FMI Baja II, Baja II 36WL, Baja II 36WIL, Baja II 36WS, Baja II 36WIS Installation Instructions Manual

BAJA
II
FirePlac
e
Manufacturers
Wood
Burning
Fireplace
Incorporated
Models:
36WL
Circulating (Louvered)
~~fI/
36WIL
Circulating (Louvered) Fully Insulated
~
~
36WS Non-Circulating (Smooth Face)
36WIS Non-Circulating (Smooth Face) Fully Insulated
INSTALLATION INSTRUCTIONS
SAVE
THIS
BOOK
This book is valuable. In addition to instructing you on how to install and maintain your appliance, it also contains information that will enable you to obtain replacement parts or accessory items when needed. Keep it with your other important papers.
This fireplace is approved for use as a wood burning fireplace or for use with a vented gas log approved to ANS Z21.60,
Z21.84or RGA 2-72 standards or for use with a vent-free gas log heater approved to ANS Z21.11.2 standard. A DESA hood must be installed when using a vent-free gas log heater (see Accessories, p. 10).
WARNING: ALWAYS LEAVE GLASS DOORS FULLY OPENED OR FULLY CLOSED WHEN OPERATING THIS FIREPLACE.
SQUARE
CHASE-
TOP
ROUND TOP TERMINA nON
TERMINATION
~
o o
1-------1
IN. AIRSPACE
TO COMBUSTIBLE
MATERIAL
LOUVERS ON
MODELS
36WL
AND 36'ML ONLY
NO COMBUSTIBLE
MATERIAL
ON FACE
AIR KIT
K/O
GAS LINE
K/O
9
1/4
r
15 1/2--1
ALL DIMENSIONS IN THIS MANUAL ARE IN INCHES UNLESS OTHERWISE SPECIFIED
DESAINTERNATIONAL
PIN 107180-01
- _ • WARNOCK HERSEY
2701 INDUSTRIAL DRIVE
REVB
LISTED
P.O. BOX 90024
-
2/01
BOWLING
GREEN,
KY 42102-9004
www.desatech.com
CONTENTS
1.
INTRODUCTION
PG.2
2.
SELECTING LOCATION
PG.2
3.
MINIMUM CLEARANCES
PG.2
4.
FRAMING AND INSTALLING
PG.3
5.
HEARTH EXTENSION
PG.3
6.
OUTSIDE AIR
KIT
INSTALLA TION
·PG.4
7.
8.
FAN
KIT
ASSEMBLY
CHIMNEY PIPE INSTALLATION
,
....
PG.4
PG.4,5,6
9.
TERMINA TIONS
10. FINISHING YOUR FIREPLACE
11. MANTELS
PG.6
PG.7
PG.7
12. GLASS DOORS
PG.7
13. GAS LINE INSTALLATIONS
PG.8
14. CHIMNEY OFFSET
PG.9
15. DAMPER OPERATION
PG.lO
16. TECHNICAL SERVICE
: 7. REPLACEMENT PARTS AND ACCESORIES ---- _
PG.I0
PG.ll
For more information, visit
WWHJ.desaJech.com
FOR
YOUR
SAFETY
• Do not store or use gasoline or any other flammable vapors or liquids in the vicinity
of
this or any other
appliance.
• Due to high temperatures, the appliance should be located out
of
traffic and away from furniture and
draperies.
• Do not place clothing or other flammable materials on or near the appliance.
NEVER
leave children unattended when a fire is
burning in the fireplace.
WARNING:
IMPROPER INSTALLATION, ADJUST­MENT, ALTERATION, SERVICE OR MAINTENANCE CAN
CAUSE INJURY,
PROPERTY
DAMAGE, OR
LOSS OF LIFE.
REFER
TO THIS
MANUAL
FOR ASSISTANCE OR ADDITIONAL INFORMATION. CONSULT A QUALIFIED
INSTALLER
OR
LOCAL
DISTRIBUTOR.
CHECK
LOCAL
CODES
BEFORE
INSTALLING THIS FIREPLACE.
INTRODUCTION
BEFORE
YOU
BEGIN
• Before beginning the installation
of
the fireplace, read
these instructions through, completely.
• These DESA components and fireplace are safe when installed according to this Installation Manual. Unless you use DES A components, which has been designed and
tested for the fireplace system, you may cause a fire
hazard.
• The DESA warranty will be voided by and DESA disclaims any responsibility for the following actions:
a) Modification
of
the fireplace, components, doors, blower,
fans, air inlet system and damper control.
b) Use
of
any component part not manufactured or approved
by DESA in combination with a
DESA
fireplace system.
PROPER
INSTALLATION is the most important step in
ensuring safe and continuous operation
of
the fireplace. Consult the local building codes as to the particular requirements concerned with the installation
of
all factory built fireplaces. Although grounding may not be required by oode the manufacturer recommends it.
WARNING:
DO
NOT
INSTALL A
FIREPLACE
INSERT
IN THIS BOX UNLESS
THE
MANUFACTURER'S
INSTRUCTIONS WITH
THE
INSERT
SPECIFICALLY
STATE THIS FIREPLACE HAS
BEEN
TESTED
FOR
USE WITH THE INSERT.
This
fireplace
is
intended
to be
used
as a
decorative
appliance
and
is
not
intended
to be
used
to
heat
the
home.
This wood burning fireplace complies with UL 127 standard as a FACTORY BUILT FIREPLACE.
SELECTING
LOCATION To determine the safest and most efficient location for the fireplace, you must take into consideration the following
guidelines:
1. The location must allow for proper clearances (see figures
1 & 2).
2. Consider a location where the fireplace would not be
affected by drafts, air conditioning ducts, windows or doors.
3. A location that avoids the cutting
of
joists or
roof
rafters
will make installation easier.
4. An outside air kit is available with this fireplace.
For
more details refer to section on outside air kit installation
on page 3.
MINIMUM
CLEARANCES
TO
COMBUSTIBLES:
• Back and sides
of
fireplace
.314"
Min.
Note: the % " clearance is not required at the nailing flanges
• Ceiling to Top
of
Opening 67-7/8" Min.
• Floor* 0" Min.
*See step 2
of
"Installing the Fireplace" below
• Wall to front
of
Fireplace 36" Min.
• Perpendicular Wall to Opening
of
Unit 14" Min.
• Top Spacers 0" Min.
• Mantel Clearances see page 7
"Finishing your Fireplace"
• Chimney Outer Pipe
Surfaces........................
I
" M '
m.
WARNING: DO NOT PACK REQUIRED AIR SPACES WITH
INSULATION OR OTHER MATERIALS.
MINIMUMIMAXIMUM
CHIMNEY
HEIGHT:
The
MINIMUM
height
of
the chimney, measured from the
base
of
the fireplace to the flue gas outlet ofthe termination, is
11.5 feet for straight flue or a flue with one elbow set. The
maximum distance between elbows is 2 feet. For systems with
2 elbow sets, the
MINIMUM
height is 22 feet. The maximum
height
of
any system is 50 feet. This measurement includes the
fireplace, chimney sections and the height
of
the termination
assembly at the level
of
the flue gas outlet (see pg. 6, fig. 16).
FRAMING
AND
INSTALLING
THE
FIREPLACE STEP 1: Frame the opening for the fireplace using the dimensions shown in figure 1 or 2. STEP 2:
If
the fireplace is to be installed directly on carpeting, tile (other than ceramic), or any combustible material other than wood flooring; the fireplace must be installed upon a metal or wood panel extending the full width and depth
of
the
fireplace.
STEP 3: Set the fireplace directly in front
of
this opening and slide the unit back until the nailing flanges touch the side framing .
STEP 4: Check the level
of
the fireplace and shim with sheet
metal
if
necessary.
For mare information, visit www.desatech.com
2
--------
STEP 5: Before securing fireplace to prepared framing, the ember protector (provided), must be placed between the hearth extension (not supplied), and under the bottom front edge
of the fireplace to protect against glowing embers falling through. If the fireplace is to be installed on a raised platform, a Z-type ember protector (not supplied) must be fabricated to fit your required platform height. The ember protector should extend under the fireplace a minimum
of
I-W'. The ember
protector 'should be made
of
galvanized sheet metal (28ga. minimum) to prevent corrosion. STEP 6: Using screws or nails, secure the fireplace to the framing through flanges located on the sides
of
the fireplace
(see figure 4).
I
q~
I I I
I
9
3/8"
37
11
/16"
Figure 1
'FRAMING DIMENSION
I--
38 1/2"----1
c....======-:::J
t
I
,------l
I
I
I I
I
I
I I
I
L-~
I
L
______
J
I
-
'-----
c....======-=:J
'---
1
32
9116'
~--\--¥-~_l
Figure 2
CORNER
INSTALLATIONS
-----
65
3116'
-----
0389
HEARTH
EXTENSION:
A hearth extension projecting a minimum
of
16" in front
of
and a minimum
of
8" beyond each side
of
the fireplace opening is required to protect combustible floor construction in front of the fireplace. Fabricate a hearth extension using a material which meets the following specifications: a layer
of non-combustible, inorganic material having a thermal conductivity of K=0.84 BTU IN/FT. HR. F (or less) at I" thick. [For example, if the material selected has a K factor
of
0.25, such as glass fiber, the following formula would apply.
0.25/0.84 x 1.0" = 0.30 thickness required. Thermal conductivity "K"
of
materials can be obtained from the
manufacturer or supplier of the non-combustible material.]
If the hearth extension is to be covered, use non-combustible material such as tile, slate, brick, concrete, metal, glass, marble, stone etc. Provide a means to prevent the hearth
3
extension from shifting and seal the gap between the fireplace frame and hearth extension with a non-combustible material (see figure 3).
fiREPLACE
~T
SEAl
CAP
SWO\IIl
[WeER
PROTECTOR
7.
so.!.
CAP
MER
PROTECllll
OI8ER
PROT(CTQR
EWBER
PROT(CTCIl
Figure 3
HEARTH
EXTENSIONS
WARNING: HEARTH EXTENSION IS TO BE INSTALLED ONLY AS ILLUSTRATED.
NAILING
FLANGE
D1257
NAIL
OR/
SCREW
Figure 4
OPTIONAL
OUTSIDE AIR
KIT
(MODEL AK4 / AK4F) The installation of an outside air kit should be installed during the rough framing of the fireplace due to the nature
of
its
location. Outside combustion air can be accessed through a
vented crawl space (AK4F) or through a sidewall (AK4). See
accessories on page 10 for details.
SE"CURE"
TO COLLARS WITH
AIR INLET
CffBROW
",,[TAL TAPE:.
SCREWS
OR
nf
STRAPS.
r.o
_.
or
I/~
1/
N'
.. IIlU
V£NT HOOD
RfQUIRfD
0:
/"
FOR WAll INSTALLATION
Figure 5
For mare information, visit
WWtII.desatech.com
ASSEMBLING
AND
INST
ALLING
THE
DOUBLE
FAN
KIT
ASSEMBLY:
VCBK3E
A Fan Kit is optional (for Models W36C & IW36C only) with
this fireplace. Use
of
blowers or fans other than manufactured by DESA voids the warranty. Fan is operated by simply pressing the rocker switch in the lower right comer
of
the fireplace face (see figure 6). NOTE:
Fireplace must be wired to the house electrical system in'order for fan to operate. This fan system does not require a wall switch. Electrical connections are made through the cover on the side of
the fireplace illustrated in Figure 7. Use 14 AWG copper wire for all connections. Be certain the fireplace is properly grounded.
ROCKER
SWITCH
ELECTRICAL
~~ ~
~d;TER
PLATE
~~
~
~
::::::::::::
GROUND SCREW
STRAIN
RELIEF
~II~
.~.§
Figure
6
EXISTING ..J' BOX
IN FIREPLACE
\~OVER
PLATE WITH
.--
STRAIN RELIEF
TO WALL SWITCH -
10' 14GA, W/GROUND ROMEX ADDED TO
FIREPLACE AT THE
FACTORY. '"
WIRE NUT (TYP.)
~
Figure 7
CHIMNEY
PIPE
The DESA chimney system consists
of
12, 18, 24, 36 and 48 inch, snap-lock double-wall pipe segments, planned for maximum adaptability to individual site requirements. Actual lengths gained after fitting overlaps must be taken into consideration (lineal gain) chart:
UNEAL GAIN: THE
ACruAl
lIIEASlJRABLE
LENGTH
OF A
PART AfTER
TWO
OR I.IORE
PARrs ARE
CONNECTED.'
12
3/8
GALVANIZED
OUTER
PIPE
and are given in the following
LINEAL GAIN
PART NO.
DESCRIPTION
GAIN (IN.)
~=
FIREPLACE 37
1/2
12-BDM PIPE
SECTION
10
5/8
la-8DM
PIPE SECTION 16
5/8
24 80M PIPE
SECTION
23
5/8
36 80M
PIPE SECTION
34
5/8
48 80M
PIPE SECTION
46 5 8
RT-BDM ROUND
TERWINA
liON
6
7/8
RfL-8DM ROUND
TER!r,lINAllON
7
3/'
RTT-8D1r~
ROUND
lERWfNAllON
SUP SECTION
1-1/111011-1/8_
RTTL-8DM
RO.JND
TERt"INAllON
W/ SLIP SECTION
&-1n-toll-ln·
ET 80M
SQUARE
CHASE-TOP
12
ETO 80M
SQUAAtDiAS£-TOP
./
MESH
12
ETL 80M
5OUAAECHASE-fOP
'It !l..I'SE:CTKlN
11015
ETLO-BDt.A
l~EIt.a:15E.rrTl(1lo.
11
TtI1,-1/<!
• Tl-tE UNEAL GAIN fOR Tl-tE TIRI.IINA nONS IS ;:;; I.IEASURED TO THE
nur
GAS OUTL£T HEIGHT, 0
Figure
8
WALL
CHIMNEY
SYSTEM
Each double wall chimney section consists
of
a galvanized outer pipe, a stainless steel inner flue pipe and a wire spacer. The pipe sections must be assembled independently as the chimney is installed. When starting chimney directly to the fireplace, the inner flue pipe section must be installed first with the lanced side up. The outer pipe section can then be installed over the flue pipe section with the hemmed end up. Press down on each pipe section until the lances securely engage the hem on the fireplace starter. The wire will assure the proper spacing between the inner and outer pipe sections.
WARNING:
The opening in the collar around the
chimney at the top
of
the fireplace must not be obstructed.
Never use blown insulation to fill the chimney enclosure.
Continue to assemble chimney sections as outlined above, making sure that both the inner and outer pipe sections are locked together. When installing double wall "snap lock" chimney together, it is important to assure the joint between the chimney sections is locked. Check by pulling chimney upward after locking. The chimney will not come apart if properly locked.
It
is not necessary to add screws to keep the
chimney together (Exception - see page 5 figure 10).
INSTRUCTIONS
WHEN
ELBOW
OFFSET
OF
CHIMNEY
IS
NEEDED:
(30E-8DM)
TO INSTALL ELBOWS
1. To achieve desired offset, you may install combinations of
12", 18", 24", 36" and 48" length
of
double wall pipe
(SEE SINGLE OFFSET CHART, FIGURE 9 & 11).
OFFSET
CHART
(22-50 FT. SYSTEM
HEIGHT)
RISE
CHIMNEY LENGTH
OFFSET
48" 36"
24"
18"
12"
B
A
ELBOW
SET ONLY
16 -3/8
4 - 3/8
1
25 - 1/2
9 - 3/4
1
30 - 3/4
12 - 3/4
1
15 34 - 3/4
1
1
40
18
1
46-1/4
21 - 1/4
1
1
23 - 3/4 49 - 1/4
1
27 - 3/4 56 - 3/4
1
1
60 - 3/4
30
1
66 1
33
1
71 1
36
2
75
38 - 1/4
1
1
1
80
-1/4
41-1/4
2
86 - 3/4
45
1
1
1
46 - 3/4 89 - 1/2
1
1
97
51
1
2
101
53 - 1/4
106-1/4
2
56 - 1/4
1
1
1
59 - 1/4 111 - 1/2
1
115
-1/2
2
61 - 3/4
1
2
120 - 3/4
64 - 3/4
2
1
68 - 1/4 127
1
1
130 2
70
1
2
137
-1/2
1
74 - 1/4
1
2
141
-1/2
1
76 - 3/4
4
79-
3/4
146-
3/4
For more information, visit www.desatech.com
4
2. Chimney weight above offset rests on return elbow.
FIRESTOP
SPACERS: (V3600FS-8DM)
Straps must be securely nailed to rafters or joists (see figure 9, details a
& b).
3. Maximum length of pipe between supports (return elbow or 12S-8DM) is 6'
of
angled run. Maximum
of
two (2) 6'
angled run sections per chimney system (see figure 11).
SEE
DETAIL
A
D
to
....
co o
Figure 9
DETAIL
A
All joints between offset should be secured with two screws, only on the outer pipe, and shall not penetrate the inner stainless.
Figure 11 *TYPICAL
OFFSET
INSTALLATIONS
*For systems with 2 elbow sets, the minimum height is 22 ft. The maximum height for any system is 50 ft.
Firestop spacers are required at each point where the chimney penetrates a floor space. Their purpose is to establish and maintain the required clearance between the chimney and the combustible materials. When the pipe passes through a framed opening into a living space above, the firestop must be placed onto the ceiling from below as shown in figure 12.
LIVING SPACE
ABOVE CEILING
FJRESTOP
SPACER
SCREWS OR STAPLES
(MIN. OF B)
Figure 12
PENETRA
TING
THE
ROOF:
To maintain a I-inch clearance to the pipe on a roof with a pitch, a rectangular opening must be cut. STEP
1: Determine the center point through which the pipe
will penetrate the roof. STEP
2: Determine the center point
of
the roof. Pitch is the distance the floor drops over a given span, usually 12 inches. A 6/12 pitch means that the roof drops 6 inches for each 12
inches one measure horizontally down the roof.
STEP
3: Use the roof-opening chart (figure 13) below to determine the correct opening length and flashing required. STEP
4: Remove the shingles around the opening measured
and cut out this section.
STEP 5: Add the next sections
of
the pipe until the end penetrates the roofline. Check to see that the proper clearances are maintained. Extend chimney by adding sections of
double wall pipe until pipe is a minimum
of
30 inches above the highest point of the roof cutout. Termination and chimney must extend a minimum
of
36 inches above the
highest point where it passes through roof.
PITCH SLOPE
(degrees)
OPENING "A" MAX
(inches)
USE FLASHING
MODEL NO.
FLAT 0
15
V6F-8DM
0-6/12
26.6
16 - 1/8
V6F-8DM
6/12 - 12/12 45.0
20 - 3/8
V12F-8DM
Figure 13
For more information, visit www.desatech.com
5
FLASHING
INSTALLATION:
(V6F-8DM
or
VI2F-8DM)
that can be used for flashing or chase and ET-8DM, ETO-
Determine the flashing to be used with the roof-opening chart. Slide flashing over pipe until base is flat against roof. Replace as many shingles as needed to cover exposed area and flashing
base. Secure in position by nailing through shingles (see figure 14). DO
NOT
NAIL
THROUGH
FLASHING
CONE.
CHIMNEY PIPE
STORM~
COLLAR
~
FLASHING
Figure 14
INSTALLING
FLASHING
ON A METAL
ROOF:
When installing the flashing on a metal
roof
it is required that
putty tape be used between the flashing and the roof. The flashing must be secured to the
roof
using #8 x y.." screws and
then sealed with
roof
coating to prevent leakage through the
screw holes. A
roof
coating must also be applied around the
perimeter
of
the flashing to provide a proper seal.
STORM
COLLAR
INSTALLATION:
(SCI
or
SC2) Place storm collar over pipe and slide down until it is snug against the open edge
of
the flashing (see figure 15). Use SC 1 for all round terminations and SC2 for all terminations with slip sections.
FLASHING
Figure 15
TERMINATIONS I SPARK
ARRESTOR: The fireplace system must be terminated with the listed round top or chase
terminations, In any case, refer to the installation
instructions supplied with the termination, The terminations approved for this fireplace are the RT-8DM and RTL-8DM
8DM,
El'L-8DM
and
ETLO-8DM
for chase style termination
only. Figure 16 shows an RTL-8DM round top
termination .
RTL-BDM
ATTACH
BRACKET
111111f------
TABS TO OUTER
PIPE (.3
PLACES)
FLUE GAS OUTl.ET
SECURE WITH
--OF"
TER~INA
nON CAP
SCREWS
~
FLUE PIPE OF
_
RTL-8D~
INSIDE INNER
PIPE OF
CHI~NEV
CAULK
Figure 16
CAUTION:
Do not seal openings on the rooftop flashing. Follow the installation instructions provided with the termination being used.
Terminations with 16" slip pipe sections are available. The RTT-8DM and
RTTL-8DM
are approved for flashing
installations.
When
needed, these adjustable terminations may be used in combination with the pipe assembly to achieve the correct chimney height. NOTE:
In the rare instance there is a problem with side driven rain or wind or the chimney is not drafting properly, an ADS­8DM Anti Draft Shield can be used with round terminations,
CHASE
INSTALLATIONS: Instructions for chase installations are included with the chase style termination chosen. In a multiple chase installation, be sure to provide adequate distance between terminations to prevent smoke spillage from one termination to another. We suggest that terminations be separated at least 24 inches, center to center and stacked at vertical height difference
of
18
inches (see figure 17).
Figure 17
For more information, visit www.desatech.com
6
10
FOOT
RULE:
All flue gas outlet
of
chimney termination must extend a
minimum
of
3 feet in height above the highest point where it
passes through the roof and must be at least 2 feet above the highest point
of
the roof that is within a horizontal distance
of
10 feet (see figure 18).
Figure 18
FINISHING
THE
FIREPLACE:
Combustible materials, such as wallboard, gypsum board, sheet rock, drywall, plywood, etc may make direct contact
~ith
sides and top periphery
of
the fireplace fflce.
It
is Important that combustible materials do not overlap the face itself. Brick, glass, tile or other non-combustible materials may overlap the front face provided they do not obstruct essential openings like louvered slots or any other opening. When overlapping with a non-combustible facing material use only non-combustible mortar or adhesive.
MANTELS:
A mantel may be installed if desired (see figure 19). Woodwork such as wood trims, mantels, or any other combustible material projecting from the front face must not be placed within 9 inches
of
the fireplace opening (and within
6 inches
of
the top louver opening). Combustible materials
above 9 inches and projecting more than
1-112
inches from the fireplace face must not be placed less than 12 inches from the top
of
the opening
of
the fireplace (NFPA
SID
211, Sec. 7-
3.3.3).
-.~
""noN
or
&'OO£l. J8W(I)L I
Figure 19 MINIMUM FRONT AND
TOP
CLEARANCES
Mantels or any other combustible materials such as wallboard sheet rock, drywall, plywood, etc. butt up to the side
of
the
black metal face
of
the fireplace. The clearances from the side
of
the fireplace to any combustible material and wall should
fall within the limits shown in figure 20.
TOP VIEW OF FIREPlACE
\
/
<EXAMPLE 1
<EXAMPLE 2 /
/
NO MAT
CO""""""
j
FAC
~Rb~L
F~~EBOX
./
/
~'"'""~
FIREPLACE
I'
BOTH
SIDES-j
I-
~
Figure 20
VI/(I
I I
9
5/8
L 8 15/16
8
1/4
LI--
7 9116
.L+-+-
/
6
7/8
/
6
3/16
5
1/2
t3
I
4
13/16
~
4 118 -
3
7/16
2
3/4
2 1/16
1
3/8
1t/16
2 3 4 5 6 7 8 9 10 It 12 13 14
INCHES
MiDimum
14 iochcsfromperpendicular side
",aU
MINIMUM SIDE CLEARANCE
*Example 1 (figure 20): The face
of
a mantel, bookshelf, etc.
is made
of
combustible materials and protrudes 2-%" from the wall the fireplace is installed in. This combustible material must be a minimum
of
4" from the side
of
the fireplace
opening, *Example 2 (figure 20): The face
of
a mantel, bookshelf, etc.
is made
of
combustible materials and protrudes 11/16" from the wall the fireplace is installed in. This combustible material can butt up against the side
of
the fireplace (i.e. 1" from the
fireplace opening).
OPERATING
GUIDELINES AND MAINTENANCE INSTRUCTIONS GLASS DOORS
Glass doors are optional with the fireplace. When the fireplace is in operation, doors must be in the FULLY OPEN or FULLY CLOSED position only or a fire hazard may be created (see figure 21). A fireplace equipped with glass doors operates much differently than a fireplace with an open front. A fireplace with glass doors has a limited amount
of
air for combustion. Excessive heat within the fireplace can result if too large a fire is built or if the combustion air gate is not completely open. The following tips should be followed to assure that both the fireplace and the glass door retain their beauty and function properly. Both flue damper and the glass doors must be fully open before starting the fire. This will provide sufficient combustion air and maintain safe temperatures in the firebox.
BI-FOLD GLASS
DOORS
-
r
I
......
......
FULLY
CLOSED
FIREPLACE
FRON
T
Figure 21
-J"
~
f
!--FULLY OPEN
--
N
r-,
FIREPLACE
FRONT
0
For more information, visitwww.desatech.com
7
IMPORT
ANT: The glass must be allowed to wann slowly and evenly. The tempered glass will withstand a gradual temperature rise to 550 degrees Fahrenheit, which is more than a normal fire will generate. Such materials as pitch/wax laden logs, very dry mill end lumber, and large amounts
of paper or cardboard boxes can create an excessively hot fire and should not be burned in this fireplace. Always keep the fire well back from the doors and never allow flames to contact the glass.
WARNING: Fireplaces equipped with glass doors should be operated only with door fully opened or doors fully closed. Doors, if left partly open, may draw gas and flame out
of
the fireplace opening creating risks
of
both fire and
smoke.
CLEANING THE GLASS:
Clean
the
glass
with
any
commercial
glass
cleaner
or
soap
and
water.
DO NOT
use
any
abrasive
material to
clean
the
glass.
DO NOT
clean
the
glass
with
any
cool
water
if
the
glass
is still hot
from
the
fire.
OPTIONAL
GAS LINE
INSTALLATION GAS LINE HOOK UP SHOULD BE DONE BY YOUR SUPPLIER OR A QUALIFIED SERVICE PERSON. NOTE: BEFORE YOU PROCEED, MAKE SURE YOUR GAS SUPPLY IS TURNED OFF. A gas line may be installed for the purpose
of
installing a vented or vent-free gas appliance available through your local distributor.
.Use only
liz
inch black iron pipe and appropriate fittings. When installing a gas line, a shut-off valve designed for installation outside the appliance is recommended. STEP
1: To install, remove the knockout indentation on the refractory, (or firebrick), wall located approximately 2 inches above the refractory hearth floor. The knockout indentation must be firmly tapped with any solid object until it is released. Remove fragmented portions
of
refractory (see figure 22).
AFTER
~~I/
GAS LINE
CONDUIT
REMOVE.
INSULATION
T£MPORARILY
NOT
DISCARD)
SIDE FIREBRICK
ourSIOE OF
FINISHED SIDE
FIREPLACE
REMOVE:
KNOCKOUT
(DO
REFRACTORY
..
()
KNOCKOUT
PLUG
REMOVING
REMOVE BY TAPPING
GAS LINE COVER
L/CHTLY WITH
A
PLATE, REPLACE
1/2"
DOWEL
0<40
SCREWS
Figure 22
STEP
2: Remove gas line cover plate on rear
of
fireplace and null out insulation from gas line conduit sleeve. Save insulation for reuse. STEP
3: Run a
liz
inch black iron gas line into the fireplace through the gas line conduit sleeve. Provide sufficient gas line into fireplace chamber for fitting connection (see figure 23). NOTE: Secure incoming gas line to wood framing to provide rigidity for threaded end.
SIDE FIREBRICK FINISHED SIDE
GAS LINE
PROVIDE ENOUGH
CONDUIT
THREADED
END
FOR FITTING
CONNECTION
REPACK
INSULATION
SEAL OPENING
WITH REFRACTORY
CEMENT
STEP
4: Repack insulation around gas line and into sleeve opening. Seal any gaps between gas line and refractory knockout hole with refractory cement or commercial furnace cement. Install the gas appliance or cap-off gas line if desired.
The
gas
pipe is intended for connection to an unvented (vent-
free) or a decorative
gas
appliance (vented
gas
log).
CAUTION: All gas piping and connections must be tested for leaks after the installation is completed. After ensuring that the gas valve is on, apply a soap and water solution to all connections and joints. Bubbles forming show a leak. Correct all leaks at once. DO NOT USE AN OPEN FLAME FOR LEAK TESTING AND DO NOT OPERATE ANY APPLIANCE IF A LEAK IS DETECTED.
Ifyou wish to install an unvented (vent-free)
gas
log set,
ONLY
UNVENTED
GAS
LOG
SETS
WHICH
HAVE
BEEN
FOUND
TO
COMPLY
WITH
THE
STANDARD
FOR
UNVENTED
ROOM
HEATERS,
ANSI
Z21.11.2, ARE TO BE
INSTALLED
IN
THIS FIREPLACE.
NOTE: A DESA
hood
must
be installed
when
using an
unvented
gas
log
set
(see accessories on page 10).
WARNING:
DO NOT OPERATE AN UNVENTED GAS LOG SET IN THIS FIREPLACE WITH THE CHIMNEY REMOVED.
If you install a decorative
gas
appliance (vented
gas
log), the
decorative
gas
appliance must comply with the
Standard
for
Decorative
Gas
Appliances for Installation in solid fuel
burning Fireplaces, ANS Z21.60-1996, Z21.84
or
RGA 2-72, and shall also be installed in accordance with the National Fuel Gas
code,
ANS Z223.1-1996.
WARNING:
If
the fireplace has been used for wood
burning, the firebox and chimney must be cleaned
of soot, creosote and ashes by a qualified chimney cleaner. Creosote will ignite if highly heated.
WARNING:
WHEN USING A DECORATIVE VENTED GAS LOG, THE DAMPER MUST BE REMOVED OR PERMANENTLY LOCKED IN THE FULLY OPENED POSITION.
For mare information, visit www.destuech.com
8
MINIMUM
HEIGH
T OF 22 FT.
MAXIMUM
HEIGH
T OF 50 FT.
(\\1TH
TWO
ELBOW
SETS)
RT-BDM
RT-BDM
EFTECTIVE
1'£JGHT
OF
l'ER..........nON CAP
MAXIMUM
RT-BDM
RT-BOM
HEIGHT
Eff!CTI'l£
HEIGHT
OF
EFFECTIVE
HEIGHT
OF
TERwl
....
An~
CAP
---
ITRl.IlN
....
TION
CAP
50 FT.
11.5 FT. 11.5 FT.
MINIMUM
MINIMUM
HEIGHT
HEIGHT
[ill]
STANDARD
INSTAU..HIO~
DAMPER
OPERATION:
The damper handle to open and close the damper blade is located inside the firebox at the center towards the back wall. Pushing the handle back in the keyway slot will free the damper blade to automatically open. To close, reach in and push the handle back into the keyhole slot then pull down and forward to lock it in place (see figure 24).
0751
0750
Figure
24
D1J09
ALTER.""lAl'E
INSTALLATIONS
WARNING: Risk
of
fire! Replace grate with DESA model 107001-01 grate only. This grate has been designed to keep the operation
of
your fireplace safe and efficient.
FOR FURTHER OPERA TlNG GUIDELINES, INSTRUCTIONS AND WARRANTY INFORMATION PLEASE REFER TO YOUR HOMEOWNERS GUIDE OR CONTACT YOUR AUTHORIZED DEALER.
TECHNICAL SERVICE
You may have further questions about installation, operations, or troubleshooting.
If
so, contact The Technical Service Department at 1-888-427-8322. When calling, have the model number
of
the fireplace ready.
For more information, visit www.desatech.com
9
Loading...