FLYGT 3153 Installation, Operation And Maintenance Manual

Page 1
Installation,
Operation, and
Maintenance Manual
Flygt 3153
Page 2
Page 3
Table of Contents
Introduction and Safety.........................................................................................................................3
Introduction..........................................................................................................................................3
Safety terminology and symbols....................................................................................................3
Environmental safety........................................................................................................................4
User safety.........................................................................................................................................5
Ex-approved products.....................................................................................................................6
Product warranty...............................................................................................................................7
Transportation and Storage..................................................................................................................9
Inspect the delivery.............................................................................................................................9
Inspect the package.........................................................................................................................9
Inspect the unit..................................................................................................................................9
Transportation guidelines..................................................................................................................9
Precautions........................................................................................................................................9
Position and fastening......................................................................................................................9
Lifting..................................................................................................................................................9
Temperature ranges for transportation, handling and storage..................................................10
Handling at freezing temperature................................................................................................10
Unit in as-delivered condition.......................................................................................................10
Lifting the unit out of liquid...........................................................................................................10
Storage guidelines............................................................................................................................11
Storage location.............................................................................................................................11
Freezing precautions.....................................................................................................................11
Long-term storage..........................................................................................................................11
Table of Contents
Product Description.............................................................................................................................12
Pump design......................................................................................................................................12
Parts....................................................................................................................................................13
Monitoring equipment.....................................................................................................................14
Optional sensors.............................................................................................................................14
The data plate....................................................................................................................................14
Approvals...........................................................................................................................................15
Product approvals for hazardous locations.................................................................................15
EN approval plate...........................................................................................................................15
IEC approval plate..........................................................................................................................16
FM approval plate..........................................................................................................................16
Product denomination......................................................................................................................17
Installation.............................................................................................................................................18
Install the pump.................................................................................................................................18
Authority regulation.......................................................................................................................18
Fasteners.........................................................................................................................................18
Install with P-installation.................................................................................................................19
Install with S-installation.................................................................................................................20
Install with T/Z-installation.............................................................................................................21
Make the electrical connections......................................................................................................22
General precautions.......................................................................................................................22
Requirements..................................................................................................................................22
Cables..............................................................................................................................................23
Earthing (Grounding).....................................................................................................................23
Connect the motor cable to the pump........................................................................................23
Flygt 3153 Installation, Operation, and Maintenance Manual 1
Page 4
Table of Contents
Connect the motor cable to the starter and monitoring equipment.......................................24
Cable charts....................................................................................................................................25
Sensor-connection.........................................................................................................................31
Check the impeller rotation.............................................................................................................33
Operation..............................................................................................................................................35
Precautions.........................................................................................................................................35
Noise level..........................................................................................................................................35
Start the pump...................................................................................................................................35
Maintenance.........................................................................................................................................37
Maintenance guidelines...................................................................................................................37
Torque values....................................................................................................................................38
Empty the coolant..........................................................................................................................39
Fill with coolant...............................................................................................................................41
Service the pump..............................................................................................................................42
Inspection........................................................................................................................................43
Major overhaul................................................................................................................................44
Service in case of alarm.................................................................................................................44
Replace the impeller.........................................................................................................................44
Replace the impeller for wet installation.....................................................................................44
Replace the impeller for dry installation......................................................................................52
Troubleshooting...................................................................................................................................62
Introduction.......................................................................................................................................62
The pump does not stop when a level sensor is used.................................................................63
The pump starts-stops-starts in rapid sequence...........................................................................63
The pump runs but the motor protection trips.............................................................................64
The pump delivers too little or no water........................................................................................65
Technical Reference............................................................................................................................67
2 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 5
Introduction and Safety
Introduction
Purpose of this manual
The purpose of this manual is to provide necessary information for:
• Installation
• Operation
• Maintenance
CAUTION:
Read this manual carefully before installing and using the product. Improper use of the
product can cause personal injury and damage to property, and may void the warranty.
NOTICE:
Save this manual for future reference, and keep it readily available at the location of the
unit.
Introduction and Safety
Safety
WARNING:
•
The operator must be aware of safety precautions to prevent physical injury.
• Any pressure-containing device can explode, rupture, or discharge its contents if it is over-pressurized. Take all necessary measures to avoid over-pressurization.
• Operating, installing, or maintaining the unit in any way that is not covered in this manual
could cause death, serious personal injury, or damage to the equipment. This includes any modification to the equipment or use of parts not provided by Xylem. If there is a question regarding the intended use of the equipment, please contact an Xylem representative before proceeding.
• This manual clearly identifies accepted methods for disassembling units. These methods must be adhered to. Trapped liquid can rapidly expand and result in a violent explosion and injury. Never apply heat to impellers, propellers, or their retaining devices to aid in their removal.
• Do not change the service application without the approval of an authorized Xylem representative.
CAUTION:
You must observe the instructions contained in this manual. Failure to do so could result in physical injury, damage, or delays.
Safety terminology and symbols
About safety messages
It is extremely important that you read, understand, and follow the safety messages and regulations carefully before handling the product. They are published to help prevent these hazards:
• Personal accidents and health problems
• Damage to the product
• Product malfunction
Flygt 3153 Installation, Operation, and Maintenance Manual 3
Page 6
Introduction and Safety
Hazard levels
Hazard level Indication
Hazard categories
DANGER:
WARNING:
CAUTION:
A hazardous situation which, if not avoided, will result in death or serious injury
A hazardous situation which, if not avoided, could result in death or serious injury
A hazardous situation which, if not avoided, could result in minor or moderate injury
• A potential situation which, if not avoided, could
NOTICE:
result in undesirable conditions A practice not related to personal injury
•
Hazard categories can either fall under hazard levels or let specific symbols replace the ordinary hazard level symbols.
Electrical hazards are indicated by the following specific symbol:
Electrical Hazard:
These are examples of other categories that can occur. They fall under the ordinary hazard levels and may use complementing symbols:
•
• Cutting hazard
• Arc flash hazard
Magnetic hazard
Magnetic hazards are indicated by a specific symbol that replaces the typical hazard level symbols:
CAUTION:
Environmental safety
The work area
Always keep the station clean to avoid and/or discover emissions.
Crush hazard
4 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 7
Waste and emissions regulations
Observe these safety regulations regarding waste and emissions:
• Appropriately dispose of all waste.
• Handle and dispose of the processed liquid in compliance with applicable
environmental regulations.
• Clean up all spills in accordance with safety and environmental procedures.
• Report all environmental emissions to the appropriate authorities.
WARNING:
Do NOT send the product to the Xylem manufacturer if it has been contaminated by any nuclear radiation. Inform Xylem so that accurate actions can take place.
Electrical installation
For electrical installation recycling requirements, consult your local electric utility.
Recycling guidelines
Always recycle according to these guidelines:
Follow local laws and regulations regarding recycling if the unit or parts are
1.
accepted by an authorized recycling company.
2. If the first guideline is not applicable, then return the unit or parts to your Xylem
representative.
Introduction and Safety
User safety
General safety rules
Safety equipment
These safety rules apply:
• Always keep the work area clean.
• Pay attention to the risks presented by gas and vapors in the work area.
• Avoid all electrical dangers. Pay attention to the risks of electric shock or arc flash
hazards.
• Always bear in mind the risk of drowning, electrical accidents, and burn injuries.
Use safety equipment according to the company regulations. Use this safety equipment within the work area:
• Hard hat
• Safety goggles, preferably with side shields
• Protective shoes
• Protective gloves
• Gas mask
• Hearing protection
• First-aid kit
• Safety devices
NOTICE:
Never operate a unit unless safety devices are installed. Also see specific information about safety devices in other chapters of this manual.
Electrical connections
Electrical connections must be made by certified electricians in compliance with all international, national, state, and local regulations. For more information about requirements, see sections dealing specifically with electrical connections.
Flygt 3153 Installation, Operation, and Maintenance Manual 5
Page 8
Introduction and Safety
Hazardous liquids
The product is designed for use in liquids that can be hazardous to your health. Observe these rules when you work with the product:
• Make sure that all personnel who work with biologically hazardous liquids are
• Observe strict personal cleanliness.
Wash the skin and eyes
vaccinated against diseases to which they may be exposed.
Follow these procedures for chemicals or hazardous fluids that have come into contact with your eyes or your skin:
Condition Action
Chemicals or hazardous fluids in eyes
1. Hold your eyelids apart forcibly with your fingers.
2. Rinse the eyes with eyewash or running water for at least 15 minutes.
3. Seek medical attention.
Chemicals or hazardous fluids on skin
1. Remove contaminated clothing.
2. Wash the skin with soap and water for at least 1 minute.
3. Seek medical attention, if necessary.
Ex-approved products
Follow these special handling instructions if you have an Ex-approved unit.
Personnel requirements
These are the personnel requirements for Ex-approved products in potentially explosive atmospheres:
• All work on the product must be carried out by certified electricians and Xylem-
authorized mechanics. Special rules apply to installations in explosive atmospheres.
• All users must know about the risks of electric current and the chemical and physical
characteristics of the gas, the vapor, or both present in hazardous areas.
• Any maintenance for Ex-approved products must conform to international and national
standards (for example, IEC/EN 60079-17).
Xylem disclaims all responsibility for work done by untrained and unauthorized personnel.
Product and product handling requirements
These are the product and product handling requirements for Ex-approved products in potentially explosive atmospheres:
• Only use the product in accordance with the approved motor data.
• You must fully submerge the Ex-approved product during normal operation. Dry
running during service and inspection is only permitted outside the classified area.
• Before you start work on the product, make sure that the product and the control panel
are isolated from the power supply and the control circuit, so they cannot be energized.
• Do not open the product while it is energized or in an explosive gas atmosphere.
• Make sure that thermal contacts are connected to a protection circuit according to the
approval classification of the product, and that they are in use.
• Intrinsically safe circuits are normally required for the automatic level-control system by
the level regulator if mounted in zone 0.
• The yield stress of fasteners must be in accordance with the approval drawing and the
product specification.
6 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 9
• Do not modify the equipment without approval from an authorized Xylem
representative.
• Only use parts that are provided by an authorized Xylem representative.
Guidelines for compliance
Compliance is fulfilled only when you operate the unit within its intended use. Do not change the conditions of the service without the approval of an Xylem representative. When you install or maintain explosion proof products, always comply with the directive and applicable standards (for example, IEC/EN 60079–14).
Minimum permitted liquid level
See the dimensional drawings of the product for the minimum permitted liquid level according to the approval for explosion proof products. If the information is missing on the dimensional drawing, the product must be fully submerged. Level-sensing equipment must be installed if the product can be operated at less than the minimum submersion depth.
Monitoring equipment
For additional safety, use condition-monitoring devices. Condition-monitoring devices include but are not limited to the following:
• Level indicators
• Temperature detectors
Introduction and Safety
Product warranty
Coverage
Limitations
Xylem undertakes to remedy defects in products from Xylem under these conditions:
• The faults are due to defects in design, materials, or workmanship.
• The faults are reported to an Xylem representative within the warranty period.
• The product is used only under the conditions described in this manual.
• The monitoring equipment incorporated in the product is correctly connected and in
use.
• All service and repair work is done by Xylem-authorized personnel.
• Genuine Xylem parts are used.
• Only Ex-approved spare parts and accessories authorized by Xylem are used in Ex-
approved products.
The warranty does not cover defects caused by these situations:
• Deficient maintenance
• Improper installation
• Modifications or changes to the product and installation made without consulting
Xylem
• Incorrectly executed repair work
• Normal wear and tear
Xylem assumes no liability for these situations:
• Bodily injuries
• Material damages
• Economic losses
Warranty claim
Xylem products are high-quality products with expected reliable operation and long life. However, should the need arise for a warranty claim, then contact your Xylem representative.
Flygt 3153 Installation, Operation, and Maintenance Manual 7
Page 10
Introduction and Safety
Spare parts
Xylem guarantees that spare parts will be available for 15 years after the manufacture of this product has been discontinued.
8 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 11
Transportation and Storage
Inspect the delivery
Inspect the package
1. Inspect the package for damaged or missing items upon delivery.
2. Note any damaged or missing items on the receipt and freight bill.
3. File a claim with the shipping company if anything is out of order.
If the product has been picked up at a distributor, make a claim directly to the distributor.
Inspect the unit
1. Remove packing materials from the product.
Dispose of all packing materials in accordance with local regulations.
2. Inspect the product to determine if any parts have been damaged or are missing.
3. If applicable, unfasten the product by removing any screws, bolts, or straps.
For your personal safety, be careful when you handle nails and straps.
4. Contact your sales representative if anything is out of order.
Transportation and Storage
Transportation guidelines
Precautions
WARNING:
• Stay clear of suspended loads.
• Observe accident prevention regulations in force.
Position and fastening
The unit can be transported either horizontally or vertically. Make sure that the unit is securely fastened during transportation, and cannot roll or fall over.
Lifting
WARNING:
Crush hazard. The unit and the components can be heavy. Use proper lifting methods
• and wear steel-toed shoes at all times.
• Lift and handle the product carefully, using suitable lifting equipment.
• The product must be securely harnessed for lifting and handling. Use eyebolts or lifting lugs if available.
• Always lift the unit by its lifting handle. Never lift the unit by the motor cable or by the hose.
• Do not attach sling ropes to shaft ends.
Flygt 3153 Installation, Operation, and Maintenance Manual 9
Page 12
Transportation and Storage
Lifting equipment
Lifting equipment is always required when handling the unit. It must fulfill the following requirements:
• The minimum height (contact Xylem for information) between the lifting hook and the
• The lifting equipment must be able to hoist the unit straight up and down, preferably
• The lifting equipment must be securely anchored and in good condition.
• The lifting equipment must support weight of the entire assembly and must only be
• Two sets of lifting equipment must be used to lift the unit for repair work.
• The lifting equipment must be dimensioned to lift the unit with any remaining pumped
• The lifting equipment must not be oversized.
floor must be sufficient to lift the unit.
without the need for resetting the lifting hook.
used by authorized personnel.
media in it.
NOTICE:
Oversized lifting equipment could cause damage if the unit should stick when being lifted.
Temperature ranges for transportation, handling and storage
Handling at freezing temperature
At temperatures below freezing, the product and all installation equipment, including the lifting gear, must be handled with extreme care.
Make sure that the product is warmed up to a temperature above the freezing point before starting up. Avoid rotating the impeller/propeller by hand at temperatures below the freezing point. The recommended method to warm the unit up is to submerge it in the liquid which will be pumped or mixed.
NOTICE:
Never use a naked flame to thaw the unit.
Unit in as-delivered condition
If the unit is still in the condition in which it left the factory - all packing materials are undisturbed - then the acceptable temperature range during transportation, handling and storage is: –50°C (–58ºF) to +60°C (+140ºF).
If the unit has been exposed to freezing temperatures, then allow it to reach the ambient temperature of the sump before operating.
Lifting the unit out of liquid
The unit is normally protected from freezing while operating or immersed in liquid, but the impeller/propeller and the shaft seal may freeze if the unit is lifted out of the liquid into a surrounding temperature below freezing.
Units equipped with an internal cooling system are filled with a mixture of water and 30% glycol. This mixture remains a flowing liquid at temperatures down to –13°C (9°F). Below – 13°C (9°F), the viscosity increases such that the glycol mixture will lose its flow properties. However, the glycol-water mixture will not solidify completely and thus cannot harm the product.
Follow these guidelines to avoid freezing damage:
10 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 13
1. Empty all pumped liquid, if applicable.
2. Check all liquids used for lubrication or cooling, both oil and water-glycol mixtures, for
the presence of water. Change if needed.
Storage guidelines
Storage location
The product must be stored in a covered and dry location free from heat, dirt, and vibrations.
NOTICE:
• Protect the product against humidity, heat sources, and mechanical damage.
• Do not place heavy weights on the packed product.
Freezing precautions
The unit is frost-proof while operating or immersed in liquid, but the impeller/propeller and the shaft seal may freeze if the unit is lifted out of the liquid into a surrounding temperature below freezing.
Follow these guidelines to avoid freezing damage:
When Guideline Before storage
Transportation and Storage
• The unit must be allowed to run for a short time after raising it to discharge remaining pumped liquid.
This does not apply to impeller/propeller units.
• The discharge opening must be covered in a suitable way, or placed facing down so that any still remaining pumped liquid runs out.
• If present, the cooling jacket must be drained manually by opening the air vent screws at the top of the cooling jacket.
Long-term storage
After storage If the impeller/propeller is frozen, it must be thawed by immersing the unit
in liquid before operating the unit.
NOTICE:
Never use a naked flame to thaw the unit.
If the unit is stored more than 6 months, the following apply:
• Before operating the unit after storage, it must be inspected with special attention to the seals and the cable entry.
• The impeller/propeller must be rotated every other month to prevent the seals from sticking together.
Flygt 3153 Installation, Operation, and Maintenance Manual 11
Page 14
Product Description
Product Description
Pump design
The pump is submersible, and driven by an electric motor. For a list of pump version and corresponding motor type, see Motor data (page 67).
Intended use
The product is intended for moving wastewater, sludge, raw and clean water. Always follow the limits that are given in Application limits (page 67). If there is a question regarding the intended use of the equipment, please contact an Xylem representative before proceeding.
WARNING:
In explosive or flammable environments, only use Ex- or MSHA-approved pumps.
NOTICE:
Do NOT use the pump in highly corrosive liquids.
Spare parts
Pressure class
• Modifications to the unit or installation should only be carried out after consulting with Xylem.
Original spare parts and accessories that are authorized by Xylem are essential for
• compliance. The use of other parts can invalidate any claims for warranty or compensation. For more information contact your Xylem representative.
LT Low head MT Medium head HT High head SH Super high head
12 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 15
Parts
1
11
10
9
8
7
2
3
6
12
13
14
WS000850A
4
5
WS006171A
Product Description
Figure 1: Without cooling jacket
Figure 2: With cooling jacket
PositionPart Description
1 Monitoring
sensor 2 Shaft Stainless steel, with an integrated rotor 3 Cooling without
jacket 4 Cooling with
jacket 5 Flow diffuser Provides heat transfer from the coolant to the pumped fluid. 6 Seal housing Includes a coolant that lubricates and cools the seals; the housing acts as a buffer
7 Impeller N-impeller, a semi-open, two-vane impeller 8 Inspection
chamber 9 FLS10 For information about FLS10, see Monitoring equipment (page 14). 10 Mechanical seals Made of one of the following alternatives:
11 Main bearings Consisting of a two-row angular contact ball bearing 12 Motor For information about the motor, see Motor data (page 67).
Optional sensor. For information about sensors, see Monitoring equipment (page 14).
The pump is cooled by the ambient liquid.
The motor is cooled by a closed loop system. An integrated coolant pump circulates the coolant whenever the pump is operated.
between the pumped fluid and the electric motor
Equipped with an FLS10 leakage sensor to prevent damages to the motor
• Alternative 1
• Inner seal: corrosion-resistant cemented carbide WCCR/WCCR
• Outer seal: corrosion-resistant cemented carbide WCCR/WCCR
• Alternative 2
• Inner seal: corrosion-resistant cemented carbide/Aluminum oxide WCCR/Al2O
• Outer seal: silicon carbide RSiC/RSiC
3
Flygt 3153 Installation, Operation, and Maintenance Manual 13
Page 16
2
1312 14
22
21
20
17 18 1916159 10 11
8
7
6
5
4
3
1
23
24
WS006257A
Product Description
PositionPart Description
13 Thermal contact/
Thermistors 14 Support bearing Consisting of a two-row ball bearing
Monitoring equipment
The following applies to the monitoring equipment of the pump:
• The stator incorporates three thermal contacts connected in series that activate the alarm and stops the pump at overtemperature
• The thermal contacts open at 140°C (285°F).
• Ex-approved pumps must have thermal contacts connected to the control panel.
• The sensors must be connected to either the MiniCAS II monitoring equipment or an equivalent equipment.
• The monitoring equipment must be of a design that makes automatic restart impossible.
• The pump is supplied with an inspection sensor FLS 10 for sensing the presence of any liquid in the inspection chamber.
• Information in the junction box shows if the pump is equipped with optional sensors.
Optional sensors
Thermistor Thermistors are optional sensors for measuring the temperature. They are
connected in series in the stator and activate the alarm at overtemperature. Thermistors are not applicable to Ex-approved pumps.
For information about the thermal contact and thermistors, see Monitoring equipment (page 14).
NOTICE:
Thermistor must never be exposed to voltages higher than 2.5 V. If the voltage exceeds this value, for example when the control circuit is tested, the thermistors will be destroyed.
The data plate
The data plate is a metal label located on the main body of the products. The data plate lists key product specifications. Specially approved products also have an approval plate.
1. Curve code/Propeller code
2.
Serial number, see Product denomination (page 17)
3. Product number
14 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 17
4. Country of origin
5. Additional information
6. Phase; type of current; frequency
7. Rated voltage
8. Thermal protection
9. Thermal class
10. Rated shaft power
11. International standard
12. Degree of protection
13. Rated current
14. Rated speed
15. Maximum submergence
16. Direction of rotation: L=left, R=right
17. Duty class
18. Duty factor
19. Product weight
20. Locked rotor code letter
21. Power factor
22. Maximum ambient temperature
23. Read installation manual
24. Notified body. Only for EN-approved Ex-products
Figure 3: The data plate
Approvals
Product approvals for hazardous locations
Product Description
Pump Approval
• 3153.091
• 3153.095
• 3153.390
• 3153.810
• 3153.830
European Norm (EN)
• ATEX Directive
• EN 60079-0, EN 60079-1, EN 1127-1
• I M2 Ex d I
• 3153.850
• II 2 G Ex d IIB T3
EN approval for cable entry:
• Certificate number: INERIS 02ATEX9008 U
• II 2 G Ex d IIC or I M2 Ex d I
IEC
• IECEx scheme
• IEC 60079–0, IEC 60079–1
• Ex d I
• Ex d IIB T3
Factory Mutural (FM)
• Class I. Div 1. Group C and D
• Dust ignition proof for use in Class II. Div 1. Group E, F and G
• Suitable for use in Class III. Div 1. Hazardous Locations
EN approval plate
This illustration describes the EN approval plate and the information contained in its fields.
Flygt 3153 Installation, Operation, and Maintenance Manual 15
Page 18
1 2 3
4
5
6 7
8
9 10
12
11
13
14
15
WS003972A
WS001279B
21
876
3
4
5 9
10
11
12
13
1
2
WS003973A
Product Description
IEC approval plate
1. Approval
2. Approval authority + approval number
3. Approval for Class I
4. Approved drive unit
5. Stall time
6. Starting current/Rated current
7. Duty class
8. Duty factor
9. Input power
10. Rated speed
11. Controller
12. Additional information
13. Maximum ambient temperature
14. Serial number
15. ATEX marking
This illustration describes the IEC approval plate and the information contained in its fields.
International Norm; not for EU member countries.
1. Approval
2. Approval authority + approval number
3. Approved for drive unit
4. Stall time
5. Starting current/Rated current
6. Duty class
7. Duty factor
8. Input power
9. Rated speed
10. Controller
11. Additional information
12. Max. ambient temperature
13. Serial number
FM approval plate
This illustration describes the FM approval plate and the information contained in its fields.
1. Temperature class
2. Maximum ambient temperature
16 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 19
Product denomination
1
NP 3085
2 3
WS006265A
3085.183
1 2
NP
WS006262A
1
NP 3085.183 - 951 0163
2 3 4
WS006269A
Sales denomination
The sales denomination consists of the four-digit sales code and two letters that indicate the hydraulic end and type of installation.
This is an example of a sales denomination, and an explanation of its parts.
1. Hydraulic part
2. Installation type
3. Sales code
Product code
The product code consists of nine characters divided into two parts. This is an example of a product code, and an explanation of its parts.
Product Description
Serial number
1. Sales denomination
2. Version
The serial number is used for identification of an individual product, and is divided into four parts.
This is an example of a serial number, and an explanation of its parts.
1. Product code
2. Production year
3. Production cycle
4. Running number
Flygt 3153 Installation, Operation, and Maintenance Manual 17
Page 20
Installation
Installation
Install the pump
WARNING:
• Electrical shock hazard. Check that the cable and cable entry have not been damaged during transport before installing the pump.
• Note that special rules apply to installation in explosive atmospheres.
• Make sure that the unit cannot roll or fall over and injure people or damage property.
• Do not install CSA-approved products in locations that are classified as hazardous in the
national electric code, ANSI/NFPA 70-2005.
• Do not install the starter equipment in an explosive zone unless it is explosion-proof rated.
WARNING:
A permanent-magnet motor generates voltage when the shaft is rotating. Ensure that the shaft can not rotate before performing any electrical installation.
Authority regulation
Fasteners
NOTICE:
Do not run the pump dry.
•
• Never force piping to make a connection with a pump.
• Always remove all debris and waste material from the sump, inlet piping, and
discharge connection, before you install the pump.
These requirements apply:
Use the pump dimensional drawing in order to ensure proper installation.
•
• In S-, T-, and Z-installations the pump must be equipped with cooling jacket
• Provide a suitable barrier around the work area, for example, a guard rail.
• Check the explosion risk before you weld or use electric hand tools.
• Always check the impeller rotation before lowering the pump into the pumped liquid.
• If the unit has a permanent magnet motor, ensure that you have read and understood
all safety instructions regarding permanent magnet motors.
Vent the tank of a sewage machine station in accordance with local plumbing codes.
WARNING:
Only use fasteners of the proper size and material.
•
• Replace all corroded fasteners.
• Make sure that all fasteners are properly tightened and that there are no missing fasteners.
18 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 21
Install with P-installation
WS006259A
In the P-installation, the pump is installed on a stationary discharge connection, and operates either completely or partially submerged in the pumped liquid. These requirements and instructions only apply when the installation is made according to the dimensional drawing.
Installation
Figure 4: P-installation
These items are required:
• Guide bars
• Guide bar bracket for attaching the guide equipment to the access frame or to the
upper part of the sump
• Level regulators or other control equipment for start, stop, and alarm
• Cable holder for holding the cable and regulating the height of the level regulators
• Access frame (with covers) to which the upper guide bar bracket and cable holder can
be attached
• Discharge connection for connecting the pump to the discharge line
The discharge connection has a flange which fits the pump casing flange and a bracket for attaching the guide equipment.
• Fasteners for the discharge connection
• Anchor bolts
1. Run a cable between the sump and the stator and monitoring equipment.
Make sure that the cable is neither sharply bent, nor pinched. Install the access frame:
2.
a) Place the access frame in position and align it horizontally. b) Grout the frame in place.
3. Grout the anchor bolts in place.
Be careful when you align and position the discharge connection in relation to the access frame.
4. Place the discharge connection in position, and tighten the nuts.
5. Install the guide bars:
a) Secure the guide bars in the bracket. b) Check that the guide bars are placed vertically. Use a level or a plumb line.
6. Connect the discharge pipe to the discharge connection.
Flygt 3153 Installation, Operation, and Maintenance Manual 19
Page 22
WS006270A
Installation
7. Prepare for the level regulator:
a) Bolt the cable holder to the access frame. b) Attach the level regulator cable to the cable holder and adjust the height of the
level regulator.
c) Protect bolts and nuts with a corrosion-preventive compound.
8. Lower the pump along the guide bars.
9. Secure the motor cable:
a) Fasten the permanent lifting device to the pump and to the access frame. For
example, you can use a stainless-steel lifting chain with shackles.
b) Fasten the cable to the cable holder.
Make sure that the cable cannot be sucked into the pump inlet or that it is neither sharply bent, or pinched. Support straps are required for deep installations.
c) Connect the motor cable and the starter and monitoring equipment according to
the separate instructions. Make sure that the impeller rotation is correct. For more information, see Check the
impeller rotation (page 33).
Clean all debris from the sump before starting the pump.
Install with S-installation
In the S-installation, the pump is transportable and intended to operate either completely or partially submerged in the pumped liquid. The pump is equipped with a connection for hose or pipe and stands on a base stand.
These requirements and instructions only apply when the installation is made according to the dimensional drawing. For information about the different installation types, see Parts List.
Figure 5: S-installation
1. Run the cable so that it has no sharp bends. Make sure that it is not pinched, and
cannot be sucked into the pump inlet.
2. Connect the discharge line.
3. Lower the pump into the sump.
4. Place the pump on the base and make sure it cannot fall over or sink.
Alternatively, the pump can be suspended with a lifting chain just above the sump bottom. Make sure that the pump cannot rotate at startup or during operation.
5. Connect the motor cable and the starter and monitoring equipment according to the
separate instructions. Make sure that the impeller rotation is correct. For more information, see Check the
impeller rotation (page 33).
20 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 23
Install with T/Z-installation
WS006272A
WS006273A
In the T-installation, the pump is installed in a vertical position in a dry well next to the wet sump. These requirements and instructions only apply when the installation is made according to the dimensional drawing.
In the Z-installation, the pump is installed in a horizontal position on a support stand in a dry well next to the wet sump, and a bell-mouth is connected to the inlet pipe. These requirements and instructions are for Z-installations that comply to the dimensional drawing.
Installation
Figure 7: Z-installation
Figure 6: T-installation
These items are required:
• Support stand and anchor bolts for anchoring the pump to a base
• Inlet elbow for connecting the suction line and discharge line
• Shut-off valves that allow you to remove the pump from service
• Air vent on the discharge side between the pump and the check valve
• Level regulators or other control equipment for start, stop, and alarm
NOTICE:
The risk of freezing is particularly high in T- or Z-installations.
1. Fasten the pump:
Use the anchor bolts to bolt the support stand to the concrete base.
a) b) Bolt the pump to the support stand and the suction connection.
2. Make sure that the pump is vertical for the T-installation or horizontal for the Z-
installation.
3. Connect the suction line and discharge line.
4. Connect the motor cable and the starter and monitoring equipment according to the
separate instructions. Make sure that the impeller rotation is correct. For more information, see Check the
impeller rotation (page 33).
5. Make sure that the weight of the pump does not put strain on the piping.
Flygt 3153 Installation, Operation, and Maintenance Manual 21
Page 24
Installation
Make the electrical connections
General precautions
Electrical Hazard:
• A certified electrician must supervise all electrical work. Comply with all local codes and regulations.
• Before starting work on the unit, make sure that the unit and the control panel are isolated from the power supply and cannot be energized. This applies to the control circuit as well.
• Leakage into the electrical parts can cause damaged equipment or a blown fuse. Keep the end of the motor cable above the liquid level.
• Make sure that all unused conductors are insulated.
• There is a risk of electrical shock or explosion if the electrical connections are not correctly carried out or if there is fault or damage on the product.
• A permanent-magnet motor generates voltage when the shaft is rotating. Ensure that the shaft can not rotate before performing any electrical installation.
WARNING:
Do not install the starter equipment in an explosive zone unless it is explosion-proof rated.
Requirements
CAUTION:
If the pump is equipped with automatic level control and/or internal contactor, there is a risk of sudden restart.
These general requirements apply for electrical installation:
• The supply authority must be notified before installing the pump if it will be connected
to the public mains. When the pump is connected to the public power supply, it may cause flickering of incandescent lamps when started.
• The mains voltage and frequency must agree with the specifications on the data plate.
If the pump can be connected to different voltages, then the connected voltage is specified by a yellow sticker close to the cable entry.
•
The fuses and circuit breakers must have the proper rating, and the pump overload protection (motor protection breaker) must be connected and set to the rated current according to the data plate and if applicable the cable chart. The starting current in direct-on-line start can be up to six times higher than the rated current.
• The fuse rating and the cables must be in accordance with the local rules and
regulations.
• If intermittent operation is prescribed, then the pump must be provided with
monitoring equipment supporting such operation.
• If stated on the data plate, then the motor is convertible between different voltages.
• The thermal contacts/thermistors must be in use.
• For FM-approved pumps, FLS must be connected and in use in order to meet approval
requirements.
22 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 25
Cables
Earthing (Grounding)
Installation
These are the requirements to follow when you install cables:
• The cables must be in good condition, not have any sharp bends, and not be pinched.
• The sheathing must not be damaged and must not have indentations or be embossed
(with markings, etc.) at the cable entry.
• The cable entry seal sleeve and washers must conform to the outside diameter of the
cable.
• The minimum bending radius must not be below the accepted value.
• If using a cable which has been used before, a short piece must be peeled off when
refitting it so that the cable entry seal sleeve does not close around the cable at the same point again. If the outer sheath of the cable is damaged, then replace the cable.
Contact an Xylem service shop.
• The voltage drop in long cables must be taken into account. The drive unit’s rated
voltage is the voltage measured at the cable connection point in the pump.
• The screened cable must be used according to the European CE requirements if a
Variable Frequency Drive (VFD) is used. For more information, contact your Xylem representative (VFD-supplier).
Electrical Hazard:
• You must earth (ground) all electrical equipment. This applies to the pump equipment, the driver, and any monitoring equipment. Test the earth (ground) lead to verify that it is connected correctly.
• If the motor cable is jerked loose by mistake, the earth (ground) conductor should be the last conductor to come loose from its terminal. Make sure that the earth (ground) conductor is longer than the phase conductors. This applies to both ends of the motor cable.
• Risk of electrical shock or burn. You must connect an additional earth- (ground-) fault protection device to the earthed (grounded) connectors if persons are likely to come into physical contact with the pump or pumped liquids.
Connect the motor cable to the pump
CAUTION:
Leakage into the electrical parts can cause damaged equipment or a blown fuse. Keep the end of the motor cable above the liquid level.
Flygt 3153 Installation, Operation, and Maintenance Manual 23
Page 26
1
2
WS006002A
Installation
1. Entrance cover
2. O-ring
For more information about the cable entry, see the Parts list.
1. Remove the entrance cover and the O-ring from the stator housing.
This provides access to the terminal board.
2. Check the data plate to see which connections are required for the power supply.
3. Arrange the connections on the terminal board in accordance with the required power
supply. Links (jumper strips) are not used with the Y/D start.
4. Connect the mains leads (L1, L2, L3, and earth (ground)) according to applicable cable
chart. The earth (ground) lead must be 100 mm ( 4.0 in.) longer than the phase leads in the
junction box of the unit.
5. Make sure that the pump is correctly connected to earth (ground).
6. Connect the control leads to the applicable terminal board.
7. Make sure that any thermal contacts incorporated in the pump are properly connected
to the terminal board.
8. Install the entrance cover and the O-ring on the stator housing.
9. Fasten the screws on the entrance flange so that the cable insertion assembly bottoms
out.
Connect the motor cable to the starter and monitoring equipment
WARNING:
Do not install the starter equipment in an explosive zone unless it is explosion-proof rated.
24 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 27
WS003681A
Installation
NOTICE:
• Either thermal contacts or thermistors are incorporated in the pump.
• Thermal contacts must never be exposed to voltages higher than 250 V, breaking
current maximum 4 A. It is recommended that they are connected to 24 V over separate fuses to protect other automatic equipment.
1. If thermal contacts are included in the pump installation, connect the T1 and T2 control
conductors to the MiniCAS II monitoring equipment.
NOTICE:
Ex-approved products must always have the thermal contacts connected irrespective of the ambient temperature.
2. If thermistors are included in the pump installation, and screened or auxiliary cable is
used, then connect T1(1) and T2(2) to thermistor relay or MAS 711, and T3(3) and T4 (4) to MiniCAS II or MAS 711.
3. Connect the mains leads (L1, L2, L3, and earth [ground]) to the starter equipment.
For information about the phase sequence and the color codes of the leads, see Cable
charts (page 25).
4. Ensure that the warning label is attached to the cable end. In case the label is missing,
attach the spare label to the cable end. The label is delivered with the pump.
Cable charts
Description
5. Check the functionality of the monitoring equipment:
a) Check that the signals and the tripping function work properly. b) Check that the relays, lamps, fuses, and connections are intact.
Replace any defective equipment.
This topic contains general connection information. It also provides cable charts that show connection alternatives for use with different cables and power supply.
Flygt 3153 Installation, Operation, and Maintenance Manual 25
Page 28
WS000509C
L2
L3L1
L1
L3L2
T1
T2
L1 L2 L3
T3 T4T1 T2
U1
V1
W1
U2
W2
V2
U1
V1
W1
W2
U2
V2
U1
V1
W1
GC
W2
U2
V2
L1
L2
L3
*YE
GN/YE
WH
L1
U1
U2
W2
V2
W1
V1
L3
L2
WS004133C
Installation
Connection locations
Figure 8: Phase sequence
The figures in this section illustrate how to interpret the connection strip symbols.
1. Stator leads
2. Terminal board
3. Motor cable leads
4. Stator (internal connection illustrated)
26 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 29
L1 L2 L3
T3 T4T1 T2
43
21
5
10
8
CLS
6
FLS
7
FLS 10
11
9
WS004134A
Colors and markings of leads
Motor Connection
Colors and marking of the main leads
773 29 00/2
COLOR STANDARD
STATOR LEADS
BN = Brown
U1,U5 = RD
BK = Black
U2 = GN
WH = White
V1,V5 = BN
OG = Orange
V2 = BU
GN = Green
W1,W5 = YE
GN/YE = Green-Yellow
W2 = BK
RD = Red
T1,T2 = WH or YE GY = Grey BU = Blue YE = Yellow
*SUBCAB AWG * * Ground conductor is stranded around core GC=Ground check
Mains
SUBCAB 7GX
SUBCAB 4GX
3
Screenflex 7GX
Screenflex 4GX
SUBCAB AWG
SUBCAB Screened
L1
BK 1
BN
RD
BN
L2
BK 2
BK
BK
BK
L3
BK 3
GY
WH
GY
L1
BK 4
-
-
-
L2
BK 5
-
-
-
L3
BK 6
-
-
-
GN/YE
GN/YE
GN/YE
**Screen/PE from cores
Screen (WH)
Screen (WH)
-
Screen (WH)
GC
-
-
YE
-
6 LEADS
Terminal clamps 6 stator leads
Motor Connection
Colors and marking of the main leads
773 29 00/2
One cable
COLOR STANDARD
STATOR LEADS
BN = Brown
U1,U5 = RD
BK = Black
U2 = GN
WH = White
V1,V5 = BN
OG = Orange
V2 = BU
GN = Green
W1,W5 = YE
GN/YE = Green-Yellow
W2 = BK
RD = Red
T1,T2 = WH or YE GY = Grey BU = Blue YE = Yellow
*SUBCAB AWG * * Ground conductor is stranded around core GC=Ground check
U1
W2
V1
U2
W1
V2
Mains
SUBCAB 7GX
SUBCAB 4GX
3
Screenflex 7GX
Screenflex 4GX
SUBCAB AWG
SUBCAB Screened
L1
BK 1
BN
RD
BN
L2
BK 2
BK
BK
BK
L3
BK 3
GY
WH
GY
L1
BK 4
-
-
-
L2
BK 5
-
-
-
L3
BK 6
-
-
-
GN/YE
GN/YE
GN/YE
**Screen/PE from cores
Screen (WH)
Screen (WH)
­Screen (WH)
GC
-
-
YE
-
L1
U1
RD
U1
W2
L3
W2
BK
V1
BN
V1
GN
U2
L2
U2
W1
YE
W1
V2
BU
V2
WS004551B
Installation
1. Starter equipment and mains leads (L1, L2, L3)
2. Earth (ground)
3. Functional ground
4. Control leads (T1, T2, T3, T4)
5. Thermal contact
6. FLS
7. FLS 10
8. CLS
9. Thermistor
10. Level sensor
11. Capacitor
Color code standard
Code Description BN Brown BK Black WH White OG Orange GN Green GNYE Green-Yellow
Flygt 3153 Installation, Operation, and Maintenance Manual 27
Page 30
WS003903A
Terminal clamps 6 stator leads
U1
W2
V1
U2
W1
V2
Y
One cable
Two cables
L1
U1
U2
W2
V2
W1
V1
L2
L3
L1
1
U1
RD
U1
L1
L3
2
V1
BN
V1
1
L3
L2
2
W1
1
YE
W1
L2
2
GN
U2
W2
BK
BU
V2
GN/YE
*YE
GC
WH
L1
U1
RD
U1
W2
L3
W2
BK
V1
BN
V1
GN
U2
L2
U2
W1
YE
W1
V2
BU
V2
WS003803A
Installation
Motor connection
Code Description RD Red GY Grey BU Blue YE Yellow
Figure 9: Terminal clamps, 6 stator leads
Connections included
• 6–leads connection (page 28)
• 9-leads connection (page 29)
• Screened cable connection (page 30)
6–leads connection
If a separate control cable is used, then the control cores in the motor cable are never used.
One cable (left) and two cables (right) Y-connection.
Figure 10: Y-connection
One cable (left) and two cables (right) D-connection.
28 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 31
D
One cable
Two cables
L1
U1
V2
U2
V1
W1
W2
L2
L3
L1
U1
RD
U1
W2
L3
W2
BK
V1
BN
V1
GN
U2
L2
U2
W1
YE
W1
V2
BU
V2
L1
U1
1
L1
U1
RD
BK
W2
L3
2
W2
V1
BN
V1
1
L3
GN
U2
L2
2
U2
W1
YE
1
W1
L2
2
V2
BU
V2
GN/YE
*YE
GC
WH
WS003804A
Figure 11: D-connection
WS003805A
Y/D
One cable
Two cables
L1:1
L3:1
L2:1
L1:2
L3:2
L2:2
U1
V1
W1
U2
V2
W2
1
L1
U1
2
RD
4
L1
U1
BK
2
W2
W2
3
L3
V1
1
BN
6
L3
V1
GN
U2
2
2
U2
L2
YE
W1
1
W1
5
L2
V2
2
V2
BU
1
L1
U1
RD
U1
1
4
W2
2
L1
W2
BK
3
L3
V1
BN
V1
1
6
L3
GN
U2
2
2
L2
U2
W1
YE
W1
1
5
L2
2
V2
BU
V2
GN/YE
*YE
GC
WH
Y
D
Only applicable to 70mm2 terminal clamp
L1
U1
U1
1
RD
L3
1
V1
BN
V1
L2
YE
W1
1
W1
GN
U2
BU
V2
BK
L1
RD
U1
1
U1
BK
W2
L3
W2
BN
V1
1
V1
U2
L2
U2
GN
1
W1
YE
W1
V2
BU
V2
GN/YE
*YE
GC
WH
WS003813A
One cable (left) and two cables (right)Y/ D-connection.
Installation
Figure 12: Y/D-connection
Y and D-connection, only applicable to 70 mm2 terminal clamp.
Figure 13: Y or D-connection
9-leads connection
Flygt 3153 Installation, Operation, and Maintenance Manual 29
If a separate control cable is used, then the control cores in the motor cable are never used.
One cable (left) and two cables (right) Y-parallel connection.
Page 32
WS003826A
One cable
Two cables
Y-
L1
U1
U5
U2
W2
W1
V2
V5
L2
W5
V1
L3
L1
U1
U1
RD
U5
RD
U5
L3
BN
V1
V1
BN
V5
L2
V5
W1
YE
W1
YE
W5
W5
GN
U2
BU
V2
BK
W2
L1
RD
U1
1
L1
U1
RD
U5
L3
2
U5
BN
V1
1
L3
V1
BN
V5
L2
2
V5
YE
W1
1
L2
W1
W5
YE
W5
2
GN
U2
BU
V2
BK
W2
GN/YE
*YE
GC
WH
WS003837B
Y-SER
Two cables
L1
U1
U2
U5
W5
W1
W2
V5
V2
V1
L2
L3
1
L1
RD
U1
U1
2
L1
L3
BN
V1
1
L3
V1
L2
2
YE
W1
1
L2
2
W1
GN
U2
RD
U5
BU
V2
BN
V5
BK
W2
YE
W5
GN/YE
*YE
GC
WH
One cable
L1
RD
U1
U1
RD
U5
L3
U5
GN
U2
V1
BN
V1
L2
V5
BN
V5
W1
BU
V2
W5
YE
W1
YE
W5
BK
W2
WS003815A
Screened SUBCAB & FGB Screened
Cable without sep. ground conductor Screen as ground conductor
GN/YE shrink hose
BN
BK
GY
L1
L2 L3
Mini CAS
Mini CAS+AUX
FGB Screened
T1 (WH)
T2 (WH)
T3 (WH)
T4 (WH)
T1 (WH)
T2 (WH)
T3 (WH)
T4 (WH)
T1 (WH)
T2 (WH)
Installation
Figure 14: Y-parallel connection
One cable (left) and two cables (right) Y-serial connection.
Figure 15: Y-serial connection
Screened cable connection
Cable without separate ground conductor. Screen as ground conductor.
Figure 16: Screened SUBCAB and FGB Screened
* For screened SUBCAB T3 and T4 shall also be twisted separately.
30 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 33
WS003824A
Screenflex and SUBCAB with functional ground
* For screened SUBCAB T3 & T4 shall also be twisted separately
T1 and T2 twisted*
White insulation hose
Screen
GN/YE
L1
L2
L3
T1
T2
BN
BK
GY
T1 and T2
White insulation hose
twisted*
Screen
BK
BK
BK
BK
BK
BK
GN/YE
1
2
3
4
5
6
T1
T2
Figure 17: Screenflex and SUBCAB with functional ground
WS003843A
Color and marking of control leads
Control
SUBCAB 4GX/7G and
Screenflex
SUBCAB AWG
SUBCAB Screened
T1
WH T1
OG
WH T1
T2
WH T2
BU
WH T2
T3
-
-
WH T3
T4
-
-
WH T4
WS003850A
Sensor terminal clamps
T15
T16
T1
T2
Sensor-connection
Connection to the pump
Installation
Figure 18: Color and marking of control leads
Figure 19: Sensor terminal clamps
Flygt 3153 Installation, Operation, and Maintenance Manual 31
Page 34
WS003855A
FLS + Thermal detectors
FLS
TC
Max 12 V
WH/YE
T1
Control leads
T1/*OG/1
+7
Mini
BN
T2
CAS
WH/YE
T2/*BU/2
-5
BN
T15
**T3
*SUBCAB AWG
**T4
**Screened SUBCAB
WS003876A
FLS + Thermistor
T1
Control leads
Max
RD
T1/1
Thermistor
2.5 V
RD
T2
T2/2
relay
T15
Max
FLS
BN/BU
T3/3
+7
Mini
12 V
BN/BU
T16
T4/4
CAS
-5
WS003869A
Thermal detectors FLS Disconnected
FLS
TC
Max 12 V
WH/YE
T1
Control leads
T1/*OG/1
+7
Mini
BN
T2
CAS
T2/*BU/2
-5
WH/YE
T15
BN
**T3
*SUBCAB AWG
**T4
**Screened SUBCAB
Installation
FLS 10 and Thermal detectors
∞ Ohm Overtemperature 1200 Ohm OK 430 Ohm Leakage
FLS 10 and Thermistor
T=25°C (77°F) R ≤ 100 Ohm T=135°C (275°F) (T T=145°C (293°F) (T
Thermal detectors, FLS disconnected
32 Flygt 3153 Installation, Operation, and Maintenance Manual
REF
REF
–5°C (23°F)) R ≤ 550 Ohm +5°C (41°F)) R ≤ 1330 Ohm
Page 35
Connection to the monitoring equipment
24 V AC/DC
R
CC
P
C
L2
L1
102
6
7 +T1
T15
T2
FLS10
5 -
11
1
12 VDC
9
8
10S
4
3
WS002623B
WS006253A
MiniCAS II
Check the impeller rotation
Installation
C Pump contactor CC Control circuit L1 Caution light (leakage) L2 Caution light (stator over-temperature) P Pump main supply R Reset switch
WARNING:
The starting jerk can be powerful.
1. Start the motor. Stop the motor after a few seconds.
2.
3. Check that the impeller rotates according to this illustration.
Flygt 3153 Installation, Operation, and Maintenance Manual 33
Page 36
Installation
The correct direction of impeller rotation is clockwise when you look at the pump from above.
4. If the impeller rotates in the wrong direction, transpose two phase leads (3-phase) and do this procedure again.
34 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 37
Operation
Precautions
WARNING:
• Never operate the pump without safety devices installed.
• Never operate the pump with the discharge valve closed.
• Make sure you have a clear path of retreat.
• Never work alone.
CAUTION:
If the pump is equipped with automatic level control and/or internal contactor, there is a risk of sudden restart.
Distance to wet areas
Electrical Hazard:
Risk of electrical shock. Make sure no one gets closer than 20 m (65 ft.) to the unit when being in contact with the pumped or mixed liquid.
Operation
Noise level
NOTICE:
The noise level of the product is lower than 70 dB. However, the noise level of 70 dB may be exceeded in some installations and at certain operating points on the performance curve. Make sure that you understand the noise level requirements in the environment where the pump is installed. Failure to do so may result in hearing loss or violation of local laws.
Start the pump
Electrical Hazard:
A permanent-magnet motor generates voltage when the shaft is rotating. Ensure that the shaft can not rotate before performing any electrical installation.
WARNING:
If you need to work on the pump, make sure that it is isolated from the power supply and
•
cannot be energized.
• Make sure that the unit cannot roll or fall over and injure people or damage property.
• In some installations, the pump and the surrounding liquid may be hot. Bear in mind the
risk of burn injuries.
• Make sure nobody is close to the unit when it is started. The unit will jerk in the opposite
direction of the impeller rotation.
Flygt 3153 Installation, Operation, and Maintenance Manual 35
Page 38
Operation
NOTICE:
Make sure that the rotation of the impeller is correct. For more information, see Check the impeller rotation.
1. Remove the fuses or open the circuit breaker, and check that the impeller can be rotated freely.
2. Conduct insulation test phase to ground. To pass, the value must exceed 5 megohms.
3. Check that the monitoring equipment works.
4. Start the pump.
36 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 39
Maintenance
Precautions
WARNING:
• Always follow safety guidelines when working on the product. See Introduction and
Safety (page 3).
• Disconnect and lock out electrical power before installing or servicing the pump.
• Make sure that the unit cannot roll or fall over and injure people or damage property.
• Rinse the unit thoroughly with clean water before working on the unit.
• Rinse the components in water after dismantling.
WARNING:
Electrical hazard. A permanent magnet motor produces voltage when the shaft is rotating. The conductors must be insulated.
CAUTION:
• Magnetic stray fields may damage cardiac pacemaker and other medical implants. Stay
clear of any magnetic stray fields that can occur near an open or disassembled permanent-magnet synchronous motor, or near a separate rotor of such a motor. Keep magnetic media away, including credit cards and watches.
Crush hazard during disassembly or assembly of a permanent-magnet synchronous
•
motor. Fingers or other body parts can be trapped and injured. Magnetic items such as tools attracted to the rotor can also cause personal injury.
• Assembly and disassembly of permanent-magnet synchronous motors must be
performed by qualified personnel and according to relevant instructions.
Maintenance
Make sure that you follow these requirements:
•
• Allow all system and pump components to cool before you handle them.
• Make sure that the product and its components have been thoroughly cleaned.
• Do not open any vent or drain valves or remove any plugs while the system is
• If the unit has a permanent magnet motor, ensure that you have read and understood
Maintenance guidelines
During maintenance and before reassembly, always remember to perform these tasks:
• Clean all parts thoroughly, particularly O-ring grooves.
• Change all O-rings, gaskets, and seal washers.
• Lubricate all springs, screws, and O-rings with grease. During reassembly, always make sure that existing index markings are in line. The reassembled drive unit must always be insulation-tested and the reassembled pump
must always be test-run before normal operation.
Check the explosion risk before you weld or use electrical hand tools.
pressurized. Make sure that the pump is isolated from the system and that pressure is relieved before you disassemble the pump, remove plugs, or disconnect piping.
all safety instructions regarding permanent magnet motors.
Flygt 3153 Installation, Operation, and Maintenance Manual 37
Page 40
Maintenance
Torque values
All screws and nuts must be lubricated to achieve correct tightening torque. Screws that are screwed into stainless steel must have the threads coated with suitable lubricants to prevent seizing.
If there is a question regarding the tightening torques, please contact a sales representative.
Screws and nuts
Table 1: Stainless steel, A2 and A4, torque Nm (ft-lbs)
Property class
50 1.0 (0.74) 2.0 (1.5) 3.0 (2.2) 8.0 (5.9) 15 (11) 27 (20) 65 (48) 127 (93.7) 220 (162) 434 (320) 70, 80 2.7 (2) 5.4 (4) 9.0 (6.6) 22 (16) 44 (32) 76 (56) 187 (138) 364 (268) 629 (464) 1240
100 4.1 (3) 8.1 (6) 14 (10) 34 (25) 66 (49) 115 (84.8) 248 (183) 481 (355) — —
Table 2: Steel, torque Nm (ft-lbs)
Property class
8.8 2.9 (2.1) 5.7 (4.2) 9.8 (7.2) 24 (18) 47 (35) 81(60) 194 (143) 385 (285) 665 (490) 1310
10.9 4.0 (2.9) 8.1 (6) 14 (10) 33 (24) 65 (48) 114 (84) 277 (204) 541 (399) 935 (689) 1840
12.9 4.9 (3.6) 9.7 (7.2) 17 (13) 40 (30) 79 (58) 136 (100) 333 (245) 649 (480) 1120
Hexagon screws with countersunk heads
M4 M5 M6 M8 M10 M12 M16 M20 M24 M30
(915)
M4 M5 M6 M8 M10 M12 M16 M20 M24 M30
(966.2)
(1357) 2210
(825.1)
For hexagon socket head screws with countersunk head, maximum torque for all property classes must be 80% of the values for property class 8.8 above.
(1630)
38 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 41
Change the coolant
1
2
2
1
2
2
WS001480A
WS001505A
WS002122A
This image shows the plugs that are used to change the coolant.
Figure 20: With a cooling jacket
Maintenance
Figure 21: Without a cooling jacket
Empty the coolant
WARNING:
The seal housing may be pressurized. Hold a rag over the inspection/ filling plugs to prevent splatter.
1. Empty the coolant in the inspection chamber:
1. Inspection plug
2. Coolant plugs
Remove the inspection plug.
a)
Figure 22: Without a cooling jacket
b) Pump out any coolant from the inspection chamber, as shown here.
Flygt 3153 Installation, Operation, and Maintenance Manual 39
Figure 23: With a cooling jacket
Page 42
WS001471A
WS001463A
Maintenance
c) Replace the inspection plug and O-ring and tighten.
Tightening torque: 44 Nm (33 ft-lbs)
2. Empty the coolant:
a) Place the pump in a horizontal position, or leave it upright to use a pump to empty
the coolant.
b) If the pump is laid in a horizontal position, place a container under the pump. c) Remove the coolant plugs and empty the coolant.
40 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 43
WS001411A
WS001412A
Maintenance
Fill with coolant
Figure 24: With a cooling jacket
Figure 25: Without a cooling jacket
Use a coolant that is a mixture of 70% water and 30% monopropylene glycol. The coolant should prevent corrosion and be nonpoisonous (generally recognized as safe by the FDA as food additives under part 184 and 182).
NOTICE:
Clean water with an anti-corrosive is an acceptable coolant when there is no risk of freezing.
1. Fill with coolant until it overflows through the opposite hole, as shown here.
Quantity: approximately
• 2.2 L (2.3 qt.) without cooling jacket
• 10.5 L (11.2 qt.) with cooling jacket
Flygt 3153 Installation, Operation, and Maintenance Manual 41
Page 44
WS001469A
Maintenance
Figure 26: With cooling jacket
2. Replace the O-rings.
3. Tighten the coolant plugs.
Tightening torque: 44 Nm (33 ft-lbs)
Service the pump
Type of service Purpose Inspection interval
Initial inspection To make a check up of the pump
Periodical inspection To prevent operational interruptions
Figure 27: Without cooling jacket
condition by an authorized Xylem service representative and, based on the result and findings from these measures, to determine the intervals for periodical inspection and major overhaul for the specific installation.
and machine breakdown. Measures to secure performance and pump efficiency are defined and decided for each individual application. It can include such things as impeller trimming, wear part control and replacement, control of zinc-anodes and control of the stator.
Within the first year of operation.
Up to 12,000 hours or 3 years, whichever comes first.
Applies to normal applications and operating conditions at media (liquid) temperatures <40°C.
Major overhaul To secure a long operating lifetime
NOTICE:
Shorter intervals may be required when the operating conditions are extreme, for example with very abrasive or corrosive applications or when the liquid temperatures exceed 40°C (104°F).
42 Flygt 3153 Installation, Operation, and Maintenance Manual
for the product. It includes replacement of key components and the measures taken during an inspection.
Up to 24,000 hours or 6 years, whichever comes first.
Applies to normal applications and operating conditions at media (liquid) temperatures <40°C.
Page 45
Inspection
Maintenance
Service item Action
Cable
1. If the outer jacket is damaged, replace the cable.
2. Check that the cables do not have any sharp bends and are not pinched.
Connection to power Check that the connections are properly tightened.
Electrical cabinets Check that they are clean and dry.
Impeller
1. Check the impeller clearance.
2. Adjust the impeller, if necessary.
Inspection chamber
1. Drain all liquid, if any.
2. Check the resistance of the leakage sensor. Normal value approx.1200 ohms, alarm approx. 430 ohms.
Insulation Use a megger maximum 1000 V.
1. Check that the resistance between the earth (ground) and phase lead is more than 5 megohms.
2. Conduct a phase-to-phase resistance check.
Junction box Check that it is clean and dry.
Level regulators Check the condition and functionality.
Lifting device Check that local safety regulations are followed.
Lifting handle
1. Check the screws.
2. Check the condition of the lifting handle.
3. Replace if necessary.
O-rings
1. Replace the oil plug O-rings.
2. Replace the O-rings at the entrance or junction cover.
3. Grease the new O-rings.
Overload protection and other
Check the correct settings.
protections
Personnel safety devices Check the guard rails, covers, and other protections.
Rotation direction Check the impeller rotation.
Seal housing
1. Fill with new coolant, if necessary.
2. Check that the freezing point is lower than -13°C (9°F).
Terminal board Check that the connections are properly tightened.
Thermal contacts Normally closed circuit; interval 0–1 ohm.
Thermistor Check the resistance is between 20–250 ohms and the measured
voltage is maximum 2 V DC.
Voltage and amperage Check the running values.
Flygt 3153 Installation, Operation, and Maintenance Manual 43
Page 46
Maintenance
Major overhaul
For a major overhaul, take this action in addition to the tasks listed under Inspection.
Service item Action
Support and main bearing Replace the bearings with new bearings.
Mechanical seal Replace with new seal units.
Service in case of alarm
For information about indication values for sensors, see Sensor-connection (page 31).
Alarm source Action
FLS10
The thermistor/Thermal contact
The overload protection Check that the impeller can rotate freely.
Replace the impeller
Required tools:
• 12 mm hexagon bit adapter with an extension of at least a 100 mm (4 in.)
• Rod (wood or plastic) for locking the impeller in place.
WARNING:
• If you fail with the impeller installation, you must redo the installation procedure from the beginning.
• A worn impeller and/or pump housing can have very sharp edges. Wear protective gloves.
• When laying the pump on its side, do not allow the weight of the pump to rest on any
portion of the impeller. The impeller must not be allowed to make contact with the concrete floor or other hard and rough surfaces.
1. Drain the fluid in the inspection chamber. Fill with new coolant if necessary.
2. Check the freezing point (lower than -13°C or 9°F).
Check the inspection chamber again after one week of operation. If leakage has occurred:
1. Drain the fluid.
2. Change the mechanical seal unit.
3. Replace with new coolant.
1. Check the coolant level (pump with cooling jacket).
2. Check the start and stop levels.
Replace the impeller for wet installation
Remove the impeller: wet installation
CAUTION:
Wear heavy work gloves when you handle impellers. The sharp edges can cause physical injury.
1. Place the pump in a horizontal position. Remove the impeller:
2.
44 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 47
WS001482A
WS001450A
WS001490A
Maintenance
a) Remove the flush valve cover and its O-ring. b) Lock the impeller in place by inserting a rod through the hole. c) Remove the impeller screw.
d) Turn the adjustment screw counterclockwise until the impeller breaks free from the
shaft.
e) Hand-tighten the impeller screw to prevent it from falling off.
f) Remove the rod.
3. Raise the pump.
4. Remove the drive unit from the pump housing:
Flygt 3153 Installation, Operation, and Maintenance Manual 45
Page 48
WS006264A
WS001477A
Maintenance
a) Remove the pump housing screws.
b) Remove the drive unit from the pump housing.
5. Remove the impeller: a) Place the drive unit horizontally.
b) Remove the impeller screw.
46 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 49
WS006263A
c) Remove the impeller and the conical sleeve.
WS001461B
Maintenance
Install the impeller: wet installation
1. Mount the impeller: a) Make sure that the end of the shaft is free from burrs.
Polish off any flaws with a fine emery cloth.
b) Grease the shaft end.
NOTICE:
Surplus grease can cause the impeller to become loose. Remove surplus grease from conical and/or cylindrical surfaces of shafts and/or sleeves.
Flygt 3153 Installation, Operation, and Maintenance Manual 47
Page 50
WS002057A
WS002058A
WS001759A
Maintenance
c) Grease the conical sleeve, the threads of the adjustment screw, the washer, and the
impeller screw. Always use a new impeller screw.
d) Adjust the adjustment screw so that it is flush with the sleeve.
e) Fit the sleeve and impeller to the shaft.
Hand-tighten the impeller screw to prevent it from falling off.
f)
48 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 51
WS006256A
WS003664A
WS003665A
Maintenance
2. If applicable, check that the clearance between the impeller and the insert ring is maximum 1 mm (0.04 in.) radial. If not, send the pump for service.
The insert ring is pressed into the seal housing cover.
3. Fit the pump housing: a) Fit a new and greased O-ring on the seal housing cover.
b) Grease the pump housing screws. c) Raise the drive unit. d) Place the drive unit into the pump housing.
Flygt 3153 Installation, Operation, and Maintenance Manual 49
Page 52
WS006260A
WS001482A
Maintenance
e) Adjust its position so that the inspection hole is on the same side as the flush valve. f) Tighten the screws in diagonal sequence.
For tightening torque, see Torque values (page 38).
4. Remove the impeller screw: a) Place the pump horizontally.
b) Lock the impeller in place by inserting a rod through the hole. c) Remove the impeller screw and the washer.
5. Adjust the impeller: a) Using a hexagon-bit adapter, turn the adjustment screw clockwise until the impeller
makes contact with the pump housing. For tightening torque, see Torque values (page 38).
b) Tighten it a further 1/8 turn (45°).
50 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 53
WS001451A
6. Fasten the impeller:
WS001486A
a) Fit the greased washer and impeller screw. b) Tighten the impeller screw.
For tightening torque, see Torque values (page 38).
c) Tighten it a further 1/8 turn (45°).
Maintenance
d) Remove the rod used to lock the impeller. e) Fit the O-ring and flush valve cover and fasten it with screws.
For tightening torque, see Torque values (page 38).
f) Check that the impeller can rotate freely.
CAUTION:
Beware of the pinch point hazard between the rotating impeller and the guide pin.
7. Check that the clearance between the impeller and the insert ring is 0.1–0.5 mm (0.004–0.02 in.).
Flygt 3153 Installation, Operation, and Maintenance Manual 51
Page 54
WS003730A
WS003731A
WS001504A
Maintenance
8. If applicable, adjust clearance to 0.1–0.5 mm (0.004–0.02 in.) between the guide pin and the impeller.
Replace the impeller for dry installation
Remove the impeller: dry installation
1. Remove the drive unit from the pump housing: a) Remove the pump housing screws.
52 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 55
WS001539A
WS001477A
Maintenance
b) Remove the drive unit from the pump housing.
2. Remove the impeller:
Place the drive unit horizontally.
a) b) Lock the impeller as shown in the figure. c) Remove the impeller screw.
Flygt 3153 Installation, Operation, and Maintenance Manual 53
Page 56
WS001494A
WS001461B
Maintenance
d) Turn the adjustment screw counterclockwise until the impeller breaks free from the
shaft.
e) Remove the impeller and the conical sleeve.
Install the impeller: dry installation
1. Prepare the sleeve: a) Make sure that the end of the shaft is free from burrs.
Polish off any flaws with a fine emery cloth.
b) Grease the shaft end.
NOTICE:
Surplus grease can cause the impeller to become loose. Remove surplus grease from conical and/or cylindrical surfaces of shafts and/or sleeves.
54 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 57
WS002057A
WS002058A
WS002106A
Maintenance
c) Grease the conical sleeve, the threads of the adjustment screw, the washer, and the
impeller screw. Always use a new impeller screw.
d) Unscrew the adjustment screw approximately 5 mm (0.2 in.).
e) Measure and note the distance A.
Flygt 3153 Installation, Operation, and Maintenance Manual 55
Page 58
A
WS001472A
WS006256A
Maintenance
2. Mount the impeller: a) Fit the sleeve and the impeller to the shaft.
b) Fit the impeller screw and washer and tighten.
56 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 59
WS001492A
3. Make sure that the O-ring is removed from the seal housing cover.
WS002008A
WS001475A
Maintenance
4. Measure the trim distance: a) Place the drive unit in the pump housing.
Make sure that the drive unit is parallel with the pump housing by hand-tightening the pump housing screws.
b) Check the distance between the seal housing cover and the pump housing with a
feeler gauge. Check diagonally at four points.
Flygt 3153 Installation, Operation, and Maintenance Manual 57
Page 60
WS002089A
B
WS001473A
WS001477A
Maintenance
c) Note the largest distance B.
d) Lift the drive unit out of the pump housing and remove the impeller and conical
sleeve.
5. Trim to the correct distance:
Calculate the measure C according to the formula shown in the image.
a)
58 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 61
C=A-B-0.5 mm
WS001475A
WS001492A
Maintenance
b) Turn the adjustment screw until C is reached.
6. Fasten the impeller: a) Fit the sleeve, impeller, greased washer with a greased impeller screw.
b) Tighten the impeller screw.
For tightening torque, see Torque values (page 38).
c) Tighten it further 1/8 turn (45°).
7. If applicable, check that the clearance between the impeller and the insert ring is maximum 1 mm (0.04 in.) radial. If not, send the pump for service.
The insert ring is pressed into the seal housing cover.
Flygt 3153 Installation, Operation, and Maintenance Manual 59
Page 62
WS003664A
WS003665A
WS002056A
Maintenance
8. Install the drive unit in the pump housing: a) Fit a new and greased O-ring to the seal housing cover.
b) Place the drive unit in the pump housing.
60 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 63
WS001475A
WS001478A
Maintenance
c) Adjust the position of the drive unit so that the inspection hole is on the same side
as the flush valve.
d) Tighten the greased screws diagonally.
For tightening torque, see Torque values (page 38).
If you need to adjust the impeller, redo the replace the impeller procedure from the beginning.
Flygt 3153 Installation, Operation, and Maintenance Manual 61
Page 64
Troubleshooting
Troubleshooting
Introduction
Follow these guidelines when troubleshooting the pump:
• Disconnect and lock out the power supply except when conducting checks that require voltage.
• Make sure that no one is near the pump when the power supply is reconnected.
• When troubleshooting electrical equipment, use the following:
• Universal instrument multimeter
• Test lamp (continuity tester)
• Wiring diagram
The pump does not start
WARNING:
Always disconnect and lock out power before servicing to prevent unexpected startup. Failure to do so could result in death or serious injury.
WARNING:
Electrical hazard. A permanent magnet motor produces voltage when the shaft is rotating. The conductors must be insulated.
NOTICE:
Do NOT override the motor protection repeatedly if it has tripped. Doing so may result in equipment damage.
Cause Remedy
An alarm signal has been triggered on the control panel.
The pump does not start automatically, but can be started manually.
Check that:
•
The impeller rotates freely.
• The sensor indicators do not indicate an alarm.
• The overload protection is not tripped. If the problem still persists: Contact the local Xylem service shop.
Check that:
• The start level regulator is functioning. Clean or replace if necessary.
• All connections are intact.
• The relay and contactor coils are intact.
• The control switch (Man/Auto) makes contact in both positions. Check the control circuit and functions.
The installation is not receiving voltage.
62 Flygt 3153 Installation, Operation, and Maintenance Manual
Check that:
• The main power switch is on.
• There is control voltage to the start equipment.
• The fuses are intact.
• There is voltage in all phases of the supply line.
Page 65
Cause Remedy
• All fuses have power and that they are securely fastened to the fuse holders.
• The overload protection is not tripped.
• The motor cable is not damaged.
The impeller is stuck. Clean:
• The impeller
• The sump in order to prevent the impeller from clogging again.
If the problem persists, refer to the Flygt Service Guide on the web or contact the local Xylem service shop. Always state the serial number of your pump when you contact Xylem, see Product Description (page 12).
The pump does not stop when a level sensor is used
WARNING:
Always disconnect and lock out power before servicing to prevent unexpected startup. Failure to do so could result in death or serious injury.
Troubleshooting
WARNING:
Electrical hazard. A permanent magnet motor produces voltage when the shaft is rotating. The conductors must be insulated.
Cause Remedy
The pump is unable to empty the sump to the stop level.
There is a malfunction in the level­sensing equipment.
The stop level is set too low. Raise the stop level.
If the problem persists, refer to the Flygt Service Guide on the web or contact the local Xylem service shop. Always state the serial number of your pump when you contact Xylem, see Product Description (page 12).
Check that:
•
There are no leaks from the piping and/or discharge connection.
• The impeller is not clogged.
• The non-return valve(s) are functioning properly.
• The pump has adequate capacity. For information: Contact the local Xylem service shop.
• Clean the level regulators.
• Check the functioning of the level regulators.
• Check the contactor and the control circuit.
• Replace all defective items.
The pump starts-stops-starts in rapid sequence
Cause Remedy
The pump starts due to back-flow which fills the sump to the start level again.
Flygt 3153 Installation, Operation, and Maintenance Manual 63
Check that:
Page 66
Troubleshooting
Cause Remedy
• The distance between the start and stop levels is sufficient.
• The non-return valve(s) work(s) properly.
• The length of the discharge pipe between the pump and the first non-
return valve is sufficiently short.
The self-holding function of the contactor malfunctions.
If the problem persists, refer to the Flygt Service Guide on the web or contact the local Xylem service shop. Always state the serial number of your pump when you contact Xylem, see Product Description (page 12).
Check:
• The contactor connections.
• The voltage in the control circuit in relation to the rated voltages on the coil.
• The functioning of the stop-level regulator.
• Whether the voltage drop in the line at the starting surge causes the contactor's self-holding malfunction.
The pump runs but the motor protection trips
WARNING:
Always disconnect and lock out power before servicing to prevent unexpected startup. Failure to do so could result in death or serious injury.
WARNING:
Electrical hazard. A permanent magnet motor produces voltage when the shaft is rotating. The conductors must be insulated.
NOTICE:
Do NOT override the motor protection repeatedly if it has tripped. Doing so may result in equipment damage.
Cause Remedy
The motor protection is set too low. Set the motor protection according to the data plate and if applicable the
cable chart.
The impeller is difficult to rotate by hand.
The drive unit is not receiving full voltage on all three phases.
The phase currents vary, or they are too high.
• Clean the impeller.
•
Clean out the sump.
• Check that the impeller is properly trimmed.
• Check the fuses. Replace fuses that have tripped.
• If the fuses are intact, notify a certified electrician.
Contact the local Xylem service shop.
64 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 67
Cause Remedy
Troubleshooting
The insulation between the phases and ground in the stator is defective.
The density of the pumped fluid is too high.
There is a malfunction in the overload protection.
If the problem persists, refer to the Flygt Service Guide on the web or contact the local Xylem service shop. Always state the serial number of your pump when you contact Xylem, see Product Description (page 12).
1. Use an insulation tester. With a 1000 V DC megger, check that the
insulation between the phases and between any phase and ground is > 5 megohms.
2. If the insulation is less:
Contact the local Xylem service shop.
Make sure that the maximum density is 1100 kg/m3 (9.2 lb/US gal)
• Change the impeller, or
• Change to a more suitable pump.
• Contact the local Xylem service shop.
Replace the overload protection.
The pump delivers too little or no water
WARNING:
Always disconnect and lock out power before servicing to prevent unexpected startup. Failure to do so could result in death or serious injury.
WARNING:
Electrical hazard. A permanent magnet motor produces voltage when the shaft is rotating. The conductors must be insulated.
NOTICE:
Do NOT override the motor protection repeatedly if it has tripped. Doing so may result in equipment damage.
Cause Remedy
The impeller rotates in the wrong direction.
One or more of the valves are set in the wrong positions.
The impeller is difficult to rotate by hand.
• If it is a 3-phase pump, transpose two phase leads.
•
If it is a 1-phase pump: Contact the local Xylem service shop.
• Reset the valves that are set in the wrong position.
• Replace the valves, if necessary.
• Check that all valves are correctly installed according to media flow.
• Check that all valves open correctly.
• Clean the impeller.
• Clean out the sump.
• Check that the impeller is properly trimmed.
The pipes are obstructed. Clean out the pipes to ensure a free flow.
The pipes and joints leak. Find the leaks and seal them.
Flygt 3153 Installation, Operation, and Maintenance Manual 65
Page 68
Troubleshooting
Cause Remedy
There are signs of wear on the
Replace the worn parts.
impeller, pump, and casing.
The liquid level is too low.
• Check that the level sensor is set correctly.
• Depending on the installation type, add a means for priming the pump, such as a foot valve.
If the problem persists, refer to the Flygt Service Guide on the web or contact the local Xylem service shop. Always state the serial number of your pump when you contact Xylem, see Product Description (page 12).
66 Flygt 3153 Installation, Operation, and Maintenance Manual
Page 69
Technical Reference
Application limits
Data Description
Liquid temperature 40°C (104°F) maximum
For P- and S-installations without cooling jacket, the pump can be operated only when the sump level is at least 10 mm above the stator housing.
Warm-liquid version (only with cooling jacket): 70°C (158°F) maximum Ex-approved pumps: 40°C (104°F) maximum
Liquid density 1100 kg/m³ (9.2 lb per US gal) maximum
Technical Reference
Motor data
pH of the pumped media (liquid)
Depth of immersion 20 m (65 ft) maximum
Other For the specific weight, current, voltage, power ratings, and speed of the pump, see
Feature Description
Motor type
Frequency 50 or 60 Hz
Supply 3-phase
Starting method
Maximum starts per hour
5.5–14
the data plate of the pump.
• 3153.091/.095/.181/.185/.350/.390: Squirrel-cage induction motor
• 3153.800/.810/.820/.830/.840/.850: Line-started, permanent-magnet synchronous motor
• Direct on-line
• Star-delta
• Soft starter
30 evenly spaced starts per hour
Code compliance IEC 60034-1
Rated output variation ±10%
Voltage variation without overheating
Voltage imbalance tolerance
Stator insulation class H (180°C [360°F])
Flygt 3153 Installation, Operation, and Maintenance Manual 67
±10%, provided that it does not run continuously at full load
2%
Page 70
Page 71
Page 72
Xylem |’zīləm|
1) The tissue in plants that brings water upward from the roots
2) A leading global water technology company
We're 12,500 people unified in a common purpose: creating innovative solutions to meet our world's water needs. Developing new technologies that will improve the way water is used, conserved, and re-used in the future is central to our work. We move, treat, analyze, and return water to the environment, and we help people use water efficiently, in their homes, buildings, factories and farms. In more than 150 countries, we have strong, long-standing relationships with customers who know us for our powerful combination of leading product brands and applications expertise, backed by a legacy of innovation.
For more information on how Xylem can help you, go to xyleminc.com
895381_13.0_en.US_2012-08_IOM.3153.091/.095/.181/.185/.350/.390/.800/.810/.820/.830/.840/.850
Xylem Water Solutions AB Gesällvägen 33 174 87 Sundbyberg Sweden Tel. +46-8-475 60 00 Fax +46-8-475 69 00 http://tpi.xyleminc.com
Visit our Web site for the latest version of this document and more information
The original instruction is in English. All non­English instructions are translations of the original instruction.
©