FMI CTS User Manual

p
CTS Series: CT1, CT2, CT1V, & CT2V
Chemical Treatment Systems
INSTALLATION & OPERATING INSTRUCTIONS
OVERVIEW:
The CTS from Fluid Metering Inc. is the solution for accurate, maintenance-free injection of liquid sodium hydroxide (Caustic Soda) typically used for pH adjustment, as well as other chemicals used in water and wastewater treatment applications.
The CTS Pump Module is a unique valveless pump design consisting of a rotating and reciprocating (CeramPump®) ceramic piston, direct coupled to a variable speed drive motor. The CTS pump injects the caustic soda directly into the main water stream, at back pressures up to 125 psi.
Page 1of 9
The C100A Variable Speed Controller from Fluid Metering, Inc. provides an ideal control interface for the CTS. The C100A supplies a variable 0-90VDC power source which can be controlled either manually using a from panel mounted rotary dial, or electronically via a 4-20 mA control input.
CTS Pump Module
and C100A Variable S
* Other commercially available controllers may work, however we recommend contacting FMI for details.
eed Controller
IN-CTS-13
1/4/13 HW
pp
SPECIFICATIONS
CTS Chemical Treatment System
Supply Voltage: 0-90 VDC** CTS Supply: 1/4” FNPT CTS Outlet: 1/4” FNPT
IMPORTANT NOTE: Supply and Outlet fittings contain Buna-N material which is not compatible with fluids containing chlorine. Do not use the CTS with hypochlorite, chloramine, or any fluids which contain chlorine compounds in ANY concentration.
Output Volume: 6.5 GPH max. - CT1(V) 15 GPH max.- CT2(V) Output Pressure: 125 psi max.
Environment: Humidity: 100% RH non-condensing Temp: non-freezing to 104°F
Enclosure: Gasketed Fiberglass w/ vent holes. Dimensions: 15 1/2” x 13 3/8” x 6 3/4” Weight: 18.6 lbs. (8.4 kg) ** 0-90 VDC su
lied by C100A
INSTALLATION & SETUP CTS MOUNTING (See diagram page 3)
For optimal performance, mount the CTS as close to and above the chemical supply reservoir. Securely fasten the CTS to a wall location with its right side convenient to the Sodium Hypochlorite supply vessel. There are 2 mounting holes (5/16” dia) on each side of the CL enclosure. Utilize all holes for most secure mounting and mount at least 1 ft. above supply reservoir.
Diagram 1 (below) shows the mounting hole locations.
Diagram 2
Electrical & Fluid Connections
Diagram 1
Mounting Holes
IMPORTANT NOTE: There are 2 vent holes located at the top front of the enclosure (under the upper lip of the enclosure cover). Do not close, seal, or obstruct these vent openings. They are designed to prevent hazardous gases from building up in the
ELECTRICAL
On the upper left side of the CTS enclosure is a 7/8” conduit opening for the electrical supply (0-90 VDC source from the C100A or customer supplied voltage controller). Electrical supply wiring should be 3 conductor, minimum 22 AWG. Attach wiring to the lower 3 spade lugs of the terminal block as shown below in Diagram 3. Connect the ground wire to the left most spade lug. Connect the drive wires to the remaining 2 spade lugs.
It is recommended that electrical connections be coated with a corrosion protectant such as Aqua­lube or equivalent.
Note: The CTS is designed so that the motor will turn in the proper direction, regardless of input
Diagram 3
Terminal Wiring
polarity.
Page 2 of 9
IN-CTS-13
1/4/13 HW
FLUIDIC CONNECTIONS
The CTS has two 1/4” FNPT fluid connections. The INLET (Supply) connection is a 1/4” FNPT fitting
located on the lower right side of the enclosure and connects the CTS with the chemical supply reservoir (carboy, tank, etc.) Inlet tubing is customer supplied and should be semi-rigid and sized adequately t o accommodate the required flow rate to prevent cavitation. Minimum recommended inlet tubing diameter is 1/2” I.D.
The OUTLET (Dispense) connection is a 1/4” FNPT fitting located on the upper right side of the enclosure and connects the fluid output of the pump to the water source to be treated, typically a water main. The CTS is designed to pump against 125 psi backpressure, and therefore all plumbing on the discharge side of the pump should rated for 250 psi. It is recommended that 1/4” O.D. polyethylene tubing is used for the output tubing.
Installation Notes:
1) Be careful not to over-tighten fittings to the CTS box as the bulkheads are made of PVC and may crack.
2) For optimal performance, mount the CTS as close to the source as possible and above it.
3) The CHLORITROL backflow concerns typically associated with diaphragm and peristaltic pumps. Because the inlet and outlet fluid path of FMI’s CeramPump® valveless piston pump are never interconnected, a backflow check valve is usually not required. However, local code requires a check valve on the inlet side of the pump, refer to the “Tips & Troubleshooting” section of this instruction manual.
®
was designed to overcome
1 ft. min
Diagram 4
Fluidic System Overview
ADJUSTING FLOW RATE Mechanical Adjustment: By adjusting the angle of
the high pressure pump head (pump head on right side of drive) using the adjustment knob, piston displacement can be increased and decreased, which in turn will vary flow rate. Diagram 5 shows the minimum (0%), maximum (100%), and factory set (50%) pump head positions.
Electronic Adjustment: The C100A Variable Speed Controller varies pump speed and has both manual and electronic control modes.
For manual speed adjustment, set the C100A mode on MANUAL and use the rotary dial to increase or decrease pump speed.
Page 3 of 9
PUMP HEAD ANGLE
(Displacement Adjustment)
Diagram 5
IN-CTS-13
1/4/13 HW
Loading...
+ 6 hidden pages