FläktGroup ECO SIDE Installation And Maintenance Manual

INSTALLATION AND MAINTENANCE MANUAL
ECO SIDE
eCO Side - Installation and Maintenance Manual
2
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
1. SAFETY INSTRUCTIONS ................................................................................3
VDI 6022 ............................................................................................................3
2. DESCRIPTION OG THE UNIT .......................................................................... 4
3. TRANSPORT AND PLACEMENT ..................................................................5
4. CONNECTIONS
4.1 Duct connections .....................................................................................6
4.2 Post heater, electrical (9 kW) .............................................................6
4.3 Post heater, hot water ...........................................................................6
4.4 Cooling coil, water ...................................................................................7
4.5 Valve and valve actuator ...................................................................... 7
4.6 Damper ........................................................................................................ 7
4.7 Silencer ........................................................................................................ 7
5. ELECTRICAL CONNECTIONS
5.1 Fuse protection ........................................................................................8
5.2 Electrical data...........................................................................................8
5.3 Main supply ...............................................................................................8
5.4 Connection of control panel ................................................................9
6. CONNECTION OF EXTERNAL COMPONENTS
6.1 Electrical post heater (Size 06, 9 kW) .........................................10
6.2 Post heater, hot water .........................................................................10
6.3 Cooling coil, water ................................................................................10
6.4 Cooling coil, DX ......................................................................................10
6.5 Damper .....................................................................................................10
6.6 Temperature sensors ...........................................................................11
6.7 Extended / Forced ventilation ..........................................................11
6.8 Fire protection function .......................................................................11
6.9 Summary alarm .....................................................................................11
7. WIRING DIAGRAMS ...............................................................................12
8. TESTING OF FUNCTIONS.......................................................................15
9. CONTROL PANEL, OPEERATIONS, COMMISSIONING
9.1 General .......................................................................................................16
9.2 Home screen overview ......................................................................17
9.3 Sub menus ..............................................................................................19
9.4 Date/time, language ...........................................................................20
9.5 Advanced settings for installers and sevice personnel ..........21
9.6 Commissioning Wizard .....................................................................22
9.7 Schedules ................................................................................................ 26
10. CONTROL FUNCTIONS
10.1 Rotor, heating and cooling .............................................................29
10.2 Temperature controls ......................................................................29
10.3 Freeze protection ...............................................................................31
10.4 Defrost function ...................................................................................31
10.5 Cooling recovery ................................................................................31
10.6 Night cooling ........................................................................................31
10.7
Pressure or Constant flow control .......................................32
11. COMMUNICATION
11.1 Modbus, RS485 ...................................................................................33
11.2 Modbus, TCP/IP .................................................................................33
11.3 Webserver ............................................................................................33
12. PARAMETER LIST ........................................................................................ 34
13. MAINTENANCE
13.1 General ...................................................................................................40
13.2 Filter........................................................................................................ 40
13.3 Rotary Heat Exchanger ................................................................... 41
13.4 Post heater, hot water ..................................................................... 42
13.5 Post heater, electrical .................................................................... 43
13.6 Cooling coil, water ............................................................................ 43
13.7 Fans ........................................................................................................ 44
13.8 Service schedule .............................................................................. 45
14. DECLARATION OF CONFORMITY ............................................................46
15. DISPOSAL ....................................................................................................... 47
CONTENTS
eCO Side - Installation and Maintenance Manual
3
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
OPERATION OF AIR HANDLING UNITS
AND ACCESSORIES
WARNING
Before taking the air handling unit into
operation fit any unused connections with protective mesh.
In addition, all electrotechnical and me
­chanical safety devices must be installed before taking the air handling unit into operation.
– Before opening the unit check that its power has been
disconnected.
– Take care when opening the isolating valves for the hot
water to the air heater. There is a risk of water hammer or steam discharge.
– When servicing or inspecting the unit, turn off the
safety switch before opening the inspection doors. Reset all safety devices before restarting.
– The clearance in front of electric heaters and electrical
cabinets shall conform to applicable electrical safety regulations.
– Use the control panel to stop the unit.
– The unit’s hatches are fitted with locking handles.
Ensure that the unit is always left locked, and that the keys cannot be accessed by unauthorized persons.
– Do not open inspection hatches when the unit is in
operation.
– Use protective gloves during installation and service.
1. SAFETY INSTRUCTIONS
Installation may only be
carried out by qualified personnel.
VDI 6022
eCO Side is designed in accord­ance to hygiene standard VDI 6022 and is easy to clean with no place where dirt can accumulate. Nonmetallic part, have been chosen as proven free of micro bac
-
terial or mold growth.
Following the VDI 6022, AHU should ensure a physiologically favourable indoor climate and a hygienically perfect indoor air quality.
The eCO Side is designed in order, not to endanger health, not to disturb the condition and the thermal comfort, not to lead to odour nuisance and to prevent exposure and impact of inorganic and organic pollutants.
eCO Side - Installation and Maintenance Manual
4
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
FANS
The unit has two plug fans with EC motors.
ROTARY HEAT EXCHANGER
The speed controlled rotor is fitted with a purge sector and a ro­tation sensor.
CONTROL SYSTEM
The ISYteq Mini control system is integrated with the unit and is ready for use with a large number of functions.
COMPONENTS
The unit can be supplied in left-hand or right-hand configurations. Left-hand configurations is mirror-reversed to right-hand. Refer to the order code in Technical Instruction.
2. DESCRIPTION OF THE UNIT
FILTER
Bag filter class (F7) ePM1 50% on both supply and extract air.
POST HEATER, HOT WATER
Hot water coil containing copper tubes and aluminum fins. Pipe connection ø15 mm. Freeze protection temperature sensor is included. Max operating pressure 3.0 MPa.
POST HEATER, ELECTRICAL
The heater for size 03 and 04 is built-in. For size 06 the heater is duct mounted.
TOP RIGHT HAND CONFIGURATION RDSP, bb = 12 or 14 BOTTOM RIGHT-HAND CONFIGURATION RDSP, bb = 11 or 13
EXHAUST AIR UPWARDS RDSP, bb = 11 or 13 and c = 2
1 Outdoor air sensor GT3 2 Supply filter 3 Rotary heat exchanger with rotation sensor 4 Supply fan 5 Electrical heater including overheating
protection alternativelyhot water coil
with freeze protection GT5 6 Supply air sensor GT1 7 Extract air sensor GT12 8 Control equipment 9 Extract filter 10 Exhaust fan 11 Pressure guard
Outdoor air
Supply air
Extract air
Exhaust air
3 4 5 61 2
1011 8 79
64
8
5
3 79
10
1 211
eCO Side - Installation and Maintenance Manual
5
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
SOUND TRANSMISSION
When a unit is positioned next to a wall, low frequency sound can generate vibrations in the wall, even if the sound level from the unit is acceptable. Generally the unit should be positioned against a wall adYescent to a room that is not sensitive for noise. When this is not possible the unit should be positioned 400-500 mm from the wall.
Duct lead-through must be designed with care so that rigid connections between the duct and wall do not occur. In addition, the seal around the duct must be carefully installed to prevent the transmission of noise to adYescent areas. For sensitive in
­stallations it may be a good idea to connect ducts using flexible connections.
If the floor structure is weak, noise can be transmitted to other areas in the building. Use of a heavy insulating mat can prevent that problem.
TRANSPORT
Use a fork lift truck, pallet truck or platform trolley for transport on site. The unit can be lifted from the front or from the side.
To move size 06 through a 900 mm opening remove the door and the center strut. See section 13.3.
3. TRANSPORT AND PLACEMENT
UNIT WEIGHT
Size 03 = 260 kg Size 04 = 300 kg Size 06 = 400 kg
SPACE REQUIREMENTS
Make sure that it is enough space around the unit for routine service work, such as replacing filters and cleaning the fan and casing.
Consideration has to be taken for future replacement of com ponents.
PLACEMENT
The unit can be placed directly onto the surface if this is flat and horizontal, otherwise use adjustable feet.
Available as accessory RDTZ-13.
Size B1 S
03 1683 730 04 1782 780 06 1945 861
B1 = width with open doors S = minimum space for service*)
* in front of the control cabinet there has to be enough space
according to local electrical regulations.
B1
S
eCO Side - Installation and Maintenance Manual
6
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
NOTE! The weight of the duct system
with components must not lay weight on the unit.
4. CONNECTIONS
4.1 DUCT CONNECTIONS
Size 03 (Ø250 mm) and 04 (Ø315 mm) have circular duct connec­tions. Size 06 has rectangular duct connections (600 x 300 mm).
4.2 POST HEATER, ELECTRICAL
The electrical post heater for size 06 is duct mounted, see sepa­rate instruction. The rectangular connection is PG on the unit and the accessories. If the unit is selected with flange connection the unit is delivered with an adapter for flange. This can be placed on the unit or on the accessories. If the accessories are not placed directly at the unit more adapters are available with the code RDTZ-25-06-1.
4.3 POST HEATER, HOT WATER
Connect the pipes for the heating coil inside the unit according to pictures below. View from gables.
NOTE! To avoid freezing the temperatures for frost protection must not be set too low. If the building has to be left unheated for long periods during winter, the water must be drained from both the pipework and the heating coil.
WARNING! Wear protective gloves when using a fin comb.
Warning - hot water!!
FläktGroup takes no responsibility neither for the connection of air heaters to the heating system, nor for damage or injury caused by incorrect planning, installation or maintenance of this system. Pipework, valves etc. are to be designed due to pressure drop and function, not the dimensions of the air heater connections. The weight of the pipe work system with components must not lay weight on the water coil.
PIPE CONNECTION
Size 03 = 3/8” Size 04 = 12 mm Size 06 = 12 mm Maximum operating pressure 3.0 MPa
PREVENTING FREEZING
There is a risk of freezing in the hot water coil at low outdoor temperatures. This can cause water damage. The risk can appear:
1. if the temperature of the water is too high. The risk increases
in spring and autumn. Adjust the water temperature in relation to the outdoor air temperature.
2. if the post heater is oversized. Decrease the temperature of
the water to increase the water flow.
FINS
Any deformed fins can be adjusted using fin comb EQAZ-14.
VENTING
The air must be properly vented from the system to ensure good function. The venting is made through the pipe system.
Supply air bottom, right-hand version Supply air bottom, left-hand version
Supply air top, right-hand version Supply air top, left-hand version
Ø22.5
Ø22.5
03=108 04= 93 06=111
03=108 04= 93
06=111
03=238 04=272 06=304
03=135 04=132 06= 93
03=238 04=272 06=304
03=135 04=132 06= 93
03=108 04= 93 06=111
Ø22.5
Ø22.5
03=108 04= 93
06=111
03=238 04=272 06=304
03=491 04=559 06=534
03=238 04=272 06=304
03=491 04=559 06=534
eCO Side - Installation and Maintenance Manual
7
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
When installing a 3-way valve check as follows:
Mixture from A/B to AB
Splitting from AB to A/B
4.6 DAMPER
Duct mounted damper with a spring return on/off actuator. The actuator has to be connected to the terminal block in the electri
­cal cabinet. Size 03 and 04 have circular duct connections and size 06 has rectangular. The damper is designed for duct insula
­tion of up to 50 mm.
4.7 SILENCER, DUCT MOUNTED
Size 03 and 04 have circular duct connections and size 06 has rectangular. Fire resistance rating EI30. The distance to the fan has to be at least 300 mm.
4. CONNECTIONS
4.4 COOLING COIL, WATER
The cooling coils have circular duct connections with rubber ring seals. For size 06 a converter from rectangular to circular is available as an accessory (RDTZ-24). The cooler has to be installed horizontally and the distance to nearest bend has to be at least 600 mm. Venting and draining is carried out via the pipe system. The pipe connection, Ø 22 mm, is located on the outlet end, is smooth and is intended for a compression fitting. The drainage tray is in stainless steel and has an R 1/2” connection. Maximum operating pressure 1.0 MPa and maximum operating temperature 150° C.
4.5 VALVE AND VALVE ACTUATOR ACTUATORS FOR HEATING SV1 AND COOLING SV2
Connected to terminal in electrical cabinet. Stroke length 5.5 mm. Intended for assembly on 2-way and 3-way valves of the type VVG44 or VXG44.
ACCEPTED INSTALLATION METHODS
VALVE FOR HEATING AND COOLING
The valve and valve actuator can be easily installed without special tools. A particle filter should be fitted before the valve to extend its service life.
2-WAY VALVE VVG
The flow is increased by turning the spindle inwards, the flow is reduced by moving the spindle outwards. Note that the 2-way valve cannot be used as a 3-way valve.
The flow direction is indicated by an arrow.
ACCEPTED INSTALLATION METHODS
3 - WAY VA LVE V X G
The bypass is closed by turning the spindle inwards, the bypass is opened by turning the spindle outwards.
ACCEPTED INSTALLATION METHODS
eCO Side - Installation and Maintenance Manual
8
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
5. ELECTRICAL CONNECTIONS
5.3 MAIN SUPPLY
NY BILD!
5.1 FUSE PROTECTION
Size Unit with Hot water coil Electrical coil
03
Supply 1 x 230 V 3 x 400 V Fuse 10 A 10 A
04
Supply 1 x 230 V 3 x 400 V Fuse 10 A 16 A
06
Supply 1 x 230 V 1 x 230 V
1)
Fuse 10 A 10 A
1)
Duct mounted heater size 06 has sparate supply.
5.2 ELECTRICAL DATA
MOTORS
Size Power, kW Current, A
03 0,385 x 2 2,5 x 2 04 0,50 x 2 2,2 x 2 06 0,75 x 2 3,3 x 2
ELECTRICAL POST HEATER
Power, kW Current, A Voltage, V
4 10 2 x 400 6 15 2 x 400
9
1)
13 3 x 400
1)
Duct mounted heater size 06 has sparate supply.
Units with built-in electrical heater, main supply 3 x 400V.
Units with hot water coil can be supplied with 1 x 230V.
Units with duct mounted electrical heater can be supplied with 1 x 230V.
Units are not available for 3 x 230V..
The main supply cable must be fitted with an external safety switch located close to the unit. Connect main supply to terminals U, V, W, N and PE in the control box.
eCO Side - Installation and Maintenance Manual
9
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
5. ELECTRICAL CONNECTIONS
1. Open the control panel using a screwdriver.
5.4 CONNECTION OF CONTROL PANEL
The control panel is connected when delivered from factory and provided with a magnet for easy handling. For wall mounting see below.
2. Lift the display out of the enclosure.
3. Push the connection cable through a suitable hole and if needed make an outlet for the cable in the side of the cover.
4. Mount the enclosure directly on the wall.
5. Connect the cable to the back of the display as shown above. Note. Please do not touch the electronics.
6. Push back the display in the enclosure.
NOTE! The control panel is only for indoor use.
eCO Side - Installation and Maintenance Manual
10
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
6.1 ELECTRICAL POST HEATER (SIZE 06, 9 KW)
Duct mounted. Separate supply 3 x 400V, 16 A.
Connect alarm, start and control signal to the control box in the unit. eCO Side is preconfigured for electrical post heater.
(Electrical heater for size 03 and 04 is built-in in the unit, no further connections are needed).
Component Terminal Connection Remark
Electrical heater 9 kW
CP1/SK1 Heater
1 – 2 C- NO
Start signal
ALM CP1
43 – 44 NO - C
Alarm, overheating (NC)
SV1 CTRL
35 – 36 Y - M
Control signal 0-10 V
Supply 3 x 400 V
Not from the unit
6.2 POST HEATER, HOT WATER
Circulation pump (CP1) and valve actuator (SV1) connects according to table below.
Component Terminal Connection Remark
Circulation pump CP1
CP1/SK1 Heater
1 – N – PE
Pump supply (230 V max 2A
1)
CP1/SK1 Heater
2 - 3 NO – L1
Loop only with circulation pump
ALM CP1
43 – 44 NO - C
Voltfree alarm input
(NO, configurable) Valve actuator SV1
SV1 CTRL
35 – 36 – 37 - 38
Y – M – G – G0
1)
The current consumption for CP1 and CP2 is limited to 2 A.
6. CONNECTION OF EXTERNAL COMPONENTS
6.3 COOLING COIL, WATER
Circulation pump (CP2) and valve actuator (SV2) connects according to table below.
Component Terminal Connection Remark
Circulation pump CP2
CP2/DX Cooler
4 – N – PE
Pump supply (230 V max 2A
1)
CP2/DX Cooler
5 - 6 NO – L1
Loop only with circulation pump
ALM CP2/DX45 – 46
NO - C
Voltfree alarm input
(NO, configurable) Valve actuator SV2
SV2 CTRL
39 – 40 – 41 - 42
Y – M – G – G0
1)
The current consumption for CP1 and CP2 is limited to 2 A.
6.4 COOLING COIL, DX
The unit can manage cooling DX, 1-step. Note that the coil is not included in the delivery of the unit. For configuration see control functions.
Component Terminal Connection Remark
DX-cooling, 1-step
CP2/DX Cooler
4 – 5 C – NO
Start: 10 % Stop: 0 %
ALM CP2/DX
45 – 46 NO - C
Voltfree alarm input (NO, configurable)
6.5 DAMPER
On/off actuator with spring return, 15 Nm, 24 VAC.
Component Terminal Connection Remark
Damper ST1
29 – 30 G – G0
Exhaust air damper if used is connected in parallel (Maximum 2 dampers)
Use the cable flange on the top of the unit to connect all external accessories.
For information about how to connect available accessories see below.
eCO Side - Installation and Maintenance Manual
11
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
6. CONNECTION OF EXTERNAL COMPONENTS
6.6 TEMPERATURE SENSORS
The unit is provided with:
Supply air sensor GT1, located at supply air spigot.
Outdoor air sensor GT3, located at outdoor air spigot.
Frost protection sensor GT5 (when hot water coil is used), located on the return pipe of the coil.
When using cooling coil or duct mounted post heater a supply temperature sensor (GT1) is supplied for duct mounting. Then there is no supply air sensor mounted in the unit.
Room sensor GT2 (accessory) is supplied when the unit is con
­figured for room temperature control. Then there is no exhaust air sensor mounted in the unit.
The room sensor is intended for wall mounting and needs to have good air circulation and not direct sun light. Cable is not included.
Component Terminal Connection Remark
Supply air sensor
GT1
25 – 26 B – M
Standard sensor is replaced with a duct mounted sensor when using cooling coil or duct mounted heater
Room sensor
GT2
27 – 28 B – M
Replaces exhaust air sensor GT12 when room control is selected
6.7 EXTENDED / FORCED VENTILATION
For external electronic timer, push button, PIR or other volt free contact. Electronic timer and/or PIR if ordered is supplied separately. When using a push button the time has to be set in the control panel.
Component Terminal Connection Remark
Timer 1 TMR1
31 - 32 NO - C
Can also be used for PIR
Timer 2 TMR2
33 – 34 NO - C
Can also be used for PIR
Function of aux. inputs Timer 1 (T1) and Timer 2 (T2) can be selected according to the following tables.
TIMER FUNCTION 1 (DEFAULT)
Timer 1 Timer 2
Manual/Automatic Mode 0 0 Trickle 1 0 Normal 0 1 Boost 1 1
TIMER FUNCTION 2
Timer 1 Timer 2
Manual/Automatic Mode 0 0 Trickle 1 0 Boost 0 1 Stop 1 1
TIMER FUNCTION 3
Timer 1 Timer 2
Manual/Automatic Mode 0 0 Normal 1 0 Boost 0 1 Stop 1 1
TIMER FUNCTION 4
Timer 1 Timer 2
Stop 0 0 Manual/Automatic Mode 1 0 Stop 0 1 Boost 1 1
TIMER FUNCTION 5
Timer 1 Timer 2
Stop 0 0 Manual/Automatic Mode 1 0 Stop 0 1 Normal 1 1
6.8 FIRE PROTECTION FUNCTION
External fire alarm to stop the unit can be connected to terminals in the control box. Smoke detectors and fire dampers cannot be connected directly to the air handling unit, a separate fire system is needed.
Component Terminal Connection Remark
Fire protection function
FIRE
23 – 24
NC – C
6.9 SUMMARY ALARM
The alarm output can be configured to indicate A-alarms or both A- and B-alarms.
Component Terminal Connection Remark
Summary alarm
ALARM
21 – 22
NO – C
Voltfree contact Maximum load 24 V, 200 mA
eCO Side - Installation and Maintenance Manual
12
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
7. WIRING DIAGRAMS
Outside the AHU Not in FläktGroup’s delivery
Outside the AHU Not in FläktGroup’s delivery
eCO Side - Installation and Maintenance Manual
13
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
7. WIRING DIAGRAMS
Control panel
ISYteq Touch 3.5”
Control board
eCO Side - Installation and Maintenance Manual
14
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
7. WIRING DIAGRAMS
EXTERNAL CONNECTIONS DIAGRAM 230/400 V
EXTERNAL CONNECTIONS DIAGRAM 24 V
eCO Side - Installation and Maintenance Manual
15
FläktGroup DC_10176GB_20180924_R3 Specifications are subject to alteration without notice
STARTING THE UNIT
When the electrical connections are made and all the accesso­ries are mounted the unit is ready to start up.
1. Turn the safety switch to 1 (ON).
2. Start the unit.
DAMPERS
Check that all dampers opens and closes correctly.
VALVE ACTUATORS
Check that valve actuators for heating and cooling works correctly.
DIRECTION OF ROTATION
Check that the direction of rotation for the heat exchanger corre­sponds to the alternatives below.
LEFT-HAND VERSION:
The rotor should rotate upwards when looking from the front.
RIGHT-HAND VERSION:
The rotor should rotate downwards when looking from the front.
AIR FLOW MEASUREMENT
The eCO Side has measuring nipples for air flow measurement. Using a measuring pressure Dpm (Pa) and a constant (k) the air flow q (R/W) can be calculated using the following equation:
NOTE! When the unit is supplied with Constant Air Volume Control there will be no measuring nipples on top of the unit.
TEMPERATURE CORRECTION
The air flow formula above applies to air with a temperature of +20 °C. At other air temperatures the air flow must be corrected using the formula:
The value of the constant (k) is shown in the table below.
q =
1000
k
Dp
m
x
Size
03 04 06
k-value extract air fan
58,4 51,5 49,2
k-value supply air fan
62,5 52,1
51,4
The measuring pressure, Dpm, is the difference between the pressure in the empty section at the fan inlet and the pressure inside the inlet cone. A manometer (RDTZ-56) can be connected to view the measuring pressure. This is used as a reference for monitoring the unit.
If the unit is supplied with Constant Air Volume control the air flow can be read in the control panel.
q = q
20
(273 + t)
293
, m
3
/s
8. TESTING OF FUNCTIONS
q = actual air flow q
20
= calculated air flow in formula abowe
t = current temperature in ° C
FILTER, FINAL PRESSURE DROP
It is time to replace the filters when the final pressure drop is reached, see table below.
SIZE 03
Air flow m3/s 0,15 0,25 0,35
Supply air/Extract air 119 148 177
SIZE 04
Air flow m3/s 0,15 0,25 0,35
Supply air/Extract air 125 142 159
SIZE 06
Air flow m3/s 0,15 0,25 0,35
Supply air/Extract air 121 139 157
FILTER MONITOR
When using filter monitors use the values in the table above. If the unit is supplied with Constant Pressure control increase the final pressure drop with 50 Pa.
Loading...
+ 33 hidden pages