EchoPod DS14 Ultrasonic Level Switch & Controller
®
Application
The general purpose ultrasonic level switch provides
continuous level detection up to 49.2” (1.25m) with 4
programmable relays for level switch or level control
functions, and is congured via our free WebCal
software. The embedded level controller can lower
cost by replacing external control hardware. This
non-contact liquid level sensor is ideally suited
for corrosive, sticky or dirty liquids, and is broadly
selected for small day tank, skid, IBC, sump and
process tank level applications.
®
Features
• Level detection, switch and control functions up to
49.2” (1.25m)
• Conguration is fast and easy via WebCal software
and USB adapter
• Narrow 2” beam width and short 2” dead band
optimized for small tanks
• Four (4) programmable relays rated @ 1A / 60VA for
switch, pump or valve control and fail-safety
• 1 pump or valve with 3 alarms
• 2 pumps (lead-lag) with 2 alarms
• 2 pumps (duplexing) with 2 alarms
• 4 independent switch point alarms
• PVDF transducer and 6P polycarbonate enclosure for
corrosive liquids
• Automatic temperature compensation for accurate
measurement
Success
Metal parts are often
painted in dip tanks
to achieve a clean,
uniform coating. In
this process, sus-
pended parts are
briey submerged,
and then removed
to rack dry in temperature and humidity controlled
rooms. Dip tanks are generally 2’ to 4’ deep with level
and mixer automation. Here an EchoPod multi-func-
tion level sensor controls the ll valve on each tank
with a high and low level alarm. Additionally, the two-
wire, 4-20 mA level measurement signal is monitored
by the PLC. An optic level switch is also deployed as
a redundant high level alarm.
Compatible Products
PodView®
Level Indicator
LI40
© 2018 Flowline Inc. • 10500 Humbolt Street Los Alamitos, CA 90720 • 562.598.3015 • www.owline.com • DS300220 REV C
EchoPod DS14 Ultrasonic Level Switch & Controller
Ordering Notes
1) EchoPod can not be configured
without the Fob USB interface tool
(LI99-1001) and Web Cal. One Fob
will configure all EchoPods.
2) WebCal is a free download from our
website at www.flowline.com
(Windows® XP Compatible, USB 2.0).
®
®
®
Specications
Range: 49.2” (1.25m)
Accuracy: 0.125” (3mm)
Resolution: 0.019” (0.5mm)
Dead band: 2” (5cm)
Beam width: 2” (5cm)
Conguration: WebCal® PC
Windows® USB 2.0
Memory: Non-volatile
Supply voltage: 12-24 VAC / VDC
Consumption: 0.5W
Contact type: (4) SPST relays, 1A
Contact fail-safe: Power loss: Hold last
Power on: Open, close
or hold last
Hysteresis: Selectable
Process temp.: F: 20° to 140°
C: -7° to 60°
Temp. comp.: Automatic
Ambient temp.: F: -31° to 140°
C: -35° to 60°
Pressure: MWP = 30 PSI (2 bar)
Enclosure rating: Type 6P, encapsulated,
corrosion resistant &
submersible
Encl. material: Polycarbonate
Strain relief mat: Santoprene
Trans. material: PVDF
Cable jacket mat: Polyurethane
Cable type: 9-conductor, shielded
Cable length: 48” (1.2m)
Process mount: 1” NPT (1” G)
Mount gasket: Viton®
Classication: General purpose
Compliance: CE, RoHS
Approvals: cFMus
Dimensions
(1.2 m)
2.00"
(51 mm)
Blk
Wht
Gry
Blu
Org
Yel
Pur
Brn
- Return
- TX (Out)
- RX (In)
- Rly 1
- Rly 2
- Rly 3
- Rly 4
- Rly Com
Conguration
LI99-1001
The level sensor is congurable via
our free WebCal PC software and
Fob USB adapter. The sensors are
offered with and without Fobs. Fobs
are universal and can be used to
congure any WebCal compatible
product.
2.70" (69 mm)
.89"
1" NPT
(1" G)
Download your free copy of WebCal
in English or Chinese at
www.owline.com/webcal.php.
Fittings
For optimum performance, install the level sensor using the below
recommended or direct equivalent ttings.
P/N Description
LM52-1400 2” NPT x 1” NPT (Sch. 40)
LM52-1800 2” NPT x 1” NPT (Sch. 80)
LM52-1410 2” Socket x 1” NPT (Sch. 40)
LM52-1810 2” Socket x 1” NPT (Sch. 80)
LM52-1850 1” NPT Flange - 150# (Sch. 80)
LM50-1001-1 1” NPT Bracket, Polypropylene
Ordering
Process mount (1)
0 NPT (US)
1 G (Metric)
Fob USB interface (2)
0 Without Fob
1 With Fob
© 2018 Flowline Inc. • 10500 Humbolt Street Los Alamitos, CA 90720 • 562.598.3015 • www.owline.com • DS300220 REV C
DS14-
Notes
1) Install the level sensor using Flowline
installation ttings or equivalents.
2) The level sensor is congured via our WebCal
software and one LI99-1001 Fob USB adapter.
The level sensor is offered with and without
a Fob. Fobs are universal and can be
used to congure any WebCal compatible
product. WebCal is a free download from our
website at www.owline.com/webcal.php.