FM Electronics FM4000X, FM4001 Installation Instructions Manual

FAULT FINDING GUIDE
CUSTOMER HAD AN ALARM Ask them to press the Full set button and tell you
what indicators are on.
The LED's indicate the cause of the alarm and also the setting status at the time.
MAINS LED FLASHING Mains failure (Restore supply) ZONE LED FLASHING (in exit) Check that doors and windows are closed.
Flashing with tamper LED. (A detector has an open tamper). Flashing with Battery LED. (The detectors battery needs replacing).
ALARM LED ON Full alarm. The LEDs indicate what caused the alarm. If Engineer reset is programmed into the panel an engineer reset will be required before the system can be re-armed.
FLASHING WITH ZONE LED A detector on soak test has trig­gered whilst the sys­tem was armed.
FLASHING WITHOUT A ZONE LED An engineer reset is required. BATTERY LED ON The control panel's battery is disconnected or needs re-
placement.
FLASHING: Detector has a low battery. The zone LED will flash to indicate which one.
SIGNALLING LED ON The system is being blocked by a continuous transmission.
FLASHING If flashing on its own, an external line monitor has
signalled that the telephone line is at fault. Flashing together with a zone indicator. The system is set as a supervised system and the detector indicated by the flashing zone LED has failed to report in. ( Re­site the detector where there is good radio reception. Use the RSSI output to check.
CONTACT TRANSMITTER NOT WORKING Check the magnetic contact is operating correctly. Open lid and check what zone it should be on. Go into the panel engineer mode and check if it has been programmed onto the correct zone. Note: the panel will not allow you to program a detector onto two zones. When pro­grammed onto a zone any previous zone allocation will be deleted.
PIR NOT WORKING The detector needs 6 minutes to settle on power up. Set the control into operator walk test mode and walk test the detector with the cover removed. Removing the cover opens the tamper and overrides the 2 minute inhibit timer. If the test jumper inside is fitted and the cover replaced it overrides the 2 minute inhibit, but allows you to walk test it without a tamper alarm.
CUSTOMER HAS FORGOTTEN THEIR CODE Open the panel and short out the MEM jumper. The user and engineer codes will be restored to the factory defaults 1234 & 4679. No other programming is affected.
15
OFF
PART SET
FULL SET
ZONES
PANIC
FIRE
FM4000X and FM4001 CONTROL PANEL
INSTALLATION INSTRUCTIONS
SIGNALLING
TAMPER
LOW BATTERY
ALARM
MAINS ON
CI-123 iSS 2
FM Electronics Ltd Manufacturer of quality wireless products
FM4000X
2 6 J u n 1 5 : 4 1 : 2 2 P a n e l d i s a r m e d
1
CONTENTS
14
+
+
_
_
5
6
8
7
9
10
111213
4
3
2
1
5 6 7 8
4
3
2
1
ANTENNA
GROUND
TAMPER
MEM
Jumper
ZONE 1
LINE FAULT INPUT
12V AUX
Max 500mA
+ LATCH
-ve SIREN
-ve STROBE
FULL SET IN
PART SET IN
LED 2
LED 1
-ve DIALLER
-ve TAMPER RETURN
17V a.c.Input
EXIT
SOUNDER
Volume level
adjust
Link 5 to 4 if -ve
from SAB is not
connected to 5.
Hard wired
arming
Alarm
outputs
DIALLER OUTPUTS
RSSI RESET
Aux.
Armed
Panic
Fire
Jamming
Low battery
Auto report fail
Alarm
EXIT TERMINATE PUSH
ZONE 2 / PA
1A AUX
2A BAT
L.S.
FUSES
+
VOLTMETER CONNECTION
-
Plug lead from
4001 on here
FM4000X CONTROL PANEL
Control panel connections. Description of operation 2, 14
LCD display connections. Description of operation 2, 13
Installation procedure. 3 Programming 4
Adding Detectors 5 Adding Remote controls 6 Exit Entry times 6 Siren output programming 6 Zone option programming 7 Options 27 to 50 8 - 10
Remote engineer reset 10 Antenna tamper module 11 Wired arming connections 12 S.A.B. connections 12 LCD unit connection diagram 13 FM4000X Connection diagram 14 Fault finding 15
Page
2
FM4000X CONNECTIONS
CONNECTIONS (RIGHT HAND SIDE)
1-4 12V Auxiliary supply output. Maximum load current 500mA
5 Tamper -ve return. If connecting a Self Actuating Bell (SAB) then connect the
-ve tamper return to this terminal. If not fitting a SAB this terminal must be connected to -ve Aux..
6. This terminal provides a +ve output on alarm which is reset next time the panel is armed. It is provided for use with hard wired detectors that have a latching LED facility.
7. -ve to trigger Siren. Goes from open circuit to 0v to operate a bell or siren. Max 500mA. Resets after the bell time set in engineer program.
8. -ve Strobe. Goes from open circuit to 0v in alarm to operate a strobe. Remains on until the system is disarmed.
9. Dialler trigger output. Is provided for triggering an autodialler. This output goes to 0v on full alarm. Once triggered it remains until the panel is disarmed so as not to trigger any more until the system is turned off.
10 Fault LED output for remote wired arming. Indicates that a fault is present which will prevent arming.
11. System Off LED output for remote hard wired arming. Indicates when disarmed.
12. Part Set hard wired arming input. Apply +12v to arm. Remove to unset.
13
PLUG ON DIALLER
CONNECTORS
LCD CONTRAST
ADJUST
8
76
5
4
3
2
1
TAMPER OUTPUT
FM4001 LCD DISPLAY
DIALLER OUTPUTS
+12V INPUT
0V INPUT
-BAT
+BAT
BATTERY
FUSE 1A
MAIN FUSE 1A
PARALLEL PRINTER
CONNECTOR
CLOSED
LOW BATTERY
AUXILIARY
JAMMING
AUTO REPORT FAIL
ALARM
P.A.
FIRE
13. Full Set hard wired arming input. Apply +12v to arm. Remove to unset.
CONNECTIONS ALONG BOTTOM EDGE
HARD WIRED INPUTS 1 & 2 Must be linked out if not used. These inputs are normally closed, opening in alarm. Zone 2 can be programmed to be a PA zone.
EXIT TERMINATE PUSH Connection for a normally open push button which sets the alarm when pressed during the exit time.
LINE FAULT INPUT Normally closed input. Open for line fault. To trigger with applied negative, leave the link in place and apply 0v for line fault.
DIALLER OUTPUTS 1-8 These outputs are for connection to a digital communicator employing +ve removed trigger inputs.
The outputs go from +5v to 0v in alarm.
These outputs are also available on the FM4001
RECEIVED SIGNAL STRENGTH INDICATION (RSSI) For connection to a digital voltmeter to indicate the Signal Strength of a transmission received from a detector. (Refer to section on using the RSSI output).
FM4001 CONNECTIONS
The FM4000 LCD unit is supplied with a connecting lead which plugs into the FM4000x expansion port connector. Mount the LCD display at a height of about 4ft 6in. so that the display can be viewed correctly. Mount the FM4000X directly below the LCD unit and plug in the connecting lead.
2. Complete the User Record
The back pages of the user instruction booklet should be completed and left with the operator for their reference. It gives them information about the zones etc.
3. Complete a system record sheet
System record sheets should be completed before commencing programming. This acts as a reference when programming and can form part of the installation records.
4. Locate the control panel
For best radio coverage the control panel is best located at a central point in the building. The higher it is the better for radio reception. (Do not mount at floor level on a ground floor)
Metal objects cause radio reflections which oppose the signal being received from the detector with a resultant reduction in the received signal strength. Metalwork close by can result in complete cancellation, therefore do not site the control panel or detectors near to large metal objects, metal piping, girders, concentrations of mains cabling, fuse boxes etc.
Consider the ease of wiring to the external siren when making your choice.
The Panel may be temporarily sited whilst a test is carried out to verify the reception from distant detectors.
The panels must be fixed using the three fixing points provided. Ensure that the LCD display on the FM4001 is approx. 4ft 6 in. high for ease of viewing and that the FM4000X is mounted directly below it. For larger installations a remote tamper protected antenna is available.
FM4001 CONNECTIONS cont..
3
12
11 12 13
10
1
470R Resistors
Fault LED (If required) Armed LED (If required)
+12V
WIRED KEYPAD / KEYSWITCH ARMING
Part
Full
Off
Bell sw-
Bell sw+
Tamper feed
Tamper return
Strobe +
Strobe -
-ve Hold off
+ve Hold off
7
1
3
5
8
Connections on the FM4000 main board
SAB CONNECTION TO THE FM4000
12v SUPPLY TO THE FM4001
Connect to the 12v aux output of the FM4000x
TAMPER OUTPUT.
Clean contact normally closed output. Tamper return from the siren can be routed via this contact. If the tamper is operated a tamper alarm will occur.
STAND-BY BATTERY
Connections are provided for an additional stand-by battery inside the FM4001 for situations where a battery is required in addition to the one already in the FM4000x .
LINE FAULT OUTPUT TO FM4000X
This output is used when employing a plug on dialler. The dialler should be programmed for -ve applied on line fault. This connection can then be connected to the line fault input on the FM4000. (Leave the link fitted in the line fault input) .
DIALLER OUTPUTS 1 - 8
These outputs are identical to the 8 outputs in the FM4000x. They are provided for convenience since it is easier to locate a digi dialler into the FM4001. See connection diagrams at back of manual.
INSTALLATION
The factory defaults for the user and engineer codes are:­USER CODE = 1 2 3 4 ENG CODE = 4 6 7 9
The recommended installation procedure is as follows:
1. Label detectors.
Label each detector with its zone number for reference during installation and for later service reference.
Mains supply to the control panel must be provided by a competent electrician to the current issue of the IEE regulations.
A 12v sealed lead acid stand-by battery should be connected after all wiring has been completed and tested. 12v 2.3AH is recommended.
5. Program detectors onto the panel
Each detector has an internal "Learn" jumper. To add a detector to the system: Go into the engineer program. Select the zone and device number. Short out the learn jumper on the detector. Remove the learn jumper after programming. The detector transmits its identity together with a learn bit. The panel stores the detectors identity code and adds it to the chosen zone. (Refer to engineer programming section)
6. Carry out range test
If you keep a 4174 remote control for testing, you can program this onto the system and then go to each detector location in turn and verify that the control can be armed and disarmed from all detector locations.
7. Mount the detectors
Refer to the detector instructions for recommended mounting positions. As reflections from metalwork act to cancel the transmission, avoid siting near to any metalwork. Reflections like this can often be overcome by a small movement in position of 15 to 20cm.
8. Making panel program changes.
Complete a system record sheet before making any changes. Once programmed the program is stored in none volatile memory, so data will remain stored even in the event of complete power failure.
INSTALLATION cont...
9. Radio test using the RSSI output
To measure the signal strength received from a detector. i) Connect a Voltmeter to the RSSI output terminals. ii) Press the reset button next to the RSSI terminals. The voltmeter should now read zero volts.
iii) Go to the detector and operate the learn jumper. iv) Return to the panel. The voltmeter now displays a voltage representing the strength of the transmission received. It will ignore any other transmissions and only respond to the learn message or a Panic or Off message from a remote control or panic button.
The voltage reading should be a minimum of 1.0v.
The readings for each detector can be recorded on the system record sheet for future reference.
10. Full system test
A walk test facility is provided in the Operating instructions. This may be used to do a test of the detectors only. Once the Sounders and dialler have been connected and the installation completed a full test with remote signalling should be carried out.
PROGRAMMING
1. Enter the engineers code 4 6 7 9 The Alarm led will flash slowly to indicate that you are in the program mode.
2. Key in the two digit program number. (The zone led's indicate which option is set.)
3. Key in the option required (The zone led's indicate your choice)
4. Press the Full Set key to exit that
4
11
Displays the software issue of the 4000X panel, press full set to exit.
REMOTE ENGINEER RESET FACILITY
When an alarm occurs which requires an engineer reset, the user can call the Central Station and obtain the access code number to key in to the panel. The panel zone LED's will illuminate randomly. From the LED's the Central Station operator can refer to a reference table and instruct the user what code to enter to perform an engineer reset. Next time the alarm operates the reset code number will have changed.
Coax to FM4000 Antenna input termi­nals ( Inner to top terminal outer to bottom terminal ).
Remove link to make antenna tamper active.
+12V
0V
If LED is ON tamper is
open ( Antenna
disconnected ).
BNC connector for remote antenna.
GND/OUTER
SIGNAL/INNER
Alternative connection for remote antenna.
Tamper return To FM4000 terminal 5.
-ve tamper feed from SAB ( If SAB not used link this terminal to 0V ).
Mount the module to the right hand side of the transformer in the FM4000 with the single screw supplied.
4005 ANTENNA TAMPER MODULE
The 4005 is for use with tampered remote antennas. When fitted into the FM4000 panel the -ve tamper return from an external siren is connected to this module as shown below.
Always mount the remote antenna away from other wiring, any other metal objects and as high as practically possible to obtain the best working range from the 4000X control panel.
The output from the receiver can be heard on the panel loudspeaker. Press the full set key to exit.
46 DISPLAY ENGINEERS LOG
Press keys 1 to 8 to view the last 8 events. Most recent is displayed on key 1. Key 9 shows the last "First to Alarm" Press the full set key to exit.
47 CHANGE ENGINEERS ACCESS CODE
Key in a 4 digit code twice.
48 LEAVE ENGINEER MODE
If any devices have their tampers open, the display shows which zones are tampered and will generate an error beep. The tampers must be restored before leaving engineer mode by pressing 48 again.
49. DIALLER OUTPUT FOR PA 1= PA Triggers PA dialler output 0= PA Triggers both PA and ALARM dialler outputs* Press the full set key to exit.
50. HARD WIRED PA ON ZONE 2
1= Zone2 is a PA zone 0= Zone2 is a standard zone* Press the full set key to exit.
This feature enables hardwired PA buttons to be connected to the panel via the zone 2 hardwire input.
CAUTION: Radio devices including PIRS and contacts programmed onto zone 2 will also trigger a PA alarm if this option is selected.
51 FINAL EXIT SET
1= Yes 0= No* If yes the exit time will terminate when the final exit door is closed.
52 REMOTE CONTROL FULL SET EXIT TIME
5
program step.
5.
When finished with programming key
in 48 to exit engineer mode.
ERROR CORRECTION VIA PART SET KEY
If you accidentally enter an engineer program number and change an option value, you can undo the change by pressing the Part Set key before exiting the program step via the Full Set key.
EXAMPLE: To set the Full set exit timer to 1 minute. Key in 4 6 7 9 The alarm indicator will illuminate to indicate that you are now in engineer program mode
Key in 1 2 To select Full set exit time (program No. 12.)
Key in 6 To select the 1 minute option. Zone 6 LED indicates your choice Press the Full Set button to exit program
step. Note: The Full set button must be pressed
to exit from each program step. Until the Full Set button is pressed any key press just changes your choice of option.
Key in the next program Number you wish to change.
When all programming is complete Key in 48 to exit engineer mode
LEARNING DEVICES
When installing the system you may find it easier to label each detector with its zone number and learn them into the panel before installation. Once programmed into the panel's memory,
DETECTOR PROGRAMMING
the information will not be lost even when power is removed from the panel.
01 PROGRAM DEVICES ONTO ZONE 1
Select program number 01. The LCD display will show "LEARN ZONE 1 DEVICE ?
The LEDs 1 to 8 indicate which of the 8 devices are already programmed onto zone 1.
Use keys 1 to eight to select the device number.
Short out the learn jumper on the detector and ensure that the learn pins are not left
permanently shorted.
The panel will emit 2 short blips to indicate that it has learnt the detector. The corresponding LED will illuminate and the LCD will display the unique 5 digit identity code of the device with the message LEARNT OK. If the device was already programmed on the system at a different location the message will say MOVED FROM xx (where xx is the old zone and device number). If a device was already programmed in the location the LCD will show the message ALREADY STORED and the new device will overwrite it. Automatically deleting the old one.
Press the Full Set key to exit. DELETING DEVICES FROM ZONE 1
Select program number 01. The LCD display will show LEARN ZONE 1 DEVICE ?
The LEDs 1 to 8 indicate which of the 8 devices are already programmed onto zone 1.
Use keys 1 to eight to select the device number to be deleted. If a device did exist at that location the LCD will show ALREADY STORED.
10
1=2s 2=5s 3=10s 4=15s 5=20s 6=30s 7=1min 8=infinite This applies to remote control and remote keypad only. The exit time when armed from the panel keypad (option 12) is not affected.
53 REMOTE CONTROL PART SET EXIT TIME
Enables the exit time to be set for part set via the remote control / keypad. The exit time set by option 13 still applies when arming from the panel keypad. 1=2s 2=5s 3=10s 4=15s 5=20s 6=30s 7=1min 8=infinite
54 ABORT (not operational on this version)
55 VERIFICATION (not operational on this version)
56 DIALLER TEST
Key in 56 followed by a number key to operate a dialler channel. The number selected will be displayed. 1= Jamming 2= Low Battery 3= Alarm 4= Supervisory failure 5= Auxilliary Alarm 6= System Armed 7= Panic Alarm 8= Fire Alarm Press full set key when test is completed.
57. DIALLER TRIGGER INVERT
All the dialler outputs are positive removed as the default setting, but can be inverted to Negative removed if required. To invert an output key in 57 followed by the required output to be inverted, using the same list as used for the dialler test.
Press full set key when outputs have been selected, outputs will change to the selected settings when the full set key is pressed.
58. DISPLAY SOFTWARE ISSUE.
programming). Up to 8 Fire detectors can be programmed onto the Fire zone, i.e. devices 101 to 108. The LCD display will refer to the Fire detectors as F1 to F8. Press the Full Set key to exit.
11 REMOTE CONTROLS
Key in 111 to program the first Remote Control onto the system. The Panic button is operated instead of a learn jumper. Up to 8 Remote Controls can be programmed onto the system, i.e. devices 111 to 118. The LCD display will refer to the remote controls as R1 to R8. Press the Full Set key to exit.
EXIT ENTRY
12 FULL SET EXIT TIME
1= 2 secs 2= 1O secs 3= 2O secs* 4= 3O secs 5= 45 secs 6= 1 min. 7= 2 mins. 8= Infinite Press Full Set to exit
* = FACTORY DEFAULT
13 PART SET EXIT TIME
1= 2 secs 2= 5 secs 3= 1O secs* 4= 15 secs 5= 20 secs 6= 30 secs 7= 1 mins. 8= As full set exit time. Press Full Set to exit
14 ENTRY TIME
1= 1 sec 2=10 secs 3 = 20 secs 4= 30 secs* 5= 40 secs 6= 50 secs 7= 1 min. 8= 2 mins. Press Full Set to exit
SIREN
00 INVERT SIREN OUTPUT
Normally -ve applied in alarm. (0v in alarm) 0 = -ve applied in alarm
DETECTOR PROGRAMMING cont...
6
To delete the device press PART SET and OFF keys together. The LCD will show that the device has been deleted.
Press the Full Set key to exit
02 PROGRAM DEVICES ONTO
ZONE 2
03 PROGRAM DEVICES ONTO
ZONE 3
04 PROGRAM DEVICES ONTO
ZONE 4
05 PROGRAM DEVICES ONTO
ZONE 5
06 PROGRAM DEVICES ONTO
ZONE 6
07 PROGRAM DEVICES ONTO
ZONE 7
08 PROGRAM DEVICES ONTO
ZONE 8
09 RADIO PANIC BUTTONS
Key in 091 to program the first PA button onto the system. The Panic button is operated instead of a learn jumper. Up to 8 Panic buttons can be programmed onto the PA zone, i.e. devices 091 to 098. The LCD display will refer to the panic buttons as P1 to P8. Press the Full Set key to exit.
10 FIRE ALARM DEVICES
Key in 101 to program the first Fire detector onto the system. Short out the learn jumper. (Ensure learn jumper is removed after
entry time when unsetting from Full Set. (If a mains relay was connected via this output a mains courtesy light could be switched on by disarming from outside with a remote control.)
1= Courtesy strobe on O=off* Press the full set key to exit.
33 WALK THROUGH ZONES BECOME FINAL EXIT IN PART SET
To prevent false alarms in part set it is often useful to make walk through zones initiate the entry timer.
1= Yes O= No* Press the full set key to exit.
34 JAMMING
1 = Jamming generates a full alarm when set O= indicator only* Press the full set key to exit. (Jamming is signalled to the dialler outputs.)
35 MAINS FAILURE & PANEL LOW BATTERY PREVENTS ARMING
1 = Mains failure or Panel battery failure prevents arming. O = Does not prevent arming* Press the full set key to exit
36 REMOTE CONTROL UNSETS ONLY IN ENTRY
1= Unset only after entry timer has been started. O= Unset not inhibited* Press the full set key to exit.
37 DIALLER DELAYED (20 second abort time) 1= Delayed O= Instant * Press the full set key to exit
9
38 NO EXTERNAL BELL OR DIALLER IN PART SET
(Internal bells only in Part Set). 1= Internal sounder only in Part Set. O= Dialler and siren In both full or part set* Press the full set key to exit
39 LINE FAULT IN DAYTIME AUDIBLE
1= Audible and visual 0= visual only* Press the full set key to exit.
40 SUPERVISORY
Do not select supervisory unless all your detectors are 4600 series. Do not select supervisory if using zoned Panic buttons. 1= Supervision O= No supervision* Press the full set key to exit.
41 SUPERVISORY FAULT
1= audible when unset O = silent when unset* Press the full set key to exit
42 ENGINEER RESET
1= Engineer reset O = No* Press the full set key to exit.
43 REARMING
1= none 2= once 3= twice 4= always* Press the full set key to exit
44 RESTORE ENTIRE NV RAM TO FACTORY DEFAULT VALUES
Short out the MEM link while keying in 44. All zone LED's will come on, the panel will emit a long bleep and will go out of engineering mode into the day state. WARNING: This will delete all detectors from the system.
45 AUDIBLE RECEIVE MODE
28 DOUBLE BUTTON P.A.
(To activate a panic from a remote control, both PA & OFF buttons must be pressed simultaneously) The factory default is single button. 1= Double O= Single*
Press the full set key to exit.
29 SILENT PART SET
1= Silent O= Audible* Press the full set key to exit.
30 UPSTAIRS / DOWNSTAIRS
This option tells the panel to accept part set button as a separate alarm system.) e.g.. The Part Set button becomes the alarm system in the flat & the Full set button is a separate alarm system in the office. In this mode the user can set either one or the other, or both systems by selection when arming.
1 = Select Upstairs/Downstairs mode. O= Normal Part / Full set mode.* Press the full set key to exit.
31 8 SECOND STROBE WHEN FINAL SET AND UNSET
If selected the strobe output operates for 8 seconds at the moment the panel is full set. i.e. when the exit timer terminates. The strobe also operates for 8 seconds when the panel is Unset from Full Set.
1 = 8 sec. Strobe 0 = No 8 second strobe Press the full set key to exit.
32 COURTESY STROBE IN FULL SET ENTRY / EXIT
If selected the strobe output terminal 8 operates when Full setting the panel. The strobe output also operates for the
The factory default is
all zones allowed to be omitted except zone 1. The zone LED's indicate which zones are allowed to be omitted. Use the keys 1 to 8 to select or deselect zones. The 0 key deletes all. Press the full set key to exit.
2O FINAL EXIT ZONES
(Zones that start the entry time) The factory default is zone 1 only. The zone LED's indicate which zones will start the entry timer. Use the keys 1 to 8 to select or deselect zones. The 0 key deletes all. Press the full set key to exit.
21 WALK THROUGH ZONES
The factory default is none. The zone LED's indicate which zones are walk through during entry. Use the keys 1 to 8 to select or deselect walk through zones. The 0 key deletes all. Press the full set key to exit.
22 IGNORE ZONE IF FIRST TO ALARM
(Double Knock)
Alarm only if two zones are triggered. The factory default is none. The zone LED's indicate which zones are double knock. Use the keys 1 to 8 to select or deselect double knock zones. The 0 key deletes all. Press the full set key to exit.
23 AUXILIARY ZONES
Technical alarm. i.e.. Freezer giving internal audible and technical alarm channel of dialler. The factory default is none. The zone LED's indicate which zones are auxiliary zones. Use the keys 1 to 8 to select or deselect aux. zones.
8
7
1 = -ve removed in alarm
15 BELL DURATION
1= Silent 2= 15 secs 3= 2 mins. 4= 3 mins. 5=10 mins. 6 = 15 mins. 7= 20 mins.* 8= Continuous Press Full Set to exit
16 BELL DELAY
1= 0 mins.* 2= 1 mins. 3= 3 mins. 4= 4 mins. 5= 5 mins. 6 = 6 mins 7=7 mins* 8= 10 mins Press Full Set to exit
ZONE PROGRAMMING
IMPORTANT: Remember that all devices on a particular zone will respond to the zone option selected. So if zone 1 has final exit detectors, all detectors on zone 1 must also be final exit.
17 FULL SET ZONES
The factory default is all zones active. The zone LED's indicate which zones are active in full set.
Use the keys 1 to 8 to select or deselect zones. The 0 key deletes all. Press the full set key to exit.
18 PART SET ZONES
The factory default is zones 1 to 4 active. The zone LED's indicate which zones are active in part set. Use the keys 1 to 8 to select or deselect zones. The 0 key deletes all. Press the full set key to exit.
19 OMIT PERMIT ZONES
(The zones that the user is allowed to omit)
The 0 key deletes all. Press the full set key to exit.
24 24 HOUR ZONES
The factory default is none. The zone LED's indicate which zones are 24 hour. Use the keys 1 to 8 to select or deselect 24 hour zones. The 0 key deletes all. Press the full set key to exit.
NOTE: If you do not want a 24 hour zone to be omitted, remove the zone from omit permit via program No.19.
25 SOAK TEST ZONES
The factory default is none. The zone LED's indicate which zones are on soak test.
Use the keys 1 to 8 to select or deselect soak test zones. The 0 key deletes all. Press the full set key to exit.
26 CHIME ZONES
The factory default is none. The zone LED's indicate which zones are on chime. Use the keys 1 to 8 to select or deselect chime zones. The 0 key deletes all. Press the full set key to exit.
OTHER PROGRAMS
27 P.A. SILENT / AUDIBLE
The factory default is audible. 1= Silent O= Audible * Press the full set key to exit.
IMPORTANT NOTE Programming detectors is different to the standard FM4000. e.g. Key in 012 to select device 2 on zone 1. The LED's will indicate which devices are already programmed on
that zone & if the LCD expansion unit is fitted the LCD will also dis­play the zone selected.
Refer to page 5 of Installation instructions). IMPORTANT NOTE Programming detectors is different to the standard FM4000. e.g. Key in 012 to select device 2 on zone 1. The LED's will indicate which devices are already programmed on
that zone & if the LCD expansion unit is fitted the LCD will also dis­play the zone selected. Refer to page 5 of Installation instructions).
IMPORTANT NOTE Programming detectors is different to the standard FM4000. e.g. Key in 012 to select device 2 on zone 1. The LED's will indicate which devices are already programmed on
that zone & if the LCD expansion unit is fitted the LCD will also dis­play the zone selected. Refer to page 5 of Installation instructions).
IMPORTANT NOTE Programming detectors is different to the standard FM4000. e.g. Key in 012 to select device 2 on zone 1. The LED's will indicate which devices are already programmed on
that zone & if the LCD expansion unit is fitted the LCD will also dis­play the zone selected.
Refer to page 5 of Installation instructions). IMPORTANT NOTE Programming detectors is different to the standard FM4000. e.g. Key in 012 to select device 2 on zone 1. The LED's will indicate which devices are already programmed on
that zone & if the LCD expansion unit is fitted the LCD will also dis­play the zone selected. Refer to page 5 of Installation instructions).
IMPORTANT NOTE Programming detectors is different to the standard FM4000. e.g. Key in 012 to select device 2 on zone 1. The LED's will indicate which devices are already programmed on
that zone & if the LCD expansion unit is fitted the LCD will also dis­play the zone selected. Refer to page 5 of Installation instructions).
Loading...