Flybox Vigilus Operating Manual

Revision 1.0, 18/7/2017
For firmware version 2.14
Flybox
®
Operating manual
Page intentionally left blank
SECTIONS
INSTRUMENT CONFIGURATION
OPERATING INSTRUCTIONS
TECHNICAL SPECIFICATIONS
Flybox
VIGILUS - Operating manual
®
Rev. 1.0
Thank you for purchasing a Flybox® product. We hope it fully satisfy you and makes your flights pleasant and secure. Developing Vigilus, our intent was to create a compact but complete Engine Information System , easy to install and use.
SYMBOLS USED IN THE MANUAL
NOTE: Used to highlight important informations.
CAUTION: Used to warn the user and indicate a potentially
hazardous situation or improper use of the product.
WARNING: Used to indicate a dangerous situation that can cause personal injury or death if the instruction is disregarded.
VIGILUS - Operating manual
Flybox
Rev. 1.0
®
Important notices & warnings
NOTE: Keep this manual in the aircraft.
This document must accompany the instrument in the event of change of ownership.
NOTE: This device is intended for installation onto non type certified aircraft only, because it has no aviation certifications. Refer to your local aviation authorities to check if this device may be installed in your aircraft.
CAUTION: Read entirely this manual before installing the instrument in your aircraft, and follow the installation and operating instructions described here.
CAUTION: The pilot must understand the operation of this instrument prior to flight, and must not allow anyone to use it without knowing the operation. Don't use this instrument in flight until you are sure of the correct operating of the same.
CAUTION: When the installation is finished you must do a test, prior to flight, switching on all the possible source of electric noise and checking the properly operation of this instrument.
CAUTION: The software of this instrument can be subject to change, update, addition or removal of functions, so also the operating mode of the instrument can be subject to change. Always refer to the installation and operating manual updated with the software version used in your instrument. To obtain updated manuals, please visit www.flyboxavionics.it.
Flybox
VIGILUS - Operating manual
®
Rev. 1.0
Important notices & warnings
WARNING: Responsibility for installation lies entirely with the
installer. Responsibility for operations lies entirely with the operator. Responsibility for any calibration, settings or any other customization lies with the person performing these operations.
WARNING: Do not solely rely on this instrument to determine the primary engine informations. Always compare the informations provided with other primary instruments to recognize eventual malfunctions.
IMPORTANT: If you do not agree with the notices above do not install this instrument in your aircraft, but return the product for a refund.
Microel s.r.l. reserves the right to change or improve its products. Information in this document is subject to changes without notice.
WARNING: For safety reasons, the Vigilus operational procedures must be learned on the ground.
WARNING: It’s up to the installer to check the correctness of the settins for its engine, even using one of the Vigilus preset, because engine manufacturers may change parameters without notice. The engine preset of the Vigilus are a help but needs to be checked by the installer.
VIGILUS - Operating manual
Flybox
Rev. 1.0
®
Contents
SECTION 1............................................................11
1.1 PRIMARY ACTIONS AFTER INSTALLATION....................11
1.2 PANEL INDICATORS AND COMMANDS.........................13
1.3 INSTRUMENT CONFIGURATION..................................14
1.3.1 ENTERING & BROWSING THE MENUs...........................14
1.3.2 MAIN MENU:.............................................................16
1.3.3 SETTINGS MENU:......................................................16
1.3.4 INSTRUMENTS MENU:................................................16
EGT SETUP MENU:........................................................17
CHT SETUP MENU:........................................................19
OAT (OUTSIDE AIR TEMP.) SETUP MENU:........................22
CAT (CARBURETOR AIR TEMP.) SETUP MENU:..................23
FUEL PRESSURE SETUP MENU:.......................................24
FUEL LEVEL SETUP MENU:.............................................26
OIL PRESSURE SETUP MENU:.........................................28
OIL TEMPERATURE SETUP MENU:...................................30
RPM SETUP MENU:........................................................32
MAP SETUP MENU:........................................................33
VOLT SETUP MENU:......................................................34
Flybox
VIGILUS - Operating manual
®
Rev. 1.0
AMP SETUP MENU:........................................................36
GB T (GEARBOX TEMPERATURE) SETUP MENU:................37
ROTOR SETUP MENU:....................................................39
1.3.5 GLOBAL SETTINGS MENU:..........................................41
AIRCRAFT SETUP..........................................................41
GPS SETUP..................................................................43
SERIAL PORTS SETUP...................................................43
AUDIO SETTINGS.........................................................44
UNITS SETUP...............................................................45
PAGES SETUP...............................................................46
1.3.6 FUEL COMPUTER MENU:.............................................47
1.3.7 ABOUT MENU:...........................................................49
1.3.8 FIRMWARE UPGRADE MENU:.......................................50
1.3.9 BACKUP AND RESTORE MENU:....................................51
1.4 FUEL FLOW TRANSDUCER CALIBRATION.....................52
1.5 FUEL LEVEL SENSORS CALIBRATION...........................54
1.5.1 FUEL LEVEL SENSORS CHECKINGS..............................58
1.6 FUEL COMPUTER ACTIVATION....................................59
SECTION 2............................................................60
2.1 USING THE VIGILUS.................................................60
VIGILUS - Operating manual
Flybox
Rev. 1.0
®
2.2 PAGE1: Main engine data page...................................61
2.2.1 TEMPERATURE PAGE..................................................68
2.3 PAGE2: Chronometer page........................................69
2.4 PAGE3: Fuel management page..................................71
2.5 PAGE4: Hourmeter page............................................75
SECTION 3............................................................77
3.1 ALARMS..................................................................77
3.2 SENSOR ALARMS......................................................78
SECTION 4............................................................79
4.1 DATALOGGER..........................................................79
SECTION 5............................................................84
5.1 VIGILUS DEFAULT CONFIGURATION TABLE..................84
TECHNICAL SPECIFICATIONS..........................................86
WARRANTY:..................................................................88
Page intentionally left blank
VIGILUS - Operating manual
Flybox
11
Rev. 1.0
®
SECTION 1
1.1 PRIMARY ACTIONS AFTER INSTALLATION
WARNING: Do not fly until you have performed at least
the actions indicated below:
1 - Select the engine type: the first parameter to setup is the engine selection, because it reset all the parameters to the default value. The engine selection can be made by entering in
the Main menu → Settings → Global Settings → Aircraft as
explained in chap.1.3.5.
2 - Tank level sensors: (if connected). It's indispensable to perform the calibration for all the tank level sensors connected to the Vigilus. Without performing calibration and settings no indication will be furnished. It is responsibility of the user to check during the first flights and over time the goodness of the calibration and therefore the instrument indications. The verification can be done in any moment, for example b y simply checking the quantity put to fill the tank: if you k n o w that the tank filled contain 40 liters and the Vigilus i n d i c a t e as remaining quantity 10.0 liter, you know that to fill the tank you must put approximately 30 liters. Of course keeping in mind that in ground the indications will be different that in flight because of the flight's attitude. This problem is present also in the traditional analog gauge indicators, but is more difficult to detect because of the non-numeric indication. Another verification is, in case of low remaining quantity (i.e. 4~5 liters), drain and measure it.
Flybox
VIGILUS - Operating manual
12
®
Rev. 1.0
Primary actions after installation
3 - Fuel computer: (if installed). If it's installed the fuel flow transducer, BEFORE rely on informations provided by the fuel computer section you must:
- Verify that the K-factor set in the Vigilus is pertinent to the installed fuel flow transducer (for the Flybox® TFTHP is 416400).
- Execute the fuel flow transducer calibration as explained in chapter 1.4. Without calibration the fuel computer informations may be wrong, even if the nominal K-factor is correct for the fuel flow transducer used. After calibration, the K-factor should have been calculated automatically and at best for every single installation. You must still check for some time if the remaining quantity indicated are reliable compared to the refuelling performed. For example, if the instrument indicate a remaining quantity of 35 liters and you know that the tanks capacity is 80 liters, filling the tanks should require approximately 45 liters; in case of much difference redo the calibration. Consider also that, during use, little errors accumulate and if you never fill the tanks you never “reset” all these errors.
VIGILUS - Operating manual
Flybox
13
Rev. 1.0
®
F1
pushbutton
Display
Knob with
pushbutton
1.2 PANEL INDICATORS AND COMMANDS
The knob with pushbutton can be rotated (for example to increment or decrement a value) or pressed like a pushbutton (for example to enter in a submenu). Inside the menus it’s always indicated the meaning of the pushbuttons (for example: exit, back, etc…)
Display cleaning:
To clean the display use the supplied smooth cloth, slightly moistened with cleaner. Use a cleaner that is specified as safe for anti-reflective coatings. CAUTION: Avoid any chemical cleaners or solvents that can damage the display anti-reflective coating or plastic components. Do not use cleaners containing ammonia.Do not spray water or cleaner directly onto the display.
F2
pushbutton
Flybox
VIGILUS - Operating manual
14
®
Rev. 1.0
1.3 INSTRUMENT CONFIGURATION
Before using the Vigilus you need to configure it; read completely this chapter and follow step by step the sections to completely configure all the sensors, alarms and preferences available.
1.3.1 ENTERING & BROWSING THE MENUs
Press the knob for 1 second to enter in the main menu:
Press the EXIT pushbutton to exit the menu.
Rotate the knob to select an item of the menu.
Click the knob to enter in the selected item.
For example, to change the display brightness:
Rotate the knob to select the “Brightness” item.
Click the knob and the item become highlighted in flashing red: it means that you can edit this value by rotating the knob.
Click again the knob to store the new value for the brightness OR press the “ESC” pushbutton to exit without saving the changes.
VIGILUS - Operating manual
Flybox
15
Rev. 1.0
®
Entering & browsing the menus
Instrument configuration
Also when inside a parameters page, the editing philosophy is the same, for example:
On this example, by rotating the knob you select the parameter that you want to edit (the selected parameter is highligted in red).
If you don’t want to store the new value press “Esc” pushbutton to cancel the editing or press “Exit” pushbutton to exit the menu and return to the main pages.
If you click the knob the highlight become flashing red to indicate that you are editing that parameter. Rotate the knob to change the value and press the knob to store the new value
Flybox
VIGILUS - Operating manual
16
®
Rev. 1.0
Instrument configuration
Brightness: display brightness adjustment (1=min. brightness, 16=max. brightness). Default value=16.
Data Logger: enter in the datalogger menu (see section 4).
Settings: enter in the settings menu (see next chapter).
1.3.2 MAIN MENU:
1.3.3 SETTINGS MENU:
1.3.4 INSTRUMENTS MENU:
On this menu you can set all the parameters for each available measurement. On the right window there is a preview of the thresolds for the selected item; click the knob to enter in a item.
VIGILUS - Operating manual
Flybox
17
Rev. 1.0
®
Egt setup menu
Thresholds: set the thresholds of the EGT bars: min value (bottom of the bar), yellow threshold, red threshold and max value (top of the bar).
Mapping: although we recommend to perform a clean installation, with this feature it’s possible to reassign or disable the different EGT inputs available in the remote module: for example you can assign the input#1 of the remote module
EGT SETUP MENU:
EGT THRESHOLDS SUBMENU:
EGT MAPPING SUBMENU:
to the engine cylinder#3 and so on. You can also disable each inputs, useful for example if a sensor fails and you don’t want to display the indication for that sensor.
Instrument configuration
Flybox
VIGILUS - Operating manual
18
®
Rev. 1.0
Egt setup menu
Alarm = ON/OFF:
enable/disable the alarm (alert indication on display) that occurs when a EGT measurement exceeds the red threshold (default=ON).
Voice = ON/OFF: enable/disable the audio alert notification on EGT alarms (default=ON).
Repeat: Set the number of times that the vocal alarm for the EGT is repeated on the audio output (range:1~5, default=1).
Auto reset = ON/OFF: if set to ON, if a alarm condition is activated but the measurement that activated this alarm has dropped below the alarm threshold, the Vigilus automatically reset the alarm indication. If set to OFF, the user must manually reset the alarm indication, even if the measurement that activated this alarm has dropped below the alarm threshold (default=ON).
Out map: you can choose to enable one of the four outputs available on the remote module when the alarm is activated, useful for example to turn on an alarm light on the cockpit. Set to zero to disable this function (default=0).
Unit: °C / °F: Set the unit of measure for the EGT temperatures; choose between °Celsius (°C) or °Fahrenheit (°F). Default=°C.
Filter: This parameter affect the readings and the gauges displayed: a low value means that the readings will be more fast and unfiltered (but subject to fluctuations), an high value means that the readings will be more slow and stable (range: 0~999, default=100).
EGT ALARMS SUBMENU:
Instrument configuration
VIGILUS - Operating manual
Flybox
19
Rev. 1.0
®
Cht setup menu
Thresholds: set the thresholds of the CHT bars: min value (bottom of the bar), yellow threshold, red threshold and max value (top of the bar).
Mapping: although we recommend to perform a clean installation, with this feature it’s possible to reassign or disable the different CHT inputs available in the remote module: for example you can assign the input#1 of the remote module
CHT THRESHOLDS SUBMENU:
CHT MAPPING SUBMENU:
to the engine cylinder#3 and so on. You can also disable each inputs, useful for example if a sensor fails and you don’t want to display the indication for that sensor.
CHT SETUP MENU:
Instrument configuration
Flybox
VIGILUS - Operating manual
20
®
Rev. 1.0
Cht setup menu
For example, for Rotax 912/914 engines the default situation will be the following:
Since the Rotax engines are provided with two CHT sensors, but the first is for the cylinder#2 and the second is for the cylinder#3, this configuration make sure that the first input of the remote module (where is connected the first sensor) is referred to the cylinder#2, while the second input of the remote module (where is connected the second sensor) is referred to the cylinder#3; the third and fourth inputs are disabled (Enab. = OFF).
Alarm = ON/OFF:
enable/disable the alarm (alert indication on display) that occurs when a CHT measurement exceeds the red threshold (default=ON).
CHT ALARMS SUBMENU:
Voice = ON/OFF: enable/disable the audio alert notification on CHT alarms (default=ON).
Repeat: Set the number of times that the vocal alarm for the CHT is repeated on the audio output (range:1~5, default=1).
Instrument configuration
VIGILUS - Operating manual
Flybox
21
Rev. 1.0
®
Cht setup menu
Auto reset = ON/OFF: if set to ON, if a alarm condition is activated but the measurement that activated this alarm has dropped below the alarm threshold, the Vigilus automatically
reset the alarm indication. If set to OFF, the user must manually reset the alarm indication, even if the measurement that activated this alarm has dropped below the alarm threshold.
(default=ON)
Out map: you can choose to enable one of the four outputs available on the remote module when the alarm is activated, useful for example to turn on an alarm light on the cockpit. Set to zero to disable this function (default=0).
Type: Select the type of CHT sensors installed:
TCJ: J-type thermocouples P1K: PT1000 resistive sensors ROX: standard ROTAX CHT sensors (default)
NOTE: It's not possible to mix different type of CHT
sensors (i.e. 2 Rotax + 2 thermocouples).
Unit: °C / °F: Set the unit of measure for the CHT temperatures; choose between °Celsius (°C) or °Fahrenheit (°F).Default=°C.
Filter: This parameter affect the readings and the gauges displayed: a low value means that the readings will be more fast and unfiltered (but subject to fluctuations), an high value means that the readings will be more slow and stable (range: 0~999, default=100).
Instrument configuration
Flybox
VIGILUS - Operating manual
22
®
Rev. 1.0
OAT setup menu
OAT (OUTSIDE AIR TEMP.) SETUP MENU:
Thresholds: set the min value (bottom of the bar) and the max value (top of the bar).
OAT THRESHOLDS SUBMENU:
Type: Select the type of OAT sensor installed: P1K: PT1000 resistive sensors (default). NO: No sensor installed (disable the indication).
Unit: °C / °F: Set the unit of measure for the OAT temperature;
choose between °Celsius (°C) or °Fahrenheit (°F).Default=°C.
Filter: This parameter affect the readings and the gauges
displayed: a low value means that the readings will be more fast and unfiltered (but subject to fluctuations), an high value means that the readings will be more slow and stable (range: 0~999, default=100).
Instrument configuration
VIGILUS - Operating manual
Flybox
23
Rev. 1.0
®
CAT setup menu
CAT (CARBURETOR AIR TEMP.) SETUP MENU:
Thresholds: set the min value (bottom of the bar), the yellow threshold and the max value (top of the bar).
CAT THRESHOLDS SUBMENU:
Type: Select the type of CAT sensor installed: P1K: PT1000 resistive sensors (default). NO: No sensor installed (disable the indication).
Unit: °C / °F: Set the unit of measure for the CAT temperature;
choose between °Celsius (°C) or °Fahrenheit (°F).Default=°C.
Filter: This parameter affect the readings and the gauges
displayed: a low value means that the readings will be more fast and unfiltered (but subject to fluctuations), an high value means that the readings will be more slow and stable (range: 0~999, default=100).
Instrument configuration
Flybox
VIGILUS - Operating manual
24
®
Rev. 1.0
Fuel press. setup menu
FUEL PRESSURE SETUP MENU:
Thresholds: set the min value (bottom of the bar), the low red threshold, the high red threshold and the max value (top of the bar).
FUEL P. THRESHOLDS SUBMENU:
Alarm = ON/OFF:
enable/disable the alarm (alert indication on display) that occurs when the oil pressure is outside of the green zone (either high or low). Default=ON.
FUEL P. ALARMS SUBMENU:
Voice = ON/OFF: enable/disable the audio alert notification on fuel pressure alarms (default=ON).
Instrument configuration
VIGILUS - Operating manual
Flybox
25
Rev. 1.0
®
Fuel press. setup menu
Repeat: Set the number of times that the vocal alarm for the fuel pressure is repeated on the audio output (range:1~5, default=1).
Auto reset = ON/OFF: if set to ON, if a alarm condition is activated but the measurement has returned in the green zone, the Vigilus automatically reset the alarm indication. If set to OFF, the user must manually reset the alarm indication, even if the measurement has returned in the green zone (default=ON).
Out map: you can choose to enable one of the four outputs available on the remote module when the alarm is activated, useful for example to turn on an alarm light on the cockpit. Set to zero to disable this function (default=0).
Sensor = ON/OFF: Set to ON if you have installed the fuel pressure sensor, set to OFF if you have not installed it (the indication will be disabled).Default=ON.
Unit = Bar / Psi: Set the unit of measure for the fuel pressure indication.Default=Bar.
Filter: This parameter affect the readings and the gauges displayed: a low value means that the readings will be more fast and unfiltered (but subject to fluctuations), an high value means that the readings will be more slow and stable (range: 0~999, default=100).
Instrument configuration
Flybox
VIGILUS - Operating manual
26
®
Rev. 1.0
Fuel level setup menu
FUEL LEVEL SETUP MENU:
TANKS SUBMENU:
Number = 1/2/3: Set the number of fuel level sensors installed and connected to the remote module. If you have not connected any fuel level sensors, set to zero. If you set one tank, it will be named “Main tank”.
If you set two tanks, they will be named “Left tank” and “Right tank”. Default=2.
LEFT/MAIN/RIGHT TANK SUBMENU:
Instrument configuration
VIGILUS - Operating manual
Flybox
27
Rev. 1.0
®
Fuel level setup menu
Sensor: Set the fuel level sensor type installed for the selected tank:
RES+” for resistive fuel sensors that increase resistance as you add fuel (default).
RES-” for resistive fuel sensors that decrease resistance
as you add fuel.
If you don't know what type of resistive sensors are
installed please see chapter 1.5.1 “Fuel level sensors checkings”.
CAP” for capacitive fuel sensors.
DRES” for fuel sensors model “DRES”.
Res: Set the amount of fuel below which is activated the alarm of low fuel level for the selected tank (range:1~40 l, default=8l).
FUEL LEVEL ALARMS SUBMENU:
Alarm = ON/OFF: enable/disable the alarm (alert indication on display) for the low fuel on any of the available tanks (default=ON).
Voice = ON/OFF: enable/disable the audio alert notification on low fuel alarms (default=ON).
Repeat: Set the number of times that the vocal alarm for the fuel levels is repeated on the audio output (range:1~5, default=1).
Out map: you can choose to enable one of the four outputs available on the remote module when the alarm is activated, useful for example to turn on an alarm light on the cockpit. Set to zero to disable this function (default=0).
CALIBRATIONS SUBMENU:
Calibration of the fuel tanks (see chapter 1.5 "Fuel level sensors calibration").
Instrument configuration
Flybox
VIGILUS - Operating manual
28
®
Rev. 1.0
Oil press. setup menu
OIL PRESSURE SETUP MENU:
Thresholds: set the min value (bottom of the bar), the low red threshold, the low yellow threshold, the high yellow threshold, the high red threshold and the max value (top of the bar).
OIL P. THRESHOLDS SUBMENU:
Alarm = ON/OFF:
enable/disable the alarm (alert indication on display) that occurs when the oil pressure is too low (below the low yellow threshold) or too high (above the high red threshold). Default=ON,
OIL P. ALARMS SUBMENU:
Voice = ON/OFF: enable/disable the audio alert notification on oil pressure alarms (default=ON).
Repeat: Set the number of times that the vocal alarm for the oil press. is repeated on the audio output (range:1~5, default=1).
Instrument configuration
Loading...
+ 64 hidden pages