FMI U36H, U42S, U42H, U50S, U50H Owner's Operation And Installation Manual

...
Page 1
PFS
US
UNVENTED (VENT-FREE)
UNIVERSAL FIREBOX
OWNER’S OPERATION AND
INSTALLATION MANUAL
®
INDOOR VENT FREE (V)U(36,42,50)(H,S) SERIES
INDOOR/OUTDOOR VENT FREE (V)Q(36,42,50)(H,S)(R) SERIES
FIREBOX WITH INSULATION
WARNING: If the information in this manual is not
followed exactly, a re or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other ammable
— WHAT TO DO IF YOU SMELL GAS
— Installation and service must be performed by a quali-
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
vapors and liquids in the vicinity of this or any other appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
ed installer, service agency or the gas supplier.
For more information, visit www.fmiproducts.com
Page 2
WARNING: Improper installation, adjustment, al­teration, service or maintenance can cause injury or property damage. Refer to this manual for correct in­stallation and operational procedures. For assistance or additional information consult a qualied installer, service agency or the gas supplier.
WARNING: Carefully review the instructions sup­plied with the decorative type unvented room heater for the minimum replace size requirement.
DO NOT INSTALL THE APPLIANCE IN THIS FIREBOX, UNLESS THIS FIREBOX MEETS THE MINIMUM DIMEN-
SIONS REQUIRED FOR THE INSTALLATION.
WARNING: FOR USE ONLY WITH A LISTED, GAS­FIRED UNVENTED DECORATIVE ROOM HEATER NOT
TO EXCEED 40,000 BTU/H.
DO NOT BUILD A WOOD FIRE.
TABLE OF CONTENTS
Safety .................................................................. 2
Local Codes......................................................... 4
Product Features ................................................. 4
Locating Firebox .................................................. 4
Product Specications ......................................... 5
Air For Combustion and Ventilation ..................... 8
This appliance may be installed in an aftermarket,* permanently located, manufactured (mobile) home, where not prohibited by local codes.
* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer
This firebox has been tested under Z21.91b-2007 for use with approved ANSI Z21.11.2 decorative type unvented room heater.
Installation ......................................................... 10
Firebrick Wall Installation ................................... 14
Gas Line Installation .......................................... 15
Technical Service............................................... 17
Replacement Parts ............................................ 17
Parts .................................................................. 18
Warranty ..............................................Back Cover
SAFETY
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, op­erate or service this replace. Improper use of this replace can cause serious injury or death from burns, re, explo­sion, electrical shock and carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
www.fmiproducts.com
124384-01A2
Page 3
SAFETY
Continued
WARNING: Any change to this rebox or its controls can be dangerous.
WARNING: Do not allow fans
to blow directly into the rebox. Avoid any drafts that alter burner ame patterns. Ceiling fans can create drafts that alter burner ame patterns. Altered burner patterns can cause sooting.
WARNING: Do not use a blow­er insert, heat exchanger insert or other accessory not approved for use with this rebox.
Due to high temperatures, the appliance should be located out of trafc and away from furniture and draperies.
Do not place clothing or other ammable material on or near the appliance. Never place any objects in the rebox or on logs.
Firebox front and screen be­comes very hot when running rebox. Keep children and adults
away from hot surfaces to avoid
burns or clothing ignition. Fire­box will remain hot for a time after shutdown. Allow surfaces to cool before touching.
Carefully supervise young chil-
dren when they are in the room
with rebox.
Keep the replace area clear and free from combustible materials, gasoline, and other ammable vapors and liquids.
124384-01a 3
www.fmiproducts.com
You must operate this replace with the provided fireplace screen and hood in place. Make sure these parts are in place and screens are closed before running installed gas log heater. Replace hood with
FMI PRODUCTS, LLC model
109511-01 50", 109511-02 42", or 109511-03 36" only. This hood has been designed to keep the operation of your replace safe and efcient.
1. Do not use this rebox as a wood burning replace. Use only decorative unvented
room heaters (log sets).
2. Do not add extra logs or ornaments such as
pine cones, vermiculite or rock wool. Using
these added items can cause sooting.
3. Use only the provided hood. See Parts, page 30.
4. Vent-free gas log heaters installed in these
reboxes require fresh air ventilation to
run properly. See Air for Combustion and Ventilation, page 8.
5. Do not run vent-free heaters installed in
these reboxes
• where ammable liquids or vapors are
used or stored
• under dusty conditions
6. Do not use this rebox to cook food or
burn paper or other objects.
7. Turn unit off and let cool before servicing.
Only a qualied service person should service and repair rebox.
8. Operating vent-free heaters installed in
these reboxes above elevations of 4,500
feet could cause pilot outage.
9. Do not use the rebox if it has been under water.
10. Before using furniture polish, wax, carpet
cleaner or similar products, turn heater off. If heated, the vapors from these prod-
ucts may create a white powder residue within burner box or on adjacent walls
and furniture.
11. Provide adequate clearances around air
openings.
Page 4
LOCAL CODES
Install and use rebox with care. Follow all
local codes. In the absence of local codes, use the latest edition of The National Fuel Gas Code ANSI Z223.1/NFPA 54*. Firebox must
be electrically grounded in accordance with
the National Electrical Code, ANSI/NFPA70 (latest edition).
*Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park Quincy, MA 02269
State of Massachusetts: The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts.
Sellers of unvented propane or natural gas-fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upon sale of the unit.
Vent-free gas products are prohibited for bedroom and bathroom installation in
the Commonwealth of Massachusetts.
PRODUCT FEATURES
OPERATION
This rebox is designed for use with approved
ANSI Z21.11.2 decorative type unvented room heaters. (Physical size limitations apply. Refer
to minimum rebox requirements supplied with log heater.) It requires no outside vent-
ing or chimney making installation easy and inexpensive.
LOCATING FIREBOX
PLANNING
Plan where you will install the rebox. This will save time and money later when you install the rebox. Before installation, consider the following:
1. Where rebox will be located. Allow for wall and ceiling clearances (see Installa-
tion Clearances, page 11).
2. Everything needed to complete installation.
3. These models CANNOT be installed in a bedroom unless maximum Btu rating of installed vent-free log set is less than 10,000 Btu/hr.
4. Proper air for combustion and ventilation (page 8).
www.fmiproducts.com
124384-01A4
Page 5
36" MODELS
PRODUCT SPECIFICATIONS
54
30 1/2"
11
1
/2"
30"
7
7
29"
7
4
/8"
3
/4"
3
1
/8"
50"
5
/16"
36
7"
/8"
36"
1
45
/8"
7
/16"
9
5
/16"
3
Figure 1 - 36" Models (V)U36(H,S) and (V)Q36(H,S)(R) Series
(Picture may vary from actual replace)
22 1/2"
1
35
36" HEARTH
3
7
/8"
1
/8"
11
1
20
/4"
19"
(Ref.)
1
1
/4"
/4"
124384-01a 5
www.fmiproducts.com
Page 6
42" MODELS
3
/8"
32
PRODUCT SPECIFICATIONS
Continued
5
30
/16"
26 3/8"
21
23"
3
/4"
(Ref.)
54 1/2"
11
3
41
3
3
/4"
1
/8"
30"
7
7"
7
/8"
42"
1
/8"
51
4 7/8"
36
50"
5
/16"
7
9
/16"
5
3
/16"
/8"
42" HEARTH
3
8
/4"
13"
1
1
/4"
Figure 2 - 42" Models (V)U42(H,S) and (V)Q42(H,S)(R) Series
(Picture may vary from actual replace)
www.fmiproducts.com
124384-01A6
Page 7
50" MODELS
3
32
/8"
PRODUCT SPECIFICATIONS
Continued
5
38
/16"
34 3/8"
21
23"
3
/4"
(Ref.)
54
7
/8"
3
/4"
3
1
11
/8"
1
/2"
30"
4
50"
3
49
/8"
50" HEARTH
1
/4"
1
365/16"
7
7
7
/8"
7"
50"
1
/8"
59
/16"
9
5
3
/16"
3
8
/4"
13"
Figure 3 - 50" Models (V)U50(H,S) AND (V)Q50(H,S)(R) Series
(Picture may vary from actual replace)
124384-01a 7
www.fmiproducts.com
Page 8
AIR FOR COMBUSTION AND VENTILATION
WARNING: This heater shall
not be installed in a room or space unless the required volume of in­door combustion air is provided by the method described in the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, the International Fuel Gas Code, or applicable lo-
cal codes. Read the following in­structions to insure proper fresh air for this and other fuel-burning appliances in your home.
Today’s homes are built more energy efcient than ever. New materials, increased insulation and new construction methods help reduce heat loss in homes. Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in. Dur­ing heating months, home owners want their
homes as airtight as possible. While it is good to make your home energy
efcient, your home ne eds to breathe. Fresh
air must enter your home. All fuel-burning ap­pliances need fresh air for proper combustion and ventilation.
Exhaust fans, replaces, clothes dryers and fuel burning appliances draw air from the house to operate. You must provide adequate fresh air for these appliances. This will insure proper
venting of vented fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three
following ventilation classications:
1. Unusually Tight Construction
2. Unconned Space
3. Conned Space The information on pages 8 through 10 will help
you classify your space and provide adequate
ventilation.
Unusually Tight Construction
The air that leaks around doors and windows
may provide enough fresh air for combustion and ventilation. However, in buildings of un­usually tight construction, you must provide additional fresh air.
www.fmiproducts.com
Unusually tight construction is dened as
construction where:
a. walls and ceilings exposed to the out-
side atmosphere have a continuous water vapor retarder with a rating of one perm (6 x 10 less with openings gasketed or sealed
and
b. weather stripping has been added on
openable windows and doors and
c. caulking or sealants are applied to
areas such as joints around window and door frames, between sole plates and oors, between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines and at other openings.
If your home meets all of the three criteria
above, you must provide additional fresh air. See Ventilation Air From Outdoors, page 10.
If your home does not meet all of the three
criteria above, proceed to Determining Fresh-Air Flow For Firebox Location.
Conned and Unconned Space
The National Fuel Gas Code, ANSI Z223.1/ NFPA 54 denes a conned space as a space
whose volume is less than 50 cubic feet per
1,000 Btu per hour (4.8 m3 per kw) of the ag­gregate input rating of all appliances installed
in that space and an unconned space as a space whose volume is not less than 50 cubic
feet per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating of all appliances installed in that space. Rooms communicating
directly with the space in which the appliances
are installed*, through openings not furnished
with doors, are considered a part of the un­conned space.
* Adjoining rooms are communicating only if
there are doorless passageways or ventilation grills between them.
-11
kg per pa-sec-m2) or
DETERMINING FRESH-AIR FLOW FOR FIREBOX LOCATION
Determining if You Have a Conned or Unconned Space
Use this work sheet to determine if you have a conned or unconned space.
Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.
124384-01A8
Page 9
Or
Remove Door into Adjoining
Room, Option
3
Ventilation Grills
Into Adjoining Room,
Option 2
Ventilation
Grills Into
Adjoining
Room,
Option 1
12"
12"
AIR FOR COMBUSTION AND VENTILATION
Continued
1. Determine the volume of the space (length
x width x height).
Length x Width x Height =__________cu. ft.
(volume of space)
Example: Space size 22 ft. (length) x 18 ft.
(width) x 8 ft. (ceiling height) = 3,168 cu. ft.
(volume of space)
If additional ventilation to adjoining room
is supplied with grills or openings, add the
volume of these rooms to the total volume of the space.
2. Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.
________ (volume of space) x 20 = (Maxi-
mum Btu/Hr the space can support)
Example: 3,168 cu. ft. (volume of space) x 20 =
63,360 (maximum Btu/Hr space can support)
3. Add the Btu/Hr of all fuel burning appliances in the space.
Vent-free replace _________ Btu/Hr Gas water heater* _________ Btu/Hr
Gas furnace _________ Btu/Hr Vented gas heater _________ Btu/Hr Gas replace logs _________ Btu/Hr Other gas appliances* + _________ Btu/Hr Total = _________ Btu/Hr * Do not include direct-vent gas appliances.
Direct-vent draws combustion air from the
outdoors and vents to the outdoors.
Example:
Gas water heater _________ Btu/Hr Vent-free replace + _________ Btu/Hr
Total = _________ Btu/Hr
40,000 39,000 79,000
4. Compare the maximum Btu/Hr the space
can support with the actual amount of Btu/Hr
used.
_______ Btu/Hr (maximum the space can
support)
_______ Btu/Hr (actual amount of Btu/Hr
used)
Example: 63,360 Btu/Hr (maximum the
space can support)
79,000 Btu/Hr (actual amount of
Btu/Hr used)
The space in the example is a conned space
because the actual Btu/Hr used is more than the
maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:
A. Rework worksheet, adding the space of an
adjoining room. If the extra space provides an
unconned space, remove door to adjoining room or add ventilation grills between rooms.
B. Vent room directly to the outdoors. See
C. Install a lower Btu/Hr replace, if lower Btu/
124384-01a 9
See Ventilation Air From Inside Building.
Ventilation Air From Outdoors, page 10.
Hr size makes room unconned.
www.fmiproducts.com
If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the
space is an unconned space. You will need
no additional fresh air ventilation.
WARNING: If the area in which
the heater may be operated does not meet the required volume for indoor combustion air, combus­tion and ventilation air shall be provided by one of the methods described in the National Fuel
Gas Code, ANSI Z223.1/NFPA 54, the International Fuel Gas Code,
or applicable local codes.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconned space. When ventilating to an adjoining unconned space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the oor on the wall connecting the two spaces (see options 1 and 2, Figure 4). You can also remove door
into adjoining room (see option 3, Figure 4 ).
Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation for required size of ventilation
grills or ducts.
Figure 4 - Ventilation Air from Inside
Building
Page 10
Outlet Air
Ventilated Attic
Outlet Air
Inlet Air
Inlet Air
Ventilated
Crawl Space
To
Crawl
Space
To Attic
AIR FOR COMBUSTION AND VENTILATION
Continued
Ventilation Air From Outdoors
Provide extra fresh air by using ventilation
grills or ducts. You must provide two perma­nent openings: one within 12" of the ceiling and one within 12" of the oor. Connect these
items directly to the outdoors or spaces open to the outdoors. These spaces include attics
and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Air for Combustion and Ventilation for required size
of ventilation grills or ducts. IMPORTANT: Do not provide openings for
inlet or outlet air into attic if attic has a thermo-
stat-controlled power vent. Heated air entering the attic will activate the power vent.
INSTALLATION
Figure 5 - Ventilation Air from Outdoors
WARNING: A qualied ser­vice person must install rebox. Follow all local codes.
WARNING: Never install
rebox
• in a bedroom or bathroom*
• in a recreational vehicle
• where curtains, furniture,
clothing, or other ammable objects are less than 36" from front or 42" from top of rebox; for side clearances see Figure 4, page 11
• in high trafc areas
• in windy or drafty areas * Unless installed log set is rated
at 10,000 Btu/Hr or less.
CAUTION: Log heaters installed in this rebox create warm air currents. These currents
move heat to wall surfaces next
to rebox. Installing rebox next to vinyl or cloth wall coverings or operating rebox where impuri­ties (such as, but not limited to, to­bacco smoke, aromatic candles, cleaning uids, oil or kerosene lamps, etc.) in the air exist, may discolor walls or cause odors.
www.fmiproducts.com
NOTICE: The rebox identica­tion label (including model num­ber, serial number, clearances, etc.) is located on a chain under the bottom refractory.
IMPORTANT: Vent-free gas log heaters add
moisture to the air. Although this is benecial, installing rebox in rooms without enough ventilation air may cause mildew to form from
too much moisture. See, page 8.
IMPORTANT: Make sure the rebox is level. If rebox is not level, log set will not work
properly.
Note: Your rebox is designed to be used in
zero clearance installations. Wall or framing material can be placed against any exterior surface on the rear, sides, top or bottom of
your rebox, except where standoff spacers
are integrally attached. If standoff spacers are
attached to your rebox, these spacers can be placed directly against wall or framing ma­terials. Use the dimensions shown for rough
opening to create the easiest installation.
Use dimensions shown for rough openings
to create the easiest installation (see Built-In Firebox Installation, page 12).
124384-01A10
Page 11
INSTALLATION CLEARANCES
Supplied Firebox Hood Must Be Used at All Times
Wire-mesh Screen
Firebox
Noncombustible Material May Project Off this Surface above the Firebox Hood
Mantel Shelf
Note: Any portion of the mantel shelf must NOT extend beyond this profile.
12" 16" 20"
1
1
/
2"
6
3
/
4
"
12"
Note: All vertical measurements are from top of fireplace hood opening to bottom of mantel shelf. These minimum clearances replace any other recommended clearances supplied with your ANSI Z21.11.2 approved gas logs.
Wall board or facing material (above firebox) may be of combustible material, including decorative mantel ornaments or other similar projec­tions off of the facing material.
Framing Material
minimum clearances. If you can, provide greater clearances from oor, ceiling, and adjoin­ing wall.
Carefully follow the instructions below. This will ensure safe installation.
Minimum Wall and Ceiling Clearances (see Figure 6)
A. Clearances from the side of the replace
Example: The face of a mantel, bookshelf,
B. Clearances from the top of the rebox
C. When the rebox is installed directly on
D. Clearances from the bottom of rebox to
These reboxes can be installed as free­standing units against a wall with approved
cabinet mantels that may be available from your retailer or supplier, or as a built-in unit. The clearances are the same for either instal­lation method.
*Minimum 16" from Side Wall
124384-01a 11
INSTALLATION
Continued
WARNING: Maintain the
cabinet to any combustible material and
wall should follow diagram in Figure 6.
etc. is made of combustible material and protrudes 3 1/2" from the wall. This com-
bustible material must be 4" from the side of the replace cabinet (see Figure 4).
opening to the ceiling should not be less
than 42".
carpeting, tile or other combustible mate-
rial, other than wood ooring, the rebox should be installed on a metal or wood panel extending the full width and depth
of the enclosure.
the oor is 0".
Example
Figure 6 - Minimum Clearance for
Combustible to Wall
*
www.fmiproducts.com
Mantel Clearances for Built-In Installation
If placing custom mantel above built-in re­box, you must meet the minimum allowable clearance between mantel shelf and top of rebox opening shown in Figure 7. These are the minimum allowable mantel clearances for a safe installation. Use larger clearances wherever possible to minimize the heating of
objects and materials placed on the mantel.
CAUTION: Do not allow the
vent-free gas log heater to touch or extend beyond the replace screen.
NOTICE: Surface temperatures of adjacent walls and mantels become hot during operation. Walls and mantels above the firebox may become hot to the touch. If installed properly, these temperatures meet the requirement of the national product standard. Follow all
minimum clearances shown in
this manual.
Figure 7 - Minimum Mantel Clearances
for Built-In Installation
Page 12
INSTALLATION
Continued
NOTICE: If your installation does not meet the minimum clear­ances shown, you must do one
of the following:
• raise the mantel to an accept-
able height
• remove the mantel
BUILT-IN FIREBOX INSTALLATION
Built-in installation of this rebox involves installing rebox into a framed-in enclosure. This makes the front of rebox ush with wall. If installing a mantel above the rebox, you must follow the clearances shown in Figure 7, page 11. Follow these instructions to install the rebox in this manner.
1. Frame in rough opening. The rebox fram-
ing should be constructed of 2 x 4 lumber
or heavier. Use dimensions and rough
opening layout in Figure 8. Adjust framing
so that rebox ushes with nished wall
surface. If installing in a corner, use dimen­sions in Figure 9, for rough opening.
2. Install gas piping to rebox location. See
Installing Gas Line on page 14 and Con­necting to Gas Supply in log set owner’s
manual.
3. Carefully set firebox in front of rough
opening with back of rebox inside wall
opening.
4. Carefully insert rebox into rough opening.
5. Attach rebox to wall studs using nails or wood screws through holes in nailing ange (see Figure 10).
6. Install and properly test gas log heater.
Follow installation instructions included with the vent-free gas log heater that is
being installed.
IMPORTANT: When nishing your rebox, combustible materials such as wall board, gypsum board, sheet rock, drywall, plywood,
etc. may be butted up next to the sides and top
of the rebox. Combustible materials should never overlap the rebox front facing.
WARNING: Do not allow any
combustible materials to overlap the rebox front facing.
IMPORTANT: Noncombustible materials such as brick, tile, etc. may overlap the front fac­ing, but should never cover any necessary openings.
WARNING: Do not allow non-
combustible materials to cover any necessary openings.
54.625"
45.375" (36" Models)
51.375" (42" Models)
59.375" (50" Models)
Figure 8 - Framing Dimensions
Maintain 1 Clearance at Sides
61" (36" Models) 65" (42" Models) 71" (50" Models)
86.5" (36" Models) 92" (42" Models)
100" (50" Models)
and Back of Fireplace
Figure 9 - Corner Installation
Nails or Wood
Screws
30.125"
28.250"
(36" Models)
1
/2"
1
1
/2" Clearance Not Required at Nailing Flanges
Figure 10 - Attaching Firebox to Wall
www.fmiproducts.com
Nailing Flanges
Studs
124384-01A12
Page 13
INSTALLATION
Continued
WARNING: Use only non-
combustible mortar or adhe­sives when overlapping the front facing with noncombustible facing material.
Cabinet Mantel
INSTALLING FIREBOX USING OPTIONAL CUSTOM BUILT MANTELS
WARNING: A qualied ser­vice person must install rebox. Follow all local codes.
This rebox may be installed using a cabinet mantel against a wall in your home. The rebox and cabinet mantel can be installed directly on the oor. Mantels may be avail-
able from your retailer or custom built for your home.
1. Assemble cabinet mantel as instructed.
2. Install gas piping to rebox location. See Installing Gas Line, page 14. You may have to cut an access hole in the oor or wall to run gas line to rebox. Make sure to locate access hole so cabinet mantel will cover it when installed (see Figure 11).
3. Place rebox on oor in desired location. Make sure mantel will be ush against wall when installed.
4. Carefully slide cabinet mantel over rebox. Be careful not to scratch rebox, cabinet mantel, ooring, etc., when installing (see
Figure 12).
5. Install and properly test gas log heater.
Follow installation instructions included with the vent-free gas log heater that is
being installed.
Gas Line Access Hole (Either Side of Firebox)
Figure 11 - Installing Cabinet Mantel
(Mantel May Vary From Illustration)
Figure 12 - Inserting Firebox Into Cabinet
Mantel (Mantel May Vary From Illustration)
Gas Piping
124384-01a 13
www.fmiproducts.com
Page 14
REFRACTORY PANEL INSTALLATION
UPPER CORNER
IMPORTANT: Installation of brick should be done after the re­place is placed in a permanent location.
1. Remove screen assemblies and all hard-
ware components out of the rebox. The bottom panel is preinstalled in the rebox.
Make sure the bottom refractory panels is
centered in the rebox and ush with the front of the replace.
2. Place cardboard on top of bottom refac­tory panel as a protection to prevent ship­ping and scratching during installation of the other panels.
LEFT BRICK PANEL
3. Install rear refractory panel. This panel
has a top and bottom. To determine which is which, match up the pattern on the rear panel with the left and right sides before
installing the rear panel. Make sure panel is center before continuing.
4. Install the right and left refractory panels
with the gas line knockouts orientated down toward the bottom refractory. Align the left and right panels with the rear panel
so the grout lines line up.
5. Install the upper corner brackets and
tighten set screws (Figure 13).
BRACKET (2x)
REAR BRICK
PANEL
BOTTOM BRICK PANEL
ASH PANEL
Figure 13 - Installing Refractory Panels
www.fmiproducts.com
RIGHT BRICK
PANEL
124384-01A14
Page 15
REFRACTORY PANEL INSTALLATION
Continued
INSTALLING SCREEN
1. Slide round end of screen rod into rings at top of screen. Attach one push-on nut to end of rod before attaching last ring of screen.
2. Insert the round end screen rod into hole on the left and right side of smoke shelf (Figure 14).
3. Mount at end of screen rod with #10 x 5/8"
to center of smoke shelf.
4. Install other screen rod in same manner.
OPTIONAL GAS LINE INSTALLATION
Rating Plate
Figure 14 - Installing Fireplace Screen
Hole for Screen
Rod
Leading Bricks
Gas line hook up should be done by your
supplier or a qualied service person.
Note: Before you proceed, make sure your gas supply is turned off.
Use only a 1/2" black iron pipe and appropri­ate ttings.
1. Remove knockout indentation on refrac-
tory or rebrick wall located above refrac­tory hearth oor. Knockout indentation must be rmly tapped with any solid object such as a 1/2" dowel until it is released.
Remove fragmented portions of refractory (see Figure 15).
2. Remove gas line cover plate located on either side of replace and pull out insula­tion from gas line conduit sleeve. Save
insulation for reuse. Replace screws.
3. Run a 1/2" black iron gas line into replace
through the rear at gas line conduit sleeve (if using a raised platform, add height). Provide
sufcient gas line into replace chamber for tting connection (see Figure 16).
Note: Secure incoming gas line to wood
framing to provide rigidity for threaded end.
4. Repack insulation around gas line and into
sleeve opening. Seal any gaps between gas line and refractory knockout hole with
refractory cement or commercial furnace cement, Install the gas appliance or cap-off gas line if desired.
Outside of Fireplace
Gas Line Conduit
Insulation
Gas Conduit Cover
Figure 15 - Gas Line Access
Outside of Fireplace
Gas Line Conduit
Repack Insulation
Figure 16 - Gas Line Installation
Remove
Knockout
Incoming
1/2" Black
Iron Pipe
Seal Opening
with
Refractory Cement
Side Firebrick Finished Side
1/2" Dowel
Brick with
Access Hole
Side Firebrick Finished Side
Provide Enough Threaded End for Fitting Connection
124384-01a 15
www.fmiproducts.com
Page 16
OPTIONAL GAS LINE INSTALLATION
Continued
CAUTION: All gas piping
and connections must be tested
for leaks after the installation
is completed. After ensuring that the gas valve is on, apply soap and water solution to all connections and joints. Bubbles forming show a leak. Correct all leaks at once. DO NOT USE AN OPEN FLAME FOR LEAK
TESTING AND DO NOT OPER-
ATE ANY APPLIANCE IF A LEAK IS DETECTED. LEAK TESTING
SHOULD BE DONE BY A QUALI-
FIED SERVICE PERSON.
WARNING: Do not operate an unvented gas log set in this re­place with the chimney removed.
A gas line or gas log lighter may be installed for the purpose of installing a vented or vent­free decorative gas appliance incorporating an
automatic shutoff device and complying with
the Standard for Decorative Gas Appliances for Installation in Vented Fireplaces, ANSI Z21.60 or American Gas Association draft requirements for Gas Fired Log Lighters for Wood Burning Fireplaces, Draft NO. 4 dated August, 1993.
If you install a decorative gas appliance (vented gas log), the decorative gas appliance
must comply with the Standard for Decorative Gas Appliance for Installation in Solid Fuel Burning Fireplaces, ANS Z21.60 or Z21.84
and shall also be installed in accordance with
the National Fuel Gas Code, ANSI 7223NFPA 54 latest edition.
If you wish to install an unvented (vent-free) gas log set, only unvented gas log sets which have been found to comply with the standard
for unvented room heaters, ANSI Z21.11.2 are
to be installed in this replace.
WARNING: If the replace has been used for wood burning, the rebox and chimney must be
cleaned of soot, creosote and
ashes be a qualied chimney cleaner. Creosote will ignite if heavily heated.
WARNING: When using a decorative vented gas log, the damper must be removed or permanently locked in the fully open position and the glass doors must be in the fully open position.
www.fmiproducts.com
124384-01A16
Page 17
TECHNICAL SERVICE
You may have further questions about in­stallation, operation, or troubleshooting. If so, contact FMI PRODUCTS, LLC at 1-866-328-4537.
REPLACEMENT PARTS
If this product is missing a part or has a broken component, please do not return it to the store.
Call FMI PRODUCTS, LLC at 1-866-328-4537 to answer questions and replace parts under warranty.
Note: Use only original replacement parts.
This will protect your warranty coverage for parts replaced under warranty.
ACCESSORIES
OPTIONAL OUTSIDE AIR KIT FOR FLOOR INSTALLATION - AK4F
When calling please have your model and se-
rial numbers of your replace ready. You can also visit our web site at
www.fmiproducts.com.
When calling or writing, please have your model and serial numbers of your replace
ready. Model and serial number information are in
the replace's rating plate located under the
ash box.
OPTIONAL OUTSIDE AIR KIT FOR SIDEWALL INSTALLATION - AK4
124384-01a 17
www.fmiproducts.com
Page 18
PARTS
9
MODELS (V)U(36,42,50)(H,S) AND (V)Q(36,42,50)(H,S)(R) SERIES
8
11
7
12
6
15/16
10
5
19
22
1
20
21
20
14
13
4
11
3
11
2
17
14
18
12
13
14
15/16
www.fmiproducts.com
124384-01A18
Page 19
This list contains replaceable parts used in your rebox. When ordering parts, follow the
PARTS
instructions listed under Replacement Parts on page 17 of this manual.
KEY NO. PART NO. DESCRIPTION QTY.
(V)U36
1 ** Face Assembly • • • • • • 1 2 ** Firebox Bottom Assembly • • • • • • 1 3 ** Firebox Bottom • • • • • • 1 4 ** Firebox Surround • • • • • • 1 5 ** Insulation Pan Support • • • • • • 1 6 ** Insulation Pan • • • • • • 1 7 ** Top Insulation • • • • • • 1 8 110454-03 Fireplace Top 36" 1
110454-02 Fireplace Top 42" 1
110454-01 Fireplace Top 50" 1 9 23490SA Standoff • • • • • • 4 10 ** Fireplace Surround Assembly • • • • • • 1 11 109720-02 Clearance Spacer • • • • • • 6 12 117891-01 Fireplace Handle Bracket • • • • • • 4 13 20042 Outside Air Cover Plate • • • • • • 2 14 21171 Gas Conduit Cover • • • • • • 4 15 109752-01 Conduit One • • • • • • 2 16 109752-02 Conduit Two • • • • • • 2 17 ** Heat Shield Support • • • • • • 1 18 123298-03 Ash Box Assembly • • • • • • 1 19 ** Firebox Top • • • • • • 1 20 109457-03 Screen 36" 2
109457-02 Screen 42" 2
109457-01 Screen 50" 2
117556-03 Screen 36" Stainless 2
117556-02 Screen 42" Stainless 2
117556-01 Screen 50" Stainless 2 21 20806 Screen Rod 36" 2
110146-03 Screen Rod 42" 2
110146-02 Screen Rod 50" 2
117568-03 Screen Rod 36" Stainless 2
117568-02 Screen Rod 42" Stainless 2
117568-01 Screen Rod 50" Stainless 2 22 109511-01 Hood 50" 1
109511-02 Hood 42" 1
109511-03 Hood 36" 1
109511-04 Hood Stainless 36" 1
109511-05 Hood Stainless 42" 1
109511-06 Hood Stainless 50" 1
PARTS AVAILABLE NOT SHOWN
109714-02 Side Firebrick Wall Spacers • • 4
114913-01 Rear Firebrick Wall Spacers • • 2
114913-01 Rear Firebrick Wall Spacers • • • • 6
** Not a eld replaceable part.
(V)U42
(V)U50
(V)Q36
(V)Q42
(V)Q50
124384-01a 19
www.fmiproducts.com
Page 20
PARTS
6
MODELS (V)U(36,42,50)(H,S) AND (V)Q(36,42,50)(H,S)(R) SERIES
Picture may vary from actual
4
6
3
2
5
1
www.fmiproducts.com
124384-01A20
Page 21
This list contains replaceable parts used in your rebox. When ordering parts, follow the
PARTS
instructions listed under Replacement Parts on page 23 of this manual.
KEY NO. PART NO. DESCRIPTION QTY.
1 116084-02 Hearth 36" Red • • 1
111426-02 Hearth 42" Red • • 1 111428-02 Hearth 50" Red • • 1
2 116082-02 Right Stacked 36" Red 1
116087-02 Right Herringbone 36" Red 1 125832-02 Right Stacked 42" Red 1 125835-02 Right Herringbone 42" Red 1 125838-02 Right Stacked 50" Red 1 125841-02 Right Herringbone 50" Red 1
3 116081-02 Left Stacked 36" Red 1
116086-02 Left Herringbone 36" Red 1 125833-02 Left Stacked 42" Red 1 125836-02 Left Herringbone 42" Red 1 125839-02 Left Stacked 50" Red 1 125842-02 Left Herringbone 50" Red 1
4 116083-02 Rear Stacked 36" Red 1
116088-02 Rear Herringbone 36" Red 1 125831-02 Rear Stacked 42" Red 1 125834-02 Rear Herringbone 42" Red 1 125837-02 Rear Stacked 50" Red 1 125840-02 Rear Herringbone 50" Red 1
5 116091-02 Ash Panel 36" Red • • 1
111425-02 Ash Panel 42" Red • • 1
111430-02 Ash Panel 50" Red • • 1
6 110822-01 Corner Refractory Bracket • • • • • 2
U36S, Q36SR
U36H, Q36HR
U42S, Q42SR
U42H, Q42HR
U50S, Q50SR
U50H, Q50HR
124384-01a 21
www.fmiproducts.com
Page 22
This list contains replaceable parts used in your rebox. When ordering parts, follow the
PARTS
instructions listed under Replacement Parts on page 23 of this manual.
KEY NO. PART NO. DESCRIPTION QTY.
1 116084-01 Hearth 36" Natural White • • 1
111426-01 Hearth 42" Natural White • • 1
111428-01 Hearth 50" Natural White • • 1
2 116082-01 Right Stacked 36" Natural White 1
116087-01 Right Herringbone 36" Natural White 1 125832-01 Right Stacked 42" Natural White 1 125835-01 Right Herringbone 42" Natural White 1 125838-01 Right Stacked 50" Natural White 1 125841-01 Right Herringbone 50" Natural White 1
3 116081-01 Left Stacked 36" Natural White 1
116086-01 Left Herringbone 36" Natural White 1 125833-01 Left Stacked 42" Natural White 1 125836-01 Left Herringbone 42" Natural White 1 125839-01 Left Stacked 50" Natural White 1 125842-01 Left Herringbone 50" Natural White 1
4 116083-01 Rear Stacked 36" Natural White 1
116088-01 Rear Herringbone 36" Natural White 1 125831-01 Rear Stacked 42" Natural White 1 125834-01 Rear Herringbone 42" Natural White 1 125837-01 Rear Stacked 50" Natural White 1 125840-01 Rear Herringbone 50" Natural White 1
5 116091-01 Ash Panel 36" Natural White • • 1
111425-01 Ash Panel 42" Natural White • • 1
111430-01 Ash Panel 50" Natural White • • 1
6 110822-01 Corner Refractory Bracket • • • • • 2
VU36S, Q36S,VQ36S
VU36H, Q36H, VQ36H
VU42S, Q42S, VQ42S
VU50S, Q50S, VQ50S
VU42H, Q42H, VQ42H
VU50H, Q50H, VQ50H
www.fmiproducts.com
124384-01A22
Page 23
NOTES
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
_____________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________
124384-01a 23
www.fmiproducts.com
Page 24
WARRANTY
KEEP THIS WARRANTY
Model (
located on product or identication tag
Serial No. (
located on product or identication tag
Date Purchased __________________________
Keep receipt for warranty verication.
FMI PRODUCTS, LLC LIMITED WARRANTIES
Standard Warranty: FMI PRODUCTS, LLC warrants this new product and any parts thereof to be free from defects in material and workmanship for a period of four (4) years from the date of rst purchase from an authorized dealer provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s warnings and instructions.
For products purchased for commercial, industrial or rental usage, this warranty is limited to 90 days from the date of rst purchase.
Limited Warranty: FMI PRODUCTS, LLC warrants factory reconditioned products and any parts thereof to be free from defects in material and workmanship for 30 days from the date of rst purchase from an authorized dealer provided the product has been installed, maintained and operated in accordance with FMI PRODUCTS, LLC’s warnings and instructions.
The following terms apply to all of the above warranties:
Always specify model number and serial number when contacting the manufacturer. To make a claim under this warranty the bill of sale or other proof of purchase must be presented.
This warranty is extended only to the original retail purchaser when purchased from an authorized dealer, and only when installed by a qualied installer in accordance with all local codes and instructions furnished with this product.
This warranty covers the cost of part(s) required to restore this product to proper operating condition and an allow­ance for labor when provided by a FMI PRODUCTS, LLC Authorized Service Center or a provider approved by FMI PRODUCTS, LLC. Warranty parts must be obtained through authorized dealers of this product and/or FMI PRODUCTS, LLC who will provide original factory replacement parts. Failure to use original factory replacement parts voids this warranty.
Travel, handling, transportation, diagnostic, material, labor and incidental costs associated with warranty repairs, unless expressly covered by this warranty, are not reimbursable under this warranty and are the responsibility of the owner.
Excluded from this warranty are products or parts that fail or become damaged due to misuse, accidents, improper
installation, lack of proper maintenance, tampering, or alteration(s).
This is FMI PRODUCTS, LLC’s exclusive warranty, and to the full extent allowed by law; this express warranty excludes any and all other warranties, express or implied, written or verbal and limits the duration of any and all implied warranties, including warranties of merchantability and tness for a particular purpose to four (4) years on new products and 30 days on factory reconditioned products from the date of rst purchase. FMI PRODUCTS, LLC makes no other warranties regarding this product.
FMI PRODUCTS, LLC’s liability is limited to the purchase price of the product, and FMI PRODUCTS, LLC shall not be liable for any other damages whatsoever under any circumstances including indirect, incidental, or consequential
damages.
Some states do not allow limitations on how long an implied warranty lasts or the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.
This warranty gives you specic legal rights, and you may also have other rights which vary from state to state.
For information about this warranty contact:
Factory Reconditioned Products
Terms Common to All Warranties
) _____________________________
) __________________________
New Products
2701 S. Harbor Blvd.
Santa Ana, CA 92704
1-866-328-4537
www.fmiproducts.com
124384-01 Rev.A 03/11
Loading...