Fluke 922 Service Guide

HVAC pressure
applications with
the Fluke 922
For contractors troubleshooting pressure, a lot depends on system peculiarities. Are the installation instructions with the equip­ment? Is the start-up performance report with them? Is the TAB (test and balance) report available? Do you understand the
Application Note
control system? More often than not, it seems, you can only answer yes to the last question. You rely on your experience, knowledge, and tools to check the funda­mentals. And for that much, at least, Fluke can help.
Pressure measurement
Pressure is measured in sev­eral different scales. Pounds per square inch (psi), inches of water column (in. wc), inches of mercury column (in. hg), and millionths of a meter of mercury column (microns) are the most typical in HVAC work.
Bourdon gauges are the tradi­tional choice for higher pressure readings in psi. Finer precision measurements use mercury col­umn scales. And for the most precise measurements—and most low pressure measurements in HVAC—inches water column is the standard.
The following chart compares these common pressure scales and their precision.
Using the Fluke 922 low pressure differential meter in a duct traverse.
F r o m t h e F l u k e D i g i t a l L i b r a r y @ w w w . f l u k e . c o m / l i b r a r y
Atmospheric Pressure 1 psi 1” hg 1” wc
14.696 psia 1 psi 0.019 psi 0.0361 psi
29.921 “ hg 2.036” hg 1” hg 0.0736” hg
406.8” wc 27.68” wc 13.595” wc 1” wc
Of the many different low pressure measuring instruments used over the years, electronic manometers/micromanometers (very low pressure gauges) now offer durability, precision, accuracy, and the significant time saving convenience of fully automatic calculations as well as minimum-maximum-average and memory functions.
How pressure sensing
Total Pressure
Airflow
Airflow
Pitot-Static Tube
Pitot Tube
Static Pressure
Static Pressure
Total Pressure
Airflow
Airflow
Airflow
Airflow
Static Tip
works
The Fluke 922 is a low pres­sure differential meter used in traditional manometer or micro­manometer applications. It has a range of +/-16” wc, resolution of 0.001” wc, and over-pres­sure protection of 10 psi at each high and low pressure port. With a single tube connected to its high or low port, the meter will display positive or negative pressure relative to the ambi­ent pressure at the meter’s open port. For a pressure differential at two remote points, use tubing to connect the higher pressure sensing point to the “+” port and the lower pressure sensing point to the “-” port.
The meter uses a variety of sensing probes and fittings to access the type and location of pressure measurement points. These can be as simple as a straight metal tube for check­ing draft, a “Tee” for tapping into pressure sensing tubing connected to a pressure switch, a Pitot tube for sensing total pressure, a Pitot-Static tube for sensing both total and/or static pressure, or a static pressure tip.
Pressure applications
Draft pressures: Draft pressures are negative relative to ambient pressures at the burner. Measur­ing and controlling draft is a crit­ical step in combustion tests and influences net thermal efficiency of the appliance. Draft is created by vertical vents or powered sidewall vent systems connected to fossil fuel equipment. Like too much air, excessive draft through a heat exchanger increases the velocity of the combustion prod­ucts containing heat, thereby reducing the contact time in the heat exchanger. Follow guide­lines from the manufacturer or standards authority.
Over-fire draft: Power burn­ers typically have specifications related to over-fire draft, which relates to the velocity of com­bustion products through the heat exchanger. This over-fire draft typically is slightly nega­tive (-0.01” wc to -0.02” wc) but, depending on burner type and application, may be slightly positive (0.01” wc to 0.02” wc). Follow guidelines from the man­ufacturer or standards authority.
Draft inducer pressure: Category I fan-assisted gas appli­ances utilize a combustion air inducer to create draft through the appliance and deliver the combustion products to a nega­tive pressure vent. A pressure switch is normally connected to the inlet side of the inducer to ensure a minimum draft has been established before allowing an ignition sequence to begin or continue. For testing, a “Tee” taps into the pressure sensing tubing, to monitor the draft created by the inducer. This is an important value to benchmark at appliance installation. While the pressure switch ratings list cut-in and cut-out (or differential) pressures, without a benchmark you can’t evaluate changes within the appliance or vent over time. Follow guidelines from the manufacturer.
Pressure effects and measurements
Pressure is an integral part of HVAC equipment design, system design, func­tion, application, control and diagnostics. Pressure determines
• cleanliness of airside devices (pressure drop across filters, evaporators, etc.)
• boiler steam temperature
• the saturation temperature of a fluid (boiling temperature of a liquid, the con­densing temperature of a vapor)
• the direction of fluid flow (fluids flow from higher to lower pressures)
• fluid volume flow rate (pressure drop across an orifice)
• whether or not a control or safety switch will make or break (high/low pressure switches, draft proving switches)
• the availability of a fluid to perform work (oxygen/nitrogen tank pressures, gas supply pressures, duct static pressures)
Pressure also
• senses zone device positions, modu lates VFD drives, bypass dampers and valves
• affects solubility of air in water
• contributes to flue gas velocity (stack draft)
-
2 Fluke Corporation HVAC pressure applications with the Fluke 922
Options for sensing probes and fittings when accessing pressure measurement points.
Combustion air blower pres-
sure differential: Category IV
direct vent gas appliances typi­cally use a combustion air blower to ensure airflow through the vent system and appliance before ignition. In most cases, a pres­sure differential switch monitors pressure differential across an orifice. Greater pressure differen­tial indicates more airflow, lower differential indicates less airflow. In this case, two tees are needed to tap into both the high and low pressure sensing tubes con­nected to the pressure differen­tial switch. This is an important value to benchmark during appli­ance installation. Pressure differ­ential depends on the length of connected vent and the applica­tion. If this value is benchmarked when installed, degradation to differential created by heat exchanger, condensate or vent problems is more likely to be detected before a failure occurs. If not benchmarked, there’s no way to evaluate degradation. Follow guidelines from the manufacturer.
Fan effects on combustion
pressures: When checking stack
draft, over-fire draft or combus­tion air inducer/blower pressure differential, an abrupt change in pressure when the blower starts may indicate a compromise between the flue passages and the air passages. Fan pressure can easily be 15 times or more greater than flue passage pres­sure (-0.03” wc draft vs 0.5” ESP), so abruptly changing draft pressures commonly indicate heat exchanger leaks. Gradual changes in draft pressures most likely mean combustion air sup­ply problems or vent problems, especially when accompanied by rising CO and CO2, and fall­ing O2 levels in the combustion products. This can be caused by insufficient make-up air or return leaks, especially in spaces that are considered confined (less than 50 cu ft per 1,000 Btu input) or tight construction. Use the Fluke 922 to compare equipment room pressure to outside pressure before and dur-
the equipment room can often compensate for this engineering design deficiency.
VAV (Variable Air Volume)
control: Pressure sensors are
often used to control VFD (vari­able frequency drive motor) RPM. For instance, a supply duct pres­sure sensor can modulate the RPM of a VFD, based on pressure changes caused by a combina­tion of open and closed zone dampers. Exhaust VFD blowers may modulate RPM based on pressure differential between the occupied space and outdoors. In each of these cases, the VFD var­ies RPM to maintain a relatively consistent pressure or pressure differential. The Fluke 922 can be used to monitor or check the calibration of these sensors.
CAVB (Constant Air Volume
with Bypass) damper control:
Equipment with a constant RPM blower may need to simulate VAV in the supply duct, when zoning is used. The control is similar to a true VAV system. A pressure sensor monitors supply and modulates a bypass damper. The damper relieves pressure from the supply to the return, maintaining a consistent supply static pressure. The Fluke 922 can monitor or check the calibra­tion of these sensors.
Pressure differential defrost
control: Some enthalpy wheels
use a differential pressure sen­sor to determine if a defrost cycle is needed during cold weather. A pressure differential increase (indicating a frost build up) will cycle the outdoor air intake blower off , so it can use the indoor air to defrost the wheel. The Fluke 922 can be used to monitor pressure differential, check the calibration of the sen­sor, or test defrost operation. Some air-to-air heat pumps use a pressure switch to monitor pressure drop across the outdoor coil to determine if frost build-up warrants a defrost cycle. In that circumstance, the Fluke 922 can be used to monitor defrost pres­sure differential, since restricted airflow may indicate a frosted
coil. ing equipment operation. Simply adding a small supply register in
3 Fluke Corporation HVAC pressure applications with the Fluke 922
Airside devices: Pressure drop across airside devices is published by manufacturers and is necessary for design con­siderations, including selecting equipment for satisfactory blower performance and for duct design considerations. Once installed, these same performance tables are useful in estimating airflow and determining end of life for filters. Evaporators, for instance, will have pressure drops with associated cfm’s for a clean dry coil and for a clean wet coil. High performance filters will have pressure drops with associ­ated cfm’s for a clean filter, and pressure drops with associated cfm’s for that same filter when it has reached the end of its life.
The Fluke 922 can be used with a choice of pressure sens­ing devices to check pressure drop across an airside device. If the approach to and from the device is straight, a Pitot tube can be placed on each side of the device and the difference in total pressure readings will result in pressure drop. The tube con­nected to the upstream side Pitot tube is connected to the 922 “+” port, the tube connected to the downstream side Pitot tube is connected to the “-” port, the pressure reading displayed will be the device pressure drop. If the approach is not straight to the device, then use the static sensing side of the two Pitot­Static tubes, or use two static pickups connected to the meter in the same manner.
Confirming pressure drop across the air filter bank.
TSP and ESP: Total Static Pressure (TSP) and External Static Pressure (ESP) are used in con­junction with the manufacturer’s blower performance tables to ensure that the blower perfor­mance is sufficient to overcome airside device pressure drops and the pressure drop associated with duct friction and fittings losses. Manufacturer’s blower performance tables will specify whether the tables are based on TSP or ESP. Once installed, the TSP or ESP is measured to select the appropriate fan RPM that will deliver the desired cfm. It’s important to remember that manufacturer’s blower curves are developed by AMCA test procedures that do not exhibit any system effect. Due to equip­ment installation space and configuration limitations, blower performance is rarely the same as system performance (“as-built” rarely performs exactly “as­designed”). Initial blower set up is by TSP or ESP. Duct traverses that measure actual airflow are required for final blower set up.
TSP is normally provided for commercial and industrial unitary equipment. TSP includes internal and external dynamic pressure losses the equipment fan must overcome. A static pickup is used
on the inlet side of the fan to measure static pressure and the connecting tube is connected to the “-” port on the Fluke 922. A static pickup is placed on the discharge side of the blower and the connecting tube is connected to the “+” port on the Fluke 922. The displayed pressure is the TSP.
ESP is normally provided for residential unitary equipment. ESP is provided for equipment that does not have optional components that can be added within the cabinet or when drill­ing holes to take TSP may violate equipment agency certifications. The blower tables are based on dynamic pressure losses external to the equipment, measured at the return opening and at the supply opening of the unitary equipment. Check the blower table instructions to determine whether or not the filter should be in place when measuring ESP. Place a static pickup in the return duct at the equipment return opening. Connect this tube to the “-” port of the Fluke 922. Place a static pickup in the supply duct at the equipment discharge opening before any external devices such as an external evaporator, if so equipped. Con­nect this tube to the “+” port on
the Fluke 922. The displayed reading will be the ESP.
FSP (Psf) is Fan Static Pressure and is used to independently rate a fan’s ability to overcome all system dynamic pressure losses. A Pitot tube is used on the inlet side of the fan to measure total pressure and the connecting tube is connected to the “-” port on the Fluke 922. A static pickup is placed on the discharge side of the blower and the connecting tube is connected to the “+” port on the Fluke 922. The displayed pressure is the FSP.
Conclusion
Pressure is an often-misunder­stood aspect of HVAC diagnos­tics. Everyone has refrigerant pressure gauges, but to under­stand why “the pressures are wrong,” you need to think about fluid flow and heat transfer too, instead of just adding gas to force the pressures up. And, while everyone probably has a pressure gauge, it’s not always the right kind for accurately reading low pressure systems. Now, with electronic meters like the Fluke 922, you not only get an accurate read, you can check the actual pressure differential instead of replacing pressure dif­ferential switches by default.
Using the Min/Max/Avg feature
The MIN-MAX feature on the Fluke 922, in addition to capturing minimum and maximum readings, will record and average read­ings when a fluctuating pressure, velocity, or airflow is encountered.
Once you’ve captured pressure, velocity, and/or airflow readings and stored them in memory, they can be recalled per selected mode for review and deleted individually, or as a group.
4 Fluke Corporation HVAC pressure applications with the Fluke 922
Applications for Min/Max/Avg include checking:
• static pressure variations
as zone dampers open
and close
• CAVB bypass sizing and
damper operation
The average function is most useful when air tur­bulence causes minor fluc­tuations in readings. The average feature smoothes out the slight variations, making pressure evalua­tions more accurate.
Fluke. Keeping your world
up and running.
Fluke Corporation PO Box 9090, Everett, WA USA 98206
Fluke Europe B.V. PO Box 1186, 5602 BD Eindhoven, The Netherlands
For more information call: In the U.S.A. (800) 443-5853 or Fax (425) 446-5116 In Europe/M-East/Africa +31 (0) 40 2675 200 or Fax +31 (0) 40 2675 222 In Canada (800)-36-FLUKE or Fax (905) 890-6866 From other countries +1 (425) 446-5500 or Fax +1 (425) 446-5116 Web access: http://www.fluke.com
©2006-2007 Fluke Corporation. All rights reserved. Specifications subject to change without notice. Printed in U.S.A. 3/2007 2817879 A-EN-N Rev B
®
Loading...