Commander LI90 Multi-Tank Level Controller
™
Application
The general purpose level controller displays engineering units with four
4-20 mA continuous level sensor inputs and 6 programmable relays.
Select from one of three run congurations:
Relays can be congured on a single set point (high level alarm or low
level alarm) or latched on two set points for automatic ll or empty pump or
valve control with selectable time delay. The graphic LCD display indicates
span and relay status for each input channel. An optional MicroSD card
enables data-logging storage and retrieval.
Multi-tank with 4 level sensor inputs and 4 relays1)
Pump control with 1 level sensor input and 6 relays for lift 2)
stations in simplex (one pump) or duplex (two pumps) level
control modes
Differential level with 2 level sensor inputs and 4 relays for 3)
municipal screen or rake control
®
Features
Multi-tank controller with three run mode congurations •
Easy conguration via the push button display module •
Graphic LCD display indicates channel span and relay •
status
DIN enclosure with NEMA 4X faceplate • and shallow case
Easy data logging and retrieval via optional MicroSD card •
Simulation mode for conguration testing and •
troubleshooting
Compatible Products
EchoSonic® II
Ultrasonic Level
Transmitter
EchoPod
Ultrasonic Level
Transmitter
®
EchoSpan
Ultrasonic Level
Transmitter
®
EchoTouch
Ultrasonic Level
Transmitter
Key Benets
Get PLC performance in a simple to use •
controller
Choose multi-tank, differential or pump •
controller modes of operation
Simple HMI makes conguration quick and •
easy
®
FloaTek™
Float Level
Transmitter
DeltaSpan
Pressure Level
Transmitter
™
LU28 DL14 LU83 LU20 LV55 LD32
© 2010 Flowline Inc. • 10500 Humbolt Street Los Alamitos, CA 90720 • 562.598.3015 • www.owline.com • DS301036 REV A

J1
(I1)
0V A4 A3 A2 A1 0V H1 I8 I7 I6 I5 I4 I3 I2 I1
MJ2
MJ1
2.264"
(57.5 mm)
F6
6
MNO
F7
7
PRS
F8
8
TUV
F9
9
WXY
F10
0
F1
1
QZ
F2
2
ABC
F3
3
DEF
F4
4
GHI
F5
5
JKL
ESC
ENTER
+/-
.
3.780" (96 mm)
3.780"
(96 mm)
35mm
DIN Rail
Commander LI90 Multi-Tank Level Controller
Ordering Notes
1) Optional MicroSD cards can be purchased separately
from electronic retailers.
2) For external loop power, order the LC95-1001
(120-240 VAC) power supply (24 VDC @ 0.6A).
Commander Advanced Controller
LI90 Series
LI90- 001
Commander
Sensor inputs / outputs (1) (2)
1 4 inputs / 6 relays
2 2 inputs / 2 repeaters
™
®
Specications
Display type: LCD, graphic
Display pixels: 128 x 64
Display units: Engineering
Display output: 0 to 999999
LCD indication: Relay status
Conguration: Push button
Backlight: Yes
Memory: Non-volatile
Opt. memory: MicroSD card (up to 1 GB)
Linearization: Tank shapes
Sensor inputs: -1001: (4) 4-20 mA
-2001: (2) 4-20 mA
Supply voltage: 10-30 VDC
Contact type: -1001: 6 SPST relays
-2001: No relays
Dimensions
Accessories
For enhanced exibility and performance, use the below recommended
accessories.
Consumption: 130 @ 24 VDC
Contact rating: 3A @ 30 VDC or 250 VAC
resistance load (-1001 only)
Repeater output: (2) 4-20 mA, 24 VDC
(-2001 only)
Ambient temp.: F: 32° to 122°
C: 0° to 50°
Weight: 12.5 oz (0.354 kg)
Enclosure type: 1/4 DIN, panel mount
with 35mm DIN rail
Enclosure rating: NEMA 4X (IP65) faceplate
Enclosure mat.: Polycarbonate
Classication: General purpose
Compliance: CE
Approvals: cULus
Ordering
© 2010 Flowline Inc. • 10500 Humbolt Street Los Alamitos, CA 90720 • 562.598.3015 • www.owline.com • DS301036 REV A
P/N Description
AC-DC Sensor & Indicator Power Supply
LC95-1001 100-240 VAC, 24 VDC @ 0.6A,
35mm Rail
Expansion Cards
Optional MicroSD cards are available from
electronic retailers. Expandable up to 1 GB.
Notes
Optional MicroSD cards are available from 1)
electronic retailers.
For external loop power, order the LC95-1001 2)
(120-240 VAC) power supply (24 VDC @ 0.60A).