FMI DVF42NH-HA, DVF-36NS-HA, VDVF42PH, DVF-42NS-HA, DVF36NH-HA User Manual

...
DIRECT-VENT FIREPLACE
PFS
®
US
OWNER’S OPERATION AND INSTALLATION MANUAL
MODELS (V)DVF36NS, (V)DVF36PS, (V)DVF36NH, (V)DVF36PH,
DVF-36NS-HA, DVF36NH-HA, (V)DVF42NS, (V)DVF42PS, (V)
DVF42NH, (V)DVF42PH, DVF-42NS-HA, AND DVF42NH-HA
WARNING: If the information in this manual is not
followed exactly, a re or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other ammable
vapors and liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
— Installation and service must be performed by a quali-
ed installer, service agency or the gas supplier.
INSTALLER: Leave this manual with the appliance CONSUMER: Retain this manual for future reference.
For more information, visit www.fmiproducts.com
TABLE OF CONTENTS
Safety .................................................................. 2
Local Codes......................................................... 4
Product Identication ........................................... 5
Product Features ................................................. 5
Pre-installation ..................................................... 6
Location of Termination Cap ................................ 8
Requirements for the Commonwealth of
Massachusetts ................................................. 9
Venting Installation ............................................ 10
Fireplace Installation.......................................... 16
Operation ........................................................... 22
SAFETY
WARNING: Improper instal-
lation, adjustment, alteration,
service or maintenance can
cause injury or property damage.
Refer to this manual for correct
installation and operational procedures. For assistance or
additional information consult
a qualified installer, service agency or the gas supplier.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certied kit is used.
State of Massachusetts: The
installation must be made by a licensed plumber or gas tter
in the Commonwealth of Mas-
sachusetts.
WARNING: This product
con tains a nd/or gener ates
chemicals known to the State of California to cause cancer or
birth defects or other reproduc­tive harm.
Inspecting Burners............................................. 24
Cleaning and Maintenance ................................ 24
Troubleshooting ................................................. 26
Specications .................................................... 29
Wiring Diagram .................................................. 29
Parts .................................................................. 30
Replacement Parts ............................................ 36
Technical Service............................................... 36
Service Hints ..................................................... 36
Acessories ......................................................... 36
Warranty ..............................................Back Cover
IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, op­erate or service this replace. Improper use of this replace can cause serious injury or death from burns, re, explo­sion, electrical shock and carbon monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
This vented gas replace is a sealed combus­tion gas replace designed for residential ap­plications. This replace must be installed with FMI PRODUCTS, LLC vent pipe components and terminations.
This fireplace complies with the National
Safety Standards and is listed and tested by PFS Corporation to ANSI Z21.50 standard as
vented gas replace. This replace must be installed by a qualied
(certied or licensed) service person. It brings in fresh air for combustion through the outer pipe and combustion gases are exhausted through the inner pipe. If the glass door as­sembly and venting pipe are not properly seated, connected and sealed, carbon mon­oxide leakage (spillage) can occur.
www.fmiproducts.com
125078-01B2
SAFETY
Continued
Carbon Monoxide Poisoning: Early signs of carbon monoxide poisoning resemble the u, with headaches, dizziness or nausea. If you have these signs, the replace may not be working properly. Get fresh air at once! Have replace serviced. Some people are more affected by carbon monoxide than oth­ers. These include pregnant women, people with heart or lung disease or anemia, those under the inuence of alcohol and those at high altitudes.
Natural and Propane/LP Gas: Natural and propane/LP gas are odorless. An odor-making agent is added to the gas. The odor helps you detect a gas leak. However, the odor added to the gas can fade. Gas may be present even though no odor exists.
Make certain you read and understand all warnings. Keep this manual for reference. It is your guide to safe and proper operation of this replace.
WARNING: Any change to this replace or it’s controls can be dangerous. Do not modify this replace under any circum­stances. Any parts removed for servicing must be replaced prior to operating replace.
WARNING: Do not allow fans
to blow directly into the replace. Avoid any drafts that alter burner ame patterns.
Due to high temperatures, the appliance should be located out of trafc and away from furniture and draperies.
Do not place clothing or other ammable material on or near the appliance. Never place any objects on the appliance.
Do not use this replace to cook food or burn paper or other am­mable material.
This replace reaches high tem­peratures. Keep children and
adults away from hot surface to
avoid burns or clothing ignition. Fireplace will remain hot for a time after shutdown. Allow sur­face to cool before touching.
WARNING: Do not use a blow­er insert, heat exchanger insert or other accessory not approved
Carefully supervise young chil-
dren when they are in the room
with replace.
for use with this replace.
Keep the area around your
WARNING: This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases unless
replace clear of combustible materials, gasoline and other ammable vapor or liquids. Do not run replace where these are used or stored.
a certied kit is used.
125078-01B 3
www.fmiproducts.com
SAFETY
Continued
1. For propane/LP replace, do not place propane/LP supply tank(s) inside any structure. Locate propan e/LP supp ly tank(s) outdoors. To prevent performance problems, do not use propane/LP fuel tank of less than 100 lb. capacity.
2. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do not
use any phone in your building
• immediately call your gas supplier from
a neighbor ’s phone. Follow the gas supplier's instructions
• if you cannot reach you gas supplier, call
the re department.
3. Never install the replace
• in a recreational vehicle
• in windy or drafty areas where curtains or
other combustible (ammable) objects can make contact with the replace front
• in high trafc areas
4. Turn fireplace off and let cool before servicing, installing or repairing. Only a qualied service person should install, service or repair this replace. Have re­place inspected annually by a qualied service person.
5. You must keep control compartments, burners and circulating air passages clean. More frequent cleaning may be needed due to excessive lint and dust from carpeting, bedding material, etc. Turn off the gas valve and pilot light before cleaning replace.
6. Have venting system inspected annually by a qualied service person. If needed, have venting system cleaned or repaired. See Cleaning and Maintenance, page 24.
7. Do not use any solid fuels (wood, coal, paper, cardboard, etc.) in this replace. Use only the gas type indicated on re­place nameplate.
8. This appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code,
ANSI/NFPA 70.
9. Do not use replace if any part has been exposed to or under water. Immediately call a qualied service person to arrange for replacement of the unit.
10. Do not operate replace if any log is broken.
11. Do not operate replace with glass door removed, cracked or broken.
12. Provide adequate clearances around air openings.
LOCAL CODES
Install and use replace with care. Follow all local codes. In the absence to local codes, use the current National Fuel Gas Code ANSI Z223.1/NFPA 54*. *Available from:
American National Standards Institute, Inc.
1430 Broadway
New York, NY 10018
National Fire Protection Association, Inc.
Batterymarch Park
Quincy, MA 02269
www.fmiproducts.com
125078-01B4
Outer Glass Door
Herringbone Brick Refractories
Log Set
Grate
Lower Door/ Control Cover
PRODUCT IDENTIFICATION
Flue Collar
Nailing Flange
Figure 1 - Direct Vent Fireplace
PRODUCT FEATURES
These are a few facts that can help you under­stand and enjoy your direct vent replace:
• The venting system may be routed to the outside of your home in several ways. It may vent through the roof (vertical) or it may vent to an outside/exterior wall (hori­zontal). The vent pipe installation is very important to allow for proper operation. You must follow the venting instructions very carefully for either vertical or horizontal applications.
• This replace may be installed in any room of your house provided all local codes and these installation instructions are followed.
125078-01B 5
www.fmiproducts.com
• Each time you turn on your replace, you may notice some amount of condensation on the inside of the replace glass. This is normal and will disappear after 10-20 minutes of operation.
• Your direct ve nt gas fire place system (replace and venting) is a balanced and sealed gas operating unit. It requires ap­proximately 10-20 minutes of operating time before the ame pattern stabilizes.
PRE-INSTALLATION
29" (36")
34
3
/4" (4 2") 21" (36") 25" (42")
41
1
/4" (3 6")
48 1/4" (4 2")
11 7/8" (3 6") 13 5/8" (4 2")
LOCATION AND SpACE REqUIREMENTS
Determine the safest and most efcient loca­tion for your direct vent replace. Make sure that rafters and wall studs are not in the way of the venting system. Choose a location where the heat output is not affected by drafts, air conditioning ducts, windows or doors. Figure 2 shows some common locations. Be aware of all restrictions and precautions before deciding the exact location for your replace and termination cap.
When deciding the location of your replace, follow these rules:
• Do not connect this replace venting to a chimney ue serving a separate solid-fuel burning replace or appliance.
• Due to high temperatures, do not locate this replace in high trafc areas, windy or drafty areas or near furniture or draperies.
• Proper clearances must be maintained.
• If your replace is to be installed directly on carpeting, vinyl tile or any combustible mate­rial other than wood, it must be installed on a metal or wood panel extending the full width and depth of the replace (see Figure 3).
• Your replace is designed to be used in zero clearance installations. Wall or fram­ing material can be placed directly against any exterior surface on back, sides or top of your replace, except where standoff spacers are integrally attached. If standoff spacers are attached to your replace, these s pacer s can be plac ed directly against wall or framing material. See fram­ing details, page 7.
• When locating termination cap, it is impor­tant to observe the minimum clearances shown in Figure 7, page 8.
• If recessing into a wall, you can avoid extra framing by positioning your replace against an already existing framing member.
• Do not recess termination cap into a wall or siding.
• You may paint the termination cap with 450º F (232º C) heat-resistant paint to coordinate with the exterior nish.
• There must not be any obstruction such as bushes, garden sheds, fences, decks or utility buildings within 24" from the front of the termination cap and the front of outside air vent.
• Do not locate termination cap and outside air vent where excessive snow or ice build up may occur. Be sure to clear vent ter­mination area after snow falls to prevent accidental blockage of venting system. When using snow blowers, do not direct snow towards vent termination area.
Flush with a wall
Through exterior wall enclosed in a chase
Corner installation
Figure 2 - Common Fireplace Locations
Figure 3 - Fireplace Top Dimensions
www.fmiproducts.com
125078-01B6
C
B
A
D
E
F
G
3
2
1
4
5
6
7
Wa ll
PRE-INSTALLATION
43
1
/
4
"
(36")
47
1
/
4
"
(42")
41
1/2"
(36")
48
1/2"
(42")
36
3/8"
(36")
43
3
/
8
" (42")
43" (36"), 50" (42")
42" (36"), 49" (42")
15
3/4"
(36")
19" (42")
51
3/8"
(36")
61
3
/
4
" (42")
Nailing
Tabs
Continued
CLEARANCES
Minimum clearances to combustibles for the replace are as follows:
*Back and sides 1" Perpendicular walls 6" Floor 0" Ceiling to louver opening 42" Front 36" Top of Standoffs 0" Vent (See venting instructions
for specic venting
clearances.) Combustible material with a maximum thick­ness of 5/8" may be ush with the top front of replace.
* For back and sides of replace, do not pack with insulation or other materials. 1" clearance not required at nailing anges.
NOTICE: This replace is intend­ed for use as supplemental heat. Use this replace along with your primary heating system. Do not install this replace as your primary heat source. If you have a central heating system, you may run system’s circulat­ing blower while using replace. This will help circulate the heat throughout the house.
Figure 4 - Framing Clearances with
Outside Air Flex Duct
Figure 5 - Framing Clearances for Corner
Installation
FRAMING AND FINISHING
Figure 4 shows typical framing of this replace. Figure 5 shows framing for corner installation. All minimum clearances must be met.
If you are using a separate combustible man­tel piece, refer to Figure 6 for proper instal­lation height. You can install noncombustible mantels at any height above the replace.
Note: Noncombustible mantels may discolor!
125078-01B 7
www.fmiproducts.com
Mantel
Ref.
Depth Ref.
1 14" A 16" 2 12" B 14" 3 10" C 12" 4 8" D 10" 5 6" E 8" 6 4" F 6" 7 2" G 4"
Mantel from
Top of Opening
Figure 6 - Clearances for Combustible
Mantels
Fixed
Closed
Openable
Fixed
Closed
V
V
V
V
V
V
V
V
X
X
V
X
G
G
J
F
B
B
K
N
H
I
A
N
E
L
D
B
M
A
C
B
V
V
A
G
G
B
TERMINATION CAP
AIR SUPPLY INLET
GAS METERRESTRICTED AREA
(TERMINATION PROHIBITED)
A = clearance above grade, veranda, porch, deck, or balcony [*12" (30.5 cm) minimum] B = clearance to window or door that may be opened [6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US if between 10,000 and 50,000, 12" (30 cm) in Canada if between 10,000 and 100,000; 12" (30 cm) in US if greater than 50,000, 36" (91 cm) in Canada if greater than 100,000] C = clearance to permanently closed window [minimum 12" (30.5 cm) recommended to prevent condensation on window] D = vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24" (61 cm) from the center-line of the terminal [18" (45.7 cm) minimum] E = clearance to unventilated soffit [12" (30.5 cm) minimum] F = clearance to outside corner (see below) G = clearance to inside corner (see below) H = *not to be installed above a meter/regulator assembly within 36" (91.4 cm) horizontally from the center line of the regulator
I = clearance to service regulator vent outlet [*72" (182.9 cm) minimum] J = clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other fireplace [6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US if between 10,000 and 50,000, 12" (30 cm) in Canada if between 10,000 and 100,000; 12" (30 cm) in US if greater than 50,000, 36" (91 cm) in Canada if greater than 100,000] K = clearance to a mechanical air supply inlet [*In Canada, 6 ft. (1.83m) minimum; In US 3 ft. (91 cm) above if within 10 ft. (3 m) horizontally] L = † clearance above paved side-walk or a paved driveway located on public property [*84" (213.3 cm) minimum] M = clearance under veranda, porch, deck [*12" (30.5 cm) minimum ‡] N = clearance above a roof shall extend a minimum of 24" (61 cm) above the highest point when it passes through the roof surface and any other obstruction within a horizontal distance of 18" (45.7 cm)
† vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves both dwellings* ‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor* * as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A.
Note: Local codes or regulations may require different clearances
A = 6" (15.2 cm)
Inside Corner
V
B
E
V
B = 6" (15.2 cm)
C = Maximum depth of 48" (121.9 cm) for recessed location D = Minimum width for back wall of recessed location ­ Combustible - 38" (965 mm) Noncombustible - 24" (61 cm) E = Clearance from corner in recessed location­ Combustible - 6" (15.2 cm) Noncombustible - 2" (5.1 cm)
Outside Corner Recessed Location
G
H
G = 12" (30.5 cm) minimum clearance
Balcony with No Side Wall
V
J
Combustible & Noncombustible H = 24" (61 cm) J = 20" (50.8 cm)
Balcony with Perpendicular Side Wall
C
D
C
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Openable
LOCATION OF TERMINATION CAP
Figure 7 - Minimum Clearances for Termination Cap
www.fmiproducts.com
125078-01B8
REQUIREMENTS FOR THE COMMONWEALTH OF
MASSACHUSETTS
For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall ex­haust vent termination is less than seven (7) feet above nished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satised:
INSTALLATION OF CARBON MONOXIDE DETECTORS
At the time of installation of the side wall horizon­tal vented gas fueled equipment, the installing plumber or gastter shall observe that a hard wired carbon monoxide detector with an alarm and battery backup is installed on the oor level where the gas equipment is to be installed. In addition, the installing plumber or gastter shall observe that a battery operated or hard wired car­bon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualied licensed professionals for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent oor level.
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certied.
SIGNAGE
A metal or plastic identication plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than 1/2" in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".
125078-01B 9
www.fmiproducts.com
INSpECTION
The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR
5.08(2)(a) 1 through 4. EXEMPTIONS: The following equipment is ex-
empt from 248 CMR 5.08(2)(a) 1 through 4:
• The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
• Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwell­ing, building or structure used in whole or in part for residential purposes.
MANUFACTURER REqUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
• Detailed instructions for the installation of the venting system design or the venting system components; and
• A complete parts list for the venting system design or venting system.
Gas Equipment Venting System Not
provided
When the manufacturer of a Product Ap­proved side wall horizontally vented gas fu­eled equipment does not provide the parts for venting the ue gases, but identies "special venting systems", the following requirements shall be satised by the manufacturer:
The referenced "special venting system" in­structions shall be included with the appliance or equipment installation instructions; and
• The "special venting systems" shall be Prod­uct Approved by the Board, and the instruc­tions for that system shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved side w all horizon tally vented gas fueled equipment, all venting in­structions, all parts lists for venting instruc­tions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
VENTING INSTALLATION
NOTICE: Read these instruc-
tions completely before attempt­ing installation.
These models are tested and approved for use with FMI PRODUCTS, LLC (direct vent) pipe components and terminations.
The venting system must terminate on the outside of the structure and can not be at­tached to a chimney or ue system serving a separate solid fuel or gas burning appliance. A direct vent appliance must have its own venting system. DO NOT common vent this appliance.
These models are approved to be vented either horizontally through an outside wall or vertically through a roof or chase enclosure using the following guidelines:
• When venting system terminates horizon­tally on an outside wall, you may install a standoff if the termination cap is to be installed directly on a combustible nish such as vinyl, wood, stucco, etc.
• Never run the vent downward as this may cause excessive temperatures which could cause a re.
• Vent pipe air space clearances to com­bustibles are 1" on all sides except on the horizontal sections, which requires 2" clear­ance from the top of the pipe. Where the termination cap penetrates a combustible wall, 1" air space clearance is required.
• Have replace and selected vent compo­nents on hand to help determine the exact measurements when elbowing or offsetting. Always use wall restops when penetrating walls and restops when penetrating ceil­ings or attic spaces.
• For installation of replace at elevations of 4000 feet or greater, pay special attention to venting requirement recommendations.
WARNING: Read all instruc-
tions completely and thoroughly before attempting installation.
Failure to do so could result in
serious injury, property damage or loss of life.
NOTICE: Do not seal termination
cap to vent pipe. Cap must be removable for vent inspection and maintenance.
INSTALLATION pRECAUTIONS
• Wear gl oves an d s afety glasse s f or protection
• Use extreme caution when using ladders or when on roof tops
• Be aware of electrical wiring locations in walls and ceilings
The following actions will void the warranty on your venting system:
• Ins ta llati on of an y d am aged ve nt ing component
• Unauthorized modication of the venting sys­tem (Do not cut or alter vent components)
• Installation of any component part not man u fact u red o r app r oved b y FM I
PRODUCTS, LLC
• Installation other than as instructed by these instructions
WARNING: This gas replace and vent assembly must be vented directly to the outside. The venting system must NEVER be attached to a chimney serv­ing a separate solid fuel burning appliance. Each direct vent gas appliance must use a separate vent system. Do not use com­mon vent systems.
WARNING: Vent pipe air space clearances to combus­tibles are 1" on all sides except
on the horizontal sections,
which require 2" clearances from the top of the pipe. Where the termination cap penetrates a combustible wall, 1" air space clearance is required.
NOTICE: Failure to follow these in-
structions will void the warranty.
www.fmiproducts.com
125078-01B10
INSTALLATION pLANNING
(Framing
Detail)
11
1
/2"
11
1
/2" Inside Framing
11
1
/2"
8 1/2"
Ve nt Opening
Combustible Wall
Ve nt Opening
Noncombustible Wall
There are two basic types of direct vent installation:
• Horizontal Termination
• Vertical Termination
Horizontal Termination Installation
IMPORTANT: Horizontal square terminations require only inner portion of wall restop. Hori­zontal installations using round termination require exterior portion of wall restop.
1. Set replace in its desired location and de­termine the route your horizontal venting will take. Do not secure replace until all venting has been installed. Some instal­lations require sliding replace in and out of position to make nal venting connec­tions. Figures 14 and 15 on page 12 show different congurations for venting with horizontal termination that will help you decide which application best suits your installation. Check to see if wall studs or roof rafters are in the path of your desired venting route. If they are, you may want to adjust location of replace.
2. Direct vent pipe sections and components are designed with special twist-lock con­nections.
Twist-Lock procedure: Female ends of
pipes have locking lugs (indentations). These lugs will slide straight into match­ing slots on male ends of adjacent pipes. Push pipe sections together and twist one section clockwise approximately one­quarter turn until sections are fully locked (see Figure 8).
Note: Horizontal runs of vent must be sup-
ported every three feet. Use wall straps for this purpose.
3. Assemble desired combination of pipe and elbows to replace ue collar. If there are long portions of venting run, pre-as­sembled pipe sections may be installed as subassemblies for convenience.
4. Carefully determine location where vent pipe assembly will penetrate outside wall. Center of hole should line up with center line of horizontal vent pipe. Mark wall for
an 11 1/2" x 11 1/2" square hole. Cut and
frame square hole in exterior wall where vent will be terminated. If wall being pen-
125078-01B 11
VENTING INSTALLATION
Continued
etrated is constructed of noncombustible material, such as masonry block or con­crete, a 8 1/2" hole with zero clearance is acceptable (see Figure 9).
vent termination into any wall. This will cause a re hazard.
Figure 8 - Vent Pipe Connections
Figure 9 - Vent Opening Requirements
www.fmiproducts.com
WARNING: Do not recess
Female Locking Lugs
Male Slots
Center of Hole
VENTING INSTALLATION
Continued
5. Noncombustible Exterior Wall: Position horizontal vent cap in center of the 8 1/2" round hole and attach to exterior wall with four wood screws provided. Before attaching vent cap to exterior wall, run a bead of non-hardening mastic (pliable sealant) around outside edges to make a seal between it and outside wall.
Note: Four wood screws provided should
be replaced with appropriate fasteners for stucco, brick, concrete or other types of sidings (see Figure 10).
Combustible Exterior Wall: For vinyl
siding, stucco or wood exteriors, a siding standoff may be installed between vent cap and exterior wall. Siding standoff prevents excessive heat from damaging siding materials. Siding material must be cut to accommodate standoff. Bolt vent cap to standoff. Apply non-hardening mastic around outside edge of standoff. Position standoff/cap assembly in the center of 11 1/2" square hole and attach to exterior wall with provided wood screws (see Figure 11). Siding standoff must sit ush against exterior fascia material.
6. Connecting Vent Cap with Horizontal Vent Pipe: Slide wall restop over vent pipe before connecting horizontal run to vent cap (see Figure 12).
Apply Mastic to All Four Sides
Vent Cap
Wood Screw
Carefully move replace, with vent as-
sembly attached, toward wall and insert vent pipe into horizontal termination. Pipe overlap should be a minimum of 1 1/4" (see Figure 13, page 13).
Slide wall restop against interior wall
surface and attach with screws provided. See Figure 13, page 13, for horizontal termination details.
Place replace into position and shim with
noncombustible material if needed. Nail or screw side anges to framing to secure unit in place. IMPORTANT: Make sure re- place is level before securing. If replace is not level it will not work properly.
Cut Siding Away to Fit Standoff
Standoff
Apply Mastic to All Four Sides
Figure 11 - Installing Siding Standoff
(Combustible Exterior Wall)
Wood Screw
Vent
Cap
Screws
Interior Wall Surface
Wall Firestop
Figure 10 - Installing Horizontal Vent Cap
(Noncombustible Exterior)
www.fmiproducts.com
Vent Cap (Horizontal Termination)
Screw
Figure 12 - Connecting Vent Cap with
Horizontal Vent Pipe
Horizontal Vent Pipe
125078-01B12