tenance can cause injury
or property damage. Refer
to this manual for correct
installation and operational
procedures. For assistance
or additional information
consult a qualied installer,
service agency or the gas
supplier.
This appliance may be in-
stalled in an aftermarket,*
permanently located, manufactured (mobile) home,
where not prohibited by local
codes.
This appliance is only for use
with the type of gas indicated
on the rating plate. This appliance is not convertible for
use with other gases, unless
a certied kit is used.
* Aftermarket: Completion of sale, not for
purpose of resale, from the manufacturer
State of Massachusetts: The
installation must be made by a
licensed plumber or gas tter
in the Commonwealth of Mas-
sachusetts.
www.fmiproducts.com
WARNING: This product
contains and/or generates
chemicals known to the State
of California to cause cancer or
birth defects or other reproductive harm.
IMPORTANT: Read this owner’s
manual carefully and completely
before trying to assemble, operate or service this replace.
Improper use of this replace
can cause serious injury or
death from burns, re, explosion, electrical shock and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
This fireplace complies with the National
Safety Standards and is listed and tested by
PFS Corporation to ANSI Z21.50/CSA 2.22
standard as vented gas replace.
NOTICE: Decorative product not
for use as a heating appliance.
This replace must be installed by a qualied
(certied or licensed) service person. It has
a sealed gas combustion chamber that uses
a coaxial pipe (pipe within a pipe and having
the same center) venting system. It brings in
fresh air for combustion through the outer pipe
and combustion gases are exhausted through
the inner pipe. If the glass door assembly and
venting pipe are not properly seated, connected and sealed, carbon monoxide leakage
(spillage) can occur.
Carbon Monoxide Poisoning: Early signs
of carbon monoxide poisoning resemble the
u, with headaches, dizziness or nausea. If
116035-01N2
SAFETY
Continued
you have these signs, the replace may not be working properly. Get fresh air at once! Have
replace serviced. Some people are more affected by carbon monoxide than others. These
include pregnant women, people with heart or lung disease or anemia, those under the inuence of alcohol and those at high altitudes.
Propane/LP and Natural Gas: Propane/LP and natural gas are odorless. An odor-making
agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to
the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your
guide to safe and proper operation of this replace.
WARNING: Any change to this replace or its controls can be
dangerous. Do not modify this replace under any circumstances.
Any parts removed for servicing must be replaced prior to operating replace.
WARNING: Do not use a blower insert, heat exchanger insert or
other accessory not approved for use with this replace.
WARNING: This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is not convertible for
use with other gases unless a certied kit is used.
WARNING: Do not allow fans to blow directly into the replace.
Avoid any drafts that alter burner ame patterns.
Due to high temperatures, the appliance should be located out of
trafc and away from furniture and draperies.
Do not place clothing or other ammable material on or near the
appliance. Never place any objects on the appliance.
Do not use this replace to cook food or burn paper or other ammable material.
This replace reaches high temperatures. Keep children and adults away
from hot surface to avoid burns or clothing ignition. Fireplace will remain
hot for a time after shutdown. Allow surface to cool before touching.
116035-01N3
www.fmiproducts.com
SAFETY
Continued
Carefully supervise young children when they are in the room
with replace.
Keep the area around your
replace clear of combustible
materials, gasoline and other
ammable vapor or liquids. Do
not run replace where these
are used or stored.
1. For propane/LP replace, do not place
propane/LP supply tank(s) inside any
structure. Locate propane/LP supply
tank(s) outdoors. To prevent performance
problems, do not use propane/LP fuel tank
of less than 100 lb. capacity.
2. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor’s phone. Follow the gas supplier's instructions
• if you cannot reach you gas supplier, call
the re department.
3. Never install the replace
• in a recreational vehicle
• in windy or drafty areas where curtains
or other combustible (ammable) objects
can make contact with the replace front
• in high trafc areas
4. Turn replace off and let cool before servicing, installing or repairing. Only a qualied
service person should install, service or repair this replace. Have replace inspected
annually by a qualied service person.
5. You must keep control compartments,
burners and circulating air passages
clean. More frequent cleaning may be
needed due to excessive lint and dust
from carpeting, bedding material, etc.
Turn off the gas valve and pilot light before
cleaning replace.
6. Have venting system inspected annually
by a qualied service person. If needed,
have venting system cleaned or repaired.
See Cleaning and Maintenance, page 37.
7. Do not use any solid fuels (wood, coal,
paper, cardboard, etc.) in this replace.
Use only the gas type indicated on re-
place nameplate.
8. This appliance, when installed, must be
electrically grounded in accordance with local
codes or, in the absence of local codes, with
the National Electrical Code, ANSI/NFPA 70,
or the Canadian electrical code, CSA C22.1.
9. Do not use replace if any part has been
exposed to or under water. Immediately
call a qualied service person to arrange
for replacement of the unit.
10. Do not operate replace if any log is
broken.
11. Do not operate replace with glass door
removed, cracked or broken.
12. Provide adequate clearances around air
openings.
Rear Vent
Flue Collar
Screen Door
(CDC36 Series)
PRODUCT IDENTIFICATION
Upper Louver Panel
(CD36 Series)
Glass Door
Assembly
Junction
Box
Lower Louver Panel
(CD36 Series)
Figure 1 - Top and Rear Direct-Vent Fireplaces
www.fmiproducts.com
Control Valve Variable
Input Adjustment
Top Vent
Flue Collar
Door
Latch
Nailing
Flange
Log Set
Ember
Tray
Piezo Ignitor
with Optional
Remote and
Blower Control
Mount
116035-01N4
LOCAL CODES
Install and use replace with care. Follow all
local codes. In the absence to local codes,
use the current National Fuel Gas Code ANSI
Z223.1/NFPA 54* (USA), or the current CSA -
These are a few facts that can help you understand and enjoy your direct-vent replace:
• The CD36R dedicated rear vent is best suited
for ush or corner installations when vented
horizontally through an exterior wall.
• The CD36T dedicated top vent is suited
for any application where height is necessary to terminate the venting system
either through the roof (vertical) or to gain
sufcient height and offset to vent to an
outside/exterior wall (horizontal).
• The vent pipe installation is very important
to allow for proper operation. You must select the appropriate unit for your application
and follow the venting instructions to plan
your installation.
• This replace may be installed in any room
of your house provided all local codes and
these installation instructions are followed.
• Models (V)(CD)(CDC)36R/T are equipped
with a millivolt gas control system that does
not require electricity to operate. A piezo
ignitor is provided to light the pilot without
using matches or lighters.
• Models (V)(CD)(CDC)36RE/TE are
equipped with an electronic ignition system that requires 120VAC to operate. An
electrode ignitor automatically lights the
pilot ame when the replace is turned on.
• All models can accept an optional circulat-
ing air blower when 120 VAC connection
is supplied. If you plan to install an optional
blower, do not forget to wire the replace
outlet when framing.
• Each time you turn on your replace, you
may notice some amount of condensation
on the inside of the replace glass. This
is normal and will disappear after 10-20
minutes of operation.
• Your direct-vent gas fireplace system
(replace and venting) is a balanced and
sealed gas operating unit. It is highly efcient
because it uses outside air for combustion
while independently heating the indoor air.
116035-01N5
www.fmiproducts.com
PRE-INSTALLATION
PREPARATION
LOCATION AND SPACE
REQUIREMENTS
Determine the safest and most efcient location for your FMI PRODUCTS, LLC direct-vent
replace. Make sure that rafters and wall
studs are not in the way of the venting system.
Choose a location where the heat output is
not affected by drafts, air conditioning ducts,
windows or doors. Figure 2 shows some com-
mon locations. Be aware of all restrictions and
precautions before deciding the exact location
for your replace and termination cap.
When deciding the location of your replace,
follow these rules:
• Do not connect this replace venting to a
chimney ue serving a separate solid-fuel
burning replace or appliance.
• Due to high temperatures, do not locate this
replace in high trafc areas, windy or drafty
areas or near furniture or draperies.
• Proper clearances must be maintained.
• If your replace is to be installed directly on
carpeting, vinyl tile or any combustible material other than wood, it must be installed
on a metal or wood panel extending the full
width and depth of the replace. See Figure
3, page 6.
• Your replace is designed to be used in
zero clearance installations. Wall or framing
material can be placed directly against any
exterior surface on the back, sides or top of
your replace, except where standoff spac-
ers are integrally attached. If standoff spac-
ers are attached to your replace, these
spacers can be placed directly against wall
or framing material. See framing details on
page 7.
• If you plan on installing a television or entertainment center recessed above your replace, it is recommended that you maintain
a minimum 18" above top of louver opening.
Flush with
a wall
Through exterior wall
enclosed in a chase
Figure 2 - Common Fireplace Locations
Corner
installation
PRE-INSTALLATION PREPARATION
Continued
• When locating termination cap, it is important to observe the minimum clearances
shown in Figure 7, page 7.
• If recessing into a wall, you can avoid extra
framing by positioning your replace against
an already existing framing member.
• Do not recess termination cap into a wall
or siding.
• You may paint the termination cap with
450º F (232º C) heat-resistant paint to
coordinate with the exterior nish.
• There must not be any obstruction such
as bushes, garden sheds, fences, decks
or utility buildings within 24" from the front
of the termination cap.
• Do not locate termination cap where excessive snow or ice build up may occur. Be sure
to clear vent termination area after snow falls
to prevent accidental blockage of venting
system. When using snow blowers, do not
direct snow towards vent termination area.
25"
(63.5 cm)
15"
(38.1 cm)
36"
(91.4 cm)
Figure 3 - Fireplace Bottom Dimensions
PACKAGING AND REMOVAL
The (V)CD36R/T direct vent gas replace
replace is packaged with:
• one box containing a 4-log set located on
the burner in the rebox
• one bag containing the owner’s manual
with installation instructions, operator’s
guide, and warranty information
• one bag of glowing ember material
• one bag of vermiculite hearth treatments
Remove the shrink-wrap securing the 2 carton
trays to the unit. Lift the top carton tray off
and remove the four corner posts. Discard
the bottom tray once the unit is moved into
position.
Note: On rear vent models you must remove
the berboard collar protector located on the
rear collar before installing the replace and
venting system. See Figure 4.
www.fmiproducts.com
Fire Board
Collar
Protector
Figure 4 - Removing Collar Protector
(Rear Vent Fireplace)
CLEARANCES
Minimum clearances to combustibles for the
replace are as follows:
*Back and sides 0"/cm
Perpendicular walls 12" (30.5 cm)
Floor 0"/cm
Ceiling to louver opening 40" (102 cm)
Front 36" (91.4 cm)
Top of Standoffs 0"/cm
Vent Surfaces 1" (26 mm) (See venting
instructions for specific
vent clearances.)
Mantel Clearances (See Mantel Clearances
for specifics on mantel
clearances.)
Combustible material with a maximum thickness of 5/8" may be ush with the top front
of replace.
NOTICE: This replace is intended for use as supplemental
heat. Use this replace along
with your primary heating system. Do not install this replace
as your primary heat source.
If you have a central heating
system, you may run system’s
circulating blower while using
replace. This will help circulate
the heat throughout the house.
In the event of a power outage,
you can use this replace as a
heat source.
116035-01N6
PRE-INSTALLATION PREPARATION
C
B
A
D
E
F
G
3
2
1
4
5
6
7
Continued
FRAMING AND FINISHING
Figure 5 shows typical framing of this replace.
Figure 6 shows framing for corner installation.
All minimum clearances must be met.
For overall unit dimensions, framing allowances and vent collar locations, see unit
dimensions in Figure 9, page 8.
For available accessories for this replace,
see Accessories on page 45. If you are using a separate combustible mantel piece,
refer to Figure 7 and Figure 8, page 8 for
proper height and clearances. You can install
noncombustible mantels at any height above
the replace.
Note: Noncombustible mantels may discolor!
2"x4" Flat Header
or Horizontal Cross
Member 12" Above
Top of Fireplace for
12"
(30.5
cm)
(V)(CD)(CDC)36T
Units Only
2"x4" Vertical
Double Stud
MANTEL CLEARANCES
Figure 7 shows projected mantel depths at
various heights above the top of the louver
opening. Figure 8, page 8, shows the minimum allowable distances from various mantel
components in relation to the both sides of the
replace opening.
WARNING: When nishing
appliance, do not overlap combustible materials onto the black
front face. Brick, tile, or other noncombustible materials may be
applied to the face provided that
any replace openings are not
blocked and gaps in the material
used and the face are sealed with
a noncombustible caulking.
36"
(91.4 cm)
36 1/4"
(92.1 cm)
14 3/4"
(37.5 cm)
Figure 5 - Framing Clearances for
Installation Against an Exterior Wall
5
/8" ( 16.8 cm)
6
TO CENTER
OF REAR VENT
21" (53.3 cm)
TO CENTER OF
TOP VENT
5
/8"
28
(72.7 cm)
1
/2" (6.3 cm)
2
MIN. 1" (2.6 cm)
3
/4"
56
(144 cm)
Figure 6 - Framing Clearances for Corner
Installation
116035-01N7
14 3/4"
(37.5 cm)
THESE DIMENSIONS
ALLOW FOR 1" OF
CLEARANCE AT THE
SIDES AND BACK OF
THE FIREPLACE.
HOWEVER,
0" CLEARANCE IS
ALSO PERMITTED
AT ALL SIDES WHEN
FRAMED.
Figure 8 - Side Clearances for Combustible Materials
14
(37.5 cm)
2"
(5 cm)
TO NAILING
FLANGES
(5 cm)
(5 cm)
8" (20.4 cm)
TO CENTER OF
8" TOP VENT
36
(92.1 cm)
TO NAILING
FLANGE
3
36
/4"
(93.4 cm)
38"
(96.5 cm)
1
/4"
Perpendicular
Side Wall
3
/4"
2"
36"
(91.4 cm)
FACE DIM.
2 "
33°
5/8"
(1.6 cm)
WALL SWITCH
WIREWAY
25"
(63.5 cm)
TO CENTER
OF 8"
REAR VENT
8" (20.3 cm)
GAS SUPPLY
INLET
1
4
/2" (11.4 cm)
ELECTRICAL
INLET
1
36
/4"
(92.1 cm)
FACE DIM.
37" (94 cm)
TO NAILING
FLANGE
Figure 9 - Rear/Top Common Dimensions
www.fmiproducts.com
1
2
/2 "
(6.4 cm)
15
(39 cm)
3
/8"
116035-01N8
LOCATION OF TERMINATION CAP
D
E
V
B
L
A = clearance above grade, veranda, porch, deck, or
balcony [*12" (30.5 cm) minimum]
B = clearance to window or door that may be opened
[6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US
if between 10,000 and 50,000, 12" (30 cm) in Canada
if between 10,000 and 100,000; 12" (30 cm) in US if
greater than 50,000, 36" (91 cm) in Canada if greater
than 100,000]
C = clearance to permanently closed window
[minimum 12" (30.5 cm) recommended to prevent
condensation on window]
D = vertical clearance to ventilated soffit located above the
terminal within a horizontal distance of 24" (61 cm) from
the center-line of the terminal [18" (45.7 cm) minimum]
E = clearance to unventilated soffit [12" (30.5 cm) minimum]
F = clearance to outside corner (see below)
G = clearance to inside corner (see below)
H = *not to be installed above a meter/regulator assembly
within 36" (91.4 cm) horizontally from the center line
of the regulator
† vent shall not terminate directly above a side-walk or paved driveway which is located between two
single family dwellings and serves both dwellings*
‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor*
* as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A.
Note: Local codes or regulations may require different clearances
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Inside Corner
A
A = 6" (15.2 cm)
V
C
F
V
B
TERMINATION CAP
V
Fixed
Closed
Openable
V
Openable
B
AIR SUPPLY INLET
X
B
V
Fixed
Closed
B
J
V
X
A
I = clearance to service regulator vent outlet [*72" (182.9 cm)
minimum]
J = clearance to non-mechanical air supply inlet to building
or the combustion air inlet to any other fireplace
[6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US
if between 10,000 and 50,000, 12" (30 cm) in Canada
if between 10,000 and 100,000; 12" (30 cm) in US if
greater than 50,000, 36" (91 cm) in Canada if greater
than 100,000]
K = clearance to a mechanical air supply inlet [*In Canada,
6 ft. (1.83m) minimum; In US 3 ft. (91 cm) above if within
10 ft. (3 m) horizontally]
L = † clearance above paved side-walk or a paved driveway
located on public property [*84" (213.3 cm) minimum]
M = clearance under veranda, porch, deck
[*12" (30.5 cm) minimum ‡]
N = clearance above a roof shall extend a minimum of
24" (61 cm) above the highest point when it passes
through the roof surface and any other obstruction within
a horizontal distance of 18" (45.7 cm)
C = Maximum depth of 48" (121.9 cm)
for recessed location
D = Minimum width for back wall of
recessed location Combustible - 38" (965 mm)
Noncombustible - 24" (61 cm)
E = Clearance from corner in
recessed location Combustible - 6" (15.2 cm)
Noncombustible - 2" (5.1 cm)
Figure 10 - Minimum Clearances for Termination Cap
116035-01N9
www.fmiproducts.com
REQUIREMENTS FOR THE COMMONWEALTH OF
MASSACHUSETTS
For all side wall horizontally vented gas fueled
equipment installed in every dwelling, building or
structure used in whole or in part for residential
purposes, including those owned or operated by
the Commonwealth and where the side wall ex-
haust vent termination is less than seven (7) feet
above nished grade in the area of the venting,
including but not limited to decks and porches,
the following requirements shall be satised:
INSTALLATION OF CARBON
MONOXIDE DETECTORS
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing
plumber or gastter shall observe that a hard
wired carbon monoxide detector with an alarm
and battery backup is installed on the oor level
where the gas equipment is to be installed. In
addition, the installing plumber or gastter shall
observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed
on each additional level of the dwelling, building or
structure served by the side wall horizontal vented
gas fueled equipment. It shall be the responsibility
of the property owner to secure the services of
qualied licensed professionals for the installation
of hard wired carbon monoxide detectors.
In the event that the side wall horizontally
vented gas fueled equipment is installed
in a crawl space or an attic, the hard wired
carbon monoxide detector with alarm and
battery back-up may be installed on the next
adjacent oor level.
In the event that the requirements of this
subdivision can not be met at the time of
completion of installation, the owner shall
have a period of thirty (30) days to comply with
the above requirements; provided, however,
that during said thirty (30) day period, a battery
operated carbon monoxide detector with an
alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required
in accordance with the above provisions shall
comply with NFPA 720 and be ANSI/UL 2034
listed and IAS certied.
SIGNAGE
A metal or plastic identication plate shall be
permanently mounted to the exterior of the
building at a minimum height of eight (8) feet
above grade directly in line with the exhaust
vent terminal for the horizontally vented gas
fueled heating appliance or equipment. The
sign shall read, in print size no less than 1/2" in
size, "GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS".
www.fmiproducts.com
INSPECTION
The state or local gas inspector of the side
wall horizontally vented gas fueled equipment
shall not approve the installation unless, upon
inspection, the inspector observes carbon
monoxide detectors and signage installed in
accordance with the provisions of 248 CMR
5.08(2)(a) 1 through 4.
EXEMPTIONS: The following equipment is ex-
empt from 248 CMR 5.08(2)(a) 1 through 4:
• The equipment listed in Chapter 10 entitled
"Equipment Not Required To Be Vented"
in the most current edition of NFPA 54 as
adopted by the Board; and
• Product Approved side wall horizontally
vented gas fueled equipment installed in a
room or structure separate from the dwelling, building or structure used in whole or
in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved
side wall horizontally vented gas equipment
provides a venting system design or venting
system components with the equipment, the
instructions provided by the manufacturer for
installation of the equipment and the venting
system shall include:
• Detailed instructions for the installation of
the venting system design or the venting
system components; and
• A complete parts list for the venting system
design or venting system.
Gas Equipment Venting System Not
Provided
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for
venting the ue gases, but identies "special
venting systems", the following requirements
shall be satised by the manufacturer:
•
The referenced "special venting system" instructions shall be included with the appliance
or equipment installation instructions; and
• The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list
and detailed installation instructions.
A copy of all installation instructions for all
Product Approved side wall horizontally
vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions
shall remain with the appliance or equipment
at the completion of the installation.
116035-01N10
VENTING INSTALLATION
NOTICE: Read these instruc-
tions completely before attempting installation.
These models are tested and approved for
use with FMI PRODUCTS, LLC (direct-vent)
pipe components and terminations.
The venting system must terminate on the
outside of the structure and can not be attached to a chimney or ue system serving a
separate solid fuel or gas burning appliance.
A direct-vent appliance must have its own
venting system. DO NOT common vent this
appliance.
These models are approved to be vented
either horizontally through an outside wall or
vertically through a roof or chase enclosure
using the following:
• When venting system terminates horizontally on an outside wall, you may install
a standoff if the termination cap is to be
installed directly on a combustible nish
such as vinyl, wood, stucco, etc.
• Never run the vent downward as this may
cause excessive temperatures which could
cause a re.
• Vent pipe air space clearances to combustibles are 1" on all sides except on the
horizontal sections, which requires 2" clear-
ance from the top of the pipe. Where the
termination cap penetrates a combustible
wall, 1" air space clearance is required.
• Have replace and selected vent compo-
nents on hand to help determine the exact
measurements when elbowing or offsetting.
Always use wall restops when penetrating
walls and restops when penetrating ceil-
ings or attic spaces.
• If using a venting conguration of only
horizontal venting with no vertical run, a
1/4" rise for every 12" of run toward the
termination is required.
WARNING: Read all instruc-
tions completely and thoroughly
before attempting installation.
Failure to do so could result in
serious injury, property damage
or loss of life.
IMPORTANT: Do not seal vent cap to pipe.
Cap must be removable for servicing.
NOTICE: Failure to follow these in-
structions will void the warranty.
NOTICE: Do not seal termination
cap to vent pipe. Cap must be
removable for vent inspection
and maintenance.
INSTALLATION PRECAUTIONS
• Wear gloves and safety glasses for protection
• Use extreme caution when using ladders or
when on roof tops
• Be aware of electrical wiring locations in walls
and ceilings
The following actions will void the warranty on your
venting system:
• Installation of any damaged venting compo-
nent
• Unauthorized modication of the venting system (Do not cut or alter vent components)
• Installation of any component part not manufactured or approved by FMI PRODUCTS, LLC
• Installation other than as instructed by these
instructions
WARNING: This gas replace
and vent assembly must be
vented directly to the outside.
The venting system must NEVER
be attached to a chimney serving a separate solid fuel burning
appliance. Each direct-vent gas
appliance must use a separate
vent system. Do not use common vent systems.
WARNING: Vent pipe air
space clearances to combustibles are 1" on all sides except
on the horizontal sections,
which require 2" clearances
from the top of the pipe. Where
the termination cap penetrates
a combustible wall, 1" air space
clearance is required.
116035-01N11
www.fmiproducts.com
INSTALLATION PLANNING
(Framing
Detail)
11
1
/2"
(29.2 cm)
11
1
/2" Inside Framing
(29.2 cm)
11
1
/2"
(29.2 cm)
8 1/2"
(21.6 cm)
Vent Opening
Combustible Wall
Vent Opening
Noncombustible Wall
There are two basic types of direct-vent
installation:
• Horizontal Termination
• Vertical Termination
Horizontal Termination Installation
IMPORTANT: Horizontal square terminations
require only inner portion of wall restop. Horizontal installations using round termination
require exterior portion of wall restop (see
Figure 20, page 15).
1. Set replace in its desired location and
determine route your horizontal venting
will take. Do not secure replace until all
venting has been installed. Some instal-
lations require sliding replace in and out
of position to make nal venting connections. Figures 18 through 25 on pages 14
through 17 show different congurations
for venting with horizontal termination that
will help you decide which application best
suits your installation. Check to see if wall
studs or roof rafters are in the path of your
desired venting route. If they are, you may
want to adjust location of replace.
2. Direct vent pipe sections and components
are designed with special twist-lock connections.
Twist-Lock Procedure: Female ends of
pipes have locking lugs (indentations).
These lugs will slide straight into matching slots on male ends of adjacent pipes.
Push pipe sections together and twist
one section clockwise approximately one-
quarter turn until sections are fully locked
(see Figure 11).
Note: Horizontal runs of vent must be sup-
ported every three feet. Use wall straps
for this purpose.
3. Any straight pipe section, a 45° or 90°
elbow can be used when rst connecting
the venting system to replace. Elbows
are designed to twist-lock into any of four
90° positions to direct the venting system
to the desired location. IMPORTANT: Do
not attempt to alter the conguration of
elbow by cutting, twisting, bending, etc.
4. Assemble desired combination of pipe
and elbows to replace ue collar. If there
are long portions of venting run, preas-
sembled pipe sections may be installed
as subassemblies for convenience.
VENTING INSTALLATION
Continued
5. Carefully determine location where vent
pipe assembly will penetrate outside wall.
Center of hole should line up with center
line of horizontal vent pipe. Mark wall for a
11 1/2" x 11 1/2" square hole. Cut and frame
square hole in exterior wall where vent will
be terminated. If wall being penetrated is
constructed of noncombustible material,
such as masonry block or concrete, a
8 1/2" hole with zero clearance is accept-
able (see Figure 12).
Figure 11 - Vent Pipe Connections
Figure 12 - Vent Opening Requirements
www.fmiproducts.com
Female
Locking Lugs
Male
Slots
Center
of Hole
116035-01N12
VENTING INSTALLATION
Continued
WARNING: Do not recess
vent termination into any wall.
This will cause a re hazard.
6. Noncombustible Exterior Wall: Position
horizontal vent cap in center of 8 1/2" round
hole and attach to exterior wall with four
wood screws provided. Before attaching
vent cap to exterior wall, run a bead of
non-hardening mastic (pliable sealant)
around outside edges to make a seal
between it and outside wall.
Note: Four wood screws provided should
be replaced with appropriate fasteners for
stucco, brick, concrete or other types of
sidings (see Figure 13).
Combustible Exterior Wall: For vinyl
siding, stucco or wood exteriors, a siding
standoff may be installed between vent
cap and exterior wall. Siding standoff
prevents excessive heat from damaging
siding materials. Siding material must be
cut to accommodate standoff. Bolt vent
cap to standoff. Apply non-hardening
mastic around outside edge of standoff.
Position standoff/cap assembly in center
of the 11 1/2" square hole and attach to
exterior wall with wood screws provided
(see Figure 14). Siding standoff must sit
ush against exterior fascia material.
7. Connecting Vent Cap with Horizontal
Vent Pipe: Fit outer and inner wall restop
into wall before connecting horizontal run
to vent cap (see Figure 15).
Carefully move replace, with vent assem-
bly attached, toward wall and insert vent
pipe into horizontal termination. The pipe
overlap should be a minimum of 1 1/4".
Slide wall restop against interior wall sur-
face and attach with screws provided (see
Figure 16, page 14). See Figure 17, page
14, for horizontal termination details.
Place replace into position and shim with
noncombustible material, if needed. Nail
or screw side anges to framing to secure
unit in place. IMPORTANT: Make sure re-
place is level before securing. If replace
is not level it will not work properly.
Apply Mastic to
All Four Sides
Vent Cap
Wood Screw
Figure 13 - Installing Horizontal Vent Cap
(Noncombustible Exterior)
Cut Siding Away
to Fit Standoff
Standoff
Inner Wall
Firestop
Apply Mastic to
All Four Sides
Figure 14 - Installing Siding Standoff
(Combustible Exterior Wall)
Inner Wall
Firestop
Outer Wall
Firestop
Figure 15 - Installing Outer Wall Firestop
(Combustible Exterior Wall)
Vent
Cap
Screws
116035-01N13
www.fmiproducts.com
VENTING INSTALLATION
Continued
NOTICE: Do not seal termination
cap to vent pipe. Cap must be
removable for vent inspection
and maintenance.
Vent
Cap
Inner Wall
Firestop
Pipe
Section
Figure 16 - Installing Inner Wall Firestop
Minimum Pipe
Overlap 11/4"
Direct-Vent
Pipe
Wall
Firestop
Siding Standoff
Screws
WARNING: Never run vent
downward as this may cause
excessive temperatures which
could cause a re. Operation of
improperly installed and maintained venting system could
result in serious injury, property
damage or loss of life.
Horizontal Termination Congurations
Figures 18 through 25 show different congurations and alternatives for venting with
horizontal termination. Each gure includes
a chart with critical minimum and maximum
dimensions which MUST be met.
IMPORTANT: If using a venting conguration
of only horizontal venting with no vertical run,
a 1/4" rise for every 12" of run toward the
termination is required.
GROUND FLOOR INSTALLATION REAR VENT
Recommended Applications for Rear Vent
Model (V)(CD)(CDC)36R:
• Installation using cabinet surrounds
• Through wall using round or square
termination (up to a maximum of 18" of
horizontal pipe)
• Corner installation (Using one 45° elbow
and a maximum of 18" of horizontal pipe).
Straight/Adjustable
Pipe 18" Max.
Maintain 1"
Minimum Air
Space Around
Outer Pipe When
Recommended Applications Models (V)(CD)
(CDC)36R and (V)(CD)(CDC)36T:
• Installations requiring vertical rise on build-
ing exterior.
• Installation using snorkel termination to
achieve 1 ft. above grade.
Snorkel
Termination
12"
Min.
Figure 23 - Snorkel Termination Conguration For Below Ground Installation
HORIZONTAL VENT INSTALLATIONS
USING MULTIPLE 90° ELBOWS (V)(CD)
(CDC)36T TOP VENT
The following congurations show the minimum vertical rise requirements for a horizontal
system using two 90° elbows.
Snorkel terminations are available for installa-
tions requiring a vertical rise on the exterior of
the building. If installing snorkel below grade
you must provide proper drainage to prevent
water from entering snorkel (see Figure 23).
Do not back ll around snorkel termination.
Snorkel
Termination
Wall
Firestop
90° Elbow
12" Min.
Adequate
Drainage
Snorkel
Termination
12" Min.
90°
Elbow
90°
Elbow
Venting with Two 90° Elbows
Vertical (V)
Horizontal (H)+
Horizontal (H2)
7' Min.10' Max
8' Min.12' Max
9' Min.14' Max
10' Min.16' Max
11' Min.18' Max
13' Min.20' Max
Figure 24 - Horizontal Termination Conguration For Venting Using Two 90° Elbows
(Model (V)(CD)(CDC)36T)
www.fmiproducts.com
116035-01N16
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.