INDOOR/OUTDOOR VENT FREE (V)Q(36,42,50)(H,S)(R) SERIES
FIREBOX WITH INSULATION
WARNING: If the information in this manual is not
followed exactly, a re or explosion may result causing
property damage, personal injury or loss of life.
— Do not store or use gasoline or other ammable
— WHAT TO DO IF YOU SMELL GAS
— Installation and service must be performed by a quali-
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
vapors and liquids in the vicinity of this or any other
appliance.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
phone in your building.
• Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re
department.
ed installer, service agency or the gas supplier.
For more information, visit www.fmiproducts.com
Page 2
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause injury or
property damage. Refer to this manual for correct installation and operational procedures. For assistance
or additional information consult a qualied installer,
service agency or the gas supplier.
WARNING: Carefully review the instructions supplied with the decorative type unvented room heater for
the minimum replace size requirement.
DO NOT INSTALL THE APPLIANCE IN THIS FIREBOX,
UNLESS THIS FIREBOX MEETS THE MINIMUM DIMEN-
SIONS REQUIRED FOR THE INSTALLATION.
WARNING: FOR USE ONLY WITH A LISTED, GASFIRED UNVENTED DECORATIVE ROOM HEATER NOT
IMPORTANT: Read this owner’s
manual carefully and completely
before trying to assemble, operate or service this replace.
Improper use of this replace
can cause serious injury or
death from burns, re, explosion, electrical shock and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
www.fmiproducts.com
124384-01A2
Page 3
SAFETY
Continued
WARNING: Any change to
this rebox or its controls can
be dangerous.
WARNING: Do not allow fans
to blow directly into the rebox.
Avoid any drafts that alter burner
ame patterns. Ceiling fans can
create drafts that alter burner
ame patterns. Altered burner
patterns can cause sooting.
WARNING: Do not use a blower insert, heat exchanger insert
or other accessory not approved
for use with this rebox.
Due to high temperatures, the
appliance should be located out
of trafc and away from furniture
and draperies.
Do not place clothing or other
ammable material on or near
the appliance. Never place any
objects in the rebox or on
logs.
Firebox front and screen becomes very hot when running
rebox. Keep children and adults
away from hot surfaces to avoid
burns or clothing ignition. Firebox will remain hot for a time
after shutdown. Allow surfaces
to cool before touching.
Carefully supervise young chil-
dren when they are in the room
with rebox.
Keep the replace area clear and
free from combustible materials,
gasoline, and other ammable
vapors and liquids.
124384-01a3
www.fmiproducts.com
You must operate this replace
with the provided fireplace
screen and hood in place.
Make sure these parts are in
place and screens are closed
before running installed gas
log heater. Replace hood with
FMI PRODUCTS, LLC model
109511-01 50", 109511-02 42",
or 109511-03 36" only. This hood
has been designed to keep the
operation of your replace safe
and efcient.
1. Do not use this rebox as a wood burning
replace. Use only decorative unvented
room heaters (log sets).
2. Do not add extra logs or ornaments such as
pine cones, vermiculite or rock wool. Using
these added items can cause sooting.
3. Use only the provided hood. See Parts,
page 30.
4. Vent-free gas log heaters installed in these
reboxes require fresh air ventilation to
run properly. See Air for Combustion and
Ventilation, page 8.
5. Do not run vent-free heaters installed in
these reboxes
• where ammable liquids or vapors are
used or stored
• under dusty conditions
6. Do not use this rebox to cook food or
burn paper or other objects.
7. Turn unit off and let cool before servicing.
Only a qualied service person should
service and repair rebox.
8. Operating vent-free heaters installed in
these reboxes above elevations of 4,500
feet could cause pilot outage.
9. Do not use the rebox if it has been
under water.
10. Before using furniture polish, wax, carpet
cleaner or similar products, turn heater
off. If heated, the vapors from these prod-
ucts may create a white powder residue
within burner box or on adjacent walls
and furniture.
11. Provide adequate clearances around air
openings.
Page 4
LOCAL CODES
Install and use rebox with care. Follow all
local codes. In the absence of local codes,
use the latest edition of The National Fuel Gas Code ANSI Z223.1/NFPA 54*. Firebox must
be electrically grounded in accordance with
the National Electrical Code, ANSI/NFPA70
(latest edition).
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
State of Massachusetts: The installation
must be made by a licensed plumber
or gas fitter in the Commonwealth of
Massachusetts.
Sellers of unvented propane or natural
gas-fired supplemental room heaters
shall provide to each purchaser a copy of
527 CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for
bedroom and bathroom installation in
to minimum rebox requirements supplied
with log heater.) It requires no outside vent-
ing or chimney making installation easy and
inexpensive.
LOCATING FIREBOX
PLANNING
Plan where you will install the rebox. This will
save time and money later when you install
the rebox. Before installation, consider the
following:
1. Where rebox will be located. Allow for
wall and ceiling clearances (see Installa-
tion Clearances, page 11).
2. Everything needed to complete installation.
3. These models CANNOT be installed in
a bedroom unless maximum Btu rating
of installed vent-free log set is less than
10,000 Btu/hr.
4. Proper air for combustion and ventilation
(page 8).
www.fmiproducts.com
124384-01A4
Page 5
36" MODELS
PRODUCT SPECIFICATIONS
54
30 1/2"
11
1
/2"
30"
7
7
29"
7
4
/8"
3
/4"
3
1
/8"
50"
5
/16"
36
7"
/8"
36"
1
45
/8"
7
/16"
9
5
/16"
3
Figure 1 - 36" Models (V)U36(H,S) and (V)Q36(H,S)(R) Series
(Picture may vary from actual replace)
22 1/2"
1
35
36" HEARTH
3
7
/8"
1
/8"
11
1
20
/4"
19"
(Ref.)
1
1
/4"
/4"
124384-01a5
www.fmiproducts.com
Page 6
42" MODELS
3
/8"
32
PRODUCT SPECIFICATIONS
Continued
5
30
/16"
26 3/8"
21
23"
3
/4"
(Ref.)
54 1/2"
11
3
41
3
3
/4"
1
/8"
30"
7
7"
7
/8"
42"
1
/8"
51
4 7/8"
36
50"
5
/16"
7
9
/16"
5
3
/16"
/8"
42" HEARTH
3
8
/4"
13"
1
1
/4"
Figure 2 - 42" Models (V)U42(H,S) and (V)Q42(H,S)(R) Series
(Picture may vary from actual replace)
www.fmiproducts.com
124384-01A6
Page 7
50" MODELS
3
32
/8"
PRODUCT SPECIFICATIONS
Continued
5
38
/16"
34 3/8"
21
23"
3
/4"
(Ref.)
54
7
/8"
3
/4"
3
1
11
/8"
1
/2"
30"
4
50"
3
49
/8"
50" HEARTH
1
/4"
1
365/16"
7
7
7
/8"
7"
50"
1
/8"
59
/16"
9
5
3
/16"
3
8
/4"
13"
Figure 3 - 50" Models (V)U50(H,S) AND (V)Q50(H,S)(R) Series
(Picture may vary from actual replace)
124384-01a7
www.fmiproducts.com
Page 8
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall
not be installed in a room or space
unless the required volume of indoor combustion air is provided
by the method described in the
National Fuel Gas Code, ANSI
Z223.1/NFPA 54, the International
Fuel Gas Code, or applicable lo-
cal codes. Read the following instructions to insure proper fresh
air for this and other fuel-burning
appliances in your home.
Today’s homes are built more energy efcient
than ever. New materials, increased insulation
and new construction methods help reduce
heat loss in homes. Home owners weather
strip and caulk around windows and doors to
keep the cold air out and the warm air in. During heating months, home owners want their
homes as airtight as possible.
While it is good to make your home energy
efcient, your home ne eds to breathe. Fresh
air must enter your home. All fuel-burning appliances need fresh air for proper combustion
and ventilation.
Exhaust fans, replaces, clothes dryers and
fuel burning appliances draw air from the house
to operate. You must provide adequate fresh
air for these appliances. This will insure proper
venting of vented fuel-burning appliances.
PROVIDING ADEQUATE
VENTILATION
The following are excerpts from National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space
The information on pages 8 through 10 will help
you classify your space and provide adequate
ventilation.
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion
and ventilation. However, in buildings of unusually tight construction, you must provide
additional fresh air.
www.fmiproducts.com
Unusually tight construction is dened as
construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous
water vapor retarder with a rating of
one perm (6 x 10
less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window
and door frames, between sole plates
and oors, between wall-ceiling joints,
between wall panels, at penetrations
for plumbing, electrical and gas lines
and at other openings.
If your home meets all of the three criteria
above, you must provide additional fresh
air. See Ventilation Air From Outdoors,
page 10.
If your home does not meet all of the three
criteria above, proceed to Determining
Fresh-Air Flow For Firebox Location.
Conned and Unconned Space
The National Fuel Gas Code, ANSI Z223.1/
NFPA 54 denes a conned space as a space
whose volume is less than 50 cubic feet per
1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed
in that space and an unconned space as a
space whose volume is not less than 50 cubic
feet per 1,000 Btu per hour (4.8 m3 per kw)
of the aggregate input rating of all appliances
installed in that space. Rooms communicating
directly with the space in which the appliances
are installed*, through openings not furnished
with doors, are considered a part of the unconned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation
grills between them.
-11
kg per pa-sec-m2) or
DETERMINING FRESH-AIR FLOW
FOR FIREBOX LOCATION
Determining if You Have a Conned or
Unconned Space
Use this work sheet to determine if you have
a conned or unconned space.
Space: Includes the room in which you will
install heater plus any adjoining rooms with
doorless passageways or ventilation grills
between the rooms.
124384-01A8
Page 9
Or
Remove
Door into
Adjoining
Room,
Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilation
Grills Into
Adjoining
Room,
Option 1
12"
12"
AIR FOR COMBUSTION AND VENTILATION
Continued
1. Determine the volume of the space (length
x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 22 ft. (length) x 18 ft.
(width) x 8 ft. (ceiling height) = 3,168 cu. ft.
(volume of space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume
of the space.
2. Multiply the space volume by 20 to determine
the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 3,168 cu. ft. (volume of space) x 20 =
63,360 (maximum Btu/Hr space can support)
3. Add the Btu/Hr of all fuel burning appliances
in the space.
Vent-free replace _________ Btu/HrGas water heater* _________ Btu/Hr
Gas furnace _________ Btu/Hr
Vented gas heater _________ Btu/Hr
Gas replace logs _________ Btu/Hr
Other gas appliances* + _________ Btu/Hr
Total = _________ Btu/Hr
* Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.
Example:
Gas water heater _________ Btu/HrVent-free replace + _________ Btu/Hr
Total = _________ Btu/Hr
40,000
39,000
79,000
4. Compare the maximum Btu/Hr the space
can support with the actual amount of Btu/Hr
used.
_______ Btu/Hr (maximum the space can
support)
_______ Btu/Hr (actual amount of Btu/Hr
used)
Example: 63,360 Btu/Hr (maximum the
space can support)
79,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the example is a conned space
because the actual Btu/Hr used is more than the
maximum Btu/Hr the space can support. You
must provide additional fresh air. Your options
are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides an
unconned space, remove door to adjoining
room or add ventilation grills between rooms.
B. Vent room directly to the outdoors. See
C. Install a lower Btu/Hr replace, if lower Btu/
124384-01a9
See Ventilation Air From Inside Building.
Ventilation Air From Outdoors, page 10.
Hr size makes room unconned.
www.fmiproducts.com
If the actual Btu/Hr used is less than the
maximum Btu/Hr the space can support, the
space is an unconned space. You will need
no additional fresh air ventilation.
WARNING: If the area in which
the heater may be operated does
not meet the required volume for
indoor combustion air, combustion and ventilation air shall be
provided by one of the methods
described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54,
the International Fuel Gas Code,
or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining
unconned space. When ventilating to an
adjoining unconned space, you must provide
two permanent openings: one within 12" of the
ceiling and one within 12" of the oor on the
wall connecting the two spaces (see options
1 and 2, Figure 4). You can also remove door
into adjoining room (see option 3, Figure 4 ).
Follow the National Fuel Gas Code, ANSI
Z223.1/NFPA 54, Air for Combustion and
Ventilation for required size of ventilation
grills or ducts.
Figure 4 - Ventilation Air from Inside
Building
Page 10
Outlet
Air
Ventilated
Attic
Outlet
Air
Inlet
Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
AIR FOR COMBUSTION AND VENTILATION
Continued
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two permanent openings: one within 12" of the ceiling
and one within 12" of the oor. Connect these
items directly to the outdoors or spaces open
to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, Air for
Combustion and Ventilation for required size
of ventilation grills or ducts.
IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a thermo-
stat-controlled power vent. Heated air entering
the attic will activate the power vent.
INSTALLATION
Figure 5 - Ventilation Air from Outdoors
WARNING: A qualied service person must install rebox.
Follow all local codes.
WARNING: Never install
rebox
• in a bedroom or bathroom*
• in a recreational vehicle
• where curtains, furniture,
clothing, or other ammable
objects are less than 36" from
front or 42" from top of rebox;
for side clearances see Figure
4, page 11
• in high trafc areas
• in windy or drafty areas
* Unless installed log set is rated
at 10,000 Btu/Hr or less.
CAUTION: Log heaters
installed in this rebox create
warm air currents. These currents
move heat to wall surfaces next
to rebox. Installing rebox next
to vinyl or cloth wall coverings or
operating rebox where impurities (such as, but not limited to, tobacco smoke, aromatic candles,
cleaning uids, oil or kerosene
lamps, etc.) in the air exist, may
discolor walls or cause odors.
www.fmiproducts.com
NOTICE: The rebox identication label (including model number, serial number, clearances,
etc.) is located on a chain under
the bottom refractory.
IMPORTANT: Vent-free gas log heaters add
moisture to the air. Although this is benecial,
installing rebox in rooms without enough
ventilation air may cause mildew to form from
too much moisture. See, page 8.
IMPORTANT: Make sure the rebox is level.
If rebox is not level, log set will not work
properly.
Note: Your rebox is designed to be used in
zero clearance installations. Wall or framing
material can be placed against any exterior
surface on the rear, sides, top or bottom of
your rebox, except where standoff spacers
are integrally attached. If standoff spacers are
attached to your rebox, these spacers can
be placed directly against wall or framing materials. Use the dimensions shown for rough
opening to create the easiest installation.
Use dimensions shown for rough openings
to create the easiest installation (see Built-In
Firebox Installation, page 12).
124384-01A10
Page 11
INSTALLATION CLEARANCES
Supplied
Firebox Hood
Must Be Used
at All Times
Wire-mesh
Screen
Firebox
Noncombustible
Material May
Project Off this
Surface above
the Firebox Hood
Mantel Shelf
Note: Any portion of the
mantel shelf must NOT
extend beyond this profile.
12" 16" 20"
1
1
/
2"
6
3
/
4
"
12"
Note: All vertical
measurements are
from top of fireplace
hood opening to
bottom of mantel shelf.
These minimum
clearances replace any
other recommended
clearances supplied
with your ANSI Z21.11.2
approved gas logs.
Wall board or facing
material (above
firebox) may be of
combustible material,
including decorative
mantel ornaments or
other similar projections off of the facing
material.
Framing
Material
minimum clearances. If you
can, provide greater clearances
from oor, ceiling, and adjoining wall.
Carefully follow the instructions below. This
will ensure safe installation.
Minimum Wall and Ceiling Clearances
(see Figure 6)
A. Clearances from the side of the replace
Example: The face of a mantel, bookshelf,
B. Clearances from the top of the rebox
C. When the rebox is installed directly on
D. Clearances from the bottom of rebox to
These reboxes can be installed as freestanding units against a wall with approved
cabinet mantels that may be available from
your retailer or supplier, or as a built-in unit.
The clearances are the same for either installation method.
*Minimum 16" from Side Wall
124384-01a11
INSTALLATION
Continued
WARNING: Maintain the
cabinet to any combustible material and
wall should follow diagram in Figure 6.
etc. is made of combustible material and
protrudes 3 1/2" from the wall. This com-
bustible material must be 4" from the side
of the replace cabinet (see Figure 4).
opening to the ceiling should not be less
than 42".
carpeting, tile or other combustible mate-
rial, other than wood ooring, the rebox
should be installed on a metal or wood
panel extending the full width and depth
of the enclosure.
the oor is 0".
Example
Figure 6 - Minimum Clearance for
Combustible to Wall
*
www.fmiproducts.com
Mantel Clearances for Built-In
Installation
If placing custom mantel above built-in rebox, you must meet the minimum allowable
clearance between mantel shelf and top of
rebox opening shown in Figure 7. These are
the minimum allowable mantel clearances
for a safe installation. Use larger clearances
wherever possible to minimize the heating of
objects and materials placed on the mantel.
CAUTION: Do not allow the
vent-free gas log heater to touch
or extend beyond the replace
screen.
NOTICE: Surface temperatures
of adjacent walls and mantels
become hot during operation.
Walls and mantels above the
firebox may become hot to
the touch. If installed properly,
these temperatures meet the
requirement of the national
product standard. Follow all
minimum clearances shown in
this manual.
Figure 7 - Minimum Mantel Clearances
for Built-In Installation
Page 12
INSTALLATION
Continued
NOTICE: If your installation does
not meet the minimum clearances shown, you must do one
of the following:
• raise the mantel to an accept-
able height
• remove the mantel
BUILT-IN FIREBOX INSTALLATION
Built-in installation of this rebox involves
installing rebox into a framed-in enclosure.
This makes the front of rebox ush with wall.
If installing a mantel above the rebox, you
must follow the clearances shown in Figure
7, page 11. Follow these instructions to install
the rebox in this manner.
1. Frame in rough opening. The rebox fram-
ing should be constructed of 2 x 4 lumber
or heavier. Use dimensions and rough
opening layout in Figure 8. Adjust framing
so that rebox ushes with nished wall
surface. If installing in a corner, use dimensions in Figure 9, for rough opening.
2. Install gas piping to rebox location. See
Installing Gas Line on page 14 and Connecting to Gas Supply in log set owner’s
manual.
3. Carefully set firebox in front of rough
opening with back of rebox inside wall
opening.
4. Carefully insert rebox into rough opening.
5. Attach rebox to wall studs using nails
or wood screws through holes in nailing
ange (see Figure 10).
6. Install and properly test gas log heater.
Follow installation instructions included
with the vent-free gas log heater that is
being installed.
IMPORTANT: When nishing your rebox,
combustible materials such as wall board,
gypsum board, sheet rock, drywall, plywood,
etc. may be butted up next to the sides and top
of the rebox. Combustible materials should
never overlap the rebox front facing.
WARNING: Do not allow any
combustible materials to overlap
the rebox front facing.
IMPORTANT: Noncombustible materials such
as brick, tile, etc. may overlap the front facing, but should never cover any necessary
openings.
WARNING: Do not allow non-
combustible materials to cover
any necessary openings.
combustible mortar or adhesives when overlapping the front
facing with noncombustible
facing material.
Cabinet
Mantel
INSTALLING FIREBOX USING
OPTIONAL CUSTOM BUILT
MANTELS
WARNING: A qualied service person must install rebox.
Follow all local codes.
This rebox may be installed using a cabinet
mantel against a wall in your home. The
rebox and cabinet mantel can be installed
directly on the oor. Mantels may be avail-
able from your retailer or custom built for
your home.
1. Assemble cabinet mantel as instructed.
2. Install gas piping to rebox location. See
Installing Gas Line, page 14. You may have
to cut an access hole in the oor or wall to
run gas line to rebox. Make sure to locate
access hole so cabinet mantel will cover it
when installed (see Figure 11).
3. Place rebox on oor in desired location.
Make sure mantel will be ush against
wall when installed.
4. Carefully slide cabinet mantel over rebox.
Be careful not to scratch rebox, cabinet
mantel, ooring, etc., when installing (see
Figure 12).
5. Install and properly test gas log heater.
Follow installation instructions included
with the vent-free gas log heater that is
being installed.
Gas Line
Access Hole
(Either Side
of Firebox)
Figure 11 - Installing Cabinet Mantel
(Mantel May Vary From Illustration)
Figure 12 - Inserting Firebox Into Cabinet
Mantel (Mantel May Vary From Illustration)
Gas
Piping
124384-01a13
www.fmiproducts.com
Page 14
REFRACTORY PANEL INSTALLATION
UPPER CORNER
IMPORTANT: Installation of brick
should be done after the replace is placed in a permanent
location.
1. Remove screen assemblies and all hard-
ware components out of the rebox. The
bottom panel is preinstalled in the rebox.
Make sure the bottom refractory panels is
centered in the rebox and ush with the
front of the replace.
2. Place cardboard on top of bottom refactory panel as a protection to prevent shipping and scratching during installation of
the other panels.
LEFT BRICK
PANEL
3. Install rear refractory panel. This panel
has a top and bottom. To determine which
is which, match up the pattern on the rear
panel with the left and right sides before
installing the rear panel. Make sure panel
is center before continuing.
4. Install the right and left refractory panels
with the gas line knockouts orientated
down toward the bottom refractory. Align
the left and right panels with the rear panel
so the grout lines line up.
5. Install the upper corner brackets and
tighten set screws (Figure 13).
BRACKET (2x)
REAR BRICK
PANEL
BOTTOM
BRICK PANEL
ASH PANEL
Figure 13 - Installing Refractory Panels
www.fmiproducts.com
RIGHT BRICK
PANEL
124384-01A14
Page 15
REFRACTORY PANEL INSTALLATION
Continued
INSTALLING SCREEN
1. Slide round end of screen rod into rings at
top of screen. Attach one push-on nut to end
of rod before attaching last ring of screen.
2. Insert the round end screen rod into hole
on the left and right side of smoke shelf
(Figure 14).
3. Mount at end of screen rod with #10 x 5/8"
to center of smoke shelf.
4. Install other screen rod in same manner.
OPTIONAL GAS LINE INSTALLATION
Rating
Plate
Figure 14 - Installing Fireplace Screen
Hole for Screen
Rod
Leading
Bricks
Gas line hook up should be done by your
supplier or a qualied service person.
Note: Before you proceed, make sure your
gas supply is turned off.
Use only a 1/2" black iron pipe and appropriate ttings.
1. Remove knockout indentation on refrac-
tory or rebrick wall located above refractory hearth oor. Knockout indentation
must be rmly tapped with any solid object
such as a 1/2" dowel until it is released.
Remove fragmented portions of refractory
(see Figure 15).
2. Remove gas line cover plate located on
either side of replace and pull out insulation from gas line conduit sleeve. Save
insulation for reuse. Replace screws.
3. Run a 1/2" black iron gas line into replace
through the rear at gas line conduit sleeve (if
using a raised platform, add height). Provide
sufcient gas line into replace chamber for
tting connection (see Figure 16).
Note: Secure incoming gas line to wood
framing to provide rigidity for threaded end.
4. Repack insulation around gas line and into
sleeve opening. Seal any gaps between
gas line and refractory knockout hole with
refractory cement or commercial furnace
cement, Install the gas appliance or cap-off
gas line if desired.
Outside of
Fireplace
Gas Line
Conduit
Insulation
Gas
Conduit
Cover
Figure 15 - Gas Line Access
Outside of
Fireplace
Gas Line
Conduit
Repack
Insulation
Figure 16 - Gas Line Installation
Remove
Knockout
Incoming
1/2" Black
Iron Pipe
Seal
Opening
with
Refractory
Cement
Side
Firebrick
Finished
Side
1/2" Dowel
Brick with
Access
Hole
Side
Firebrick
Finished
Side
Provide Enough
Threaded
End for Fitting
Connection
124384-01a15
www.fmiproducts.com
Page 16
OPTIONAL GAS LINE INSTALLATION
Continued
CAUTION: All gas piping
and connections must be tested
for leaks after the installation
is completed. After ensuring
that the gas valve is on, apply
soap and water solution to all
connections and joints. Bubbles
forming show a leak. Correct
all leaks at once. DO NOT USE
AN OPEN FLAME FOR LEAK
TESTING AND DO NOT OPER-
ATE ANY APPLIANCE IF A LEAK
IS DETECTED. LEAK TESTING
SHOULD BE DONE BY A QUALI-
FIED SERVICE PERSON.
WARNING: Do not operate an
unvented gas log set in this replace with the chimney removed.
A gas line or gas log lighter may be installed
for the purpose of installing a vented or ventfree decorative gas appliance incorporating an
automatic shutoff device and complying with
the Standard for Decorative Gas Appliances for
Installation in Vented Fireplaces, ANSI Z21.60
or American Gas Association draft requirements
for Gas Fired Log Lighters for Wood Burning
Fireplaces, Draft NO. 4 dated August, 1993.
If you install a decorative gas appliance
(vented gas log), the decorative gas appliance
must comply with the Standard for Decorative
Gas Appliance for Installation in Solid Fuel
Burning Fireplaces, ANS Z21.60 or Z21.84
and shall also be installed in accordance with
the National Fuel Gas Code, ANSI 7223NFPA
54 latest edition.
If you wish to install an unvented (vent-free)
gas log set, only unvented gas log sets which
have been found to comply with the standard
for unvented room heaters, ANSI Z21.11.2 are
to be installed in this replace.
WARNING: If the replace
has been used for wood burning,
the rebox and chimney must be
cleaned of soot, creosote and
ashes be a qualied chimney
cleaner. Creosote will ignite if
heavily heated.
WARNING: When using a
decorative vented gas log, the
damper must be removed or
permanently locked in the fully
open position and the glass doors
must be in the fully open position.
www.fmiproducts.com
124384-01A16
Page 17
TECHNICAL SERVICE
You may have further questions about installation, operation, or troubleshooting.
If so, contact FMI PRODUCTS, LLC at
1-866-328-4537.
REPLACEMENT PARTS
If this product is missing a part or has a broken
component, please do not return it to the store.
Call FMI PRODUCTS, LLC at 1-866-328-4537
to answer questions and replace parts under
warranty.
Note: Use only original replacement parts.
This will protect your warranty coverage for
parts replaced under warranty.
ACCESSORIES
OPTIONAL OUTSIDE AIR KIT FOR
FLOOR INSTALLATION - AK4F
When calling please have your model and se-
rial numbers of your replace ready.
You can also visit our web site at
www.fmiproducts.com.
When calling or writing, please have your
model and serial numbers of your replace
ready.
Model and serial number information are in
the replace's rating plate located under the
ash box.
OPTIONAL OUTSIDE AIR KIT FOR
SIDEWALL INSTALLATION - AK4
124384-01a17
www.fmiproducts.com
Page 18
PARTS
9
MODELS (V)U(36,42,50)(H,S) AND (V)Q(36,42,50)(H,S)(R) SERIES
8
11
7
12
6
15/16
10
5
19
22
1
20
21
20
14
13
4
11
3
11
2
17
14
18
12
13
14
15/16
www.fmiproducts.com
124384-01A18
Page 19
This list contains replaceable parts used in your rebox. When ordering parts, follow the
PARTS
instructions listed under Replacement Parts on page 17 of this manual.
116087-02 Right Herringbone 36" Red•1
125832-02 Right Stacked 42" Red•1
125835-02 Right Herringbone 42" Red•1
125838-02 Right Stacked 50" Red•1
125841-02 Right Herringbone 50" Red•1
3 116081-02 Left Stacked 36" Red•1
116086-02 Left Herringbone 36" Red•1
125833-02 Left Stacked 42" Red•1
125836-02 Left Herringbone 42" Red•1
125839-02 Left Stacked 50" Red•1
125842-02 Left Herringbone 50" Red•1
Standard Warranty: FMI PRODUCTS, LLC warrants this new product and any parts thereof to be free from defects
in material and workmanship for a period of four (4) years from the date of rst purchase from an authorized dealer
provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s
warnings and instructions.
For products purchased for commercial, industrial or rental usage, this warranty is limited to 90 days from the date
of rst purchase.
Limited Warranty: FMI PRODUCTS, LLC warrants factory reconditioned products and any parts thereof to be
free from defects in material and workmanship for 30 days from the date of rst purchase from an authorized dealer
provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s
warnings and instructions.
The following terms apply to all of the above warranties:
Always specify model number and serial number when contacting the manufacturer. To make a claim under this
warranty the bill of sale or other proof of purchase must be presented.
This warranty is extended only to the original retail purchaser when purchased from an authorized dealer, and only
when installed by a qualied installer in accordance with all local codes and instructions furnished with this product.
This warranty covers the cost of part(s) required to restore this product to proper operating condition and an allowance for labor when provided by a FMI PRODUCTS, LLC Authorized Service Center or a provider approved by
FMI PRODUCTS, LLC. Warranty parts must be obtained through authorized dealers of this product and/or FMI
PRODUCTS, LLC who will provide original factory replacement parts. Failure to use original factory replacement
parts voids this warranty.
Travel, handling, transportation, diagnostic, material, labor and incidental costs associated with warranty repairs,
unless expressly covered by this warranty, are not reimbursable under this warranty and are the responsibility of
the owner.
Excluded from this warranty are products or parts that fail or become damaged due to misuse, accidents, improper
installation, lack of proper maintenance, tampering, or alteration(s).
This is FMI PRODUCTS, LLC’s exclusive warranty, and to the full extent allowed by law; this express warranty
excludes any and all other warranties, express or implied, written or verbal and limits the duration of any and all
implied warranties, including warranties of merchantability and tness for a particular purpose to four (4) years on
new products and 30 days on factory reconditioned products from the date of rst purchase. FMI PRODUCTS, LLC
makes no other warranties regarding this product.
FMI PRODUCTS, LLC’s liability is limited to the purchase price of the product, and FMI PRODUCTS, LLC shall not
be liable for any other damages whatsoever under any circumstances including indirect, incidental, or consequential
damages.
Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental
or consequential damages, so the above limitation or exclusion may not apply to you.
This warranty gives you specic legal rights, and you may also have other rights which vary from state to state.
For information about this warranty contact:
Factory Reconditioned Products
Terms Common to All Warranties
) _____________________________
) __________________________
New Products
2701 S. Harbor Blvd.
Santa Ana, CA 92704
1-866-328-4537
www.fmiproducts.com
124384-01
Rev.A
03/11
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.