Flowline Commander Operating Manual

®
Commander LI90 Multi-Tank Level Controller
Application
The general purpose level controller displays engineering units with four 4-20 mA continuous level sensor inputs and 6 programmable relays.
Select from one of three run congurations:
Relays can be congured on a single set point (high level alarm or low level alarm) or latched on two set points for automatic ll or empty pump or
valve control with selectable time delay. The graphic LCD display indicates span and relay status for each input channel. An optional MicroSD card enables data-logging storage and retrieval.
Multi-tank with 4 level sensor inputs and 4 relays1) Pump control with 1 level sensor input and 6 relays for lift 2)
stations in simplex (one pump) or duplex (two pumps) level control modes
Differential level with 2 level sensor inputs and 4 relays for 3)
municipal screen or rake control
®
Features
DIN enclosure with NEMA 4X faceplate and shallow case
Easy data logging and retrieval via optional MicroSD card
troubleshooting
Compatible Products
EchoSonic® II
Ultrasonic Level
Transmitter
EchoPod
Ultrasonic Level
Transmitter
®
EchoSpan
Ultrasonic Level
Transmitter
®
EchoTouch
Ultrasonic Level
Transmitter
Key Benets
controller modes of operation
easy
®
FloaTek™
Float Level
Transmitter
DeltaSpan
Pressure Level
Transmitter
LU28 DL14 LU83 LU20 LV55 LD32
© 2010 Flowline Inc. • 10500 Humbolt Street Los Alamitos, CA 90720 • 562.598.3015 • www.owline.com • DS301036 REV A
J1
(I1)
0V A4 A3 A2 A1 0V H1 I8 I7 I6 I5 I4 I3 I2 I1
MJ2
MJ1
2.264"
(57.5 mm)
F6
6
MNO
F7
7
PRS
F8
8
TUV
F9
9
WXY
F10
0
F1
1
QZ
F2
2
ABC
F3
3
DEF
F4
4
GHI
F5
5
JKL
ESC
ENTER
+/-
.
3.780" (96 mm)
3.780"
(96 mm)
35mm
DIN Rail
Commander LI90 Multi-Tank Level Controller
Ordering Notes
1) Optional MicroSD cards can be purchased separately from electronic retailers.
2) For external loop power, order the LC95-1001 (120-240 VAC) power supply (24 VDC @ 0.6A).
Commander Advanced Controller LI90 Series
LI90- 001
Commander
Sensor inputs / outputs (1) (2)
1 4 inputs / 6 relays 2 2 inputs / 2 repeaters
®
Specications
Display type: LCD, graphic
Display pixels: 128 x 64
Display units: Engineering
Display output: 0 to 999999
LCD indication: Relay status
Conguration: Push button
Backlight: Yes
Memory: Non-volatile
Opt. memory: MicroSD card (up to 1 GB)
Linearization: Tank shapes
Sensor inputs: -1001: (4) 4-20 mA
-2001: (2) 4-20 mA
Supply voltage: 10-30 VDC
Contact type: -1001: 6 SPST relays
-2001: No relays
Dimensions
Accessories
For enhanced exibility and performance, use the below recommended
accessories.
Consumption: 130 @ 24 VDC
Contact rating: 3A @ 30 VDC or 250 VAC
resistance load (-1001 only)
Repeater output: (2) 4-20 mA, 24 VDC
(-2001 only)
Ambient temp.: F: 32° to 122°
C: 0° to 50°
Weight: 12.5 oz (0.354 kg)
Enclosure type: 1/4 DIN, panel mount
with 35mm DIN rail
Enclosure rating: NEMA 4X (IP65) faceplate
Enclosure mat.: Polycarbonate
Classication: General purpose
Compliance: CE
Approvals: cULus
Ordering
© 2010 Flowline Inc. • 10500 Humbolt Street Los Alamitos, CA 90720 • 562.598.3015 • www.owline.com • DS301036 REV A
P/N Description
AC-DC Sensor & Indicator Power Supply
LC95-1001 100-240 VAC, 24 VDC @ 0.6A,
35mm Rail
Expansion Cards
Optional MicroSD cards are available from
electronic retailers. Expandable up to 1 GB.
Notes
Optional MicroSD cards are available from 1)
electronic retailers.
For external loop power, order the LC95-1001 2)
(120-240 VAC) power supply (24 VDC @ 0.60A).
Loading...