Flowline LC40, LC41, LC42 User Manual

Warranty, Service & Repair
WARRANTY
Flowline warrants to the original purchaser of its products that such products will be free from defects in material and workmanship under normal use and service for a period which is equal to the shorter of one year from the date of purchase of such products or two years from the date of manufacture of such products.
This warranty covers only those components of the products which are non-moving and not subject to normal wear. Moreover, products which are modified or altered, and electrical cables which are cut to length during installation are not covered by this warranty.
Flowline’s obligation under this warranty is solely and exclusively limited to the repair or replacement, at Flowline’s option, of the prod­ucts (or components thereof) which Flowline’s examination proves to its satisfaction to be defective. FLOWLINE SHALL HAVE NO OBLIGATION FOR CONSEQUENTIAL DAMAGES TO PERSON­AL OR REAL PROPERTY, OR FOR INJURY TO ANYPERSON.
This warranty does not apply to products which have been subject to electrical or chemical damage due to improper use, accident, negli­gence, abuse or misuse. Abuse shall be assumed when indicated by electrical damage to relays, reed switches or other components. The warranty does not apply to products which are damaged during ship­ment back to Flowline’s factory or designated service center or are returned without the original casing on the products. Moreover, this warranty becomes immediately null and void if anyone other than ser­vice personnel authorized by Flowline attempts to repair the defective products.
Products which are thought to be defective must be shipped prepaid and insured to Flowline’s factory or a designated service center (the identity and address of which will be provided upon request) within 30 days of the discovery of the defect. Such defective products must be accompanied by proof of the date of purchase.
Flowline further reserves the right to unilaterally wave this warranty and to dispose of any product returned to Flowline where:
a. There is evidence of a potentially hazardous material present
with product.
b. The product has remained unclaimed at Flowline for longer than
30 days after dutifully requesting disposition of the product.
THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE OF THIS WARRANTY. This warranty and the obligations and liabilities of Flowline under it are exclusive and instead of, and the original purchaser hereby waives, all other remedies, warranties, guarantees or liabilities, express or implied. EXCLUDED FROM THIS WARRANTY IS THE IMPLIED WARRANTY OF FITNESS OF THE PRODUCTS FOR A PARTIC­ULAR PURPOSE OR USE AND THE IMPLIED WARRANTY OF MERCHANT ABILITY OF THE PRODUCTS.
This warranty may not be extended, altered or varied except by a writ­ten instrument signed by a duly-authorized officer of Flowline, Inc.
To register your product with the manufacturer, go to the Flowline website for on-line registration. The website address is as follows:
www.flowline.com
On-line Warranty Registration can be found under Contact Flowline on the Navigation Bar along the side of the home page.
If for some reason your product must be returned for factory service, go to the Flowline website listed above. Online Factory Service can be found under Contact Flowline on the Navigation Bar along the side of the home page. Click on Return Authorization to begin the registration process. You will need the following information at the time of registration:
1. Part Number and full Serial Number from product
2. Name and telephone number of someone who can answer technical questions related to the product and its application.
3. Return Shipping Address
4. Brief Description of the Symptom
5. Brief Description of the Application
Once you have received a Material Return Authorization number, ship the product prepaid in its original packing to:
Flowline Factory Service MRA _____ 10500 Humbolt Street Los Alamitos, CA 90720
To avoid delays in processing your repair, write the MRA on the shipping label. Please include the information about the malfunc­tion with your product. This information enables our service tech­nicians to process your repair order as quickly as possible.
®
Version 5.1A © 2007 FLOWLINE Inc. All rights reserved. Manual # MNC 40100 09/07
Remote Relay Controller LC40, LC41 and LC42 Series Owner’s Manual
Step One
SPECIFICATIONS
Supply voltage: 120 VAC (240 VAC), 50 - 60 Hz. Consumption: 5 Watts max. Sensor inputs: LC42: 1-3 sensors
LC41: 1-2 sensors
LC40: 1 sensor Sensor supply: 13.5 VDC @ 27 mA Relay type: LC42: (1) SPDT, (1) Latched SPDT
LC41: (1) Latched SPDT
LC40: (1) SPDT Relay rating: 250 VAC, 10A, 1/4 hp. Relay mode: Selectable, NO or NC Relay latch: ON or OFF Time delay: 0 to 60 seconds LED indication: Sensor, relay & power status Fail safety: Power fail-safe Temperature range: F: -40° to 158°
C: -40° to 70° Enclosure rating: 35 mm DIN (EN 50 022) Enclosure material: Polypropylene (U.L. 94 VO) Certificate number: LR 79326-3 CE compliance: EN 61326 EMC
EN 61010-1 safety
3.1" (79mm)
35mm
DIN Rail
3.6" (92mm)
3.9" (98mm)
1.8"
(44mm)
2.7"
(68mm)
STANDARD CONTROLLER
RELAY 1 RELAY 2
POWER
INPUT 1 INPUT 2A INPUT 2B
-
+
-
+
INVERT
DELAY
INVERT
DELAY
LATCH
ON OFF
LC4 _ - 1 0 0 1
Configuration
0 - 1 Input, 1 Relay 1 - 2 Inputs, 1 Relay 2 - 3 Inputs, 2 Relays
Remote Relay Controller
STANDARD CONTROLLER
RELAY 1 RELAY 2
POWER
INPUT 1 INPUT 2A INPUT 2B
-
+
-
+
INVERT
DELAY
INVERT
DELAY
LATCH
ON OFF
STANDARD CONTROLLER
RELAY 1
POWER
INPUT 1A INPUT 1B
-
+
INVERT
DELAY
LATCH
ON OFF
STANDARD CONTROLLER
RELAY 1
POWER
INPUT 1
-
+
INVERT
DELAY
L1 L2
GND
(+) (-)
NC
C
NO
(+)
(-)
(+) (-)
NC
C
NO
Latch/Invert Logic
Time Delay
Latch/Invert Logic
Time Delay
Sensor
Input
1A
Power
Supply
Sensor
Input
A*
Sensor
Input
A*
Relay
("Relay 1"
in LC42)
Relay
("Relay 2" in LC42)
Dimensions
Internal Controller Logic
LC42-1001 Faceplate
LC41-1001 Faceplate
LC40-1001 Faceplate
Loading...
+ 4 hidden pages