installation and operational
procedures. For assistance or
additional information consult
a qualified installer, service
agency or the gas supplier.
This appliance is only for use
with the type of gas indicated on
the rating plate. This appliance
is not convertible for use with
other gases, unless a certied
kit is used.
State of Massachusetts: The
installation must be made by a
licensed plumber or gas tter
in the Commonwealth of Mas-
sachusetts.
WARNING: This product
con tains a nd/or gener ates
chemicals known to the State
of California to cause cancer or
IMPORTANT: Read this owner’s
manual carefully and completely
before trying to assemble, operate or service this replace.
Improper use of this replace
can cause serious injury or
death from burns, re, explosion, electrical shock and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
This vented gas replace is a sealed combustion gas replace designed for residential applications. This replace must be installed with
FMI PRODUCTS, LLC vent pipe components
and terminations.
This fireplace complies with the National
Safety Standards and is listed and tested by
PFS Corporation to ANSI Z21.50 standard as
vented gas replace.
This replace must be installed by a qualied
(certied or licensed) service person. It brings
in fresh air for combustion through the outer
pipe and combustion gases are exhausted
through the inner pipe. If the glass door assembly and venting pipe are not properly
seated, connected and sealed, carbon monoxide leakage (spillage) can occur.
www.fmiproducts.com
125078-01B2
SAFETY
Continued
Carbon Monoxide Poisoning: Early signs
of carbon monoxide poisoning resemble the
u, with headaches, dizziness or nausea. If
you have these signs, the replace may not
be working properly. Get fresh air at once!
Have replace serviced. Some people are
more affected by carbon monoxide than others. These include pregnant women, people
with heart or lung disease or anemia, those
under the inuence of alcohol and those at
high altitudes.
Natural and Propane/LP Gas: Natural and
propane/LP gas are odorless. An odor-making
agent is added to the gas. The odor helps you
detect a gas leak. However, the odor added to
the gas can fade. Gas may be present even
though no odor exists.
Make certain you read and understand all
warnings. Keep this manual for reference. It
is your guide to safe and proper operation of
this replace.
WARNING: Any change to
this replace or it’s controls can
be dangerous. Do not modify
this replace under any circumstances. Any parts removed for
servicing must be replaced prior
to operating replace.
WARNING: Do not allow fans
to blow directly into the replace.
Avoid any drafts that alter burner
ame patterns.
Due to high temperatures, the
appliance should be located out
of trafc and away from furniture
and draperies.
Do not place clothing or other
ammable material on or near
the appliance. Never place any
objects on the appliance.
Do not use this replace to cook
food or burn paper or other ammable material.
This replace reaches high temperatures. Keep children and
adults away from hot surface to
avoid burns or clothing ignition.
Fireplace will remain hot for a
time after shutdown. Allow surface to cool before touching.
WARNING: Do not use a blower insert, heat exchanger insert
or other accessory not approved
Carefully supervise young chil-
dren when they are in the room
with replace.
for use with this replace.
Keep the area around your
WARNING: This appliance
is only for use with the type of
gas indicated on the rating plate.
This appliance is not convertible
for use with other gases unless
replace clear of combustible
materials, gasoline and other
ammable vapor or liquids. Do
not run replace where these
are used or stored.
a certied kit is used.
125078-01B3
www.fmiproducts.com
SAFETY
Continued
1. For propane/LP replace, do not place
propane/LP supply tank(s) inside any
structure. Locate propan e/LP supp ly
tank(s) outdoors. To prevent performance
problems, do not use propane/LP fuel tank
of less than 100 lb. capacity.
2. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor ’s phone. Follow the gas
supplier's instructions
• if you cannot reach you gas supplier, call
the re department.
3. Never install the replace
• in a recreational vehicle
• in windy or drafty areas where curtains or
other combustible (ammable) objects can
make contact with the replace front
• in high trafc areas
4. Turn fireplace off and let cool before
servicing, installing or repairing. Only a
qualied service person should install,
service or repair this replace. Have replace inspected annually by a qualied
service person.
5. You must keep control compartments,
burners and circulating air passages
clean. More frequent cleaning may be
needed due to excessive lint and dust
from carpeting, bedding material, etc.
Turn off the gas valve and pilot light before
cleaning replace.
6. Have venting system inspected annually by
a qualied service person. If needed, have
venting system cleaned or repaired. See
Cleaning and Maintenance, page 24.
7. Do not use any solid fuels (wood, coal,
paper, cardboard, etc.) in this replace.
Use only the gas type indicated on replace nameplate.
8. This appliance, when installed, must be
electrically grounded in accordance with
local codes or, in the absence of local
codes, with the National Electrical Code,
ANSI/NFPA 70.
9. Do not use replace if any part has been
exposed to or under water. Immediately
call a qualied service person to arrange
for replacement of the unit.
10. Do not operate replace if any log is
broken.
11. Do not operate replace with glass door
removed, cracked or broken.
12. Provide adequate clearances around air
openings.
LOCAL CODES
Install and use replace with care. Follow all
local codes. In the absence to local codes,
use the current National Fuel Gas Code ANSI Z223.1/NFPA 54*.
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
www.fmiproducts.com
125078-01B4
Outer
Glass Door
Herringbone Brick
Refractories
Log Set
Grate
Lower Door/
Control Cover
PRODUCT IDENTIFICATION
Flue Collar
Nailing Flange
Figure 1 - Direct Vent Fireplace
PRODUCT FEATURES
These are a few facts that can help you understand and enjoy your direct vent replace:
• The venting system may be routed to the
outside of your home in several ways. It
may vent through the roof (vertical) or it
may vent to an outside/exterior wall (horizontal). The vent pipe installation is very
important to allow for proper operation.
You must follow the venting instructions
very carefully for either vertical or horizontal
applications.
• This replace may be installed in any room
of your house provided all local codes and
these installation instructions are followed.
125078-01B5
www.fmiproducts.com
• Each time you turn on your replace, you
may notice some amount of condensation
on the inside of the replace glass. This
is normal and will disappear after 10-20
minutes of operation.
• Your direct ve nt gas fire place system
(replace and venting) is a balanced and
sealed gas operating unit. It requires approximately 10-20 minutes of operating
time before the ame pattern stabilizes.
PRE-INSTALLATION
29" (36")
34
3
/4" (4 2")
21" (36")
25" (42")
41
1
/4" (3 6")
48 1/4" (4 2")
11 7/8" (3 6")
13 5/8" (4 2")
LOCATION AND SpACE
REqUIREMENTS
Determine the safest and most efcient location for your direct vent replace. Make sure
that rafters and wall studs are not in the way of
the venting system. Choose a location where
the heat output is not affected by drafts, air
conditioning ducts, windows or doors. Figure
2 shows some common locations. Be aware
of all restrictions and precautions before
deciding the exact location for your replace
and termination cap.
When deciding the location of your replace,
follow these rules:
• Do not connect this replace venting to a
chimney ue serving a separate solid-fuel
burning replace or appliance.
• Due to high temperatures, do not locate this
replace in high trafc areas, windy or drafty
areas or near furniture or draperies.
• Proper clearances must be maintained.
• If your replace is to be installed directly on
carpeting, vinyl tile or any combustible material other than wood, it must be installed on a
metal or wood panel extending the full width
and depth of the replace (see Figure 3).
• Your replace is designed to be used in
zero clearance installations. Wall or framing material can be placed directly against
any exterior surface on back, sides or top
of your replace, except where standoff
spacers are integrally attached. If standoff
spacers are attached to your replace,
these s pacer s can be plac ed directly
against wall or framing material. See framing details, page 7.
• When locating termination cap, it is important to observe the minimum clearances
shown in Figure 7, page 8.
• If recessing into a wall, you can avoid extra
framing by positioning your replace against
an already existing framing member.
• Do not recess termination cap into a wall
or siding.
• You may paint the termination cap with
450º F (232º C) heat-resistant paint to
coordinate with the exterior nish.
• There must not be any obstruction such as
bushes, garden sheds, fences, decks or
utility buildings within 24" from the front of
the termination cap and the front of outside
air vent.
• Do not locate termination cap and outside
air vent where excessive snow or ice build
up may occur. Be sure to clear vent termination area after snow falls to prevent
accidental blockage of venting system.
When using snow blowers, do not direct
snow towards vent termination area.
Flush with a wall
Through exterior wall
enclosed in a chase
Corner
installation
Figure 2 - Common Fireplace Locations
Figure 3 - Fireplace Top Dimensions
www.fmiproducts.com
125078-01B6
C
B
A
D
E
F
G
3
2
1
4
5
6
7
Wa ll
PRE-INSTALLATION
43
1
/
4
"
(36")
47
1
/
4
"
(42")
41
1/2"
(36")
48
1/2"
(42")
36
3/8"
(36")
43
3
/
8
" (42")
43" (36"), 50" (42")
42" (36"), 49" (42")
15
3/4"
(36")
19" (42")
51
3/8"
(36")
61
3
/
4
" (42")
Nailing
Tabs
Continued
CLEARANCES
Minimum clearances to combustibles for the
replace are as follows:
*Back and sides 1"
Perpendicular walls 6"
Floor 0"
Ceiling to louver opening 42"
Front 36"
Top of Standoffs 0"
Vent (See venting instructions
for specic venting
clearances.)
Combustible material with a maximum thickness of 5/8" may be ush with the top front
of replace.
* For back and sides of replace, do not pack
with insulation or other materials. 1" clearance
not required at nailing anges.
NOTICE: This replace is intended for use as supplemental heat.
Use this replace along with
your primary heating system.
Do not install this replace as
your primary heat source. If you
have a central heating system,
you may run system’s circulating blower while using replace.
This will help circulate the heat
throughout the house.
Figure 4 - Framing Clearances with
Outside Air Flex Duct
Figure 5 - Framing Clearances for Corner
Installation
FRAMING AND FINISHING
Figure 4 shows typical framing of this replace.
Figure 5 shows framing for corner installation.
All minimum clearances must be met.
If you are using a separate combustible mantel piece, refer to Figure 6 for proper installation height. You can install noncombustible
mantels at any height above the replace.
A = clearance above grade, veranda, porch, deck, or
balcony [*12" (30.5 cm) minimum]
B = clearance to window or door that may be opened
[6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US
if between 10,000 and 50,000, 12" (30 cm) in Canada
if between 10,000 and 100,000; 12" (30 cm) in US if
greater than 50,000, 36" (91 cm) in Canada if greater
than 100,000]
C = clearance to permanently closed window
[minimum 12" (30.5 cm) recommended to prevent
condensation on window]
D = vertical clearance to ventilated soffit located above the
terminal within a horizontal distance of 24" (61 cm) from
the center-line of the terminal [18" (45.7 cm) minimum]
E = clearance to unventilated soffit [12" (30.5 cm) minimum]
F = clearance to outside corner (see below)
G = clearance to inside corner (see below)
H = *not to be installed above a meter/regulator assembly
within 36" (91.4 cm) horizontally from the center line
of the regulator
I = clearance to service regulator vent outlet [*72" (182.9 cm)
minimum]
J = clearance to non-mechanical air supply inlet to building
or the combustion air inlet to any other fireplace
[6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US
if between 10,000 and 50,000, 12" (30 cm) in Canada
if between 10,000 and 100,000; 12" (30 cm) in US if
greater than 50,000, 36" (91 cm) in Canada if greater
than 100,000]
K = clearance to a mechanical air supply inlet [*In Canada,
6 ft. (1.83m) minimum; In US 3 ft. (91 cm) above if within
10 ft. (3 m) horizontally]
L = † clearance above paved side-walk or a paved driveway
located on public property [*84" (213.3 cm) minimum]
M = clearance under veranda, porch, deck
[*12" (30.5 cm) minimum ‡]
N = clearance above a roof shall extend a minimum of
24" (61 cm) above the highest point when it passes
through the roof surface and any other obstruction within
a horizontal distance of 18" (45.7 cm)
† vent shall not terminate directly above a side-walk or paved driveway which is located between two
single family dwellings and serves both dwellings*
‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor*
* as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A.
Note: Local codes or regulations may require different clearances
A = 6" (15.2 cm)
Inside Corner
V
B
E
V
B = 6" (15.2 cm)
C = Maximum depth of 48" (121.9 cm)
for recessed location
D = Minimum width for back wall of
recessed location Combustible - 38" (965 mm)
Noncombustible - 24" (61 cm)
E = Clearance from corner in
recessed location Combustible - 6" (15.2 cm)
Noncombustible - 2" (5.1 cm)
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Openable
LOCATION OF TERMINATION CAP
Figure 7 - Minimum Clearances for Termination Cap
www.fmiproducts.com
125078-01B8
REQUIREMENTS FOR THE COMMONWEALTH OF
MASSACHUSETTS
For all side wall horizontally vented gas fueled
equipment installed in every dwelling, building or
structure used in whole or in part for residential
purposes, including those owned or operated by
the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet
above nished grade in the area of the venting,
including but not limited to decks and porches,
the following requirements shall be satised:
INSTALLATION OF CARBON
MONOXIDE DETECTORS
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing
plumber or gastter shall observe that a hard
wired carbon monoxide detector with an alarm
and battery backup is installed on the oor level
where the gas equipment is to be installed. In
addition, the installing plumber or gastter shall
observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed
on each additional level of the dwelling, building or
structure served by the side wall horizontal vented
gas fueled equipment. It shall be the responsibility
of the property owner to secure the services of
qualied licensed professionals for the installation
of hard wired carbon monoxide detectors.
In the event that the side wall horizontally
vented gas fueled equipment is installed
in a crawl space or an attic, the hard wired
carbon monoxide detector with alarm and
battery back-up may be installed on the next
adjacent oor level.
In the event that the requirements of this
subdivision can not be met at the time of
completion of installation, the owner shall
have a period of thirty (30) days to comply with
the above requirements; provided, however,
that during said thirty (30) day period, a battery
operated carbon monoxide detector with an
alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required
in accordance with the above provisions shall
comply with NFPA 720 and be ANSI/UL 2034
listed and IAS certied.
SIGNAGE
A metal or plastic identication plate shall be
permanently mounted to the exterior of the
building at a minimum height of eight (8) feet
above grade directly in line with the exhaust
vent terminal for the horizontally vented gas
fueled heating appliance or equipment. The
sign shall read, in print size no less than 1/2" in
size, "GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS".
125078-01B9
www.fmiproducts.com
INSpECTION
The state or local gas inspector of the side
wall horizontally vented gas fueled equipment
shall not approve the installation unless, upon
inspection, the inspector observes carbon
monoxide detectors and signage installed in
accordance with the provisions of 248 CMR
5.08(2)(a) 1 through 4.
EXEMPTIONS: The following equipment is ex-
empt from 248 CMR 5.08(2)(a) 1 through 4:
• The equipment listed in Chapter 10 entitled
"Equipment Not Required To Be Vented"
in the most current edition of NFPA 54 as
adopted by the Board; and
• Product Approved side wall horizontally
vented gas fueled equipment installed in a
room or structure separate from the dwelling, building or structure used in whole or
in part for residential purposes.
MANUFACTURER REqUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved
side wall horizontally vented gas equipment
provides a venting system design or venting
system components with the equipment, the
instructions provided by the manufacturer for
installation of the equipment and the venting
system shall include:
• Detailed instructions for the installation of
the venting system design or the venting
system components; and
• A complete parts list for the venting system
design or venting system.
Gas Equipment Venting System Not
provided
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for
venting the ue gases, but identies "special
venting systems", the following requirements
shall be satised by the manufacturer:
•
The referenced "special venting system" instructions shall be included with the appliance
or equipment installation instructions; and
• The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list
and detailed installation instructions.
A copy of all installation instructions for all
Product Approved side w all horizon tally
vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions
shall remain with the appliance or equipment
at the completion of the installation.
VENTING INSTALLATION
NOTICE: Read these instruc-
tions completely before attempting installation.
These models are tested and approved for
use with FMI PRODUCTS, LLC (direct vent)
pipe components and terminations.
The venting system must terminate on the
outside of the structure and can not be attached to a chimney or ue system serving a
separate solid fuel or gas burning appliance.
A direct vent appliance must have its own
venting system. DO NOT common vent this
appliance.
These models are approved to be vented
either horizontally through an outside wall or
vertically through a roof or chase enclosure
using the following guidelines:
• When venting system terminates horizontally on an outside wall, you may install
a standoff if the termination cap is to be
installed directly on a combustible nish
such as vinyl, wood, stucco, etc.
• Never run the vent downward as this may
cause excessive temperatures which could
cause a re.
• Vent pipe air space clearances to combustibles are 1" on all sides except on the
horizontal sections, which requires 2" clearance from the top of the pipe. Where the
termination cap penetrates a combustible
wall, 1" air space clearance is required.
• Have replace and selected vent components on hand to help determine the exact
measurements when elbowing or offsetting.
Always use wall restops when penetrating
walls and restops when penetrating ceilings or attic spaces.
• For installation of replace at elevations of
4000 feet or greater, pay special attention
to venting requirement recommendations.
WARNING: Read all instruc-
tions completely and thoroughly
before attempting installation.
Failure to do so could result in
serious injury, property damage
or loss of life.
NOTICE: Do not seal termination
cap to vent pipe. Cap must be
removable for vent inspection
and maintenance.
INSTALLATION pRECAUTIONS
• Wear gl oves an d s afety glasse s f or
protection
• Use extreme caution when using ladders
or when on roof tops
• Be aware of electrical wiring locations in
walls and ceilings
The following actions will void the warranty
on your venting system:
• Ins ta llati on of an y d am aged ve nt ing
component
• Unauthorized modication of the venting system (Do not cut or alter vent components)
• Installation of any component part not
man u fact u red o r app r oved b y FM I
PRODUCTS, LLC
• Installation other than as instructed by
these instructions
WARNING: This gas replace
and vent assembly must be
vented directly to the outside.
The venting system must NEVER
be attached to a chimney serving a separate solid fuel burning
appliance. Each direct vent gas
appliance must use a separate
vent system. Do not use common vent systems.
WARNING: Vent pipe air
space clearances to combustibles are 1" on all sides except
on the horizontal sections,
which require 2" clearances
from the top of the pipe. Where
the termination cap penetrates
a combustible wall, 1" air space
clearance is required.
NOTICE: Failure to follow these in-
structions will void the warranty.
www.fmiproducts.com
125078-01B10
INSTALLATION pLANNING
(Framing
Detail)
11
1
/2"
11
1
/2" Inside Framing
11
1
/2"
8 1/2"
Ve nt Opening
Combustible Wall
Ve nt Opening
Noncombustible Wall
There are two basic types of direct vent
installation:
• Horizontal Termination
• Vertical Termination
Horizontal Termination Installation
IMPORTANT: Horizontal square terminations
require only inner portion of wall restop. Horizontal installations using round termination
require exterior portion of wall restop.
1. Set replace in its desired location and determine the route your horizontal venting
will take. Do not secure replace until all
venting has been installed. Some installations require sliding replace in and out
of position to make nal venting connections. Figures 14 and 15 on page 12 show
different congurations for venting with
horizontal termination that will help you
decide which application best suits your
installation. Check to see if wall studs or
roof rafters are in the path of your desired
venting route. If they are, you may want
to adjust location of replace.
2. Direct vent pipe sections and components
are designed with special twist-lock connections.
Twist-Lock procedure: Female ends of
pipes have locking lugs (indentations).
These lugs will slide straight into matching slots on male ends of adjacent pipes.
Push pipe sections together and twist
one section clockwise approximately onequarter turn until sections are fully locked
(see Figure 8).
Note: Horizontal runs of vent must be sup-
ported every three feet. Use wall straps
for this purpose.
3. Assemble desired combination of pipe
and elbows to replace ue collar. If there
are long portions of venting run, pre-assembled pipe sections may be installed
as subassemblies for convenience.
4. Carefully determine location where vent
pipe assembly will penetrate outside wall.
Center of hole should line up with center
line of horizontal vent pipe. Mark wall for
an 11 1/2" x 11 1/2" square hole. Cut and
frame square hole in exterior wall where
vent will be terminated. If wall being pen-
125078-01B11
VENTING INSTALLATION
Continued
etrated is constructed of noncombustible
material, such as masonry block or concrete, a 8 1/2" hole with zero clearance is
acceptable (see Figure 9).
vent termination into any wall.
This will cause a re hazard.
Figure 8 - Vent Pipe Connections
Figure 9 - Vent Opening Requirements
www.fmiproducts.com
WARNING: Do not recess
Female
Locking Lugs
Male
Slots
Center
of Hole
VENTING INSTALLATION
Continued
5. Noncombustible Exterior Wall: Position
horizontal vent cap in center of the 8 1/2"
round hole and attach to exterior wall
with four wood screws provided. Before
attaching vent cap to exterior wall, run a
bead of non-hardening mastic (pliable
sealant) around outside edges to make a
seal between it and outside wall.
Note: Four wood screws provided should
be replaced with appropriate fasteners for
stucco, brick, concrete or other types of
sidings (see Figure 10).
Combustible Exterior Wall: For vinyl
siding, stucco or wood exteriors, a siding
standoff may be installed between vent
cap and exterior wall. Siding standoff
prevents excessive heat from damaging
siding materials. Siding material must be
cut to accommodate standoff. Bolt vent
cap to standoff. Apply non-hardening
mastic around outside edge of standoff.
Position standoff/cap assembly in the
center of 11 1/2" square hole and attach to
exterior wall with provided wood screws
(see Figure 11). Siding standoff must sit
ush against exterior fascia material.
6. Connecting Vent Cap with Horizontal Vent Pipe: Slide wall restop over vent
pipe before connecting horizontal run to
vent cap (see Figure 12).
Apply
Mastic to All
Four Sides
Vent Cap
Wood
Screw
Carefully move replace, with vent as-
sembly attached, toward wall and insert
vent pipe into horizontal termination. Pipe
overlap should be a minimum of 1 1/4" (see
Figure 13, page 13).
Slide wall restop against interior wall
surface and attach with screws provided.
See Figure 13, page 13, for horizontal
termination details.
Place replace into position and shim with
noncombustible material if needed. Nail or
screw side anges to framing to secure
unit in place. IMPORTANT: Make sure re-
place is level before securing. If replace
is not level it will not work properly.
Cut Siding Away to
Fit Standoff
Standoff
Apply Mastic
to All Four Sides
Figure 11 - Installing Siding Standoff
(Combustible Exterior Wall)
Wood
Screw
Vent
Cap
Screws
Interior Wall
Surface
Wall
Firestop
Figure 10 - Installing Horizontal Vent Cap
(Noncombustible Exterior)
www.fmiproducts.com
Vent Cap
(Horizontal
Termination)
Screw
Figure 12 - Connecting Vent Cap with
Horizontal Vent Pipe
Horizontal
Vent Pipe
125078-01B12
VENTING INSTALLATION
Continued
Minimum
Pipe
Direct
Vent
Pipe
Maintain 1"
Minimum Air
Space Around
Outer Pipe When
Penetrating a Wall
Horizontal Termination Congurations
Figure 14 shows a conguration for venting
with horizontal termination with a chart of
critical minimum and maximum dimensions
which MUST be met.
Overlap
4
11/
Wall
Firestop
11 1/2" x 11 1/2"
Framed Opening
Exterior Wall with Vinyl Siding
Figure 13 - Typical Horizontal
Termination Cap Mounting with
Additional Siding Standoff Installed
NOTICE: Do not seal termination
cap to vent pipe. Cap must be
removable for vent inspection
and maintenance.
WARNING: Never run vent
downward as this may cause
excessive temperatures which
could cause a re. Operation of
improperly installed and maintained venting system could
result in serious injury, property
damage or loss of life.
Siding
Standoff
Screws
High Wind
Termination
Apply
Mastic to
Outside
Edge of
Standoff
GROUND FLOOR INSTALLATION
Recommended Applications:
• Through the wall using round or square
termination
• NOT FOR CORNER INSTALLATION
1' Pipe Min On
Horizontal Run
Wall
Firestop
Horizontal High
Wind Square
Termination
64" Min. (42")
61" Min. (36")
(V) Vertical
Minimum
21"1 ft.3 ft.
33"2 ft.7 ft.
45"3 ft.11 ft.
57"4 ft.20 ft.
Figure 14 - Horizontal Termination Using
Vertical Termination Installation
Note: Vertical restrictor must be installed in
all vertical installations.
1. Determine route your vertical venting will
take. If ceiling joists, roof rafters or other
framing will obstruct venting system, consider an offset (see Figure 15, page 14)
to avoid cutting load bearing members.
Note: Pay special attention to these installation instructions for required clearances
(air space) to combustibles when passing
through ceilings, walls, roofs, enclosures,
attic rafters, etc. Do not pack air spaces
with i ns ulation. Also note maximum
vertical rise of venting system and any
maximum horizontal offset limitations.
H
Required
Vertical Pipe
V + H = 40 feet maximum
H = 20 feet maximum
One 90° Elbow
90° Elbow
V + 90· Elbow
1 ft. Min
Before
Elbow
(H) Horizontal
Maximum
125078-01B13
www.fmiproducts.com
VENTING INSTALLATION
Continued
2. Set replace in desired location. Drop a
plumb line down from ceiling to position
of replace exit ue. Mark center point
where vent will penetrate ceiling. Drill a
small locating hole at this point.
3. Drop a plumb line from inside of roof to
locating hole in ceiling. Mark center point
where vent will penetrate roof. Drill a small
locating hole at this point.
Roof Flashing
Wall Strap
45° Elbow
Ceiling Firestop
Figure 15 - Offset with Wall Strap and 45°
Elbows
Flat Ceiling Installation
1. Cut a 11 1/2" square hole in ceiling using
locating hole as a center point. Opening
should be framed to 11 1/2" x 11 1/2" inside
dimensions, as shown in Figure 8 on page
9 using framing lumber the same size as
ceiling joists. If area above ceiling is an
insulated ceiling or an attic, nail restop
from top side. This prevents loose insulation from falling into required clearance
space. If area above ceiling is a living
space, install restop below framed hole.
Firestop should be installed with no less
than three nails per side (see Figure 15).
2. Assemble desired lengths of pipe and
elbows necessary to reach from replace
ue up through restop. Be sure all pipe
and elbow connections are fully twistlocked (see Figure 8, page 11).
3. Cut a hole in the roof using locating hole
as a center point. (Cover any exposed
www.fmiproducts.com
open vent pipes before cutting hole in
roof.) The 11 1/2" x 11 1/2" hole must be
measured on the horizontal; actual length
may be larger depending on pitch of roof.
There must be a 1" clearance from vent
pipe to combustible materials. Frame
opening as shown in Figure 9, page 11.
4. Connect a section of pipe and extend up
through hole.
Note: If an offset is needed to avoid
obstructions, you must support vent pipe
every 3 feet. Use wall straps for this purpose (see Figure 15). Whenever possible,
use 45° elbows instead of 90° elbows. The
45° elbow offers less restriction to the ow
of ue gases.
5. Place ashing over pipe section(s) extending through roof. Secure base of
ashing to roof and framing with roong
nails. Be sure roong material overlaps
top edge of ashing as shown in Figure
15. There must be a 1" clearance from
vent pipe to combustible materials.
6. Continue to add pipe sections until height
of vent cap meets the minimum building
code requirements described in Figure 7
on page 8.
Note: You must increase vent height for
steep roof pitches. Nearby trees, adjoining
rooines, steep pitched roofs and other
similar factors may cause poor draft or
down-drafting in high winds. Increasing
vent height may solve this problem.
7. Twist-lock vent cap onto last section of
vent pipe.
Vent Termination Chart
Minimum Height
Roof pitchFeet Min.
Flat to 6/121
6/12 to 7/121.25
Over 7/12 to 8/121.5
Over 8/12 to 9/122
Over 9/12 to 10/122.5
Over 10/12 to 11/123.25
Over 11/12 to 12/124
Over 12/12 to 14/125
Over 14/12 to 16/126
Over 16/12 to 18/127
Over 18/12 to 20/127.5
Over 20/12 to 21/128.0
125078-01B14
VENTING INSTALLATION
Continued
Note: If vent pipe passes through any occupied ar-
eas above rst oor, including storage spaces and
closets, you must enclose pipe. You may frame
and sheetrock enclosure with standard construction material. Make sure and meet the minimum
allowable clearances to combustibles. Do not ll
any required air spaces with insulation.
Vertical Termination Congurations
Figure 17 shows the congurations for vertical
termination.
If area above is an attic or insulated area,
install restop above framed hole.
If area above is a living space, install
restop below framed hole.
Figure 16 - Installing Firestop
Vertical
Venting
V = 40' max.
Figure 17 - Vertical Venting Conguration
125078-01B15
www.fmiproducts.com
HIGH ALTITUDE INSTALLATION
Your F MI PROD UC TS, LLC d ir ect ven t
replace has been tested and approved for
elevations from 0-2000 feet.
Fireplaces for high altitude (-HA Models) are
for installations above 4,000 feet only. These
replaces are equipped with parts specic for
higher altitudes.
When installing a non-high altitude replace at
an elevation above 2000 feet, you may need
to decrease the input rating by changing the
existing burner orice to a smaller size. Reduce
input 4% for each 1000 feet above sea level.
Check with your local gas company for proper
orice size identication.
When installing this replace at an elevation
above 4500 feet, check with local authorities.
Galvanized
RF-58-12 Roof Flashing - 6/12 to 12/12 Pitch,
Galvanized
VR-58 Vertical Restrictor, Galvanized
S-58 Vinyl Siding Standoff, Galvanized
WS-58 Wall Strap
CS-58 Cathedral Ceiling Support
FP-58 Firestop Plate
SF-58 Stucco Flashing - For use with
HTS-58
RF-58 Flat Roof Flashing
FIREPLACE INSTALLATION
CHECK GAS TYPE
Use proper gas type for the replace unit you
are installing. If you have conicting gas types,
do not install replace. See retailer where you
purchased the replace for proper replace
according to your gas type.
INSTALLING GAS pIpING TO
FIREpLACE LOCATION
WA RNING: A qual i fied
service person must connect
replace to gas supply. Follow
all local codes.
CAUTION: For propane/LP
units, never connect replace directly to the propane/LP supply.
This heater requires an external
regulator (not supplied). Install
the external regulator between
the replace and propane/LP
supply.
WARN I NG: F or nat ural
gas, never connect replace to
private (non-utility) gas wells.
This gas is commonly known
as wellhead gas.
Installation Items Needed
Before installing replace, make sure you
have the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved exible gas line with gas connector (if allowed by local codes)
* An equipment shutoff valve with 1/8" NPT
tap is an acceptable alternative to test gauge
connection. Purchase the equipment shutoff
valve from your retailer.
For propane/LP connection only, the installer
must supply an external regulator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure
to between 11" and 14" of w.c. pressure. If
you do not reduce incoming gas pressure,
replace regulator damage could occur. Install
external regulator with the vent pointing down
as shown in Figure 18. Pointing the vent down
protects it from freezing rain or sleet.
CAUTION: Use only new,
black iron or steel pipe. Internally-tinned copper tubing may
be used in certain areas. Check
your local codes. Use pipe of
1/2" diameter or greater to allow
proper gas volume to replace.
If pipe is too small, undue loss
of volume will occur.
Installation must include an equipment shutoff
valve, union and plugged 1/8" NPT tap. Locate
NPT tap within reach for test gauge hook up.
NPT tap must be upstream from replace (see
Figure 19, page 17).
IMPORTANT: Install main gas valve (equipment shutoff valve) in an accessible location.
The main gas valve is for turning on or shutting
off the gas to the appliance.
External Regulator
Propane/LP
Supply Tank
Figure 18 - External Regulator with Vent
Pointing Down (Propane/LP Only)
with Vent Pointing
Down
www.fmiproducts.com
125078-01B16
FIREPLACE INSTALLATION
IN
PILOT
IN
OUT
VENT
TH
TP
TH
TP
Continued
Check your building codes for any special
requirements for locating equipment shutoff
valve to replaces.
Apply pipe joint sealant lightly to male NPT
threads. This will prevent excess sealant from
going into pipe. Excess sealant in pipe could
result in clogged replace valves.
Equipment Shutoff Valve
with 1/8" NPT Tap*
Approved
Flexible
Gas Line
3" Minimum
Cap Pipe Tee
Joint Nipple
Sediment Trap/
Figure 19 - Gas Connection
* The equipment shutoff valve may be supplied with the appliance or you can purchase
it from your retailer.
Natural - From
Gas Meter (5.5"
W.C. to 10.5" W.C.
Pressure)
Propane/LP From
External Regulator
(11" W.C. to 14"
W.C. Pressure)
Drip Leg
WARNING: Use pipe joint
sealant that is resistant to liquid
petroleum (LP) gas.
We recommend that you install a sediment
trap/drip leg in supply line as shown in Figure
19. Locate sediment trap/drip leg where it is
within reach for cleaning. Install in piping system between fuel supply and replace. Locate
sediment trap/drip leg where trapped matter
is not likely to freeze. A sediment trap traps
moisture and contaminants. This keeps them
from going into replace gas controls. If sediment trap/drip leg is not installed or is installed
wrong, replace may not run properly.
CONNECTING FIREpLACE TO GAS
SUppLY
Installation Items Needed
• 5/16" hex socket wrench or nut-driver
• sealant (resistant to propane/LP gas, not
provided)
1. Route exible gas line (provided by in-
staller) from equipment shutoff valve to
replace. Route exible gas supply line
through one of the access holes on side
of replace.
2. Attach exible gas line from gas supply to
control valve (see Figure 20).
3. Check all gas connections for leaks. See
Checking Gas Connections, page 18.
Red Surface Indicates For
Propane/LP Use Only
Gas Shutoff
Valve
Flexible
Gas Line
Do NOT
Kink
Pilot Adjustment
Outlet Pressure Tap
1/2" NPT
Incoming
Gas Line
Note:
1) Wire connections not
shown for clarity
Inlet Pressure Tap
2) * 1/8" NPT Plugged
Tapping
Figure 20 - Connecting Incoming Gas Line to Flex Gas Line
125078-01B17
www.fmiproducts.com
FIREPLACE INSTALLATION
Continued
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
WARNING: Never use an
open ame to check for a leak.
Apply noncorrosive leak detection uid to all joints. Bubbles
forming show a leak. Correct all
leaks at once.
pRESSURE TESTING GAS SUppLY
pIpING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect replace and its individual
equipment shutoff valve from gas supply
piping system. Pressures in excess of 1/2
psig (3.5 kPa) will damage replace gas
regulator.
2. Cap off open end of gas pipe where equipment shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas replace or opening
main gas valve located on or near gas
meter for natural gas replace or using
compressed air.
4. Check all joints of gas supply piping system. Apply noncorrosive leak detection
uid to all joints. Bubbles forming show a
leak. Correct all leaks at once.
5. Reconnec t fireplace and e qu ip me nt
shutoff valve to gas supply. Check reconnected ttings for leaks.
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 21).
2. Pressurize supply piping system by either
opening propane/LP supply tank valve
for propane/LP gas replace or opening
main gas valve located on or near gas
meter for natural gas replace or using
compressed air.
www.fmiproducts.com
3. Check all joints from propane/LP supply
tank or gas meter to equipment shutoff
valve (see Figure 22 or Figure 23). Apply
noncorrosive leak detection uid to all
joints. Bubbles forming show a leak.
4. Correct all leaks at once.
Equipment
Shutoff Valve
Figure 21 - Equipment Shutoff Valve
Equipment
Shutoff Valve
Propane/LP
Supply Tank
Figure 22 - Checking Gas Joints for
Propane/LP Gas Fireplace
Equipment
Shutoff Valve
Gas Meter
Figure 23 - Checking Gas Joints for
Natural Gas Fireplace
pRESSURE TESTING FIREpLACE GAS
CONNECTIONS
1. Open equipment shutoff valve (see Figure 21).
2. Open propane/LP supply tank valve for
propane/LP replace or main gas valve
located on or near gas meter for natural
gas replace.
Open
Closed
Gas Valve
Gas Valve
125078-01B18
FIREPLACE INSTALLATION
Continued
3. Make sure control knob of replace is in
the OFF position.
4. Check all joints from equipment shutoff
valve to gas valve (see Figure 22 or
Figure 23, page 18). Apply noncorrosive
leak detection uid to all joints. Bubbles
forming show a leak. Correct all leaks at
once.
5. Light replace (see Operation, page 22).
Check all other internal joints for leaks.
6. Turn off replace (see To Turn Off Gas to Appliance, page 23).
REMOVING/REPLACING GLASS
DOOR
CAUTION: Do not operate
this replace with a broken glass
door panel or without the glass
door panel securely in place.
For replacement part informa-
tion see Replacement Parts,
page 36.
CAUTION: Wear gloves and
safety glasses while handling
or re mov ing broken glass.
Do not remove if glass is hot.
Keep children and pets away
from glass.
WARNING: If replace has
been running, turn off replace.
Let cool before removing glass
doors.
Removing Glass Door
If replacement of glass is necessary, the entire
frame assembly must be replaced. Gloves
must be worn when removing/replacing glass
door. If glass is broken tape remaining glass
onto frame before removing.
1. Remove screens if installed.
2. Open bottom access panel.
3. Unlo ck 2 door l atches on bottom of
rebox.
4. Tilt open glass door 45° from the bottom
of rebox and lift up to release door from
rebox top retainer (see Figure 24).
Door
Retainer
Glass
Door
Door
Latches
Figure 24 - Removing/Replacing Door
Replacing Glass Door
1. Position door frame in front of rebox
opening with bottom of door tilted away
from rebox (see Figure 24).
2. Hook top ange of door frame over top of
rebox frame.
3. Secure 2 bottom door latches.
Bottom
Access Panel
125078-01B19
www.fmiproducts.com
FIREPLACE INSTALLATION
Continued
LAVA ROCK, DECORATIVE GRATE,
EMBER FLAKES AND SCRAP LOG
INSTALLATION
Lava rock, ember akes and scrap log pieces are
included with your replace. Install these items
while glass doors are open and/or removed.
1. Follow instructions from Removing/Re-placing Glass Door, page 19, to move
glass out of the way of this installation.
2. For 36" models only, install 3 loose logs
by placing log #1, log #2 and log #3 onto
one piece log as shown in Figure 25.
3. Place lava rock around base of burner.
Make sure burner ports are not covered
(see Figure 26).
4. Place ember akes around front and sides of
burner and on burner ports (see Figure 27).
This will create the glowing ember appearance
as the ame touches the ember akes. Do not
block burner ports or pilot ports by overlapping
ember akes in one area. It is not necessary
to use all ember material provided.
5. Place scrap log pieces randomly behind
grate as shown in Figure 28 on lava rock
and around (but not on) burner ports.
6. Place grate in front of logs as shown in
Figure 28. Be sure grate is balanced so it
does not fall or lean onto logs. Grate does
not attach to hearth assembly.
Log #3
Log #2
Log #1
Lava Rock
Figure 26 - Installing Lava Rock
Ember Flakes
Figure 27 - Installing Ember Flakes
Figure 25 - Installing Loose Logs
www.fmiproducts.com
Scrap Log Pieces
Figure 28 - Installing Scrap Log Pieces
REMOVING LOGSET/BURNER
MODULE
Connecting and Disconnecting Gas Line
WARNING: A qualied service person must connect and
disconnect replace with gas
supply. Follow all local codes.
1. Using a 5/16" hex socket wrench or nutdriver, connect or disconnect exible gas line
and control valve (see Figure 29, page 21).
2. After connecting gas line to control valve,
always test for leaks.
125078-01B20
FIREPLACE INSTALLATION
Continued
WARNING: Never use an
open ame to check for a leak.
Apply noncorrosive leak detection uid to joints. Bubbles
forming show a leak. Correct
leaks at once.
Burner Base
Log
Assembly
CAUTION: The gas supply
Spacers
shall be shut off prior to disconnecting the electrical power, if
any, before proceeding with this
installation.
CAUTION: Use gloves when
removing the log set/burner
module from your rebox. Some
metal edges may be sharp. Use
caution with log sets as logs
are fragile.
1. Remove glass door (see page 19).
2. Remove grate and all oor media (see
page 20).
3. Carefully lift and remove 3 hearth refractories from replace.
4. Remove 3 spacers from rebox bottom
(see Figure 30).
5. For 36" models only, remove 3 loose logs
from log set (see Figure 25 page 20).
6. Remove 9 screws from front and sides of
rebox burner base. Lift entire base from
unit by pulling forward to disengage from rear
ange and then lifting up (see Figure 30).
7. If needed, replace burner gasket before
reinstalling log set/burner module (see
replacement parts list on page 36.)
To Gas Supply
(Natural)
To External
Regulator
(Propane/LP)
Flexible Gas
Line, Do NOT
Kink
Figure 29 - Connecting/Disconnecting
Gas Line to Millivolt Valve
125078-01B21
Equipment
Shutoff
Valve
Millivolt
Control
Valve
www.fmiproducts.com
Battery
Housing
Cover
Firebox
Bottom
Figure 30 - Removing/Installing Burner Base
Screws
INSTALLING BATTERIES IN
WIRELESS HAND-HELD REMOTE
CONTROL AND RECEIVER
Installing Batteries in Remote Receiver
1. Open bottom access door.
2. Remove switch plate from receiver (see
Figure 31).
3. Remove battery housing cover on remote
receiver to expose battery housing (see
Figure 31).
4. Install 4 AA batteries into housing following positive and negative directions on
battery housing cover removed in step 3
(see Figure 31).
5. Replace battery housing cover and switch
plate.
6. Install 2 D batteries into AC backup battery
pack.
7. Close bottom access door.
Remote
Receiver
AA
Batteries
Screws
Switch
D Batteries
Plate
Figure 31 - Installing Receiver Batteries
(Included)
Battery
Housing
AC Backup
Battery Pack
FIREPLACE INSTALLATION
Continued
Installing Batteries in Hand-Held Remote
Control Unit
1. Remove battery cover on back of remote
control unit.
Remote
Control
Unit
2. Install 3 AAA batteries as instructed in
battery housing.
3. Replace battery cover onto remote control unit.
Battery Cover
AAA
Batteries
Figure 32 - Installing Battery in Hand-Held Remote Control Unit
(use only alkaline batteries, not included)
OPERATION
FOR YOUR SAFETY
READ BEFORE LIGHTING
WARNING: If you do not fol-
low these instructions exactly,
a re or explosion may result
causing property damage, personal injury or loss of life.
A. This appliance is equipped with an igni-
tion device which automatically lights
the pilot. Do not light pilot by hand.
B. BEFORE LIGHTING smell all around
the appliance area for gas. Be sure to
smell next to the oor because some
gas is heavier than air and will settle
on the oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do
not use any phone in your building.
• Immediately call your gas supplier
from a neighbor's phone. Follow the
gas supplier's instructions.
Battery
Housing
C. Do not use this appliance if any part
has been under water. Immediately call
a qualied service technician to inspect
the appliance and to replace any part of
the control system and any gas control
which has been under water.
LIGHTING
INSTRUCTIONS
NOTICE: During initial operation
of new replace, burning logs
will give off a paper-burning
smell. Orange ame will also
be present. Open damper or
window to vent smell. This will
only last a few hours.
1. STOP! Read the safety information in
column 1.
2. Turn off all electric power to replace.
3. Turn safety shutoff switch to the OFF
position.
4. Remove center brick/control cover.
www.fmiproducts.com
125078-01B22
OPERATION
IN
PILOT
IN
OUT
VENT
TH
TP
TH
TP
Continued
5. Turn equipment shutoff valve clockwise
to the OFF position (see Figure
33). Do not force.
6. Wait ve (5) minutes to clear out any gas.
Then smell for gas, including near the
oor. If you smell gas, STOP! Follow “B”
in the safety information page 22. If you
don't smell gas, go to the next step.
7. Turn equipment shutoff valve counter-
clockwise to the ON position. Do
not force.
8. Replace center brick/control cover.
9. Turn on all electric power to appliance.
10. Turn safety shutoff switch to the ON
position.
11. Visually locate pilot. Ignitor should begin
to spark and main burner should ignite
once ame appears at pilot.
• If lighting appliance for the rst time each
season, it may take several attempts
before supply gas can reach pilot and
main burners.
• If appliance will not stay lit after several
attempts, follow instructions under To Turn Off Gas To Appliance and call your
service technician or gas supplier.
TO TURN OFF GAS
TO AppLIANCE
1. Turn off safety shutoff switch.
2. Turn off all electric power to appliance if
service is to be performed.
3. Remove center brick/control cover.
4. Turn equipment shutoff valve clockwise
to OFF. Do not force.
5. Replace center brick/control cover.
REMOTE
OpERATION
1. Turn equipment shutoff valve to ON position. You can now turn the burner on and
off with hand-held remote control unit.
IMPORTANT: Be sure to press ON/OFF
buttons on hand-held remote control unit
for up to 3 seconds to assure proper
operation.
2. Press ON/OFF button to turn burner on
and off.
Equipment
Shutoff Valve
Figure 33 - Turning Equipment Shutoff Valve to the OFF Position
Ignitor
Pilot
Sensing Rod
Burner
Figure 34 - Pilot
125078-01B23
www.fmiproducts.com
INSPECTING BURNERS
Check pilot ame pattern and burner ame
patterns often.
pILOT ASSEMBLY
The pilot assembly is factory preset for the
proper ame. Alterations may have occurred
during shipping and handling. The pilot is
located on right hand side of burner.
The ame must envelope 1/4" of top of the
ignitor/sensor and grounding stem.
If your pilot assembly does not meet these
requirements:
• Turn the adjustment screw marked PILOT
clockwise to decrease or counterclockwise
to increase the ame to proper size (see
Figure 33, page 23). Do not remove the
adjustment screw.
• see Troubleshooting, page 26
Sensing
Rod
Ignitor/
Sensor
Pilot
Burner
BURNER FLAME pATTERN
Burner ames will be steady, not lifting or oating. Flame patterns will be different from unit
to unit and will vary depending on installation
type and weather conditions.
If the vent conguration is installed incorrectly,
ames will lift or "ghost". This can be dangerous. Inspect ames after installation to ensure
proper installation and performance.
Figure 36 shows a typical ame pattern.
If burner ame pattern differs from that de-
scribed:
• turn replace off (see To Turn Off Gas to Appliance, page 23)
• see Troubleshooting, page 26
Figure 36 - Typical Flame Pattern
Figure 35 - Correct Pilot Flame Pattern
CLEANING AND MAINTENANCE
WARNING: Turn off replace
and let cool before cleaning.
CAUTION: You must keep
control areas, burners and
circulating air passageways of
replace clean. Inspect these
areas of replace before each
use. Have replace inspected
yearly by a qualied service
person. Fireplace may need
more frequent cleaning due to
excessive lint from carpeting,
bedding material, pet hair, etc.
www.fmiproducts.com
GLASS DOORS
WARNING: Handle glass
door panels with care. Do not
strike, slam or otherwise abuse
glass. Do not operate replace
with the glass door unlatched,
removed, cracked or broken.
WARNING: Do not use
abrasive cleaners as this may
damage glass. Use a nonabrasive household glass cleaner to
clean glass. Do not clean glass
when hot.
125078-01B24
CLEANING AND MAINTENANCE
Continued
Glass must be cleaned periodically. During
start-up it is normal for condensation to form
on the inside of the glass causing lint, dust and
other airborne particles to cling to the glass
surface. During initial start-up a slight lm may
form on the glass due to paint curing. The
glass should be cleaned several times with a
non-ammonia, nonabrasive household cleaner and warm water after the rst two weeks
of operation. Thereafter, clean the glass two
or three times during each heating season,
depending on the usage and circumstances
present. Refer to Removing/Replacing Glass Door, page 19 of this manual when removing
glass door for cleaning.
WARNING: Only parts suppli ed by the m anufa cture r
should be used when replacing
broken or damaged glass door
panels (see Replacement Parts,
page 36). Glass door panel are
complete units. No substitute
materials may be used.
CAUTION: Wear gloves and
safety glasses while handling
or removing broken glass. Do
not remove if glass is hot. Keep
children and pets away from
glass.
If glass has been broken, carefully remove
glass door (see Removing/Replacing Glass Door, page 19). Vacuum all glass pieces with
a shop vac.
CAUTION: Do not vacuum if
pieces are hot.
Use only glass door replacement intended for
this replace (see Replacement Parts, page
36 for detail on ordering). No substitutions
may be made. See Removing/Replacing Glass Door, page 19 for instructions for replacing glass doors.
WARNING: Do not operate
replace with glass door un-
latched, removed, cracked or
broken.
pILOT AND BURNERS
• Remove material before cleaning burners
and replace when cleaning is complete.
• Burner and controls should be cleaned
with compressed air to remove dust, dirt
or lint.
• Use a vacuum cleaner or small, soft bristled
brush to remove excess dust, dirt or lint.
LOGS
• Use a vacuum cleaner to remove any
carbon buildup on logs.
• Replace material periodically as needed.
See Replacement Parts, page 36.
VENTING SYSTEM
Conduct annual inspection of the venting
system following these guidelines:
1. Check areas of venting system that are
exposed to the weather for corrosion (rust
spots or streaks and, in extreme cases,
holes). Have these items replaced immediately by a qualied service person.
2. Remove the vent cap and shine a ash-
light into the vent. Remove any foreign
material.
3. Check for evidence of excessive con-
densation. Continuous condensation can
cause corrosion of caps, pipes and ttings
and can be caused by having excessive
lateral runs, too many elbows or exterior
portions of the system being exposed to
cold weather.
4. Inspect joints to verify that no pipe section
or tting has been disturbed and loosened. Check mechanical supports such
as wall straps for rigidity.
125078-01B25
www.fmiproducts.com
TROUBLESHOOTING
WARNING: Turn off replace and let cool before servicing. Only
a qualied service person should service and repair replace.
CAUTION: Never use a wire, needle or similar object to clean
pilot. This can damage pilot unit.
Note: All troubleshooting items are listed in order of operation.
OBSERVED PROBLEM
Ignitor will not spark or pilot
will not light
pOSSIBLE CAUSE
1. No gas supply or shutoff
valve is OFF
2. Air in gas line
3. Construction debris clogging pilot orice
4. Low gas pressure
5. Kinked pilot line
6.
Control valve is not opening
7. No power to unit or ignition
module or power transformer is bad
REMEDY
1. Check to see if you have gas
supply and that equipment
shutoff valve is opened
2. Repeat lighting procedure
several times to purge all
air out of lines. If after repeated attempts appliance
does not light, call for qualied service and repair
3. Remove debris and dirt,
inspect and clean any other
possible obstructions
4. Contact your gas supplier
to check pressure
5. Have a qualied technician
replace pilot line
6. Replace control valve (Refer to Replacement Parts,
page 36)
7. Check that main power is
on and that all wire connections are made correctly to
ignition model (see Wiring Diagram, page 29). Check
for 24 VAC at the secondary side of transformer. If 24
VAC is present and module
does n ot o pe rate, hav e
module replaced. Otherwise have transformer replaced
www.fmiproducts.com
125078-01B26
OBSERVED PROBLEM
Pilot will not stay lit
TROUBLESHOOTING
Continued
pOSSIBLE CAUSE
1. Loose wiring on ignitor wire
to ignition module and/
or poor ground to ignition
module
2. Pil o t fla m e too l ow to
sense
REMEDY
1. Check wiring connection.
Refer to wiring diag ram
(see Wiring Diagram, page
29) and/or check ground
wire to ignition module
2. Clean and adjust pilot burner and check gas supply
and inlet pressure to unit
Not e: Ha v e a qua l if i ed
te ch ni cian replace pilot
assembly if broken or corroded
No gas to burner, although
safety shutoff switch and valve
are set to the ON position
Frequent pilot outage
Fireplace produces a clicking/
ticking noise just after burner
is lit or shut off
Slight smoke or odor during
initial operation
1. Safety shutoff switch wires
defective or too long
1. Pilot ame may be too low,
causing safety pilot to “drop
out”
2. Improper venting or excessive blockage
1. Met al expa n din g wh ile
heating or contracting while
cooling
1. Residues from manufacturing processes and logs
curing
1. Check electrical connections
1. Clean and adjust pilot ame
for maximum flame impingement on thermopile
2. Have vent system inspected, including termination
cap. Remove any restriction
or obstruction
1. This is normal with most
replaces. If noise is excessive, contact qualied
service person
1. Problem will stop after a few
hours of operation
125078-01B27
www.fmiproducts.com
TROUBLESHOOTING
Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your
building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
OBSERVED PROBLEM
Gas odor even when gas
control valve is off
Gas odor during combustion
Glass soots
Dark residue on logs or inside
of replace
pOSSIBLE CAUSE
1. Gas leak . See Warning
statement at top of page
2. Control valve defective
1. Foreign matter betwee n
control valve and burner
2. Gas leak . See Warning
statement at top of page
1. Debris around burner air
mixer
2. Improper vent conguration
1. Air holes at b urner inle t
blocked
2. Burner ame holes blocked
3. Improper venting or excessive blockage
4. Excessive amounts of embers and pan material
REMEDY
1. Locate and correct all leaks
(see Checking Gas Connections, page 18)
2. Replace control valve
1. Take apart gas tubing and
remove foreign matter
2. Locate and correct all leaks
(see Checking Gas Connections, page 18)
1. Inspect opening at base of
burner to see that it is NOT
packed with any type of
material
2. Check vent configuration
specication (see Venting Installation, page 10)
1. Clean out air holes at burner inlets. Periodically repeat
as needed
2. Remove blockage
3. Have vent system inspected, including termination
cap. Remove any restrictions or obstruction
4. Clear excess embers until
a mi ni mum gap of 1/ 2"
remains under grate
This list contains replaceable parts used in your replace. When ordering parts, follow the
instructions listed under Replacement Parts on page 36 of this manual.
2125126-01 Left Refractory, Herringbone 42" White•1
125126-02 Left Refractory, Herringbone 42" Red•1
125090-01 Left Refractory, Herringbone 36" White•1
125090-02 Left Refractory, Herringbone 36" Red•1
125123-01 Left Refractory, Stacked 42" White•1
125123-02 Left Refractory, Stacked 42" Red•1
125089-01 Left Refractory, Stacked 36" White•1
125089-02 Left Refractory, Stacked 36" Red•1
3125128-01 Right Refractory, Herringbone 42" White•
125128-02 Right Refractory, Herringbone 42" Red•1
125092-01 Right Refractory, Herringbone 36" White•
125092-02 Right Refractory, Herringbone 36" Red•1
125127-01 Right Refractory, Stacked 42" White•
125127-02 Right Refractory, Stacked 42" Red•1
125091-01 Right Refractory, Stacked 36" White•
125091-02 Right Refractory, Stacked 36" Red•1
4125129-01 Left Front Refractory 42" White••
125129-02 Left Front Refractory 42" Red••1
125093-01 Left Front Refractory 36" White••
125093-02 Left Front Refractory 36" Red••1
5125131-01 Center Front Refractory 42" White••
125131-02 Center Front Refractory 42" Red••1
125095-01 Center Front Refractory 36" White••
125095-02 Center Front Refractory 36" Red••1
6125130-01 Right Front Refractory 42" White••
125130-02 Right Front Refractory 42" Red••1
125094-01 Right Front Refractory 36" White••
125094-02 Right Front Refractory 36" Red••1
DVF42(N,P)H(-HA)
DVF36(N,P)H(-HA)
DVF42(N,P)S(-HA)
DVF36(N,P)S(-HA)
VDVF42(N,P)H
VDVF36(N,P)H
VDVF42(N,P)S
VDVF36(N,P)S
125078-01B35
www.fmiproducts.com
REPLACEMENT PARTS
Note: Use only original replacement parts.
This will protect your warranty coverage for
parts replaced under warranty.
Contact authorized dealers of this product.
If they can’t supply original replacement
pa r t(s ), ca l l F M I P R ODU CTS , LLC at
1-866-328-4537.
When calling, have ready:
• your name
• your address
• model and serial numbers of your heater
• how heater was malfunctioning
• purchase date
Usually, we will ask you to return the part to
the factory.
TECHNICAL SERVICE
You may have further questions about
installation, operation, or troubleshooting.
If so, contact FMI PROD UC TS, LLC a t
1-866-328-4537. When calling please have
your mod el a nd serial numbers of your
heater ready.
You can also visit our web site at
www.fmiproducts.com.
ACCESSORIES
Purchase these accessories from your local
dealer. If they can not supply these accessories
call FMI PRODUCTS, LLC at 1-866-328-4537
for information. You can also write to the address listed on the back page of this manual.
Brick Perimeter Trim Kit
PBS36 - Red
VPBS36 - Ivory
PBS42 - Red
VPBS42 - Ivory
Magnetic attachment, Matching refractory
brick facing surround kit.
SERVICE HINTS
When Gas pressure Is Too Low
• pilot will not stay lit
• burners will have delayed ignition
• replace will not produce specied heat
• propane/LP gas supply might be low (propane/LP units only)
You may feel your gas pressure is too low. If
so, contact your local gas supplier.
Propane/Natural Gas Conversion Kit
IMPORTANT: NOT to be used for High Altitude
(-HA) Models
PCD-36S - Propane/LP Gas Conversion Kit
NCD-36S - Natural Gas Conversion Kit
PCD-42S - Propane/LP Gas Conversion Kit
NCD-42S - Natural Gas Conversion Kit
Standard Warranty: FMI PRODUCTS, LLC warrants this new product and any parts thereof to be free from defects
in material and workmanship for a period of four (4) years from the date of rst purchase from an authorized dealer
provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s
warnings and instructions.
For products purchased for commercial, industrial or rental usage, this warranty is limited to 90 days from the date
of rst purchase.
Limited Warranty: FMI PRODUCTS, LLC warrants factory reconditioned products and any parts thereof to be
free from defects in material and workmanship for 30 days from the date of rst purchase from an authorized dealer
provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s
warnings and instructions.
The following terms apply to all of the above warranties:
Always specify model number and serial number when contacting the manufacturer. To make a claim under this
warranty the bill of sale or other proof of purchase must be presented.
This warranty is extended only to the original retail purchaser when purchased from an authorized dealer, and only
when installed by a qualied installer in accordance with all local codes and instructions furnished with this product.
This warranty covers the cost of part(s) required to restore this product to proper operating condition and an allowance for labor when provided by a FMI PRODUCTS, LLC Authorized Service Center or a provider approved by
FMI PRODUCTS, LLC. Warranty parts must be obtained through authorized dealers of this product and/or FMI
PRODUCTS, LLC who will provide original factory replacement parts. Failure to use original factory replacement
parts voids this warranty.
Travel, handling, transportation, diagnostic, material, labor and incidental costs associated with warranty repairs,
unless expressly covered by this warranty, are not reimbursable under this warranty and are the responsibility of
the owner.
Excluded from this warranty are products or parts that fail or become damaged due to misuse, accidents, improper
installation, lack of proper maintenance, tampering, or alteration(s).
This is FMI PRODUCTS, LLC’s exclusive warranty, and to the full extent allowed by law; this express warranty
excludes any and all other warranties, express or implied, written or verbal and limits the duration of any and all
implied warranties, including warranties of merchantability and tness for a particular purpose to four (4) years on
new products and 30 days on factory reconditioned products from the date of rst purchase. FMI PRODUCTS, LLC
makes no other warranties regarding this product.
FMI PRODUCTS, LLC’s liability is limited to the purchase price of the product, and FMI PRODUCTS, LLC shall not
be liable for any other damages whatsoever under any circumstances including indirect, incidental, or consequential
damages.
Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental
or consequential damages, so the above limitation or exclusion may not apply to you.
This warranty gives you specic legal rights, and you may also have other rights which vary from state to state.
For information about this warranty contact:
New products
Factory Reconditioned products
Terms Common to All Warranties
) _____________________________
) __________________________
2701 S. Harbor Blvd.
Santa Ana, CA 92704
1-866-328-4537
www.fmiproducts.com
125078-01
Rev. B
3/10