consult a qualified installer, service agency or
the gas supplier.
This appliance may be in-
stalled in an aftermarket,*
permanently l o cated,
manufactured (mobile)
home, where not prohibited by local codes.
This appliance is only for
use with the type of gas
indicated on the rating
plate. This appliance is
not convertible for use
with other gases, unless
a certied kit is used.
* Aftermarket: Completion of sale, not for
purpose of resale, from the manufacturer
www.fmiproducts.com
State of Massachusetts:
The inst allat ion m ust
be made by a licensed
plumber or gas tter in
the Commonwealth of
Massachusetts.
WARNING: This product
contai ns a nd/ or g enerate s
chemicals known to the State
of California to cause cancer or
birth defects or other reproductive harm.
IMPORTANT: Read this owner’s
manual carefully and completely
before trying to assemble, operate or service this replace.
Improper use of this replace
can cause serious injury or death
from burns, re, explosions,
electrical shock and carbon
monoxide poisoning.
DANGER: Carbon monoxide
poisoning may lead to death!
This replace must be installed by a qualied
(certied or licensed) service person. It has
a sealed gas combustion chamber that uses
a coaxial pipe (pipe within a pipe and having
the same center) venting system. It brings in
fresh air for combustion through the outer pipe
and combustion gases are exhausted through
the inner pipe. If the glass door assembly and
venting pipe are not properly seated, connected and sealed, carbon monoxide leakage
(spillage) can occur.
116646-01J2
SAFETY
Continued
Carbon Monoxide Poisoning: Early signs of
carbon monoxide poisoning resemble the u,
with headaches, dizziness or nausea. If you
have these signs, the replace may not be
working properly. Get fresh air at once! Have
replace serviced. Some people are more affected by carbon monoxide than others. These
include pregnant women, people with heart or
lung disease or anemia, those under the inuence of alcohol and those at high altitudes.
Natural and Propane/LP Gas: Natural and
propane/LP gases are odorless. An odormaking agent is added to the gas. The odor
helps you detect a gas leak. However, the
odor added to the gas can fade. Gas may be
present even though no odor exists.
Make certain you read and understand all
warnings. Keep this manual for reference. It
is your guide to safe and proper operation of
this replace.
WARNING: Any change to
this replace or its controls can
be dangerous.
WARNING: Do not use a blower insert, heat exchanger insert
or other accessory not approved
for use with this replace.
Do not use any solid fuels (wood,
coal, paper, cardboard, etc.) in this
replace. Use only the gas type indicated on replace name plate.
Carefully supervise young chil-
dren when they are in the room
with replace.
This replace reaches high temperatures. Keep children and
adults away from hot surfaces to
avoid burns or clothing ignition.
Fireplace will remain hot for a
time after shutdown. Allow surfaces to cool before touching.
Do not operate replace with
glass door removed, cracked
or broken.
116646-01J3
www.fmiproducts.com
Keep the appliance area clear
and free from combustible materials, gasoline and other ammable vapors and liquids.
Do not place clothing or other
ammable material on or near
replace. Never place any objects on replace.
1. This appliance is only for use with the type
of gas indicated on the rating plate. This
appliance is not convertible for use with
other gases unless a certied kit is used.
2. For propane/LP replace, do not place
propane/LP supply tank(s) inside any
struct ure . Locate propane/LP su pply
tank(s) outdoors. To prevent performance
problems, do not use propane/LP fuel tank
of less than 100 lbs. capacity.
3. If you smell gas
• shut off gas supply
• do not try to light any appliance
• do not touch any electrical switch; do
not use any phone in your building
• immediately call your gas supplier from
a neighbor’s phone. Follow the gas
supplier’s instructions
• if you cannot reach your gas supplier,
call the re department
4. Never install the replace
• in a recreational vehicle
• in windy or drafty areas where curtains
or other comb us tible (fl ammable )
objects can make contact with the
replace front
• in high trafc areas
5. Do not modify this replace under any
circumstances. Any parts removed for
servicing must be replaced prior to operating replace.
6. Turn fireplace off and let cool before
servicing, installing or repairing. Only a
qualied service person should install,
service or repair this replace. Have replace inspected annually by a qualied
service person.
7. You must keep control compartments,
burners and circulating air passages clean.
More frequent cleaning may be needed due
to excessive lint and dust from carpeting,
bedding material, etc. Turn off the gas valve
and pilot light before cleaning replace.
8. Have venting system inspected annually by
SAFETY Continued
a qualied service person. If needed, have
venting system cleaned or repaired. See
Cleaning and Maintenance, page 30.
9. Do not use this replace to cook food or
burn paper or other objects.
10. This appliance, when installed, must be
electrically grounded in accordance with
local codes or, in the absence of local
PRODUCT IDENTIFICATION
Upper Louver Panel
Nailing Flange
Glass Door Assembly
codes, with the National Electrical Code, ANSI/NFPA 70.
11. Do not use replace if any part has been
under water. Immediately call a qualied
service person to arrange for replacement
of the unit.
12. Do not operate replace if log is broken.
13. Provide adequate clearances around air
openings.
Flue Collar
Piezo Ignitor
Control Valve
Lower Louver Panel
Glowing
Embers
ON/OFF/REMOTE Switch
(Optional Installation)
Figure 1 - Direct-Vent Fireplace with Millivolt Ignition
LOCAL CODES
Install and use replace with care. Follow all
local codes. In the absence to local codes,
use the current National Fuel Gas Code ANSI Z223.1/NFPA 54*.
*Available from:
PRODUCT FEATURES
These are a few facts that can help you understand and enjoy your direct-vent replace:
• The venting system may be routed to the
outside of your home in several ways. It may
vent through the roof (vertical) or it may vent
to an outside/exterior wall (horizontal). The
vent pipe installation is very important to
allow for proper operation. You must follow
the venting instructions very carefully for
either vertical or horizontal applications.
• This replace may be installed in any room
of your house provided all local codes and
these installation instructions are followed.
• This replace does not require electricity
to operate.
www.fmiproducts.com
Log Set
Lava Rock
Grate Assembly
Blower Switch (Optional Installation)
American National Standards Institute, Inc.
National Fire Protection Association, Inc.
• Only the blower requires electricity if
installed. If you plan to install the blower
at a later date, outlet must be wired at the
bottom of the replace when framing.
• A piezo ignitor and ceramic electrode create
sparks to ignite the pilot light. It does not
require any matches, batteries or any other
sources of ignition to light the pilot.
• Each time you turn on your replace, you
may notice some amount of condensation
on the inside of the replace glass. This
is normal and will disappear after 10-20
minutes of operation.
• Your direct-vent gas fireplace system
(replace and venting) is a balanced and
1430 Broadway
New York, NY 10018
Batterymarch Park
Quincy, MA 02269
116646-01J4
sealed gas operating unit. It requires ap-
D
RW
FW
proximately 10-20 minutes of operating
time before the ame pattern stabilizes.
PRE-INSTALLATION PREPARATION
LOCATION AND SPACE REQUIREMENTS
Determine the safest and most efcient location
for your FMI PRODUCTS, LLC direct-vent replace. Make sure that rafters and wall studs are
not in the way of the venting system. Choose a
location where the heat output is not affected by
drafts, air conditioning ducts, windows or doors.
Figure 2 shows some common locations. Be
aware of all restrictions and precautions before
deciding the exact location for your replace and
termination cap.
When deciding the location of your replace,
follow these rules:
• Do not connect this replace venting to a
chimney ue serving a separate solid-fuel
burning replace or appliance.
• Due to high temperatures, do not locate this
replace in high trafc areas, windy or drafty
areas or near furniture or draperies.
• Proper clearances must be maintained.
• If your replace is to be installed directly on
carpeting, vinyl tile or any combustible material other than wood, it must be installed on a
metal or wood panel extending the full width
and depth of the replace. See Figure 3.
• Your replace is designed to be used in
zero clearance installations. Wall or framing
material can be placed directly against any
exterior surface on the back, sides or top of
your replace, except where standoff spacers
are integrally attached. If standoff spacers
are attached to your replace, these spacers
can be placed directly against wall or framing
material. See framing details on page 6.
• If you plan on installing a television or entertainment center recessed above your replace, it is recommended that you maintain a
minimum 18" above top of louver opening.
• When locating termination cap, it is important to observe the minimum clearances
shown in Figure 7, page 7.
• If recessing into a wall, you can avoid extra
framing by positioning your replace against
an already existing framing member.
• Do not recess termination cap into a wall
or siding.
• You may paint the termination cap with
450º F heat-resistant paint to coordinate
with the exterior nish.
• There must not be any obstruction such
116646-01J5
as bushes, garden sheds, fences, decks
or utility buildings within 24" from the front
www.fmiproducts.com
• Fireplaces with the sufx of -HA have been
designed to operate at altitudes of 4000
feet and above.
of the termination cap.
• Do not locate termination cap where excessive snow or ice build up may occur. Be sure
to clear vent termination area after snow falls
to prevent accidental blockage of venting
system. When using snow blowers, do not
direct snow towards vent termination area.
• For horizontal installations above 2,000
feet, it is recommended that a 12" extension
pipe be added before starter elbow and a
round horizontal termination be used (see
High Altitude Installation, page 16).
Flush with a wall
Through exterior wall
enclosed in a chase
Corner
installation
Figure 2 - Common Fireplace Locations
22 1/2"
16 5/8"
34 3/8"
Figure 3 - Fireplace Bottom Dimensions
CLEARANCES
Minimum clearances to combustibles for the
replace are as follows:
*Back and sides 0"
Perpendicular walls 6"
Floor 0"
Ceiling to louver opening 42"
Front 36"
Top 0"
Vent (See venting instructions for
specic venting clearances.)
Combustible material with a maximum thickness
of 5/8" may be ush with top front of replace.
* For back and sides of replace, do not pack with
insulation or other materials. 0" clearance to combustible materials are for framing purpose only.
PRODUCT FEATURES Continued
PRE-INSTALLATION PREPARATION
A
B
E
F
G
H
D
C
Nailing Tabs
C
B
A
D
E
F
G
T o p of Louver
Opening
3
2
1
4
5
6
7
Wa ll
Continued
NOTICE: This replace is intended for use as supplemental
heat. Use this replace along
with your primary heating system. Do not install this replace
as your primary heat source.
If you have a central heating
system, you may run system’s
circulating blower while using
replace. This will help circulate
the heat throughout the house.
In the event of a power outage,
you can use this replace as a
heat source.
FRAMING AND FINISHING
Figure 4 shows typical framing of this replace.
Figure 5 shows framing for corner installation.
All minimum clearances must be met.
For available accessories for this replace,
see Accessories on page 37. If you are using
a separate combustible mantel piece, refer to
Figure 6 for proper installation height. You can
install noncombustible mantels at any height
above the replace. Note: Noncombustible
A = clearance above grade, veranda, porch, deck, or
balcony [*12" (30.5 cm) minimum]
B = clearance to window or door that may be opened
[6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US
if between 10,000 and 50,000, 12" (30 cm) in Canada
if between 10,000 and 100,000; 12" (30 cm) in US if
greater than 50,000, 36" (91 cm) in Canada if greater
than 100,000]
C = clearance to permanently closed window
[minimum 12" (30.5 cm) recommended to prevent
condensation on window]
D = vertical clearance to ventilated soffit located above the
terminal within a horizontal distance of 24" (61 cm) from
the center-line of the terminal [18" (45.7 cm) minimum]
E = clearance to unventilated soffit [12" (30.5 cm) minimum]
F = clearance to outside corner (see below)
G = clearance to inside corner (see below)
H = *not to be installed above a meter/regulator assembly
within 36" (91.4 cm) horizontally from the center line
of the regulator
I = clearance to service regulator vent outlet [*72" (182.9 cm)
minimum]
J = clearance to non-mechanical air supply inlet to building
or the combustion air inlet to any other fireplace
[6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US
if between 10,000 and 50,000, 12" (30 cm) in Canada
if between 10,000 and 100,000; 12" (30 cm) in US if
greater than 50,000, 36" (91 cm) in Canada if greater
than 100,000]
K = clearance to a mechanical air supply inlet [*In Canada,
6 ft. (1.83m) minimum; In US 3 ft. (91 cm) above if within
10 ft. (3 m) horizontally]
L = † clearance above paved side-walk or a paved driveway
located on public property [*84" (213.3 cm) minimum]
M = clearance under veranda, porch, deck
[*12" (30.5 cm) minimum ‡]
N = clearance above a roof shall extend a minimum of
24" (61 cm) above the highest point when it passes
through the roof surface and any other obstruction within
a horizontal distance of 18" (45.7 cm)
† vent shall not terminate directly above a side-walk or paved driveway which is located between two
single family dwellings and serves both dwellings*
‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor*
* as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A.
Note: Local codes or regulations may require different clearances
A = 6" (15.2 cm)
Inside Corner
V
B
E
V
B = 6" (15.2 cm)
C = Maximum depth of 48" (121.9 cm)
for recessed location
D = Minimum width for back wall of
recessed location Combustible - 38" (965 mm)
Noncombustible - 24" (61 cm)
E = Clearance from corner in
recessed location Combustible - 6" (15.2 cm)
Noncombustible - 2" (5.1 cm)
Termination Clearances for Buildings with Combustible and Noncombustible Exteriors
Openable
116646-01J7
Figure 7 - Minimum Clearances for Termination Cap
www.fmiproducts.com
VENTING INSTALLATION
NOTICE: Read these instruc-
tions completely before attempting installation.
These models are tested and approved for
use with FMI PRODUCTS, LLC (direct-vent)
pipe components and terminations.
The venting system must terminate on the
outside of the structure and can not be attached to a chimney or ue system serving a
separate solid fuel or gas burning appliance.
A direct-vent appliance must have its own
venting system. DO NOT common vent this
appliance.
These models are approved to be vented
either horizontally through an outside wall or
vertically through a roof or chase enclosure
using the following guidelines:
• When venting system terminates horizontally on an outside wall, you may install
a standoff if the termination cap is to be
installed directly on a combustible nish
such as vinyl, wood, stucco, etc.
• Never run the vent downward as this may
cause excessive temperatures which could
cause a re.
• Vent pipe air space clearances to combustibles are 1" on all sides except on the
horizontal sections, which requires 2" clearance from the top of the pipe. Where the
termination cap penetrates a combustible
wall, 1" air space clearance is required.
• Snorkel terminations are required when
minimum clearance to grade cannot be
met (see Figure 16 on page 12).
• Have replace and selected vent components on hand to help determine the exact
measurements when elbowing or offsetting.
Always use wall restops when penetrating
walls and restops when penetrating ceilings or attic spaces.
• If using a venting conguration of only
horizontal venting with no vertical run, a
1/4" rise for every 12" of run toward the
termination is required.
• For installation of replace at elevations of
4000 feet or greater, pay special attention
to venting requirement recommendations.
www.fmiproducts.com
WARNING: Read all instruc-
tions completely and thoroughly
before attempting installation.
Failure to do so could result in
serious injury, property damage
or loss of life.
NOTICE: Failure to follow these in-
structions will void the warranty.
NOTICE: Do not seal vent cap
to pipe. Cap must be removable
for service.
INSTALLATION PRECAUTIONS
•
Wear gloves and safety glasses for protection
• Use extreme caution when using ladders
or when on roof tops
• Be aware of electrical wiring locations in
walls and ceilings
The following actions will void the warranty
on your venting system:
• Installation of any damaged venting component
• Unauthorized modication of the venting system (Do not cut or alter vent components)
• Installation of any component part not
manufactured or approved by FMI PRODUCTS, LLC
• Installation other than as instructed by
these instructions
WARNING: This gas replace
and vent assembly must be vented
directly to the outside. The venting
system must NEVER be attached
to a chimney serving a separate
solid fuel burning appliance. Each
direct-vent gas appliance must use
a separate vent system. Do not use
common vent systems.
WARNING: Vent pipe air space
clearances to combustibles are
1" on all sides except on the horizontal sections, which require 2"
clearances from the top of the
pipe. Where the termination cap
penetrates a combustible wall, 1"
air space clearance is required.
116646-01J8
INSTALLATION PLANNING
(Framing
Detail)
11
1
/2"
11
1
/2" Inside Framing
11
1
/2"
8 1/2"
Ve nt Opening
Combustible Wall
Ve nt Opening
Noncombustible Wall
There are two basic types of direct-vent
installation:
• Horizontal Termination
• Vertical Termination
Horizontal Termination Installation
IMPORTANT: Horizontal square terminations
require only inner portion of wall restop.
Horizontal installations using round termination require exterior portion of wall restop
available only in vent kit HTK (see Figure
14, page 11).
1. Set replace in its desired location and
determine the route your horizontal venting
will take. Do not secure replace until all
venting has been installed. Some installations require sliding replace in and out of
position to make nal venting connections.
Figures 14 through 18 on pages 11 through
13 show different congurations for venting
with horizontal termination that will help you
decide which application best suits your
installation. Check to see if wall studs or
roof rafters are in the path of your desired
venting route. If they are, you may want to
adjust the location of the replace.
2. Direct vent pipe sections and components
are designed with special twist-lock connections.
Twist-Lock Procedure: Female ends of
pipes have locking lugs (indentations).
These lugs will slide straight into matching slots on male ends of adjacent pipes.
Push pipe sections together and twist
one section clockwise approximately onequarter turn until sections are fully locked
(see Figure 8). Note: Horizontal runs of
vent must be supported every three feet.
Use wall straps for this purpose.
3. Use a 45° elbow to connect venting system to replace ue collar. The elbow is
designed to be twist-locked onto ue collar
as described in step 2. IMPORTANT: Do
not attempt to alter conguration of elbow
by cutting, twisting, bending, etc.
4. Assemble desired combination of pipe
and elbows to replace ue collar. If there
are long portions of venting run, preassembled pipe sections may be installed
as subassemblies for convenience.
116646-01J9
VENTING INSTALLATION
Continued
5. Carefully determine location where vent
pipe assembly will penetrate the outside
wall. The center of hole should line up with
center line of horizontal vent pipe. Mark
wall for a 11 1/2" x 11 1/2" square hole. Cut
and frame the square hole in exterior wall
where vent will be terminated. If wall being
penetrated is constructed of noncombustible material, such as masonry block or
concrete, a 8 1/2" hole with zero clearance
is acceptable (see Figure 9).
WARNING: Do not recess
vent termination into any wall.
This will cause a re hazard.
Female Locking Lugs
Male
Slots
Figure 8 - Vent Pipe Connections
Center
of Hole
Figure 9 - Vent Opening Requirements
www.fmiproducts.com
VENTING INSTALLATION
Continued
6. Noncombustible Exterior Wall: Position
horizontal vent cap in center of the 8 1/2"
round hole and attach to exterior wall with
four screws (see Figure 10). Note: The four
wood screws provided should be replaced
with appropriate fasteners for stucco, brick,
concrete or other types of sidings. Before
attaching vent cap to exterior wall, run
a bead of non-hardening mastic (pliable
sealant) around outside edges to make a
seal between it and outside wall.
Combustible Exterior Wall: For vinyl
siding, stucco or wood exteriors, a siding
standoff may be installed between vent
cap and exterior wall. Siding standoff
prevents excessive heat from damaging
siding materials. Siding material must be
cut to accommodate standoff. Bolt vent
cap to standoff. Apply non-hardening
mastic around outside edge of standoff.
Position standoff/cap assembly in center
of the 11
exterior wall with wood screws provided
(see Figure 11). Siding standoff must sit
ush against exterior fascia material.
7. Connecting Vent Cap with Horizontal Vent Pipe: Slide wall restop over vent
pipe before connecting horizontal run to
vent cap (see Figure 12).
Carefully move replace, with vent as-
sembly attached, toward wall and insert
vent pipe into horizontal termination. The
pipe overlap should be a minimum of 1
(see Figure 13, page 11).
1
/2" square hole and attach to
Apply Mastic to
All Four Sides
1
/4"
Slide wall restop against interior wall
surface and attach with screws provided
(see Figure 12). See Figure 13, page 11,
for horizontal termination details.
Place replace into position and shim with
noncombustible material if needed. Nail or
screw side anges to framing to secure
unit in place. IMPORTANT: Make sure re-
place is level before securing. If replace
is not level it will not work properly.
• Through the wall using round or square
termination (up to 12") adjustable pipe)
• NOT FOR CORNER INSTALLATION
45° Elbow
Horizontal High
Wind Square
Termination
Direct Vent
Pipe
Maintain 1"
Minimum Air Space
Around Outer Pipe
When Penetrating
a Wall
1
11
/2" x 11 1/2"
Framed Opening
Figure 13 - Typical Horizontal
Termination Cap Mounting with
Additional Siding Standoff Installed
Horizontal Termination Congurations
Figures 14 through 18 show different congurations and alternatives for venting with horizontal
termination. Each gure includes a chart with
critical minimum and maximum dimensions
which MUST be met. IMPORTANT: If using a
venting conguration of only horizontal venting
with no vertical run, a 1/4" rise for every 12" of
run toward termination is required.
High Wind
Termination
Apply Mastic
to Outside
Edge of
Standoff
Exterior Wall
with Vinyl Siding
NOTICE: Do not seal termination
cap to vent pipe. Cap must be
removable for vent inspection
and maintenance.
WARNING: Never run vent
downward as this may cause
excessive temperatures which
could cause a re. Operation of
improperly installed and maintained venting system could
result in serious injury, property
damage or loss of life.
Adjustable
Pipe 12"
Max.
Wall
Firestop
Square Termination
Vertical (V) Horizontal (H)
29 3/4" 17" max.
45° Elbow
Wall
Firestop
Round Termination
(Kit HTK Shown)
Figure 14 - Horizontal Termination
Conguration for Square or Round
Termination
Exterior
Portion of Wall
Firestop (Round
Termination Only)
Slide Ring
Over Elbow
to Complete
Connection
Horizontal Round
Termination
116646-01J11
www.fmiproducts.com
VENTING INSTALLATION
Continued
CORNER INSTALLATION
Recommended Applications:
• Corner ground oor installation
• Ground oor installation where pipe vents horizontally through wall (over 12" horizontal pipe)
• Basement installation where one foot clearance from ground to termination is possible
Not to Exceed
Snorkel terminations are available for installations requiring a vertical rise on exterior of
building. If installing snorkel termination below
grade, you must provide proper drainage to
prevent water from entering snorkel termination (see Figure 16). Do not back ll around
snorkel termination.
Snorkel
Termination
90° Elbow
12" Min.
Wall
Firestop
45°
Elbow
Firestop
Wall
Square
Termination
12" Min.
Snorkel
Termination
12" Min.
12" Min.
Adequate
Drainage
Figure 16 - Snorkel Termination Congurations for Below Ground Installation
www.fmiproducts.com
116646-01J12
VENTING INSTALLATION
Continued
HORIZONTAL SYSTEM INSTALLATION USING TWO 90° ELBOWS
The following congurations show the minimum vertical rise requirements for a horizontal
system using two 90° elbows.
Venting with Two 90° Elbows
Horizontal (H
Vertical (V) Horizontal (H1) Horizontal (H2)
5' min. 2' max. 6' max.
6' min. 4' max. 12' max.
7' min. 6' max. 18' max.
8' min. 8' max. 20' max.
20' max. 8' max. 20' max.
Figure 17 - Horizontal Termination Conguration for Venting Using Two 90° Elbows
1
) +
45° Elbow
Venting with Two 90° Elbows
Horizontal (H
Vertical (V) Horizontal (H2)
1
) +
5' min. 6' max.
6' min. 12' max.
7' min. 18' max.
8' min. 20' max.
45° Elbow
20' max. 20' max.
Figure 18 - Horizontal Termination Conguration for Venting Using Two 90° Elbows
with Termination at 90° with Fireplace
116646-01J13
www.fmiproducts.com
VENTING INSTALLATION
Continued
INSTALLATION FOR VERTICAL
TERMINATION
Note: Vertical restrictor must be installed in
all vertical installations.
1. Determine route your vertical venting
will take. If ceiling joists, roof rafters or
other framing will obstruct venting system,
consider an offset (see Figure 19) to avoid
cutting load bearing members. Note: Pay
special attention to these installation
instructions for required clearances (air
space) to combustibles when passing
through ceilings, walls, roofs, enclosures,
attic rafters, etc. Do not pack air spaces
with in sulat ion. Also note maxim um
vertical rise of venting system and any
maximum horizontal offset limitations.
2. Set replace in desired location. Drop a
plumb line down from ceiling to position
of replace exit ue. Mark center point
where vent will penetrate ceiling. Drill a
small locating hole at this point.
Drop a plumb line from inside of roof to
locating hole in ceiling. Mark center point
where vent will penetrate roof. Drill a small
locating hole at this point.
Roof
Flashing
Wall Strap
45° Elbow
Ceiling
Firestop
Figure 19 - Offset with Wall Strap and 45°
Elbows
Flat Ceiling Installation
1. Cut a 11 1/2" square hole in ceiling using locating hole as a center point. Opening should be
framed to 11 1/2" x 11 1/2" inside dimensions,
as shown in Figure 9 on page 9 using framing
lumber the same size as ceiling joists. If area
above the ceiling is an insulated ceiling or an
attic, nail restop from top side. This prevents
loose insulation from falling into required
clearance space. If area above ceiling is a
living space, install restop below framed
hole. Firestop should be installed with no less
than 3 nails per side (see Figure 20).
2. Assemble desired lengths of pipe and
elbows necessary to reach from replace
ue up through restop. Be sure all pipe
and elbow connections are fully twistlocked (see Figure 8, page 9).
3. Cut a hole in roof using locating hole as
a center point. (Cover any exposed open
vent pipes before cutting hole in roof.) The
11 1/2" x 11 1/2" hole must be measured
on the horizontal; actual length may be
larger depending on pitch of roof. There
must be a 1" clearance from vent pipe to
combustible materials. Frame opening as
shown in Figure 9, page 9.
4. Connect a section of pipe and extend up
through hole.
Note: If an offset is needed to avoid
obstructions, you must support vent pipe
every 3 feet. Use wall straps for this purpose (see Figure 19). Whenever possible,
use 45° elbows instead of 90° elbows. The
45° elbow offers less restriction to the ow
of ue gases and intake air.
5. Place ashing over pipe section(s) extending through roof. Secure base of
ashing to roof and framing with roong
nails. Be sure roong material overlaps
top edge of ashing as shown in Figure
19. There must be a 1" clearance from
vent pipe to combustible materials.
If area above is an
attic or insulated
area, install restop
above framed hole.
If area above is a
living space, install
restop below framed
hole.
Figure 20 - Installing Firestop
www.fmiproducts.com
116646-01J14
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.