIFICATION
Figure 1 - Product Identication
LOCAL CODES
Install and use heater with care. Follow all
local codes. In the absence of local codes,
use the latest edition of The National Fuel Gas Code, ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
National Fire Protection Association, Inc.
State of Massachusetts: The installa­tion must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts.
Sellers of unvented propane or natural
gas-red supplemental room heaters shall
provide to each purchaser a copy of 527 CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for bedroom and bathroom installation in the Commonwealth of Massachusetts.
125795-01B 5
1430 Broadway
New York, NY 10018
Batterymarch Park
Quincy, MA 02269
www.fmiproducts.com
data plates from the grate as­sembly. The data plates contain important warranty and safety information.
1. Remove logs and heater base assembly
Note: Do not pick up heater base assem-
2. Remove all protective packaging applied
3. Check heater for any shipping damage. If
UNPACKING
CAUTION: Do not remove the
from carton(s).
bly by burners. This could damage heater. Always handle base assembly by grate.
to logs and heater for shipment.
heater is damaged call FMI PRODUCTS,
LLC at 1-866-328-4537 for replacement parts before returning to dealer.
PRODUCT FEATURES
OPERATION
This heater is clean burning. It requires no outside venting. There is no heat loss out a vent or up a chimney. Heat is generated by
both realistic ames and glowing coals. This
heater is designed for vent-free operation
with ue damper closed. It has been tested
and approved to ANSI Z21.11.2 standard for unvented heaters.
SAFETY DEVICE
This heater has a pilot with an Oxygen Deple­tion Sensing (ODS) safety shutoff system. The ODS/pilot is a required feature for vent-free room heaters. The ODS/pilot shuts off the heater if there is not enough fresh air.
ELECTRONIC IGNITION SYSTEM
This heater has an electronic ignitor to light heater fuel supply.
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall
not be installed in a room or space unless the required volume of indoor combustion air is provided by the method described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, the International Fuel Gas Code, or applicable
local codes. Read the following instructions to insure proper fresh air for this and other fuel-burning appliances in your home.
Today’s homes are built more energy efcient than ever. New materials, increased insulation
and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. Dur-
ing heating months, home owners want their
homes as airtight as possible. While it is good to make your home energy
efcient, your home needs to breathe. Fresh
air must enter your home. All fuel-burning ap­pliances need fresh air for proper combustion and ventilation.
Exhaust fans, replaces, clothes dryers and
fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper venting of vented fuel-burning appliances.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 6 through 8 will help you classify your space and provide adequate ventilation.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough fresh air for combustion
and ventilation. However, in buildings of un­usually tight construction, you must provide
additional fresh air.
Unusually tight construction is dened as
construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10 less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window and door frames, between sole plates and oors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines and at other openings.
If your home meets all of the three criteria
above, you must provide additional fresh air.
See Ventilation Air From Outdoors, page 8. If your home does not meet all of the three
criteria above, proceed to Determining Fresh­Air Flow For Heater Location, page 7.
-11
kg per pa-sec-m2) or
www.fmiproducts.com
125795-01B6
AIR FOR COMBUSTION AND VENTILATION
Continued
Conned and Unconned Space
The National Fuel Gas Code, ANSI Z223.1/ NFPA 54 denes a conned space as a space
whose volume is less than 50 cubic feet per
1,000 Btu/hr (4.8 m3 per kw) of the aggregate
input rating of all appliances installed in that
space and an unconned space as a space
whose volume is not less than 50 cubic feet
per 1,000 Btu/hr (4.8 m3 per kw) of the ag-
gregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are
installed*, through openings not furnished with doors, are considered a part of the un­conned space.
* Adjoining rooms are communicating only if there are doorless passageways or ventilation grills between them.
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Conned or Unconned Space
Use this work sheet to determine if you have
a conned or unconned space.
Space: Includes the room in which you will install
replace plus any adjoining rooms with door­less passageways or ventilation grills between the rooms.
1. Determine the volume of the space (length x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 20 ft. (length) x 16 ft.
(width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support) Example: 2560 cu. ft. (volume of space) x 20
= 51,200 (maximum Btu/Hr the space can
support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
125795-01B 7
www.fmiproducts.com
Vent-free replace __________ Btu/Hr Gas water heater* __________ Btu/Hr Gas furnace __________ Btu/Hr
Vented gas heater __________ Btu/Hr Gas replace logs __________ Btu/Hr Other gas appliances* + _________ Btu/Hr Total = _________ Btu/Hr * Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the outdoors and vents to the outdoors.
Example:
Gas water heater __________ Btu/Hr Vent-free replace + _________ Btu/Hr
Total = _________ Btu/Hr
4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/ Hr used.
______Btu/Hr (maximum the space can
support)
______Btu/Hr (actual amount used) Example: 51,200 Btu/Hr (maximum the
space can support)
73,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the above example is a conned
space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can sup­port. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides an unconned space, remove door to adjoin­ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 8.
B. Vent room directly to the outdoors. See
Ventilation Air From Outdoors, page 8.
C. Install a lower Btu/Hr replace, if lower Btu/
Hr size makes room unconned.
If the actual Btu/Hr used is less than the maxi-
mum Btu/Hr the space can support, the space is an unconned space. You will need no additional
fresh air ventilation.
40,000 33,000 73,000
WARNING: If the area in which
the heater may be operated does not meet the required volume for indoor combustion air, combus­tion and ventilation air shall be provided by one of the methods described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, the International Fuel Gas Code,
or applicable local codes.
AIR FOR COMBUSTION AND VENTILATION
Outlet Air
Ventilated Attic
Outlet
A
ir
Inlet Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
Or
Remove Door into Adjoining
Room, Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilation
Grills Into
Adjoining
Room,
Option 1
12"
12"
Continued
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconned space. When ventilating to an adjoining unconned space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the oor on the
wall connecting the two spaces (see options
1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2).
Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation for required size of ventilation
grills or ducts.
Figure 2 - Ventilation Air from Inside Building
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation grills or ducts. You must provide two perma­nent openings: one within 12" of the ceiling
and one within 12" of the oor. Connect these
items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation for required size
of ventilation grills or ducts. IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a thermo­stat-controlled power vent. Heated air entering the attic will activate the power vent.
Figure 3 - Ventilation Air from Outdoors
INSTALLATION
NOTICE: This heater is intended
for use as supplemental heat. Use this heater along with your primary heating system. Do not install this heater as your pri­mary heat source. If you have a central heating system, you may run system’s circulating blower while using heater. This will help circulate the heat throughout the house. In the event of a power outage, you can use this heater as your primary heat source.
WARNING: A qualied ser­vice person must install heater. Follow all local codes.
www.fmiproducts.com
WARNING: Seal any fresh
air vents or ash clean-out doors
located on oor or wall of re­place. If not, drafting may cause pilot outage or sooting. Use a heat-resistant sealant. Do not seal chimney ue damper.
125795-01B8
INSTALLATION
Continued
WARNING: Before installing in a solid fuel burning replace, the chimney ue and rebox must be cleaned of soot, creo­sote, ashes and loose paint by a qualified chimney cleaner. Creosote will ignite if highly heated. A dirty chimney ue may
CHECK GAS TYPE
Use the correct type of gas (natural or propane/ LP). If your gas supply is not the correct gas
type, do not install heater. Call dealer where
you bought heater for proper type heater.
WARNING: This appliance is equipped for either natural gas or propane/LP gas but not both. Gas type is indicated on the rat­ing plate. Field conversion is not permitted.
create and distribute soot within the house. Inspect chimney and rebox ue for damage. If dam-
INSTALLATION AND CLEARANCES
FOR VENT-FREE OPERATION
aged, repair ue and rebox before operating heater.
WARNING: Maintain the
minimum clearances. If you can,
WARNING: Never install the
heater
• in a bedroom or bathroom
• in a recreational vehicle
where curtains, furniture, cloth-
ing or other ammable objects
are less than 36" from front, 42"
from top of heater; for side clear­ances see Figure 4, page 10
• in high trafc areas
• in windy or drafty areas
CAUTION: This heater creates
warm air currents. These currents
move heat to wall surfaces next
to heater. Installing heater next to vinyl or cloth wall coverings or operating heater where impurities (such as, but not limited to, to­bacco smoke, aromatic candles, cleaning uids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.
IMPORTANT: Vent-free heaters add moisture
to the air. Although this is benecial, installing
heater in rooms without enough ventilation air may cause mildew to form from too much moisture. See Air for Combustion and Ventila-
tion, page 6.
125795-01B 9
www.fmiproducts.com
provide greater clearances from oor, ceiling and adjoining wall.
MINIMUM FIREPLACE CLEARANCE TO
COMBUSTIBLE MATERIALS
Side Wall 16", Ceiling 42"
Floor 5", Front: 36"
LOG SIZING REQUIREMENTS
Log
Size
LMF36-SC 29" 15.5" 32.5" 22.75" LMF42-SC 29" 15.5" 39" 26.75" LMF48-SC 29'' 20'' 47'' 33''
GT24 29'' 15.5'' 32.5'' 22.75'' GT30 29'' 15.5'' 39'' 26.75'' GT36 29'' 20'' 47'' 33''
* Also approved for use in Vantage Hearth Model
VFB42, VTFB42 and VUM42 replaces.
Carefully follow the instructions below. This
will ensure safe installation into a masonry, UL127-listed manufactured replace or listed vent-free rebox.
Minimum Clearances For Side Combustible Material, Side Wall and Ceiling
A. Clearances from the side of the replace
cabinet to any combustible material and
wall should follow diagram in Figure 4,
page 10.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and protrudes 3 1/2" from the wall. This combustible material must be 4" from the
side of the replace cabinet (see Figure 4, page 10).
Minimum Firebox Size
Height Depth
Front
Width
Rear* Width
INSTALLATION
Heat Resistant Material
(A)
Continued
Note: When installing your gas logs into
a manufactured rebox, follow rebox
manufacturer’s instructions for minimum clearances to combustible materials.
B. Clearances from the top of the replace
opening to the ceiling should not be less than 42".
Noncombustible
Material Distance
Requirements for
Safe Installation
(A)
1
2" or more Noncombustible mate-
rial OK.
Between 8" and 12"
Install replace hood accessory (GA6050 or GA6053 see Accesso- ries, page 39).
Example
*
*Minimum 16" from Side Wall
Figure 4 - Minimum Clearance for
Combustible to Wall
Minimum Noncombustible Material
Clearances
If Not Using Mantel
Note: If using a mantel proceed to If Using Mantel. If not using a mantel, follow these instructions.
You must have noncombustible material(s)
above the replace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2" thick. With sheet metal, you
must have noncombustible material behind it. Noncombustible material must extend at least 8" up (for all models). If noncombustible
material is less than 12", you must install the replace hood accessory (24" and 30" Models
Only). See Figure 5 for minimum clearances.
Less than 8"
Noncombustible mate­rial must be extended to at least 8". See
Between 8" and 12",
above. If you cannot
extend material, you
must operate heater
with ue damper open.
Figure 5 - Heat Resistant Material (Slate,
Marble, Tile, etc.) Above Fireplace
If Using Mantel
You must have noncombustible material(s)
above the replace opening. Noncombustible materials (such as slate, marble, tile, etc.) must be at least 1/2" thick. With sheet metal,
you must have noncombustible material be­hind it. Noncombustible material must extend at least 8" up (for all models). If noncom-
bustible material is less than 12", you must install the replace hood accessory. Even if noncombustible material is more than 12", you may need the hood accessory to deect
heat away from your mantel shelf. See Figure
5 and Figures 6 and 7, page 11, for minimum
clearances.
www.fmiproducts.com
125795-01B10
INSTALLATION
14" Min.
Combustible Material
Noncombustible Material
Minimum Non­Combustible Material
Minimum Non­Combustible Material Height
Distances to Underside of Mantel
Top of Fireplace Opening
Underside of Mantel Shelf
12"
(A)
18" 20" 22" 24"
All minimum distances are in inches
2
1
/2
"
6"
8"
10"
Mantel Shelf
Minimum Noncombustible Material
8" Min.
12" 15" 18" 20"
2
1
/2
"
6"
8"
10"
12"
Distances to Underside of
Mantel
Hood (GA6050
or GA6053)
Top of Fireplace Opening
Underside
of Mantel
Shelf
Mantel Shelf
Hearth
5" Min.
Combustible Material
Continued
MANTEL CLEARANCES
In addition to meeting noncombustible mate-
rial clearances, you must also meet required clearances between replace opening and
mantel shelf. If you do not meet the clearances
listed below, you will need a hood.
Determining Minimum Mantel Clearance
If you meet minimum clearance between
mantel shelf and top of replace opening, a
hood is not required (see Figure 6).
Figure 6 - Minimum Mantel Clearances
Without Using Hood
Determining Minimum Mantel Clearance When Using a Hood
If minimum clearances in Figure 6, are not met, you must have a hood. When using a
hood there are still certain minimum mantel clearances required. Follow minimum clear-
ances shown in Figure 7, when using hood.
NOTICE: Surface temperatures of adjacent walls and mantels be­come hot during operation. Walls and mantels above the rebox may become hot to the touch. If installed properly, these tem­peratures meet the requirement of the national product standard.
Follow all minimum clearances
shown in this manual.
NOTICE: If your installation does not meet the minimum clear­ances shown, you must do one
of the following:
• operate the logs only with the
ue damper open
• raise the mantel to an accept-
able height
• remove the mantel
FLOOR CLEARANCES
A. If installing appliance on the oor level,
you must maintain the minimum distance of 14" to combustibles (see Figure 8).
B. If combustible materials are less than 14"
to the replace, you must install appliance at least 5" above the combustible ooring
(see Figure 9).
Figure 8 - Minimum Fireplace Clearances
Figure 7 - Minimum Mantel Clearances
125795-01B 11
When Using Hood
www.fmiproducts.com
Figure 9 - Minimum Fireplace Clearances
If Installed at Floor Level
Above Combustible Flooring
INSTALLATION
INSTALLING HEATER BASE ASSEMBLY
WARNING: You must secure
this heater to replace oor. If
not, heater will move when you
adjust controls. Moving heater may cause a gas leak.
WARNING: If installing in a sunken replace, special care is needed. You must raise the replace oor to allow access to heater control panel. This will in­sure adequate air ow and guard against sooting and controls being damaged. Raise replace oor with noncombustible mate­rial. Make sure material is secure.
Continued
3. Mark screw locations through holes in front panel of base (see Figure 11). If
installing in a brick-bottom replace, mark
screw locations in mortar joint of bricks.
4. Remove heater base from replace.
5. Drill holes at marked locations using 3/16" drill bit.
6. Attach base, through holes in back side pan­els of base, to replace oor using masonry
screws provided in hardware package (see Figure 11).
7. Connect to gas supply. See Connecting
To Gas Supply, page 13.
Heater Gas
Regulator
Flexible Gas Hose (Provided with Models, Install if
allowed by local codes)
CAUTION: Do not pick up heater base assembly by burn­ers. This could damage heater. Only handle base assembly by grates.
IMPORTANT: Make sure the heater burners are level.
Installation Items Needed
• hardware package (provided with heater)
• approved exible gas hose and ttings
provided (if allowed by local codes)
• sealant (resistant to propane/LP gas, not
provided)
• electric drill with 3/16” masonry drill bit
Note: Install optional MRC Series receiver and hand-held remote control kit (see Ac­cessories, page 39) before installing gas log heater. See installation instructions included with the kit.
1. Apply pipe joint sealant lightly to male
threads of the 3/8 NPT side of gas tting
elbow (provided) and connect to inlet
side of gas control. Remove gas tting from exible gas hose (provided) before
connecting to elbow (see Figure 10).
2. Position heater base assembly in re­place.
www.fmiproducts.com
Figure 10 - Attaching Flexible Gas Hose
to Heater Gas Regulator
Masonry Screw
Figure 11 - Attaching Base to Fireplace
Floor
125795-01B12
INSTALLATION
Continued
CONNECTING TO GAS SUPPLY
WARNING: This appliance requires a 3/8" NPT (National Pipe Thread) inlet connection to the pressure regulator.
WARNING: A qualied service person must connect heater to gas supply. Follow all local codes.
CAUTION: Never connect
propane/LP replace directly to the propane/LP supply. This heater requires an external regu­lator (not supplied). Install the external regulator between the heater and propane/LP supply.
WARNING: Never connect
natural gas replace to private (non-utility) gas wells. This gas is commonly known as wellhead gas.
Installation Items Needed
Before installing heater, make sure you have
the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved exible gas line with gas connec-
tor (if allowed by local codes) (not provided)
* An equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional equipment shutoff valve from your dealer.
For propane/LP units, the installer must
supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11" and 14" of water. If you do not re-
duce incoming gas pressure, heater regulator
damage could occur. Install external regulator
125795-01B 13
www.fmiproducts.com
with the vent pointing down as shown in Figure
12, page 14. Pointing the vent down protects it from freezing rain or sleet.
CAUTION: Use only new,
black iron or steel pipe. In­ternally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diameter or greater to allow proper gas volume to heater. If pipe is too small, undue loss of volume will occur.
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see
Figure 13, page 14).
IMPORTANT: Install equipment shutoff valve in an accessible location. The equipment shutoff valve is for turning on or shutting off the gas to the appliance.
Check your building codes for any special requirements for locating equipment shutoff
valve to replaces.
Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.
WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
Propane/LP Supply Tank
Figure 12 - External Regulator With Vent
Pointing Down
External Regulator with Vent Pointing Down
INSTALLATION
Continued
PROPANE/LP From External Regulator (11" W.C.** to 14" W.C. Pressure)
NATURAL From Gas
Meter (5" W.C.** to 10.5" W.C. Pressure)
Tee Cap Pipe Joint Nipple
Sediment Trap
Figure 13 - Gas Connection
* Purchase the optional equipment shutoff
valve from your dealer.
**Minimum inlet pressure for purpose of input
adjustment.
We recommend that you install a sediment trap in supply line as shown in Figure 13. Locate sediment trap where it is within reach for cleaning. Install in piping system between fuel supply and heater. Locate sediment trap
where trapped matter is not likely to freeze.
A sediment trap traps moisture and contami­nants. This keeps them from going into heater controls. If sediment trap is not installed or is
installed wrong, heater may not run properly.
CAUTION: Avoid damage to gas control. Hold gas control with wrench when connecting it to gas piping and/or ttings.
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and external to unit, for leaks after
installing or servicing. Correct all leaks at once.
Equipment Shutoff Valve With 1/8" NPT Tap*
Approved
Flexible Gas
Hose (if allowed
by local codes)
3" Minimum
Gas
Regulator
www.fmiproducts.com
WARNING: Never use an open ame to check for a leak. Apply a noncorrosive leak detection uid to all joints. Bubbles forming show a leak. Correct all leaks at once.
CAUTION: Make sure exter-
nal regulator has been installed between propane/LP supply and heater. See guidelines under Con- necting to Gas Supply, page 13.
PRESSURE TESTING GAS SUPPLY PIPING SYSTEM Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1. Disconnect appliance with its appliance main gas valve (control valve) and equip­ment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig will damage heater regulator.
2. Cap off open end of gas pipe where equip­ment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.
4. Check all joints of gas supply piping system.
Apply noncorrosive leak detection uid to
all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff valve to gas supply. Check reconnected
ttings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig­ure 15).
2. Pressurize supply piping system by either
opening propane/LP supply tank valve for propane/LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air.
3. Check all joints from gas meter to equip­ment shutoff valve for natural gas or pro­pane/LP supply to equipment shutoff valve for propane/LP (see Figure 15 or Figure
16). Apply noncorrosive leak detection uid
to all joints. Bubbles forming show a leak.
4. Correct all leaks at once.
125795-01B14
Loading...
+ 30 hidden pages