FlowCon SM 50-250mm Installation And Operation Instruction Manual

Page 1
FlowCon SM 50-250mm
INSTALLATION AND OPERATION INSTRUCTION
FlowCon SM 50-250mm, 2”-10”
DYNAMIC SELF BALANCING
CONTROL VALVE
Install the FlowCon SM valve either in the sup­ply or return pipework for the unit. It is recom­mended that a strainer be installed prior to the valve body to prevent damage or blockage due to debris. INSTALL THE VALVE HOUSING WITH THE
FLOW DIRECTIONAL ARROW POINTING IN THE CORRECT DIRECTION.
The valve body is available for double flange connections, i.e figure 1.
O-rings are supplied with the valve body and are used to seal the connections. Please make sure these are in place in the o-ring grooves in the inlet and
outlet of the valve body, when
installing the housing.
FlowCon SM.6 (200-250mm) contains two o-ring grooves (figure 2). Sealing is done on smallest diameter groove if 200mm flanges are used and on the largest diameter groove if 250mm flanges are used.
O-ring Groove
200mm anges
O-ring Groove
250mm anges
Figure 2
recommended to grease the o-rings with a
It is silicone grease before installation. IMPORTANT: Never use mineral oil or petrol based grease or oil on the o-rings.
Valve bodies are as standard supplied with pressure/temperature fittings (p/t plugs). Before finger mounting the p/t plugs in the body tappings, please seal the threads of the p/t plugs (DO NOT OVER TIGHTEN).
Figure 1
1A95106 - 08/2016
Denmark Dubai USA Singapore www.owcon.com
FlowCon International assumes no responsibility
for mistakes, if any, in any printed material.
Page 2
FlowCon SM 50-250mm
360º
Fitting and orientation of the actuator
To fit the actuator on the valve body, please grease the o-ring on the spindle adaptor and place the spindle adaptor on the valve spindle. Place the actuator on the spindle adaptor and place the three actuator “legs” into the three holes in the mounting bracket. Make sure that the snap ring is clicked onto the mount­ing bracket, so that the snap ring is locked at the top of the mounting bracket, but is able to rotate. Then turn the snap ring counter clockwise (upside view) approximately 1/6 of a turn until its stop points touch the actua-
The bottom side of the actuator
DYNAMIC SELF BALANCING
CONTROL VALVE
tor “legs” and the mounting is locked with a (small) click (please see figure 3 and 4).
To remove the actuator, please reverse the procedure, i.e. turn the snap ring clockwise until the actuator is loosened and lift the ac­tuator up (fig. 5). To ease removal of actuator, make sure that the valve is not fully closed.
Symbols at the bottom side of the actuator also indicate how to lock and unlock the actu­ator with the snap ring.
Spindle adaptor
Snap ring
Figure 3
Figure 6
“Actuator legs”
360º
Snap ring:
Stop points
Figure 5Figure 4
1A95106 - 08/2016
Denmark Dubai USA Singapore www.owcon.com
FlowCon International assumes no responsibility
for mistakes, if any, in any printed material.
Page 3
FlowCon SM 50-250mm
Analog - With feedback
Black
Blue
White
Green
Common 24 VAC/VDC Control Signal Feedback
Analog - With feedback
Digital - 2 position - With feedback
Black
Blue
White
Green
Common 24 VAC/VDC Control Signal Feedback
Analog - With feedback
Supply
24 VAC/VDC
Black
Blue
White
Red
Green
Common 24 VAC/VDC Open if NC, Close if NO Close if NC, Open if NO Feedback
Digital - 2 position - With feedback
Digital - 3 point floating - With feedback
Wiring instructions
Analog
DYNAMIC SELF BALANCING
CONTROL VALVE
Black
Blue
White
Green
Common 24 VAC/VDC Control Signal Feedback
Digital - 2 position
Supply
24 VAC/VDC
Black
Blue
White
Red
Green
Common 24 VAC/VDC Open if NC, Close if NO Close if NC, Open if NO Feedback
Digital - 3 point oating
Black
Blue
Supply
24 VAC/VDC
If feedback signal is not required, leave green wire detached.
Start-Up sequence
When power to the actuator is turned on, the actuator will automatically calibrate:
White
Red
Green
Common 24 VAC/VDC Open if NC, Close if NO Close if NC, Open if NO Feedback
• Valve is calibrating to determine closing point. This calibration can take up to 10 minutes depending on the valve’s position at start-up. During calibration lower part of display will show “CAL”.
• If no control signal is detected, flush is start­ ed if enabled in programming menu (enabled by default), opening valve to 5/6 of fully open. Lower part of display will show “FLUSH” until control signal is detected.
• When control signal is present, actuator will adjust to current control signal and proceed with normal operation.
At first start-up please enter programming menu to adjust actuator settings.
1A95106 - 08/2016
Denmark Dubai USA Singapore www.owcon.com
FlowCon International assumes no responsibility
for mistakes, if any, in any printed material.
Page 4
FlowCon SM 50-250mm
DYNAMIC SELF BALANCING
CONTROL VALVE
Programming Menu
The programming menu is always accesible. To enter the pro­gramming menu, please simultaneously press 6 seconds, until bottom line blinks.
Generally, press
button to go to previous step. To change the value, pls. press
or  keys, for quick scroll through values hold down the button.
Press
and  simultaneously for 6 sec. to exit programming
to accept value and go to next step and press
menu. Actuator will automatically return to operation mode if no action is detected on arrow keys during 1 minute.
All values selected in the programming menu are stored in non-volatile memory.
Step Display Description Values
0 Password.
*
*scrolling top:
ENTER PASS WORD
Disabled by default
Password: 3569266.
Only if Enabled (in step 11).
Change one digit at a time, press
to move between digits.
and
At last digit, press step.
to go to next
and  for
1 Select language.
*
*scrolling top:
SELECT LANGUAG
2 Select valve model onto which the
*
3 Choose unit scale for ow rate.
*
4 Activate Flush mode at start-up.
*
5 Select type of control signal.
*
1A95106 - 08/2016
actuator is installed.
*scrolling top:
SELECT VALVE MODEL
*scrolling top:
SELECT UNIT SCALE
*scrolling top:
SELECT FLUSH MODE
*scrolling top:
SELECT CONTROL SIGNAL
Denmark Dubai USA Singapore www.owcon.com
Default: English. Possibility to choose other languages later on (not currently an option).
Default: SM.0.0 Select from the 10 available valve models. Options: SM.1.1, SM.2.1...
Default: l/sec. Options: l/sec or l/hr or GPM.
Default: Enable. Options: Enable or Disable.
When no control signal (analog) is detected at start up, ush mode is started (5/6 of fully opened). It will be dismissed when control signal is detected.
Default: 2-10VDC. Options: 2-10VDC or 4-20mA or digital. Choose:
• 2-10VDC for VDC
• 4-20mA for mA
• Digital for 2 position or 3 point oating.
FlowCon International assumes no responsibility
for mistakes, if any, in any printed material.
Page 5
FlowCon SM 50-250mm
Step Display Description Values
6 Select minimum control value.
*
*scrolling top:
SET MINIMUM LIMIT
7 Select maximum control value.
*
*scrolling top:
SET MAXIMUM LIMIT
8 Select feedback signal.
*
*scrolling top:
SELECT FEEDBAC SIGNAL
DYNAMIC SELF BALANCING
Volt default: 2. Options: from 0-7. Increment: 0.1. mA default: 4. Options: from 0-14. Increment: 0.2.
NA if Digital (in step 5).
Volt default: 10. Options: from 3-10 and at least 3 VDC greater than the selected minimum limit. Increment: 0.1. mA default: 20. Options: from 6-20 and at least 6 mA greater than the selected minimum limit. Increment: 0.2.
NA if Digital (in step 5).
Default: AU; Automatic match of control signal if analog. Options: 0-10 VDC, 2-10 VDC or 4-20 mA or AU.
If Digital (in step 5) AU is not an option.
CONTROL VALVE
9 Set the designed maximum ow.
*
10 Select direction of rotation.
*
11 Activation of password.
*
12 Select direction of rotation when
*
Accuracy: Greatest of either ±5% of designed max. ow or ±2% of max. valve ow.
*scrolling top:
SELECT MAXIMUM FLOW
*scrolling top:
SELECT ROTAT DIRECT
*scrolling top:
ACTIVAT PASS WORD
Failsafe.
*scrolling top:
SELECT FAIL SAFE DIRECT
Default: Maximum setting. Values depend on valve model and unit scale chosen in step 2 and 3. Stepping increments as per tech note.
Default: Normally Closed (NC). Options: Normally Open (NO) or Normally Closed (NC).
Default: Disable. Options: Enable or Disable. If Enabled password is required to access alarm and programming menu.
Default: Closed. Options: Open or Closed.
Only valid for SM.0.0.0.4 (failsafe model). Failsafe direction open means opening to max. ow chosen in step 9.
Failsafe mode (only SM.0.0.0.4)
If power supply is out of range or lost, failsafe mode will be activated:
1. Approx. 80 sec. delay.
2. Actuator opens/closes valve (according to failsafe direction chosen in programming menu).
3. Actuator shuts off. If power supply is restored during action 1. or 2., failsafe mode is deactivated.
1A95106 - 08/2016
Denmark Dubai USA Singapore www.owcon.com
FlowCon International assumes no responsibility
for mistakes, if any, in any printed material.
Page 6
FlowCon SM 50-250mm
In Operation
Display Description Values
Indicates unit scale system. l/sec or l/min or GPM.
mA or VDC.
DYNAMIC SELF BALANCING
CONTROL VALVE
Indicates battery level. Basic version with no battery (SM.0.0.0.3)
Alarm indicator. Blinking if actuator is still functional (warning).
Information
Current ow rate1. Indicates current ow rate in
l/sec, l/hr or GPM.
Information
Control signal Indicates value of control signal. 0-10 VDC or 0-20 mA or Open/Stop/Close
Feedback signal Indicates value of feedback signal. 0-10 VDC or 0-20 mA.
Valve Indicates valve model. SM.1.1, SM.2.1...
Pressure range Indicates pressure range. 32-320 kPaD, 40-320 kPaD.....
Maximum ow rate Indicates selected maximum
designed ow rate.
Operational direction Indicates direction of rotation. NO or NC.
Failsafe direction Indicates failsafe direction. Open or Closed
Critical Alarm Indicates alarm error code. 01, 03, 05 (without failsafe) or 06.
Failsafe version with battery (SM.0.0.0.4) Battery level low, charging needed. Medium battery level. Battery charged.
Fully on if actuator is not working (critical).
CONTROL SIGNAL 2.0 VDC FEEDBAC SIGNAL 2.0 VDC VALVE SM. 3.1 pressur range 35-400 kpad MAXIMUM FLOW RATE 6.580 L/SEC OPERAT DIRECT NC FAIL SAFE DIRECT CLOSE ERROR CODE 01
Use  to go to next information line and  to go to the previous.
Depends on valve etc. l/sec, l/hr or GPM.
Only valid for SM.0.0.0.4
Only if critical alarm is present.
Note 1: Note that the ow rate displayed on the actuator is a calculated value based upon differential pressure being within control range. If display shows “NA” instead of current ow rate, it indicates that the ow rate is below minimum dened ow rate according
to tech note, or that valve model has not been chosen in programming menu step 2.
1A95106 - 08/2016
Denmark Dubai USA Singapore www.owcon.com
FlowCon International assumes no responsibility
for mistakes, if any, in any printed material.
Page 7
FlowCon SM 50-250mm
DYNAMIC SELF BALANCING
CONTROL VALVE
Alarm Menu
To enter the alarm menu, please simultaneously press  and  for 6 seconds. You can access the alarm menu only if an alarm is present (i.e when icon Press Press
to go to the next alarm display, press  to return to previous step.
and  simultaneously for 6 seconds to exit alarm menu. Actuator will automatically return to operation mode if no action is detected on arrow keys during 1 minute.
Display Description Action
Alarm.
is displayed).
Enter password. If enabled in programming menu step 11
Code
01 Valve/actuator is overtorqued. Operation is stopped. Actuator will retry operation
02 Actuator has reached its torque
03 Critical - over temperature. Critical: Temperature in actuator is at least 70ºC,
04 High temperature. Actuator is still functioning. Temperature in actua-
05 No Failsafe: Power supply not in
06 Control signal not detected. Operation is stopped. Alarm will automatically
07 Battery error. Battery is not properly connected. Alarm will reset
In case of ERRORS or ALARM
If actuator is still functioning (error 02, 04, 05 with failsafe and 07 with failsafe) the ALARM icon Error codes can be found in the alarm menu.
Icon Description Details
FULL ON
BLINKING
FULL ON
BLINKING
FULL ON
BLINKING
FULL ON
BLINKING
limit in the past.
range.
With Failsafe: Power supply not detected / not in range.
Disabled by default. Password: 3569266.
every 4 minutes. If over torque condition disappear, error will convert to error code 02.
Actuator is functioning. To reset the alarm simultaneously press
for 6 seconds.
motor operation is stopped. If temperature is decreasing, operation will resume.
tor is at least 50ºC as limited according to tech note. If temperature is decreasing, operation will resume.
Operation is stopped. Alarm will automatically reset when voltage is back in range.
Failsafe is activated. Alarm will automatically reset when voltage is back in range.
reset when control signal is back in range.
when battery is properly connected.
Only valid for SM.0.0.0.4.
and
will flash.
If actuator is not functioning (error 01, 03, 05 without failsafe and 06) the ALARM icon The error code will be available in the information in the upper part of the display and the alarm menu.
1A95106 - 08/2016
Denmark Dubai USA Singapore www.owcon.com
is turned on.
FlowCon International assumes no responsibility
for mistakes, if any, in any printed material.
Page 8
FlowCon SM 50-250mm
DYNAMIC SELF BALANCING
CONTROL VALVE
Auto-stroke - re-calibration
In case the valve does not operate as expect­ed, start the auto-stroke sequence to re-cali­brate the closing point of the valve and to make sure that the actuator is able to open the
and
valve fully. Press buttons
simultane-
ously for 6 seconds to start the auto-stroke.
Auto-stroke sequence
(display shows: “AUTO STROKE CYCLES”):
1. Valve is closed to determine closing point.
2. Valve is opened fully (independent of max. flow chosen).
3. System returns to normal operation.
If actuator is not able to open valve fully, an error will be displayed. An auto-stroke cannot be cancelled.
Manual override
Manual override is used to temporarily set the position of the valve regardless of the settings and control signal for the actuator.
1. Turn off power to the actuator.
2. Remove actuator from valve as described.
3. Turn spindle to the relevant position (Clock­ wise to close valve, counter clockwise to open valve). Be sure not to use more than 10 Nm torque. Please protect actuator from water while not on valve.
4. Re-mount actuator on valve as described.
5. Turn on power to the actuator when normal operation is needed.
General
Water must always be suitable treated, clean and free of debris. It is recommended that a strainer be installed prior to the valve body to prevent damage or blockage due to debris. Ensure that the valve is not in the fully closed position when filling the system with water. Further, it is recommended not to exceed maximum differential pressure control range.
Warranty obligation
Failure to abide by all recommendations as per this installation and operation instruction will void warranty.
Do not remove cover from actuator. Opening cover will void warranty.
When manually operating the valve (actuator disconnected) do not use more than 10 Nm torgue. Using more than 10 Nm torgue will void warranty.
For latest updates please see www.flowcon.com
1A95106 - 08/2016
Denmark Dubai USA Singapore www.owcon.com
FlowCon International assumes no responsibility
for mistakes, if any, in any printed material.