consult a qualified installer, service agency or
the gas supplier.
This appliance may be in-
stalled in an aftermarket,*
permanently located,
manufactured (mobile)
home, where not prohibited by local codes.
This appliance is only for
use with the type of gas
indicated on the rating
plate. This appliance is
not convertible for use
with other gases, unless
a certied kit is used.
* Aftermarket: Completion of sale, not for
purpose of resale, from the manufacturer
This direct-vent gas replace series is intended
for use with natural or
propane/LP gas only. Do
not attempt to burn any
solid fuels in these appliances.
State of Massachusetts:
The installation must
be made by a licensed
plumber or gas tter in
the Commonwealth of
Massachusetts.
WARNING: This product con-
tains and/or generates chemicals
known to the State of California
to cause cancer or birth defects
or other reproductive harm.
IMPORTANT: Check local codes
before installing this replace.
IMPORTANT: Read this owner’s
manual carefully and completely
before trying to assemble, operate or service this replace.
Improper use of this replace
can cause serious injury or
death from burns, re, explosion, electrical shock and carbon
monoxide poisoning.
www.fmiproducts.com
56131L2
SAFETY
Continued
DANGER: Carbon monoxide
poisoning may lead to death!
Before beginning the installation of replace,
read these instructions through completely.
• This FMI PRODUCTS, LLC replace and
its components are safe when installed
according to this installation manual.
Unless you use FMI PRODUCTS, LLC
components, which have been designed
and tested for the replace system, you
may cause a re hazard.
• The FMI PRODUCTS, LLC warranty will
be voided by and FMI PRODUCTS, LLC
disclaims any responsibility for the following actions:
a. Modification of the fireplace, com-
ponents, doors, air inlet system and
damper control.
b. Use of any component part not manu-
factured or approved by FMI PRODUCTS, LLC in combination with a FMI
PRODUCTS, LLC replace system.
c) Installation and/or operation in a
manner other than instructed in this
manual.
d) Burning of anything other than the type
of gas approved for use in this gas
appliance.
This appliance, when installed, must be
electrically grounded in accordance with local codes, or in the absence of local codes,
with the National Electrical Code, ANSI/NFPA 70.
The installation must conform to local codes,
or in the absence of local codes, with the
National Fuel Gas Code ANSI Z223.1.
This fireplace complies with the National
Safety Standards and is listed and tested by
PFS Corporation to ANSI Z21.50/CSA 2.22
standard as vented gas replace.
Proper installation is the most important step
in ensuring safe and continuous operation
of the replace. Consult the local building
codes as to the particular requirements
concerned with the installation of all factory
built replaces.
NOTICE: Decorative product not
for use as a heating appliance.
This replace must be installed by a qualied
(certied or licensed) service person. It has
a sealed gas combustion chamber that uses
a millivolt gas control valve with a millivolt
ignition system.
Models (V)DVF36TPNA/TPNPA series are
three-sided direct-vent gas replaces and
models (V)DVF36TSTA/TSTPA are two-sided
direct-vent gas replace replaces with sealed
combustion chambers.
Models (V)DVF36TPNEA/TPNPEA and (V)
DVF36STEA/TSTPEA use a direct spark
ignition with a 24 VAC control module. All
models have HI/LO valve that controls the
ame height. These units can be equipped
with louvers for circulating or with panels for
noncirculating operation.
Fan Kit model DVFFBK are available for these
units as an option. If you are uncertain as to
what gas your unit is equipped for, please
check the rating plate located in the interior
of the appliance opening or consult your local
FMI PRODUCTS, LLC distributor.
Carbon Monoxide Poisoning: Early signs
of carbon monoxide poisoning resemble the
u, with headaches, dizziness or nausea. If
you have these signs, the replace may not
be working properly. Get fresh air at once!
Have replace serviced. Some people are
more affected by carbon monoxide than others. These include pregnant women, people
with heart or lung disease or anemia, those
under the inuence of alcohol and those at
high altitudes.
Natural and Propane/LP Gas: Natural and
propane/LP gas are odorless. An odor-making
agent is added to the gas. The odor helps you
detect a gas leak. However, the odor added to
the gas can fade. Gas may be present even
though no odor exists.
Make certain you read and understand all
warnings. Keep this manual for reference. It
is your guide to safe and proper operation of
this replace.
WARNING: Any change to
this replace or it’s controls can
be dangerous. Do not modify
this replace under any circumstances. Any parts removed for
servicing must be replaced prior
to operating replace.
56131L3
www.fmiproducts.com
SAFETY
Continued
WARNING: Do not use a blower insert, heat exchanger insert or
other accessory not approved for use with this replace.
WARNING: This appliance is only for use with the type of gas
indicated on the rating plate. This appliance is not convertible for
use with other gases unless a certied kit is used.
WARNING: Do not allow fans to blow directly into the replace.
Avoid any drafts that alter burner ame patterns.
Due to high temperatures, the appliance should be located out of
trafc and away from furniture and draperies.
Do not place clothing or other ammable material on or near the
appliance. Never place any objects on the appliance.
Do not use this replace to cook food or burn paper or other ammable material.
This replace reaches high temperatures. Keep children and adults
away from hot surface to avoid burns or clothing ignition. Fireplace
will remain hot for a time after shutdown. Allow surface to cool
before touching.
Carefully supervise young children when they are in the room with
replace.
Keep area around your replace clear of combustible materials, gasoline and other ammable vapor or liquids. Do not run replace where
these are used or stored.
www.fmiproducts.com
56131L4
SAFETY
Continued
1. For propane/LP replace, do not place
propane/LP supply tank(s) inside any
structure. Locate propane/LP supply
tank(s) outdoors. To prevent performance
problems, do not use propane/LP fuel tank
of less than 100 lbs. capacity.
2. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do
not use any phone in your building
• immediately call your gas supplier from
a neighbor’s phone. Follow the gas supplier's instructions
• if you cannot reach you gas supplier,
call the re department
3. Never install the replace
• in a recreational vehicle
• in windy or drafty areas where curtains
or other combustible (ammable) objects
can make contact with the replace front
• in high trafc areas
4. Turn fireplace off and let cool before
servicing, installing or repairing. Only a
qualied service person should install,
service or repair this replace. Have replace inspected annually by a qualied
service person.
5. You must keep control compartments,
burners and circulating air passages
clean. More frequent cleaning may be
needed due to excessive lint and dust
from carpeting, bedding material, etc.
Turn off the gas valve and pilot light before
cleaning replace.
6. Have venting system inspected annually by a qualified service person. If
needed, have venting system cleaned or
repaired.
7. Do not use any solid fuels (wood, coal,
paper, cardboard, etc.) in this replace.
Use only the gas type indicated on re-
place nameplate.
8. Do not use replace if any part has been
exposed to or under water. Immediately
call a qualied service person to arrange
for replacement of the unit.
9.
Do not operate replace if any log is broken.
10. Do not operate replace with glass door
removed, cracked or broken.
11. Provide adequate clearances around air
openings.
12. Fireplaces with the sufx of -HA have been
designed to operate at altitudes of 4000
feet and above. For horizontal installations above 2,000 feet, it is recommended
that a 12" extension pipe be added before
starter elbow (see High Altitude Installa-
tion, page 21).
56131L5
www.fmiproducts.com
DIMENSIONS
FRONT VIEW
30"
(Opening)
25"
19
7
/8"
(Opening)
RIGHT SIDE
1 7/8"
22
5
/8"
41
1
/8"
32"
(Opening)
1
7
/8"
39
3
/4"
26
3
/8"
3"
1"
3
1
/2"
22
5
/8"
34
3
/4"
3"
BACK VIEW
TOP VIEW
(Left Side)
(Right Side)
(Front)
(Back)
24"
11
15
/
16
101/2"
1
1
/2"ø11/2"ø
10
1
/2"
BACK VIEW
TOP VIEW
Figure 1 - Peninsula Dimensions
(Left Side)
24"
1
/2"ø11/2"
(Back)
15
11
/16"
7
/8"
1
22 5/8"
ø1
(Right Side)
1
/2"
10
RIGHT SIDE
32" (Opening)
1
43
/8"
1
11
/8"
Figure 2 - See-Thru Dimensions
www.fmiproducts.com
(Front)
7
/8"
1
39 3/4"
3
26
/8"
3"
1"
FRONT VIEW
24"
25"
34
5
/8"
22
3"
2"
30"
(Opening)
56131L6
3
/4"
PRE-INSTALLATION PREPARATION
CEILING
WALL
36" Min.
36" Min.
0" Floor
LOCATION AND SPACE
REQUIREMENTS
Determine the safest and most efcient location for your FMI PRODUCTS, LLC direct-vent
replace. Make sure that rafters and wall
studs are not in the way of the venting system.
Choose a location where heat output is not
affected by drafts, air conditioning ducts, windows or doors. Be aware of all restrictions and
precautions before deciding the exact location
for your replace and termination cap.
When deciding the location of your replace,
follow these rules:
• A projection may be ideal for a new addition
on an existing nished wall. Refer to horizontal termination congurations on page
15 or vertical congurations on page 18.
• Do not connect fireplace venting to a
chimney ue serving a separate solid-fuel
burning replace or appliance.
• Due to high temperatures, do not locate
replace in high trafc areas, windy or drafty
areas or near furniture or draperies.
• Never obstruct front opening of appliance
or ow of combustion and ventilation air.
Keep control compartments accessible.
• Do not locate close to where gasoline or
other ammable liquids may be stored.
Appliance must be kept clear and free from
combustible materials.
Upper
Louver
Panel
CLEARANCES
Minimum clearances to combustibles for
replace are as follows:
*Back and sides of surround 0"
Vent Surfaces (side and bottom) 1"
Top Vent Surface (horizontal run) 2"
Ceiling to Opening 36"
Floor 0"
Wall to Front of Glass 36"
Perpendicular Wall to Opening of Unit 2"
Top Spacer 0"
NOTICE: This replace is intended for use as supplemental
heat. Use this replace along
with your primary heating system. Do not install this replace
as your primary heat source.
If you have a central heating
system, you may run system’s
circulating blower while using
replace. This will help circulate
the heat throughout the house.
In the event of a power outage,
you can use this replace as a
heat source.
MANTEL CLEARANCES
Lower
Louver
Panel
56131L7
Log Set
Figure 3 - Direct-Vent Fireplace
www.fmiproducts.com
Figure 4 - Minimum Clearances
(Peninsula Shown)
0"
36"
2"
Wall In Front Of Glass
36" Min.
Perpendicular
Wall 2" Min.
From Opening
Right Side
Surround
(0" Min.)
Left Side
Surround
(0" Min.)
TOP VIEW
21" Min.
15" Min.
12" Min.
4"
Min.
7" Min.
1
1
/2" Max.
UNIT
PRE-INSTALLATION PREPARATION
39 3/4" Min.
40
1
/
2
"
23
5
/
8
"
39 3/4"
Min.
40
1
/
2
"
23
5
/
8
"
*
Continued
Combustible Material
Minimum 1" Clearance from
Side (Only for See-Thru)
Figure 5 - Minimum Clearances
(See-Thru Shown)
Woodwork, such as wood trims, mantels and
other combustible materials should not be
placed within 7" of the opening of replace
(see Figure 6).
Combustible material above projecting more
than 1 1/2" from appliance’s front face must
not be placed less than 15" from opening
of appliance, (ref. NFPA Standard 211 Sec.
7-3.3.3)
Combustible
Material May
Be Used
Drywall (Gypsum
Board, Sheetrock, etc.)
Drywall
Safe Zone for
Projection of
Combustible
Material
2 x 4
Spacer
2 x 4
Stud
FRAMING
Once nal location has been determined,
observing clearances for vent termination,
you may construct framing using dimensions
shown in Figures 7 thru 13 depending on your
particular installation
If appliance is to be installed directly on car-
peting, tile (other than ceramic), or any combustible material other than wood ooring, the
appliance must be installed upon a metal or
wood panel extending the full width and depth
of the appliance. There are three holes on
each side of the bottom of unit where screws
can be used to secure unit to oor.
Figure 7 - Rough Opening for Installing
Peninsula Fireplace
Figure 6 - Mantel Clearances for
Peninsula and See-Thru Fireplaces
(Peninsula Shown)
www.fmiproducts.com
Platform
Must Be
Solid, Flat,
and Fully
Supported
* As required by design as long as
ceiling clearance is maintained.
Figure 8 - Rough Opening for Installing
Peninsula Fireplace on Platform
56131L8
PRE-INSTALLATION PREPARATION
39 3/4"
Min.
43
1
/
4
"
24"
3"
1" Dia. Hole
3"
2" Dia. Hole
1"
2"
Height
Depends On
Installation
10"
Square Min.
Vertical
Height
Depends on
Installation
26
3
/8"
Horizontal
Length Depends
on Installation
90
o
Elbow
45
o
Elbow
16
"
Continued
The gas supply line may be connected through
side framing or alternately through lower sub-
ooring or a platform base if provided (see
Figures 10 and 11). Depending on installation,
refer to appropriate illustrations.
20
10
1
3
/
16
"
1
/
1
2
"
/
2
"
/
15
11
Figure 11 - Alternate Gas Supply
Location
Figure 9 - Rough Opening for Installing
See-Thru Fireplace
Figure 12 - Rough Opening for Installing
Exterior Vent Terminal
Figure 10 - Hole Locations For Gas Line
and Electric Wires for Peninsula and
See-Thru Fireplaces
56131L9
www.fmiproducts.com
Figure 13 - Vent Opening Height
GENERAL VENTING
These models are approved for use with FMI
PRODUCTS, LLC 5"-8" Series, rigid type
direct vent pipe as supplied by FMI PROD-
UCTS, LLC or with approved types of exible
vent pipe (not supplied) when appropriate
sized for an 8" outer and 5" inner diameter
application.
Your replace is approved to be vented either
through the side wall, or vertically using the
following guidelines:
• Only use FMI PRODUCTS, LLC supplied
or approved types of venting components
or kits. Do not mix different types of vent
components, modify vent components or
custom fabricate vent components for use
in any one installation.
• Minimum clearance between vent pipes
and combustible materials is 1", except
where stated otherwise.
• Combustible material may be ush with
the top front of replace with a maximum
thickness of 3/4".
• Do not recess venting terminals into a wall
or siding.
• Do not install vent terminals below grade
level. Maintain a minimum height of 12"
above snow line.
• Do not terminate venting system into an
attic or garage.
• If using a venting conguration of only
horizontal venting with no vertical run, a
1/4" rise for every 12" of run toward the
termination is required.
• There must not be any obstruction such
as bushes, garden sheds, fences, decks,
or utility buildings within 24" from the front
of the termination cap.
• Do not locate termination cap where excessive snow or ice build up may occur. Be
sure to clear vent termination area after
snow falls to prevent accidental blockage of
venting system. When using snow blowers,
do not direct snow towards vent termination
area.
VENT TERMINATION CLEARANCES
The nal position of your appliance depends
on the location of the vent termination in relation to the clearances that must be observed
as shown in Figure 14, page 10.
You may avoid extra framing by positioning
your replace against an already existing
framing member. The back of the replace
may be positioned directly against a combustible wall.
*Check with local codes. In the USA, follow
the current National Fuel Gas Fuel Gas Code, ANS Z223.1 also known as NFPA 54.
www.fmiproducts.com
56131L10
Fixed
Closed
Openable
Fixed
Closed
V
V
V
V
V
V
V
V
X
X
V
X
G
G
J
F
B
B
K
N
H
I
A
N
E
L
D
B
M
A
C
B
V
V
A
G
G
B
TERMINATION CAP
AIR SUPPLY INLET
GAS METERRESTRICTED AREA
(TERMINATION PROHIBITED)
A = clearance above grade, veranda, porch, deck, or
balcony [*12" (30.5 cm) minimum]
B = clearance to window or door that may be opened
[6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US
if between 10,000 and 50,000, 12" (30 cm) in Canada
if between 10,000 and 100,000; 12" (30 cm) in US if
greater than 50,000, 36" (91 cm) in Canada if greater
than 100,000]
C = clearance to permanently closed window
[minimum 12" (30.5 cm) recommended to prevent
condensation on window]
D = vertical clearance to ventilated soffit located above the
terminal within a horizontal distance of 24" (61 cm) from
the center-line of the terminal [18" (45.7 cm) minimum]
E = clearance to unventilated soffit [12" (30.5 cm) minimum]
F = clearance to outside corner (see below)
G = clearance to inside corner (see below)
H = *not to be installed above a meter/regulator assembly
within 36" (91.4 cm) horizontally from the center line
of the regulator
I = clearance to service regulator vent outlet [*72" (182.9 cm)
minimum]
J = clearance to non-mechanical air supply inlet to building
or the combustion air inlet to any other fireplace
[6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US
if between 10,000 and 50,000, 12" (30 cm) in Canada
if between 10,000 and 100,000; 12" (30 cm) in US if
greater than 50,000, 36" (91 cm) in Canada if greater
than 100,000]
K = clearance to a mechanical air supply inlet [*In Canada,
6 ft. (1.83m) minimum; In US 3 ft. (91 cm) above if within
10 ft. (3 m) horizontally]
L = † clearance above paved side-walk or a paved driveway
located on public property [*84" (213.3 cm) minimum]
M = clearance under veranda, porch, deck
[*12" (30.5 cm) minimum ‡]
N = clearance above a roof shall extend a minimum of
24" (61 cm) above the highest point when it passes
through the roof surface and any other obstruction within
a horizontal distance of 18" (45.7 cm)
† vent shall not terminate directly above a side-walk or paved driveway which is located between two
single family dwellings and serves both dwellings*
‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor*
* as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A.
Note: Local codes or regulations may require different clearances
A = 6" (15.2 cm)
Inside Corner
V
B
E
V
B = 6" (15.2 cm)
C = Maximum depth of 48" (121.9 cm)
for recessed location
D = Minimum width for back wall of
recessed location Combustible - 38" (965 mm)
Noncombustible - 24" (61 cm)
E = Clearance from corner in
recessed location Combustible - 6" (15.2 cm)
Noncombustible - 2" (5.1 cm)
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Openable
GENERAL VENTING
Continued
56131L11
Figure 14 - Minimum Clearances for Vent Terminations
www.fmiproducts.com
REQUIREMENTS FOR THE COMMONWEALTH OF
MASSACHUSETTS
For all side wall horizontally vented gas fueled
equipment installed in every dwelling, building or
structure used in whole or in part for residential
purposes, including those owned or operated by
the Commonwealth and where the side wall ex-
haust vent termination is less than seven (7) feet
above nished grade in the area of the venting,
including but not limited to decks and porches,
the following requirements shall be satised:
INSTALLATION OF CARBON
MONOXIDE DETECTORS
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing
plumber or gastter shall observe that a hard
wired carbon monoxide detector with an alarm
and battery backup is installed on the oor level
where the gas equipment is to be installed. In
addition, the installing plumber or gastter shall
observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed
on each additional level of the dwelling, building or
structure served by the side wall horizontal vented
gas fueled equipment. It shall be the responsibility
of the property owner to secure the services of
qualied licensed professionals for the installation
of hard wired carbon monoxide detectors.
In the event that the side wall horizontally
vented gas fueled equipment is installed
in a crawl space or an attic, the hard wired
carbon monoxide detector with alarm and
battery back-up may be installed on the next
adjacent oor level.
In the event that the requirements of this
subdivision can not be met at the time of
completion of installation, the owner shall
have a period of thirty (30) days to comply with
the above requirements; provided, however,
that during said thirty (30) day period, a battery
operated carbon monoxide detector with an
alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required
in accordance with the above provisions shall
comply with NFPA 720 and be ANSI/UL 2034
listed and IAS certied.
SIGNAGE
A metal or plastic identication plate shall be
permanently mounted to the exterior of the
building at a minimum height of eight (8) feet
above grade directly in line with the exhaust
vent terminal for the horizontally vented gas
fueled heating appliance or equipment. The
sign shall read, in print size no less than 1/2" in
size, "GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS".
www.fmiproducts.com
INSPECTION
The state or local gas inspector of the side
wall horizontally vented gas fueled equipment
shall not approve the installation unless, upon
inspection, the inspector observes carbon
monoxide detectors and signage installed in
accordance with the provisions of 248 CMR
5.08(2)(a) 1 through 4.
EXEMPTIONS: The following equipment is
exempt from 248 CMR 5.08(2)(a) 1 through 4:
• The equipment listed in Chapter 10 entitled
"Equipment Not Required To Be Vented"
in the most current edition of NFPA 54 as
adopted by the Board; and
• Product Approved side wall horizontally
vented gas fueled equipment installed in a
room or structure separate from the dwelling, building or structure used in whole or
in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved
side wall horizontally vented gas equipment
provides a venting system design or venting
system components with the equipment, the
instructions provided by the manufacturer for
installation of the equipment and the venting
system shall include:
• Detailed instructions for the installation of
the venting system design or the venting
system components; and
• A complete parts list for the venting system
design or venting system.
Gas Equipment Venting System Not
Provided
When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for
venting the ue gases, but identies "special
venting systems", the following requirements
shall be satised by the manufacturer:
•
The referenced "special venting system" instructions shall be included with the appliance
or equipment installation instructions; and
• The "special venting systems" shall be Prod-
uct Approved by the Board, and the instructions for that system shall include a parts list
and detailed installation instructions.
A copy of all installation instructions for all
Product Approved side wall horizontally
vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions
shall remain with the appliance or equipment
at the completion of the installation.