FMI DVF42NH-HA, DVF-36NS-HA, VDVF42PH, DVF-42NS-HA, DVF36NH-HA User Manual

...
DIRECT-VENT FIREPLACE
PFS
®
US
OWNER’S OPERATION AND INSTALLATION MANUAL
MODELS (V)DVF36NS, (V)DVF36PS, (V)DVF36NH, (V)DVF36PH,
DVF-36NS-HA, DVF36NH-HA, (V)DVF42NS, (V)DVF42PS, (V)
DVF42NH, (V)DVF42PH, DVF-42NS-HA, AND DVF42NH-HA
WARNING: If the information in this manual is not
followed exactly, a re or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
— Installation and service must be performed by a quali-
ed installer, service agency or the gas supplier.
INSTALLER: Leave this manual with the appliance CONSUMER: Retain this manual for future reference.
For more information, visit www.fmiproducts.com
TABLE OF CONTENTS
Safety .................................................................. 2
Local Codes......................................................... 4
Product Identication ........................................... 5
Product Features ................................................. 5
Pre-installation ..................................................... 6
Location of Termination Cap ................................ 8
Requirements for the Commonwealth of
Massachusetts ................................................. 9
Venting Installation ............................................ 10
Fireplace Installation.......................................... 16
Operation ........................................................... 22
SAFETY
WARNING: Improper instal-
lation, adjustment, alteration,
service or maintenance can
cause injury or property damage.
Refer to this manual for correct
installation and operational procedures. For assistance or
additional information consult
a qualified installer, service agency or the gas supplier.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certied kit is used.
State of Massachusetts: The
installation must be made by a licensed plumber or gas tter
in the Commonwealth of Mas-
sachusetts.
WARNING: This product
con tains a nd/or gener ates
chemicals known to the State of California to cause cancer or
birth defects or other reproduc­tive harm.
Inspecting Burners............................................. 24
Cleaning and Maintenance ................................ 24
Troubleshooting ................................................. 26
Specications .................................................... 29
Wiring Diagram .................................................. 29
Parts .................................................................. 30
Replacement Parts ............................................ 36
Technical Service............................................... 36
Service Hints ..................................................... 36
Acessories ......................................................... 36
Warranty ..............................................Back Cover
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, op­erate or service this replace. Improper use of this replace can cause serious injury or death from burns, re, explo­sion, electrical shock and carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
This vented gas replace is a sealed combus­tion gas replace designed for residential ap­plications. This replace must be installed with FMI PRODUCTS, LLC vent pipe components and terminations.
This fireplace complies with the National
Safety Standards and is listed and tested by PFS Corporation to ANSI Z21.50 standard as
vented gas replace. This replace must be installed by a qualied
(certied or licensed) service person. It brings in fresh air for combustion through the outer pipe and combustion gases are exhausted through the inner pipe. If the glass door as­sembly and venting pipe are not properly seated, connected and sealed, carbon mon­oxide leakage (spillage) can occur.
www.fmiproducts.com
125078-01B2
SAFETY
Continued
Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning resemble the u, with headaches, dizziness or nausea. If you have these signs, the replace may not be working properly. Get fresh air at once! Have replace serviced. Some people are more affected by carbon monoxide than oth­ers. These include pregnant women, people with heart or lung disease or anemia, those under the inuence of alcohol and those at high altitudes.
Natural and Propane/LP Gas: Natural and propane/LP gas are odorless. An odor-making agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this replace.
WARNING: Any change to this replace or it’s controls can be dangerous. Do not modify this replace under any circum­stances. Any parts removed for servicing must be replaced prior to operating replace.
WARNING: Do not allow fans
to blow directly into the replace. Avoid any drafts that alter burner ame patterns.
Due to high temperatures, the appliance should be located out of trafc and away from furniture and draperies.
Do not place clothing or other ammable material on or near the appliance. Never place any objects on the appliance.
Do not use this replace to cook food or burn paper or other am­mable material.
This replace reaches high tem­peratures. Keep children and
adults away from hot surface to
avoid burns or clothing ignition. Fireplace will remain hot for a time after shutdown. Allow sur­face to cool before touching.
WARNING: Do not use a blow­er insert, heat exchanger insert or other accessory not approved
Carefully supervise young chil-
dren when they are in the room
with replace.
for use with this replace.
Keep the area around your
WARNING: This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases unless
replace clear of combustible materials, gasoline and other ammable vapor or liquids. Do not run replace where these are used or stored.
a certied kit is used.
125078-01B 3
www.fmiproducts.com
SAFETY
Continued
1. For propane/LP replace, do not place propane/LP supply tank(s) inside any structure. Locate propan e/LP supp ly tank(s) outdoors. To prevent performance problems, do not use propane/LP fuel tank of less than 100 lb. capacity.
2. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor ’s phone. Follow the gas supplier's instructions
• if you cannot reach you gas supplier, call
the re department.
3. Never install the replace
• in a recreational vehicle
• in windy or drafty areas where curtains or
other combustible (ammable) objects can make contact with the replace front
• in high trafc areas
4. Turn fireplace off and let cool before servicing, installing or repairing. Only a qualied service person should install, service or repair this replace. Have re­place inspected annually by a qualied service person.
5. You must keep control compartments, burners and circulating air passages clean. More frequent cleaning may be needed due to excessive lint and dust from carpeting, bedding material, etc. Turn off the gas valve and pilot light before cleaning replace.
6. Have venting system inspected annually by a qualied service person. If needed, have venting system cleaned or repaired. See Cleaning and Maintenance, page 24.
7. Do not use any solid fuels (wood, coal, paper, cardboard, etc.) in this replace. Use only the gas type indicated on re­place nameplate.
8. This appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code,
ANSI/NFPA 70.
9. Do not use replace if any part has been exposed to or under water. Immediately call a qualied service person to arrange for replacement of the unit.
10. Do not operate replace if any log is broken.
11. Do not operate replace with glass door removed, cracked or broken.
12. Provide adequate clearances around air openings.
LOCAL CODES
Install and use replace with care. Follow all local codes. In the absence to local codes, use the current National Fuel Gas Code ANSI Z223.1/NFPA 54*. *Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
www.fmiproducts.com
125078-01B4
Outer Glass Door
Herringbone Brick Refractories
Log Set
Grate
Lower Door/ Control Cover
PRODUCT IDENTIFICATION
Flue Collar
Nailing Flange
Figure 1 - Direct Vent Fireplace
PRODUCT FEATURES
These are a few facts that can help you under­stand and enjoy your direct vent replace:
• The venting system may be routed to the outside of your home in several ways. It may vent through the roof (vertical) or it may vent to an outside/exterior wall (hori­zontal). The vent pipe installation is very important to allow for proper operation. You must follow the venting instructions very carefully for either vertical or horizontal applications.
• This replace may be installed in any room of your house provided all local codes and these installation instructions are followed.
125078-01B 5
www.fmiproducts.com
• Each time you turn on your replace, you may notice some amount of condensation on the inside of the replace glass. This is normal and will disappear after 10-20 minutes of operation.
• Your direct ve nt gas fire place system (replace and venting) is a balanced and sealed gas operating unit. It requires ap­proximately 10-20 minutes of operating time before the ame pattern stabilizes.
PRE-INSTALLATION
29" (36")
34
3
/4" (4 2") 21" (36") 25" (42")
41
1
/4" (3 6")
48 1/4" (4 2")
11 7/8" (3 6") 13 5/8" (4 2")
LOCATION AND SpACE REqUIREMENTS
Determine the safest and most efcient loca­tion for your direct vent replace. Make sure that rafters and wall studs are not in the way of the venting system. Choose a location where the heat output is not affected by drafts, air conditioning ducts, windows or doors. Figure 2 shows some common locations. Be aware of all restrictions and precautions before deciding the exact location for your replace and termination cap.
When deciding the location of your replace, follow these rules:
• Do not connect this replace venting to a chimney ue serving a separate solid-fuel burning replace or appliance.
• Due to high temperatures, do not locate this replace in high trafc areas, windy or drafty areas or near furniture or draperies.
• Proper clearances must be maintained.
• If your replace is to be installed directly on carpeting, vinyl tile or any combustible mate­rial other than wood, it must be installed on a metal or wood panel extending the full width and depth of the replace (see Figure 3).
• Your replace is designed to be used in zero clearance installations. Wall or fram­ing material can be placed directly against any exterior surface on back, sides or top of your replace, except where standoff spacers are integrally attached. If standoff spacers are attached to your replace, these s pacer s can be plac ed directly against wall or framing material. See fram­ing details, page 7.
• When locating termination cap, it is impor­tant to observe the minimum clearances shown in Figure 7, page 8.
• If recessing into a wall, you can avoid extra framing by positioning your replace against an already existing framing member.
• Do not recess termination cap into a wall or siding.
• You may paint the termination cap with 450º F (232º C) heat-resistant paint to coordinate with the exterior nish.
• There must not be any obstruction such as bushes, garden sheds, fences, decks or utility buildings within 24" from the front of the termination cap and the front of outside air vent.
• Do not locate termination cap and outside air vent where excessive snow or ice build up may occur. Be sure to clear vent ter­mination area after snow falls to prevent accidental blockage of venting system. When using snow blowers, do not direct snow towards vent termination area.
Flush with a wall
Through exterior wall enclosed in a chase
Corner installation
Figure 2 - Common Fireplace Locations
Figure 3 - Fireplace Top Dimensions
www.fmiproducts.com
125078-01B6
C
B
A
D
E
F
G
3
2
1
4
5
6
7
Wa ll
PRE-INSTALLATION
43
1
/
4
"
(36")
47
1
/
4
"
(42")
41
1/2"
(36")
48
1/2"
(42")
36
3/8"
(36")
43
3
/
8
" (42")
43" (36"), 50" (42")
42" (36"), 49" (42")
15
3/4"
(36")
19" (42")
51
3/8"
(36")
61
3
/
4
" (42")
Nailing
Tabs
Continued
CLEARANCES
Minimum clearances to combustibles for the replace are as follows:
*Back and sides 1" Perpendicular walls 6" Floor 0" Ceiling to louver opening 42" Front 36" Top of Standoffs 0" Vent (See venting instructions
for specic venting
clearances.) Combustible material with a maximum thick­ness of 5/8" may be ush with the top front of replace.
* For back and sides of replace, do not pack with insulation or other materials. 1" clearance not required at nailing anges.
NOTICE: This replace is intend­ed for use as supplemental heat. Use this replace along with your primary heating system. Do not install this replace as your primary heat source. If you have a central heating system, you may run system’s circulat­ing blower while using replace. This will help circulate the heat throughout the house.
Figure 4 - Framing Clearances with
Outside Air Flex Duct
Figure 5 - Framing Clearances for Corner
Installation
FRAMING AND FINISHING
Figure 4 shows typical framing of this replace. Figure 5 shows framing for corner installation. All minimum clearances must be met.
If you are using a separate combustible man­tel piece, refer to Figure 6 for proper instal­lation height. You can install noncombustible mantels at any height above the replace.
Note: Noncombustible mantels may discolor!
125078-01B 7
www.fmiproducts.com
Mantel
Ref.
Depth Ref.
1 14" A 16" 2 12" B 14" 3 10" C 12" 4 8" D 10" 5 6" E 8" 6 4" F 6" 7 2" G 4"
Mantel from
Top of Opening
Figure 6 - Clearances for Combustible
Mantels
Fixed
Closed
Openable
Fixed
Closed
V
V
V
V
V
V
V
V
X
X
V
X
G
G
J
F
B
B
K
N
H
I
A
N
E
L
D
B
M
A
C
B
V
V
A
G
G
B
TERMINATION CAP
AIR SUPPLY INLET
GAS METERRESTRICTED AREA
(TERMINATION PROHIBITED)
A = clearance above grade, veranda, porch, deck, or balcony [*12" (30.5 cm) minimum] B = clearance to window or door that may be opened [6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US if between 10,000 and 50,000, 12" (30 cm) in Canada if between 10,000 and 100,000; 12" (30 cm) in US if greater than 50,000, 36" (91 cm) in Canada if greater than 100,000] C = clearance to permanently closed window [minimum 12" (30.5 cm) recommended to prevent condensation on window] D = vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24" (61 cm) from the center-line of the terminal [18" (45.7 cm) minimum] E = clearance to unventilated soffit [12" (30.5 cm) minimum] F = clearance to outside corner (see below) G = clearance to inside corner (see below) H = *not to be installed above a meter/regulator assembly within 36" (91.4 cm) horizontally from the center line of the regulator
I = clearance to service regulator vent outlet [*72" (182.9 cm) minimum] J = clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other fireplace [6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US if between 10,000 and 50,000, 12" (30 cm) in Canada if between 10,000 and 100,000; 12" (30 cm) in US if greater than 50,000, 36" (91 cm) in Canada if greater than 100,000] K = clearance to a mechanical air supply inlet [*In Canada, 6 ft. (1.83m) minimum; In US 3 ft. (91 cm) above if within 10 ft. (3 m) horizontally] L = † clearance above paved side-walk or a paved driveway located on public property [*84" (213.3 cm) minimum] M = clearance under veranda, porch, deck [*12" (30.5 cm) minimum ‡] N = clearance above a roof shall extend a minimum of 24" (61 cm) above the highest point when it passes through the roof surface and any other obstruction within a horizontal distance of 18" (45.7 cm)
† vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves both dwellings* ‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor* * as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A.
Note: Local codes or regulations may require different clearances
A = 6" (15.2 cm)
Inside Corner
V
B
E
V
B = 6" (15.2 cm)
C = Maximum depth of 48" (121.9 cm) for recessed location D = Minimum width for back wall of recessed location ­ Combustible - 38" (965 mm) Noncombustible - 24" (61 cm) E = Clearance from corner in recessed location­ Combustible - 6" (15.2 cm) Noncombustible - 2" (5.1 cm)
Outside Corner Recessed Location
G
H
G = 12" (30.5 cm) minimum clearance
Balcony with No Side Wall
V
J
Combustible & Noncombustible H = 24" (61 cm) J = 20" (50.8 cm)
Balcony with Perpendicular Side Wall
C
D
C
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Openable
LOCATION OF TERMINATION CAP
Figure 7 - Minimum Clearances for Termination Cap
www.fmiproducts.com
125078-01B8
REQUIREMENTS FOR THE COMMONWEALTH OF
MASSACHUSETTS
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall ex­haust vent termination is less than seven (7) feet above nished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satised:
INSTALLATION OF CARBON MONOXIDE DETECTORS
At the time of installation of the side wall horizon­tal vented gas fueled equipment, the installing plumber or gastter shall observe that a hard wired carbon monoxide detector with an alarm and battery backup is installed on the oor level where the gas equipment is to be installed. In addition, the installing plumber or gastter shall observe that a battery operated or hard wired car­bon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualied licensed professionals for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent oor level.
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certied.
SIGNAGE
A metal or plastic identication plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than 1/2" in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".
125078-01B 9
www.fmiproducts.com
INSpECTION
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a) 1 through 4. EXEMPTIONS: The following equipment is ex-
empt from 248 CMR 5.08(2)(a) 1 through 4:
• The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
• Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwell­ing, building or structure used in whole or in part for residential purposes.
MANUFACTURER REqUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
• Detailed instructions for the installation of the venting system design or the venting system components; and
• A complete parts list for the venting system design or venting system.
Gas Equipment Venting System Not
provided
When the manufacturer of a Product Ap­proved side wall horizontally vented gas fu­eled equipment does not provide the parts for venting the ue gases, but identies "special venting systems", the following requirements shall be satised by the manufacturer:
The referenced "special venting system" in­structions shall be included with the appliance or equipment installation instructions; and
• The "special venting systems" shall be Prod­uct Approved by the Board, and the instruc­tions for that system shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved side w all horizon tally vented gas fueled equipment, all venting in­structions, all parts lists for venting instruc­tions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
VENTING INSTALLATION
NOTICE: Read these instruc-
tions completely before attempt­ing installation.
These models are tested and approved for use with FMI PRODUCTS, LLC (direct vent) pipe components and terminations.
The venting system must terminate on the outside of the structure and can not be at­tached to a chimney or ue system serving a separate solid fuel or gas burning appliance. A direct vent appliance must have its own venting system. DO NOT common vent this appliance.
These models are approved to be vented either horizontally through an outside wall or vertically through a roof or chase enclosure using the following guidelines:
• When venting system terminates horizon­tally on an outside wall, you may install a standoff if the termination cap is to be installed directly on a combustible nish such as vinyl, wood, stucco, etc.
• Never run the vent downward as this may cause excessive temperatures which could cause a re.
• Vent pipe air space clearances to com­bustibles are 1" on all sides except on the horizontal sections, which requires 2" clear­ance from the top of the pipe. Where the termination cap penetrates a combustible wall, 1" air space clearance is required.
• Have replace and selected vent compo­nents on hand to help determine the exact measurements when elbowing or offsetting. Always use wall restops when penetrating walls and restops when penetrating ceil­ings or attic spaces.
• For installation of replace at elevations of 4000 feet or greater, pay special attention to venting requirement recommendations.
WARNING: Read all instruc-
tions completely and thoroughly before attempting installation.
Failure to do so could result in
serious injury, property damage or loss of life.
NOTICE: Do not seal termination
cap to vent pipe. Cap must be removable for vent inspection and maintenance.
INSTALLATION pRECAUTIONS
• Wear gl oves an d s afety glasse s f or protection
• Use extreme caution when using ladders or when on roof tops
• Be aware of electrical wiring locations in walls and ceilings
The following actions will void the warranty on your venting system:
• Ins ta llati on of an y d am aged ve nt ing component
• Unauthorized modication of the venting sys­tem (Do not cut or alter vent components)
• Installation of any component part not man u fact u red o r app r oved b y FM I
PRODUCTS, LLC
• Installation other than as instructed by these instructions
WARNING: This gas replace and vent assembly must be vented directly to the outside. The venting system must NEVER be attached to a chimney serv­ing a separate solid fuel burning appliance. Each direct vent gas appliance must use a separate vent system. Do not use com­mon vent systems.
WARNING: Vent pipe air space clearances to combus­tibles are 1" on all sides except
on the horizontal sections,
which require 2" clearances from the top of the pipe. Where the termination cap penetrates a combustible wall, 1" air space clearance is required.
NOTICE: Failure to follow these in-
structions will void the warranty.
www.fmiproducts.com
125078-01B10
INSTALLATION pLANNING
(Framing
Detail)
11
1
/2"
11
1
/2" Inside Framing
11
1
/2"
8 1/2"
Ve nt Opening
Combustible Wall
Ve nt Opening
Noncombustible Wall
There are two basic types of direct vent installation:
• Horizontal Termination
• Vertical Termination
Horizontal Termination Installation
IMPORTANT: Horizontal square terminations require only inner portion of wall restop. Hori­zontal installations using round termination require exterior portion of wall restop.
1. Set replace in its desired location and de­termine the route your horizontal venting will take. Do not secure replace until all venting has been installed. Some instal­lations require sliding replace in and out of position to make nal venting connec­tions. Figures 14 and 15 on page 12 show different congurations for venting with horizontal termination that will help you decide which application best suits your installation. Check to see if wall studs or roof rafters are in the path of your desired venting route. If they are, you may want to adjust location of replace.
2. Direct vent pipe sections and components are designed with special twist-lock con­nections.
Twist-Lock procedure: Female ends of
pipes have locking lugs (indentations). These lugs will slide straight into match­ing slots on male ends of adjacent pipes. Push pipe sections together and twist one section clockwise approximately one­quarter turn until sections are fully locked (see Figure 8).
Note: Horizontal runs of vent must be sup-
ported every three feet. Use wall straps for this purpose.
3. Assemble desired combination of pipe and elbows to replace ue collar. If there are long portions of venting run, pre-as­sembled pipe sections may be installed as subassemblies for convenience.
4. Carefully determine location where vent pipe assembly will penetrate outside wall. Center of hole should line up with center line of horizontal vent pipe. Mark wall for
an 11 1/2" x 11 1/2" square hole. Cut and
frame square hole in exterior wall where vent will be terminated. If wall being pen-
125078-01B 11
VENTING INSTALLATION
Continued
etrated is constructed of noncombustible material, such as masonry block or con­crete, a 8 1/2" hole with zero clearance is acceptable (see Figure 9).
vent termination into any wall. This will cause a re hazard.
Figure 8 - Vent Pipe Connections
Figure 9 - Vent Opening Requirements
www.fmiproducts.com
WARNING: Do not recess
Female Locking Lugs
Male Slots
Center of Hole
VENTING INSTALLATION
Continued
5. Noncombustible Exterior Wall: Position horizontal vent cap in center of the 8 1/2" round hole and attach to exterior wall with four wood screws provided. Before attaching vent cap to exterior wall, run a bead of non-hardening mastic (pliable sealant) around outside edges to make a seal between it and outside wall.
Note: Four wood screws provided should
be replaced with appropriate fasteners for stucco, brick, concrete or other types of sidings (see Figure 10).
Combustible Exterior Wall: For vinyl
siding, stucco or wood exteriors, a siding standoff may be installed between vent cap and exterior wall. Siding standoff prevents excessive heat from damaging siding materials. Siding material must be cut to accommodate standoff. Bolt vent cap to standoff. Apply non-hardening mastic around outside edge of standoff. Position standoff/cap assembly in the center of 11 1/2" square hole and attach to exterior wall with provided wood screws (see Figure 11). Siding standoff must sit ush against exterior fascia material.
6. Connecting Vent Cap with Horizontal Vent Pipe: Slide wall restop over vent pipe before connecting horizontal run to vent cap (see Figure 12).
Apply Mastic to All Four Sides
Vent Cap
Wood Screw
Carefully move replace, with vent as-
sembly attached, toward wall and insert vent pipe into horizontal termination. Pipe overlap should be a minimum of 1 1/4" (see Figure 13, page 13).
Slide wall restop against interior wall
surface and attach with screws provided. See Figure 13, page 13, for horizontal termination details.
Place replace into position and shim with
noncombustible material if needed. Nail or screw side anges to framing to secure unit in place. IMPORTANT: Make sure re- place is level before securing. If replace is not level it will not work properly.
Cut Siding Away to Fit Standoff
Standoff
Apply Mastic to All Four Sides
Figure 11 - Installing Siding Standoff
(Combustible Exterior Wall)
Wood Screw
Vent
Cap
Screws
Interior Wall Surface
Wall Firestop
Figure 10 - Installing Horizontal Vent Cap
(Noncombustible Exterior)
www.fmiproducts.com
Vent Cap (Horizontal Termination)
Screw
Figure 12 - Connecting Vent Cap with
Horizontal Vent Pipe
Horizontal Vent Pipe
125078-01B12
VENTING INSTALLATION
Continued
Minimum Pipe
Direct
Vent
Pipe
Maintain 1" Minimum Air Space Around Outer Pipe When Penetrating a Wall
Horizontal Termination Congurations
Figure 14 shows a conguration for venting with horizontal termination with a chart of critical minimum and maximum dimensions which MUST be met.
Overlap
4
11/
Wall Firestop
11 1/2" x 11 1/2"
Framed Opening
Exterior Wall with Vinyl Siding
Figure 13 - Typical Horizontal
Termination Cap Mounting with
Additional Siding Standoff Installed
NOTICE: Do not seal termination
cap to vent pipe. Cap must be removable for vent inspection and maintenance.
WARNING: Never run vent
downward as this may cause
excessive temperatures which could cause a re. Operation of improperly installed and main­tained venting system could result in serious injury, property damage or loss of life.
Siding
Standoff
Screws
High Wind Termination
Apply Mastic to Outside Edge of Standoff
GROUND FLOOR INSTALLATION
Recommended Applications:
• Through the wall using round or square termination
• NOT FOR CORNER INSTALLATION
1' Pipe Min On
Horizontal Run Wall Firestop
Horizontal High Wind Square Termination
64" Min. (42") 61" Min. (36")
(V) Vertical
Minimum
21" 1 ft. 3 ft. 33" 2 ft. 7 ft. 45" 3 ft. 11 ft. 57" 4 ft. 20 ft.
Figure 14 - Horizontal Termination Using
Vertical Termination Installation
Note: Vertical restrictor must be installed in all vertical installations.
1. Determine route your vertical venting will
take. If ceiling joists, roof rafters or other framing will obstruct venting system, con­sider an offset (see Figure 15, page 14) to avoid cutting load bearing members.
Note: Pay special attention to these instal­lation instructions for required clearances (air space) to combustibles when passing through ceilings, walls, roofs, enclosures, attic rafters, etc. Do not pack air spaces with i ns ulation. Also note maximum vertical rise of venting system and any maximum horizontal offset limitations.
H
Required
Vertical Pipe
V + H = 40 feet maximum
H = 20 feet maximum
One 90° Elbow
90° Elbow
V + 90· Elbow
1 ft. Min Before Elbow
(H) Horizontal
Maximum
125078-01B 13
www.fmiproducts.com
VENTING INSTALLATION
Continued
2. Set replace in desired location. Drop a plumb line down from ceiling to position of replace exit ue. Mark center point where vent will penetrate ceiling. Drill a small locating hole at this point.
3. Drop a plumb line from inside of roof to locating hole in ceiling. Mark center point where vent will penetrate roof. Drill a small locating hole at this point.
Roof Flashing
Wall Strap
45° Elbow
Ceiling Firestop
Figure 15 - Offset with Wall Strap and 45°
Elbows
Flat Ceiling Installation
1. Cut a 11 1/2" square hole in ceiling using locating hole as a center point. Opening should be framed to 11 1/2" x 11 1/2" inside dimensions, as shown in Figure 8 on page 9 using framing lumber the same size as ceiling joists. If area above ceiling is an insulated ceiling or an attic, nail restop from top side. This prevents loose insula­tion from falling into required clearance space. If area above ceiling is a living space, install restop below framed hole. Firestop should be installed with no less than three nails per side (see Figure 15).
2. Assemble desired lengths of pipe and elbows necessary to reach from replace ue up through restop. Be sure all pipe and elbow connections are fully twist­locked (see Figure 8, page 11).
3. Cut a hole in the roof using locating hole as a center point. (Cover any exposed
www.fmiproducts.com
open vent pipes before cutting hole in roof.) The 11 1/2" x 11 1/2" hole must be measured on the horizontal; actual length may be larger depending on pitch of roof. There must be a 1" clearance from vent pipe to combustible materials. Frame opening as shown in Figure 9, page 11.
4. Connect a section of pipe and extend up through hole.
Note: If an offset is needed to avoid
obstructions, you must support vent pipe every 3 feet. Use wall straps for this pur­pose (see Figure 15). Whenever possible, use 45° elbows instead of 90° elbows. The
45° elbow offers less restriction to the ow of ue gases.
5. Place ashing over pipe section(s) ex­tending through roof. Secure base of ashing to roof and framing with roong nails. Be sure roong material overlaps top edge of ashing as shown in Figure
15. There must be a 1" clearance from vent pipe to combustible materials.
6. Continue to add pipe sections until height of vent cap meets the minimum building code requirements described in Figure 7 on page 8.
Note: You must increase vent height for
steep roof pitches. Nearby trees, adjoining
rooines, steep pitched roofs and other
similar factors may cause poor draft or down-drafting in high winds. Increasing vent height may solve this problem.
7. Twist-lock vent cap onto last section of vent pipe.
Vent Termination Chart
Minimum Height
Roof pitch Feet Min.
Flat to 6/12 1
6/12 to 7/12 1.25 Over 7/12 to 8/12 1.5 Over 8/12 to 9/12 2
Over 9/12 to 10/12 2.5 Over 10/12 to 11/12 3.25 Over 11/12 to 12/12 4 Over 12/12 to 14/12 5 Over 14/12 to 16/12 6 Over 16/12 to 18/12 7 Over 18/12 to 20/12 7.5 Over 20/12 to 21/12 8.0
125078-01B14
VENTING INSTALLATION
Continued
Note: If vent pipe passes through any occupied ar-
eas above rst oor, including storage spaces and
closets, you must enclose pipe. You may frame and sheetrock enclosure with standard construc­tion material. Make sure and meet the minimum
allowable clearances to combustibles. Do not ll
any required air spaces with insulation.
Vertical Termination Congurations
Figure 17 shows the congurations for vertical termination.
If area above is an attic or insulated area,
install restop above framed hole.
If area above is a living space, install
restop below framed hole.
Figure 16 - Installing Firestop
Vertical Venting
V = 40' max.
Figure 17 - Vertical Venting Conguration
125078-01B 15
www.fmiproducts.com
HIGH ALTITUDE INSTALLATION
Your F MI PROD UC TS, LLC d ir ect ven t replace has been tested and approved for elevations from 0-2000 feet.
Fireplaces for high altitude (-HA Models) are for installations above 4,000 feet only. These replaces are equipped with parts specic for higher altitudes.
When installing a non-high altitude replace at an elevation above 2000 feet, you may need to decrease the input rating by changing the existing burner orice to a smaller size. Reduce input 4% for each 1000 feet above sea level. Check with your local gas company for proper orice size identication.
When installing this replace at an elevation above 4500 feet, check with local authorities.
PARTS LIST FOR VENTING KITS
AND COMpONENTS
FMI (5/8") Pipe & Vent Kits Number Description
P58-6 6" Section Double Wall Pipe,
Galvanized
P58-12 12" Section Double Wall Pipe,
Galvanized
P58-24 24" Section Double Wall Pipe,
Galvanized
P58-36 36" Section Double Wall Pipe,
Galvanized
P58-48 48" Section Double Wall Pipe,
Galvanized
PA58-712 Adjustable 7"-12" Section Double
Wall Pipe, Galvanized E58-45 45° Elbow, Galvanized E58-90 90° Elbow, Galvanized HTS-58 Horizontal Square Termination,
Galvanized HHT-58 High Wind Round Termination, Galvanized VT-58 Vertical Round Termination,
Galvanized SC-58 Storm Collar, Galvanized WF-58 Wall Firestop, Galvanized RF-58-6 Roof Flashing - 0 to 6/12 Pitch,
Galvanized RF-58-12 Roof Flashing - 6/12 to 12/12 Pitch,
Galvanized VR-58 Vertical Restrictor, Galvanized S-58 Vinyl Siding Standoff, Galvanized WS-58 Wall Strap CS-58 Cathedral Ceiling Support FP-58 Firestop Plate SF-58 Stucco Flashing - For use with
HTS-58 RF-58 Flat Roof Flashing
FIREPLACE INSTALLATION
CHECK GAS TYPE
Use proper gas type for the replace unit you are installing. If you have conicting gas types, do not install replace. See retailer where you purchased the replace for proper replace according to your gas type.
INSTALLING GAS pIpING TO FIREpLACE LOCATION
WA RNING: A qual i fied service person must connect replace to gas supply. Follow all local codes.
CAUTION: For propane/LP units, never connect replace di­rectly to the propane/LP supply. This heater requires an external regulator (not supplied). Install the external regulator between the replace and propane/LP supply.
WARN I NG: F or nat ural
gas, never connect replace to private (non-utility) gas wells. This gas is commonly known as wellhead gas.
Installation Items Needed
Before installing replace, make sure you have the items listed below.
• external regulator (supplied by installer)
• piping (check local codes)
• sealant (resistant to propane/LP gas)
• equipment shutoff valve *
• test gauge connection *
• sediment trap
• tee joint
• pipe wrench
• approved exible gas line with gas connec­tor (if allowed by local codes)
* An equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the equipment shutoff valve from your retailer.
For propane/LP connection only, the installer must supply an external regulator. The exter­nal regulator will reduce incoming gas pres­sure. You must reduce incoming gas pressure to between 11" and 14" of w.c. pressure. If you do not reduce incoming gas pressure, replace regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure 18. Pointing the vent down protects it from freezing rain or sleet.
CAUTION: Use only new,
black iron or steel pipe. Inter­nally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diameter or greater to allow proper gas volume to replace. If pipe is too small, undue loss of volume will occur.
Installation must include an equipment shutoff valve, union and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from replace (see Figure 19, page 17).
IMPORTANT: Install main gas valve (equip­ment shutoff valve) in an accessible location. The main gas valve is for turning on or shutting off the gas to the appliance.
External Regulator
Propane/LP Supply Tank
Figure 18 - External Regulator with Vent
Pointing Down (Propane/LP Only)
with Vent Pointing Down
www.fmiproducts.com
125078-01B16
FIREPLACE INSTALLATION
IN
PILOT
IN
OUT
VENT
TH
TP
TH
TP
Continued
Check your building codes for any special requirements for locating equipment shutoff valve to replaces.
Apply pipe joint sealant lightly to male NPT threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged replace valves.
Equipment Shutoff Valve with 1/8" NPT Tap*
Approved Flexible Gas Line
3" Minimum
Cap Pipe Tee Joint Nipple
Sediment Trap/
Figure 19 - Gas Connection
* The equipment shutoff valve may be sup­plied with the appliance or you can purchase it from your retailer.
Natural - From Gas Meter (5.5" W.C. to 10.5" W.C. Pressure) Propane/LP From External Regulator (11" W.C. to 14" W.C. Pressure)
Drip Leg
WARNING: Use pipe joint sealant that is resistant to liquid petroleum (LP) gas.
We recommend that you install a sediment trap/drip leg in supply line as shown in Figure
19. Locate sediment trap/drip leg where it is within reach for cleaning. Install in piping sys­tem between fuel supply and replace. Locate sediment trap/drip leg where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into replace gas controls. If sedi­ment trap/drip leg is not installed or is installed wrong, replace may not run properly.
CONNECTING FIREpLACE TO GAS SUppLY
Installation Items Needed
• 5/16" hex socket wrench or nut-driver
• sealant (resistant to propane/LP gas, not provided)
1. Route exible gas line (provided by in-
staller) from equipment shutoff valve to replace. Route exible gas supply line through one of the access holes on side of replace.
2. Attach exible gas line from gas supply to
control valve (see Figure 20).
3. Check all gas connections for leaks. See
Checking Gas Connections, page 18.
Red Surface Indicates For
Propane/LP Use Only Gas Shutoff Valve
Flexible Gas Line Do NOT Kink
Pilot Adjustment
Outlet Pressure Tap
1/2" NPT Incoming Gas Line
Note:
1) Wire connections not shown for clarity
Inlet Pressure Tap
2) * 1/8" NPT Plugged Tapping
Figure 20 - Connecting Incoming Gas Line to Flex Gas Line
125078-01B 17
www.fmiproducts.com
FIREPLACE INSTALLATION
Continued
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections, internal and external to unit, for leaks after
installing or servicing. Correct all leaks at once.
WARNING: Never use an
open ame to check for a leak. Apply noncorrosive leak detec­tion uid to all joints. Bubbles forming show a leak. Correct all leaks at once.
pRESSURE TESTING GAS SUppLY pIpING SYSTEM
Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)
1. Disconnect replace and its individual equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig (3.5 kPa) will damage replace gas regulator.
2. Cap off open end of gas pipe where equip­ment shutoff valve was connected.
3. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas replace or opening main gas valve located on or near gas meter for natural gas replace or using compressed air.
4. Check all joints of gas supply piping sys­tem. Apply noncorrosive leak detection uid to all joints. Bubbles forming show a leak. Correct all leaks at once.
5. Reconnec t fireplace and e qu ip me nt shutoff valve to gas supply. Check recon­nected ttings for leaks.
Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Fig­ure 21).
2. Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas replace or opening main gas valve located on or near gas meter for natural gas replace or using compressed air.
www.fmiproducts.com
3. Check all joints from propane/LP supply tank or gas meter to equipment shutoff valve (see Figure 22 or Figure 23). Apply noncorrosive leak detection uid to all joints. Bubbles forming show a leak.
4. Correct all leaks at once.
Equipment Shutoff Valve
Figure 21 - Equipment Shutoff Valve
Equipment Shutoff Valve
Propane/LP Supply Tank
Figure 22 - Checking Gas Joints for
Propane/LP Gas Fireplace
Equipment Shutoff Valve
Gas Meter
Figure 23 - Checking Gas Joints for
Natural Gas Fireplace
pRESSURE TESTING FIREpLACE GAS CONNECTIONS
1. Open equipment shutoff valve (see Fig­ure 21).
2. Open propane/LP supply tank valve for propane/LP replace or main gas valve located on or near gas meter for natural gas replace.
Open
Closed
Gas Valve
Gas Valve
125078-01B18
FIREPLACE INSTALLATION
Continued
3. Make sure control knob of replace is in the OFF position.
4. Check all joints from equipment shutoff valve to gas valve (see Figure 22 or Figure 23, page 18). Apply noncorrosive leak detection uid to all joints. Bubbles forming show a leak. Correct all leaks at once.
5. Light replace (see Operation, page 22). Check all other internal joints for leaks.
6. Turn off replace (see To Turn Off Gas to Appliance, page 23).
REMOVING/REPLACING GLASS
DOOR
CAUTION: Do not operate this replace with a broken glass door panel or without the glass door panel securely in place. For replacement part informa-
tion see Replacement Parts,
page 36.
CAUTION: Wear gloves and safety glasses while handling or re mov ing broken glass. Do not remove if glass is hot. Keep children and pets away from glass.
WARNING: If replace has been running, turn off replace. Let cool before removing glass doors.
Removing Glass Door
If replacement of glass is necessary, the entire frame assembly must be replaced. Gloves must be worn when removing/replacing glass door. If glass is broken tape remaining glass onto frame before removing.
1. Remove screens if installed.
2. Open bottom access panel.
3. Unlo ck 2 door l atches on bottom of rebox.
4. Tilt open glass door 45° from the bottom of rebox and lift up to release door from rebox top retainer (see Figure 24).
Door Retainer
Glass Door
Door Latches
Figure 24 - Removing/Replacing Door
Replacing Glass Door
1. Position door frame in front of rebox opening with bottom of door tilted away from rebox (see Figure 24).
2. Hook top ange of door frame over top of rebox frame.
3. Secure 2 bottom door latches.
Bottom Access Panel
125078-01B 19
www.fmiproducts.com
FIREPLACE INSTALLATION
Continued
LAVA ROCK, DECORATIVE GRATE, EMBER FLAKES AND SCRAP LOG
INSTALLATION
Lava rock, ember akes and scrap log pieces are included with your replace. Install these items while glass doors are open and/or removed.
1. Follow instructions from Removing/Re- placing Glass Door, page 19, to move glass out of the way of this installation.
2. For 36" models only, install 3 loose logs by placing log #1, log #2 and log #3 onto one piece log as shown in Figure 25.
3. Place lava rock around base of burner. Make sure burner ports are not covered (see Figure 26).
4. Place ember akes around front and sides of burner and on burner ports (see Figure 27). This will create the glowing ember appearance as the ame touches the ember akes. Do not block burner ports or pilot ports by overlapping ember akes in one area. It is not necessary to use all ember material provided.
5. Place scrap log pieces randomly behind grate as shown in Figure 28 on lava rock and around (but not on) burner ports.
6. Place grate in front of logs as shown in Figure 28. Be sure grate is balanced so it does not fall or lean onto logs. Grate does not attach to hearth assembly.
Log #3
Log #2
Log #1
Lava Rock
Figure 26 - Installing Lava Rock
Ember Flakes
Figure 27 - Installing Ember Flakes
Figure 25 - Installing Loose Logs
www.fmiproducts.com
Scrap Log Pieces
Figure 28 - Installing Scrap Log Pieces
REMOVING LOGSET/BURNER
MODULE
Connecting and Disconnecting Gas Line
WARNING: A qualied ser­vice person must connect and disconnect replace with gas supply. Follow all local codes.
1. Using a 5/16" hex socket wrench or nut­driver, connect or disconnect exible gas line and control valve (see Figure 29, page 21).
2. After connecting gas line to control valve, always test for leaks.
125078-01B20
FIREPLACE INSTALLATION
Continued
WARNING: Never use an
open ame to check for a leak. Apply noncorrosive leak de­tection uid to joints. Bubbles forming show a leak. Correct leaks at once.
Burner Base
Log Assembly
CAUTION: The gas supply
Spacers
shall be shut off prior to discon­necting the electrical power, if any, before proceeding with this installation.
CAUTION: Use gloves when removing the log set/burner module from your rebox. Some metal edges may be sharp. Use caution with log sets as logs are fragile.
1. Remove glass door (see page 19).
2. Remove grate and all oor media (see page 20).
3. Carefully lift and remove 3 hearth refrac­tories from replace.
4. Remove 3 spacers from rebox bottom (see Figure 30).
5. For 36" models only, remove 3 loose logs from log set (see Figure 25 page 20).
6. Remove 9 screws from front and sides of rebox burner base. Lift entire base from unit by pulling forward to disengage from rear ange and then lifting up (see Figure 30).
7. If needed, replace burner gasket before reinstalling log set/burner module (see replacement parts list on page 36.)
To Gas Supply (Natural)
To External Regulator (Propane/LP)
Flexible Gas Line, Do NOT Kink
Figure 29 - Connecting/Disconnecting
Gas Line to Millivolt Valve
125078-01B 21
Equipment Shutoff Valve
Millivolt Control Valve
www.fmiproducts.com
Battery Housing Cover
Firebox Bottom
Figure 30 - Removing/Installing Burner Base
Screws
INSTALLING BATTERIES IN WIRELESS HAND-HELD REMOTE
CONTROL AND RECEIVER
Installing Batteries in Remote Receiver
1. Open bottom access door.
2. Remove switch plate from receiver (see Figure 31).
3. Remove battery housing cover on remote receiver to expose battery housing (see Figure 31).
4. Install 4 AA batteries into housing follow­ing positive and negative directions on battery housing cover removed in step 3 (see Figure 31).
5. Replace battery housing cover and switch plate.
6. Install 2 D batteries into AC backup battery pack.
7. Close bottom access door.
Remote Receiver
AA
Batteries
Screws
Switch
D Batteries
Plate
Figure 31 - Installing Receiver Batteries
(Included)
Battery Housing
AC Backup Battery Pack
FIREPLACE INSTALLATION
Continued
Installing Batteries in Hand-Held Remote
Control Unit
1. Remove battery cover on back of remote control unit.
Remote Control
Unit
2. Install 3 AAA batteries as instructed in battery housing.
3. Replace battery cover onto remote control unit.
Battery Cover
AAA
Batteries
Figure 32 - Installing Battery in Hand-Held Remote Control Unit
(use only alkaline batteries, not included)
OPERATION
FOR YOUR SAFETY
READ BEFORE LIGHTING
WARNING: If you do not fol-
low these instructions exactly,
a re or explosion may result causing property damage, per­sonal injury or loss of life.
A. This appliance is equipped with an igni-
tion device which automatically lights the pilot. Do not light pilot by hand.
B. BEFORE LIGHTING smell all around
the appliance area for gas. Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electric switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
Battery Housing
C. Do not use this appliance if any part
has been under water. Immediately call a qualied service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
LIGHTING
INSTRUCTIONS
NOTICE: During initial operation of new replace, burning logs will give off a paper-burning smell. Orange ame will also be present. Open damper or window to vent smell. This will only last a few hours.
1. STOP! Read the safety information in column 1.
2. Turn off all electric power to replace.
3. Turn safety shutoff switch to the OFF position.
4. Remove center brick/control cover.
www.fmiproducts.com
125078-01B22
OPERATION
IN
PILOT
IN
OUT
VENT
TH
TP
TH
TP
Continued
5. Turn equipment shutoff valve clockwise to the OFF position (see Figure
33). Do not force.
6. Wait ve (5) minutes to clear out any gas.
Then smell for gas, including near the oor. If you smell gas, STOP! Follow “B” in the safety information page 22. If you don't smell gas, go to the next step.
7. Turn equipment shutoff valve counter-
clockwise to the ON position. Do not force.
8. Replace center brick/control cover.
9. Turn on all electric power to appliance.
10. Turn safety shutoff switch to the ON
position.
11. Visually locate pilot. Ignitor should begin
to spark and main burner should ignite once ame appears at pilot.
• If lighting appliance for the rst time each season, it may take several attempts before supply gas can reach pilot and main burners.
• If appliance will not stay lit after several attempts, follow instructions under To Turn Off Gas To Appliance and call your
service technician or gas supplier.
TO TURN OFF GAS
TO AppLIANCE
1. Turn off safety shutoff switch.
2. Turn off all electric power to appliance if service is to be performed.
3. Remove center brick/control cover.
4. Turn equipment shutoff valve clockwise
to OFF. Do not force.
5. Replace center brick/control cover.
REMOTE
OpERATION
1. Turn equipment shutoff valve to ON posi­tion. You can now turn the burner on and off with hand-held remote control unit.
IMPORTANT: Be sure to press ON/OFF
buttons on hand-held remote control unit for up to 3 seconds to assure proper operation.
2. Press ON/OFF button to turn burner on and off.
Equipment Shutoff Valve
Figure 33 - Turning Equipment Shutoff Valve to the OFF Position
Ignitor
Pilot
Sensing Rod
Burner
Figure 34 - Pilot
125078-01B 23
www.fmiproducts.com
INSPECTING BURNERS
Check pilot ame pattern and burner ame patterns often.
pILOT ASSEMBLY
The pilot assembly is factory preset for the proper ame. Alterations may have occurred during shipping and handling. The pilot is located on right hand side of burner.
The ame must envelope 1/4" of top of the ignitor/sensor and grounding stem.
If your pilot assembly does not meet these requirements:
• Turn the adjustment screw marked PILOT clockwise to decrease or counterclockwise to increase the ame to proper size (see Figure 33, page 23). Do not remove the adjustment screw.
• see Troubleshooting, page 26
Sensing
Rod
Ignitor/ Sensor
Pilot Burner
BURNER FLAME pATTERN
Burner ames will be steady, not lifting or oat­ing. Flame patterns will be different from unit to unit and will vary depending on installation type and weather conditions.
If the vent conguration is installed incorrectly, ames will lift or "ghost". This can be danger­ous. Inspect ames after installation to ensure proper installation and performance.
Figure 36 shows a typical ame pattern. If burner ame pattern differs from that de-
scribed:
• turn replace off (see To Turn Off Gas to Appliance, page 23)
• see Troubleshooting, page 26
Figure 36 - Typical Flame Pattern
Figure 35 - Correct Pilot Flame Pattern
CLEANING AND MAINTENANCE
WARNING: Turn off replace
and let cool before cleaning.
CAUTION: You must keep control areas, burners and circulating air passageways of replace clean. Inspect these areas of replace before each use. Have replace inspected yearly by a qualied service person. Fireplace may need more frequent cleaning due to excessive lint from carpeting, bedding material, pet hair, etc.
www.fmiproducts.com
GLASS DOORS
WARNING: Handle glass door panels with care. Do not strike, slam or otherwise abuse glass. Do not operate replace with the glass door unlatched, removed, cracked or broken.
WARNING: Do not use
abrasive cleaners as this may damage glass. Use a nonabra­sive household glass cleaner to clean glass. Do not clean glass when hot.
125078-01B24
CLEANING AND MAINTENANCE
Continued
Glass must be cleaned periodically. During start-up it is normal for condensation to form on the inside of the glass causing lint, dust and other airborne particles to cling to the glass surface. During initial start-up a slight lm may form on the glass due to paint curing. The glass should be cleaned several times with a non-ammonia, nonabrasive household clean­er and warm water after the rst two weeks of operation. Thereafter, clean the glass two or three times during each heating season, depending on the usage and circumstances present. Refer to Removing/Replacing Glass Door, page 19 of this manual when removing glass door for cleaning.
WARNING: Only parts sup­pli ed by the m anufa cture r should be used when replacing broken or damaged glass door panels (see Replacement Parts, page 36). Glass door panel are complete units. No substitute materials may be used.
CAUTION: Wear gloves and safety glasses while handling or removing broken glass. Do not remove if glass is hot. Keep children and pets away from glass.
If glass has been broken, carefully remove glass door (see Removing/Replacing Glass Door, page 19). Vacuum all glass pieces with a shop vac.
CAUTION: Do not vacuum if
pieces are hot.
Use only glass door replacement intended for this replace (see Replacement Parts, page 36 for detail on ordering). No substitutions may be made. See Removing/Replacing Glass Door, page 19 for instructions for re­placing glass doors.
WARNING: Do not operate
replace with glass door un-
latched, removed, cracked or
broken.
pILOT AND BURNERS
• Remove material before cleaning burners and replace when cleaning is complete.
• Burner and controls should be cleaned with compressed air to remove dust, dirt or lint.
• Use a vacuum cleaner or small, soft bristled brush to remove excess dust, dirt or lint.
LOGS
• Use a vacuum cleaner to remove any carbon buildup on logs.
• Replace material periodically as needed. See Replacement Parts, page 36.
VENTING SYSTEM
Conduct annual inspection of the venting system following these guidelines:
1. Check areas of venting system that are
exposed to the weather for corrosion (rust spots or streaks and, in extreme cases, holes). Have these items replaced im­mediately by a qualied service person.
2. Remove the vent cap and shine a ash-
light into the vent. Remove any foreign material.
3. Check for evidence of excessive con-
densation. Continuous condensation can cause corrosion of caps, pipes and ttings and can be caused by having excessive lateral runs, too many elbows or exterior portions of the system being exposed to cold weather.
4. Inspect joints to verify that no pipe section
or tting has been disturbed and loos­ened. Check mechanical supports such as wall straps for rigidity.
125078-01B 25
www.fmiproducts.com
TROUBLESHOOTING
WARNING: Turn off replace and let cool before servicing. Only
a qualied service person should service and repair replace.
CAUTION: Never use a wire, needle or similar object to clean
pilot. This can damage pilot unit.
Note: All troubleshooting items are listed in order of operation.
OBSERVED PROBLEM
Ignitor will not spark or pilot will not light
pOSSIBLE CAUSE
1. No gas supply or shutoff valve is OFF
2. Air in gas line
3. Construction debris clog­ging pilot orice
4. Low gas pressure
5. Kinked pilot line
6.
Control valve is not opening
7. No power to unit or ignition module or power trans­former is bad
REMEDY
1. Check to see if you have gas supply and that equipment shutoff valve is opened
2. Repeat lighting procedure several times to purge all air out of lines. If after re­peated attempts appliance does not light, call for quali­ed service and repair
3. Remove debris and dirt, inspect and clean any other possible obstructions
4. Contact your gas supplier to check pressure
5. Have a qualied technician replace pilot line
6. Replace control valve (Re­fer to Replacement Parts, page 36)
7. Check that main power is on and that all wire connec­tions are made correctly to ignition model (see Wiring Diagram, page 29). Check for 24 VAC at the second­ary side of transformer. If 24 VAC is present and module does n ot o pe rate, hav e module replaced. Other­wise have transformer re­placed
www.fmiproducts.com
125078-01B26
OBSERVED PROBLEM
Pilot will not stay lit
TROUBLESHOOTING
Continued
pOSSIBLE CAUSE
1. Loose wiring on ignitor wire to ignition module and/ or poor ground to ignition module
2. Pil o t fla m e too l ow to
sense
REMEDY
1. Check wiring connection. Refer to wiring diag ram (see Wiring Diagram, page
29) and/or check ground wire to ignition module
2. Clean and adjust pilot burn­er and check gas supply and inlet pressure to unit
Not e: Ha v e a qua l if i ed
te ch ni cian replace pilot assembly if broken or cor­roded
No gas to burner, although safety shutoff switch and valve are set to the ON position
Frequent pilot outage
Fireplace produces a clicking/ ticking noise just after burner is lit or shut off
Slight smoke or odor during initial operation
1. Safety shutoff switch wires defective or too long
1. Pilot ame may be too low, causing safety pilot to “drop out”
2. Improper venting or exces­sive blockage
1. Met al expa n din g wh ile heating or contracting while cooling
1. Residues from manufac­turing processes and logs curing
1. Check electrical connec­tions
1. Clean and adjust pilot ame for maximum flame im­pingement on thermopile
2. Have vent system inspect­ed, including termination cap. Remove any restriction or obstruction
1. This is normal with most replaces. If noise is ex­cessive, contact qualied service person
1. Problem will stop after a few hours of operation
125078-01B 27
www.fmiproducts.com
TROUBLESHOOTING
Continued
WARNING: If you smell gas
• Shut off gas supply.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Fol­low the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
OBSERVED PROBLEM
Gas odor even when gas control valve is off
Gas odor during combustion
Glass soots
Dark residue on logs or inside of replace
pOSSIBLE CAUSE
1. Gas leak . See Warning
statement at top of page
2. Control valve defective
1. Foreign matter betwee n control valve and burner
2. Gas leak . See Warning
statement at top of page
1. Debris around burner air mixer
2. Improper vent conguration
1. Air holes at b urner inle t blocked
2. Burner ame holes blocked
3. Improper venting or exces­sive blockage
4. Excessive amounts of em­bers and pan material
REMEDY
1. Locate and correct all leaks
(see Checking Gas Con­nections, page 18)
2. Replace control valve
1. Take apart gas tubing and remove foreign matter
2. Locate and correct all leaks
(see Checking Gas Con­nections, page 18)
1. Inspect opening at base of burner to see that it is NOT packed with any type of material
2. Check vent configuration specication (see Venting Installation, page 10)
1. Clean out air holes at burn­er inlets. Periodically repeat
as needed
2. Remove blockage
3. Have vent system inspect­ed, including termination cap. Remove any restric­tions or obstruction
4. Clear excess embers until a mi ni mum gap of 1/ 2" remains under grate
www.fmiproducts.com
125078-01B28
SPECIFICATIONS
CONTROL MODULE
BATTERY
RELAY
BATTERY PACK
REMOTE
RECIEVER
VA LV E
THTP
TP
TH
Red
Bk
"D"
SIZE
"D"
SIZE
Bn
4 "AA" SIZE
BATTERY
RedBuYlBu BkOgGn
Yl GnBn BkOgBkBk Bn
Bu
Bu
TO J-BOX
ADAPTER
IS
PILOT CONNECTORS
Bk
Red
I
S
(V)DVF36NS, (V)DVF36NH
• Rating: 33,500 Btu/hr
• Gas Type: Natural Gas Only
• Ignition: Electronic
• Manifold Pressure: 3.5" w.c.
• Minimum Inlet Supply Pressure: 5" w.c.
• Maximum Inlet Supply Pressure: 10.5" w.c.
• Front Orice: #47
• Rear Orice: #47
(V)DVF42NS, (V)DVF42NH
• Rating: 41,000 Btu/hr
• Gas Type: Natural Gas Only
• Ignition: Electronic
• Manifold Pressure: 3.5" w.c.
• Minimum Inlet Supply Pressure: 5" w.c.
• Maximum Inlet Supply Pressure: 10.5" w.c.
• Front Orice: #42
• Rear Orice: #44
(V)DVF36PS, (V)DVF36PH
• Rating: 31,000 Btu/hr
• Gas Type: Propane/LP Gas Only
• Ignition: Electronic
• Manifold Pressure: 10" w.c.
• Minimum Inlet Supply Pressure: 11" w.c.
• Maximum Inlet Supply Pressure: 13" w.c.
• Front Orice: #56
• Rear Orice: #56
(V)DVF42PS, (V)DVF42PH
• Rating: 37,000 Btu/hr
• Gas Type: Propane/LP Gas Only
• Ignition: Electronic
• Manifold Pressure: 10.0" w.c.
• Minimum Inlet Supply Pressure: 11" w.c.
• Maximum Inlet Supply Pressure: 13" w.c.
• Front Orice: #56
• Rear Orice: #55
DVF36NS-HA, DVF36NH-HA
• Rating: 33,500 Btu/hr
• Gas Type: Natural Gas Only
• Ignition: Electronic
• Manifold Pressure: 3.8" w.c.
• Minimum Inlet Supply Pressure: 5" w.c.
• Maximum Inlet Supply Pressure: 10.5" w.c.
• Front Orice: #47
• Rear Orice: #47
DVF42NS-HA, DVF42NH-HA
• Rating: 41,000 Btu/hr
• Gas Type: Natural Gas Only
• Ignition: Electronic
• Manifold Pressure: 3.8" w.c.
• Minimum Inlet Supply Pressure: 5" w.c.
• Maximum Inlet Supply Pressure: 10.5" w.c.
• Front Orice: #42
• Rear Orice: #44
WIRING DIAGRAM
www.fmiproducts.com
125078-01B 29
PARTS
1
2
3
8
32
32
33(36") 32(42")
8
9
10
11
17
22
25
26
27
7
4
5
12
16
18
19
20
29
31
30
23
24
28
21
13
14
15
6
34
35
36
MODELS (V)DVF36NS, (V)DVF36PS, (V)DVF36NH, (V)DVF36PH, DVF-36NS­HA, DVF36NH-HA, (V)DVF42NS, (V)DVF42PS, (V)DVF42NH, (V)DVF42PH, DVF-42NS-HA, AND DVF42NH-HA
www.fmiproducts.com
125078-01B30
This list contains replaceable parts used in your replace. When ordering parts, follow the
PARTS
instructions listed under Replacement Parts on page 36 of this manual.
KEY NO. PART NO. DESCRIpTION qTY.
1 122653-01 Door Assembly, 36" • • 1
122653-02 Door Assembly, 42" • • 1
2 122950-02 Bottom Door Assembly, 36" • • 1
122950-01 Bottom Door Assembly, 42" • • 1
3 121301-01 Face Assembly, 36" • • 1
121301-02 Face Assembly, 42" • • 1
4 122952-02 Screen Door Kit, 36" • • 1
122952-01 Screen Door Kit, 42" • • 1 5 ** Firebox Face • • • • 1 6 122842-03 Hearth Assembly, 36" NG 1
122842-04 Hearth Assembly, 36" Propane/LP 1
122842-01 Hearth Assembly, 42" NG 1
122842-02 Hearth Assembly, 42" Propane/LP 1
123781-01 Hearth Assembly, 36" NG, High Altitude 1
123781-02 Hearth Assembly, 42" NG, High Altitude 1 7 123210-01 Grate, 36" • • 1
123210-02 Grate, 42" • • 1 8 122652-01 Door Latch • • • • 2 9 ** Firebox Leg • • • • 4 10 ** Firebox Bottom • • • • 1 11 121431-01 Gasket, 36" 1
111913-02 Gasket, 42" • • 1 12 122919-01 Draft Diverter • • • • • • 1 13 ** Air Exchange • • • • 1 14 ** 5" Gasket • • • • 1 15 ** 5" Inner Connector • • • • 1 16 ** A/E Insulation • • • • 1 17 ** Firebox Surround • • • • 1 18 ** Firebox Top • • • • 1 19 ** Relief Assembly • • • • 2 20 ** Relief Bracket • • • • • • 4 21 ** Top Plenum • • 1 22 ** Rear Plenum • • 1 23 ** 5" Gasket • • • • 1 24 ** Connector, 8" x 3.25" • • • • • 1 25 121295-01 36" Fireplace Surround 1
121302-01 42" Fireplace Surround • • 1 26 110037-01 Electrical Duct Assembly • • • • 1 27 117891-01 Fireplace Handle • • • • 4 28 120520-01 Refractory Retainer • • • • 3 29 20280 Top Spacer • • • • 4 30 ** Top Insulation • • • • 1 31 ** Fireplace Top • • 1 32 ** Hearth Side Spacer • • • • 2,3 33 ** Hearth Front Spacer • • 1 34 123182-01 Log #1 • • 1 35 123181-01 Log #2 • • 1 36 123211-01 Log #3 • • 1
**Not a eld replaceable part.
(V)DVF36P(H,S)
(V)DVF36N(H,S)
(V)DVF42P(H,S)
(V)DVF42N(H,S)
DVF36N(H,S)-HA
DVF42N(H,S)-HA
125078-01B 31
www.fmiproducts.com
PARTS
8
15
1
2
3
4
5
7
24
6
9
4
5
10
16
14
12
13
17
25
13
11
18
19
22
23
20
21
BURNER ASSEMBLY MODELS (V)DVF36NS, (V)DVF36PS, (V)DVF36NH, (V) DVF36PH, DVF-36NS-HA, DVF36NH-HA, (V)DVF42NS, (V)DVF42PS, (V) DVF42NH, (V)DVF42PH, DVF-42NS-HA, AND DVF42NH-HA
www.fmiproducts.com
125078-01B32
PARTS
BURNER ASSEMBLY
This list contains replaceable parts used in your replace. When ordering parts, follow the instructions listed under Replacement Parts on page 36 of this manual.
KEY NO. PART NO. DESCRIpTION QTY.
1 122839-02 Burner Tube, 36" • • 1
122839-01 Burner Tube, 42" • • 1 2 ** Front Burner Assembly • • • • • 1 3 112371-15 Rear Orice, #47 NG 1
23100 Rear Orice, #56 Propane/LP 1
23101 Rear Orice, #44 NG 1
23567 Rear Orice, #55 Propane/LP 1 4 11214 Bulkhead Fitting • • • • • 2 5 116573-01 Washer, Flt 7/8"x11/4" OD • • • • • 5 6 ** Log/Burner Base • • • • • • 1 7 122122-01 Pilot, NG 1
122122-02 Pilot, Propane/LP 1
123783-01 Pilot, NG High Altitude 1 8 ** Pilot Shield • • • • • 1 9 14296 Elbow, Street 3/8" • • • • • 1 10 112371-15 Front Orice, #47 NG 1
23100 Front Orice, #56 Propane/LP 1
24771 Front Orice, #42 NG 1
23100 Front Orice, #56 Propane/LP 1 11 ** Base • • • • • • 1 12 114027-01 Grommet SC 1/2" ID 1 1/16" OD • • • • • 1 13 14399 90° Elbow, Brass 3/8" Tube x 3/8" NPT • • • • • • 2 14 111817-06 Flextube Dormont, 3/8" Dia. x 11" • • • • • 1 15 111817-09 Flextube Dormont, 3/8" Dia. x 24" • • • • • 1 16 ** Pilot Bracket • • • • • 1 17 122116-01 Dexen Valve, NG 1
122117-01 Dexen Valve, LP 1
123782-01 Dexen Valve, NG High Altitude 3.8" 1 18 112823-01 Brass T-Fitting 3/8" • • • • • • 1 19 122118-01 Control Module • • • • • 1 20 122119-01 Battery Relay • • • • • 1 21 122121-01 Battery Pack • • • • • • 1 22 122860-01 Valve Bracket • • • • • 1 23 120066-01 Remote Receiver • • • • • • 1 24 ** Log Assembly, 36" • • 1
** Log Assembly, 42" • • 1
25 123560-01 Base Valve • • • • • 1
122120-01 Wire Harness Relay • • • • 1
PARTS AVAILABLE NOT SHOWN
122123-01 AC Adapter 3V • • • 1
112799-01 Ember Flakes Kit • • • • 1
26839 Rockwool • • • • 1
GA6060 Lave Rock Kit • • 1
VTA-LS5-2 Log Scrap Kit • • • • 1
120065-01 Hand-Held Remote Transmitter • • • • 1
14253 30" Flex Line • • • 1
125078-01B 33
www.fmiproducts.com
(V) DVF36P(H,S)
(V)DVF36N(H,S)
(V)DVF42P(H,S)
(V)DVF42N(H,S)
DVF42N(H,S)-HA
DVF36N(H,S)-HA
REFRACTORY pARTS
1
2
4
5
6
3
Herringbone Brick Shown
PARTS
www.fmiproducts.com
125078-01B34
PARTS
REFRACTORY pARTS
KEY NO. PART NO. DESCRIpTION qTY.
1 125124-01 Rear Refractory, Herringbone 42" White 1
125124-02 Rear Refractory, Herringbone 42" Red 1 125088-01 Rear Refractory, Herringbone 36" White 1 125088-02 Rear Refractory, Herringbone 36" Red 1 125123-01 Rear Refractory, Stacked 42" White 1 125123-02 Rear Refractory, Stacked 42" Red 1 125087-01 Rear Refractory, Stacked 36" White 1 125087-02 Rear Refractory, Stacked 36" Red 1
2 125126-01 Left Refractory, Herringbone 42" White 1
125126-02 Left Refractory, Herringbone 42" Red 1 125090-01 Left Refractory, Herringbone 36" White 1 125090-02 Left Refractory, Herringbone 36" Red 1 125123-01 Left Refractory, Stacked 42" White 1 125123-02 Left Refractory, Stacked 42" Red 1 125089-01 Left Refractory, Stacked 36" White 1 125089-02 Left Refractory, Stacked 36" Red 1
3 125128-01 Right Refractory, Herringbone 42" White
125128-02 Right Refractory, Herringbone 42" Red 1 125092-01 Right Refractory, Herringbone 36" White 125092-02 Right Refractory, Herringbone 36" Red 1 125127-01 Right Refractory, Stacked 42" White 125127-02 Right Refractory, Stacked 42" Red 1 125091-01 Right Refractory, Stacked 36" White 125091-02 Right Refractory, Stacked 36" Red 1
4 125129-01 Left Front Refractory 42" White
125129-02 Left Front Refractory 42" Red 1 125093-01 Left Front Refractory 36" White 125093-02 Left Front Refractory 36" Red 1
5 125131-01 Center Front Refractory 42" White
125131-02 Center Front Refractory 42" Red 1 125095-01 Center Front Refractory 36" White 125095-02 Center Front Refractory 36" Red 1
6 125130-01 Right Front Refractory 42" White
125130-02 Right Front Refractory 42" Red 1 125094-01 Right Front Refractory 36" White 125094-02 Right Front Refractory 36" Red 1
DVF42(N,P)H(-HA)
DVF36(N,P)H(-HA)
DVF42(N,P)S(-HA)
DVF36(N,P)S(-HA)
VDVF42(N,P)H
VDVF36(N,P)H
VDVF42(N,P)S
VDVF36(N,P)S
125078-01B 35
www.fmiproducts.com
REPLACEMENT PARTS
Note: Use only original replacement parts. This will protect your warranty coverage for parts replaced under warranty.
Contact authorized dealers of this product. If they can’t supply original replacement pa r t(s ), ca l l F M I P R ODU CTS , LLC at 1-866-328-4537.
When calling, have ready:
• your name
• your address
• model and serial numbers of your heater
• how heater was malfunctioning
• purchase date Usually, we will ask you to return the part to
the factory.
TECHNICAL SERVICE
You may have further questions about installation, operation, or troubleshooting. If so, contact FMI PROD UC TS, LLC a t 1-866-328-4537. When calling please have your mod el a nd serial numbers of your heater ready.
You can also visit our web site at www.fmiproducts.com.
ACCESSORIES
Purchase these accessories from your local dealer. If they can not supply these accessories call FMI PRODUCTS, LLC at 1-866-328-4537 for information. You can also write to the ad­dress listed on the back page of this manual.
Brick Perimeter Trim Kit
PBS36 - Red
VPBS36 - Ivory
PBS42 - Red
VPBS42 - Ivory Magnetic attachment, Matching refractory
brick facing surround kit.
SERVICE HINTS
When Gas pressure Is Too Low
• pilot will not stay lit
• burners will have delayed ignition
• replace will not produce specied heat
• propane/LP gas supply might be low (pro­pane/LP units only)
You may feel your gas pressure is too low. If so, contact your local gas supplier.
Propane/Natural Gas Conversion Kit
IMPORTANT: NOT to be used for High Altitude (-HA) Models
PCD-36S - Propane/LP Gas Conversion Kit NCD-36S - Natural Gas Conversion Kit PCD-42S - Propane/LP Gas Conversion Kit NCD-42S - Natural Gas Conversion Kit
www.fmiproducts.com
125078-01B36
NOTES
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
125078-01B 37
www.fmiproducts.com
NOTES
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
www.fmiproducts.com
125078-01B38
NOTES
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
125078-01B 39
www.fmiproducts.com
WARRANTY
KEEP THIS WARRANTY
Model (
located on product or identication tag
Serial No. (
located on product or identication tag
Date Purchased __________________________
Keep receipt for warranty verication.
FMI PRODUCTS, LLC LIMITED WARRANTIES
Standard Warranty: FMI PRODUCTS, LLC warrants this new product and any parts thereof to be free from defects in material and workmanship for a period of four (4) years from the date of rst purchase from an authorized dealer provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s warnings and instructions.
For products purchased for commercial, industrial or rental usage, this warranty is limited to 90 days from the date of rst purchase.
Limited Warranty: FMI PRODUCTS, LLC warrants factory reconditioned products and any parts thereof to be free from defects in material and workmanship for 30 days from the date of rst purchase from an authorized dealer provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s warnings and instructions.
The following terms apply to all of the above warranties:
Always specify model number and serial number when contacting the manufacturer. To make a claim under this warranty the bill of sale or other proof of purchase must be presented.
This warranty is extended only to the original retail purchaser when purchased from an authorized dealer, and only when installed by a qualied installer in accordance with all local codes and instructions furnished with this product.
This warranty covers the cost of part(s) required to restore this product to proper operating condition and an allow­ance for labor when provided by a FMI PRODUCTS, LLC Authorized Service Center or a provider approved by FMI PRODUCTS, LLC. Warranty parts must be obtained through authorized dealers of this product and/or FMI PRODUCTS, LLC who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty.
Travel, handling, transportation, diagnostic, material, labor and incidental costs associated with warranty repairs, unless expressly covered by this warranty, are not reimbursable under this warranty and are the responsibility of the owner.
Excluded from this warranty are products or parts that fail or become damaged due to misuse, accidents, improper installation, lack of proper maintenance, tampering, or alteration(s).
This is FMI PRODUCTS, LLC’s exclusive warranty, and to the full extent allowed by law; this express warranty excludes any and all other warranties, express or implied, written or verbal and limits the duration of any and all implied warranties, including warranties of merchantability and tness for a particular purpose to four (4) years on new products and 30 days on factory reconditioned products from the date of rst purchase. FMI PRODUCTS, LLC makes no other warranties regarding this product.
FMI PRODUCTS, LLC’s liability is limited to the purchase price of the product, and FMI PRODUCTS, LLC shall not be liable for any other damages whatsoever under any circumstances including indirect, incidental, or consequential damages.
Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.
This warranty gives you specic legal rights, and you may also have other rights which vary from state to state.
For information about this warranty contact:
New products
Factory Reconditioned products
Terms Common to All Warranties
) _____________________________
) __________________________
2701 S. Harbor Blvd.
Santa Ana, CA 92704
1-866-328-4537
www.fmiproducts.com
125078-01