Flomotion Systems be6000 series Installation And Operation Manual

Page 1
BE6000 Series
Ultrasonic Flow Meter
Page 2
BE6000 Ultrasonic Flow Meter O&M Manual
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 3
BE6000 Ultrasonic Flow Meter O&M Manual
Installation and Operation Manual
BE6000 Series
Ultrasonic Transit-Time Flow Meter
July 2007
Flomotion Systems, Inc.
586 N. French Rd.
Amherst, NY 14228
U.S.A. 716-691-3941 800-909-3569
www.FlomotionSystems.com
Flomotion Systems, Inc. ~ FlomotionSystems.com
3
Page 4
BE6000 Ultrasonic Flow Meter O&M Manual
User Manual
BE6000 Ultrasonic Flow Meter
Contents
I. Introduction __________________________________________________________________6
1. Preface ___________________________________________________________________________6
2. Characteristics_____________________________________________________________________6
3. Operation Principle_________________________________________________________________7
4. Typical Applications ________________________________________________________________8
5. Packing List _______________________________________________________________________8
6. Technical Specifications _____________________________________________________________9
7. Power Connection __________________________________________________________________9
8. Cables___________________________________________________________________________10
(1) Power Cable___________________________________________________________________________ 10 (2) Output Signal Cable_____________________________________________________________________ 10 (3) Cable between transducer and pr ocessor _____________________________________________________ 10
9. Wire Connections _________________________________________________________________11
(1) Wall Mount ___________________________________________________________________________ 11
II. Installation and Operation _____________________________________________________12
1. Selecting the Measurement Point_____________________________________________________12
2. Setting the Parameters _____________________________________________________________12
3. Rapid Setup Procedure_____________________________________________________________13
4. How to Go into a Specific Window ___________________________________________________13
5. Transducer Mounting Distance ______________________________________________________13
6. Transducer Mounting Methods______________________________________________________14
(1) Signal Strength & Quality (M90)___________________________________________________________ 15 (2) Total Travel Time and Time Difference (M93) ________________________________________________ 15 (3) Time Rate (TOM/TOS* 100, M91) _________________________________________________________ 15
6. Selecting a Location for Transducer Mounting _________________________________________16
Preparing the Pipe Surface___________________________________________________________________ 16
III. Display Windows ____________________________________________________________17
1. Summary ________________________________________________________________________17
2. Descriptions ______________________________________________________________________18
(1) Flow/Totalizer Displays__________________________________________________________________ 18 (2) Initial Setup ___________________________________________________________________________ 20
III. Trouble Shooting____________________________________________________________39
Power-On self-test information, Causes and Solutions _____________________________________39 Error Code Causes and Solutions ______________________________________________________40
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 5
BE6000 Ultrasonic Flow Meter O&M Manual
Appendix 1. RS-232 Command Protocol_____________________________________________41 Appendix 2. Sound Velocity and Viscosity of Liquids __________________________________42 Appendix 3. Sound Velocity for Various Common Materials ___________________________43
Pipe Material _______________________________________________________________________43 Liner Material ______________________________________________________________________43
Appendix 4. Sound Velocity in Water (1 ATM) at different temperatures___________________44 Appendix 5. Pipe Dimensions and Weights___________________________________________45
Flomotion Systems, Inc. ~ FlomotionSystems.com
5
Page 6
BE6000 Ultrasonic Flow Meter O&M Manual
I. Introduction
1. Preface
Welcome to BE6000 series ultrasonic flow meter. Please read this instruction manual thoroughly before installation and operation.
BE6000 ultrasonic flow meter is a time-difference type ultrasonic flow meter, whose transducers are mounted clamped on pipe. It measures clean, well-distributed flows of liquids those content of suspended particles is not very high.
The system is configured as below;
Sensor Set: A pair of ultrasonic transducers mounted on the external surface on a pipe.
Processor: The processor and the transducers are connected by two double shield high frequency
cables. The processor can be monitored and controlled remotely through a PC connected via Internet. The following illustrates the configuration of the processor unit and the transducer sets;
2. Characteristics
BE6000 ultrasonic flow meter is based on single-board technology featuring high accuracy, reliability and repeatability. The merits it provides above else are;
Transducers are not intrusive. Therefore there’s no pressure drop. They are mounted on the outside wall of the pipe.
Advanced intelligent instrumentation, processing and printing (logging) according to user requirements. Almost all common flow units are used. It uses normal power, built-in battery or DC power, etc.
It uses the most advanced direct time measurement method with the resolution of 0.2 ns. Coupled with the advanced data processing functions, it provides high level of linearity.
Various output options available including analog current output, frequency output, RS-232 serial output, relay output, etc. The output options can be set by a menu or via a PC connected to the processor through a RS-232C.
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 7
BE6000 Ultrasonic Flow Meter O&M Manual
3. Operation Principle
This time-of-travel (transit-time) meter has a pair of transducers mounted on each side of the pipe. The configuration is such that the sound waves traveling between the devices are at a 45- degree angle to the direction of liquid flow. The speed of the sound signal traveling between the transducers increases or decreases depending upon the direction of transmission and the velocity of the liquid being measured. A time-differential relationship proportional to the flow can be obtained by transmitting the signal alternately in both directions.
Where
M- travel times D- inner diameter of the pipe θ transmission angle
0- sound velocity in a static fluid
C
UP- upstream travel time (reverse flow
T
As per equation (1) and (2) above, the velocity of flow is calculated as below;
direction)
DOWN- downstream travel
T time(flow direction) ΔT- difference of travel time between downstream and upstream
The ultrasonic transit-time method is suitable for measuring single-phase, pure liquids without entrained air bubbles. In industrial sites, the liquids may contain a certain level of impurities and flow conditions are often not very uniform, thereby negatively affecting the performance of the ultrasonic flow meters. But our BE6000 ultrasonic flow meter adopts the most advanced direct time measuring method that considers the influence of temperature and crude inside pipe situation in order to increase the accuracy and the reliability of the result. With the use of the zero setting function, the meter renders 0.5% accuracy.
Flomotion Systems, Inc. ~ FlomotionSystems.com
7
Page 8
BE6000 Ultrasonic Flow Meter O&M Manual
4. Typical Applications
Water supply, drainage, water purification facility
Oil field and petrochemical plants
Power plants(thermal and hydro power plants)
Steel factory and mining industries
Food and beverage plants
Paper mills
HVAC
Etc.
5. Packing List
Items included are as follows;
1 processor
1 set of transducers(2 ea)
1 transducer mounting chain
1 couplant
1 instruction manual
Test certificate
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 9
BE6000 Ultrasonic Flow Meter O&M Manual
6. Technical Specifications
Classification Performance/Parameter
Pipe
Fluid
Flow Velocity -53 to +53° F (-16 to +16 m/s) Transducer
Cable Length 16 ft (5m) Std. (longer lengths available) Flow Computer
Operating Condition
Performance
Materials Steel, Stainless Steel, Cast Iron, Plastics, Concrete,
etc.
Inner Diameter 0.5 to 236 in. (15 ~ 6000mm)
Straight Pipe Section Requirement
Types Clean, sonically conductive
Turbidity
Temperature -4° to 140° F (-20° to 60°)
Pipe Size Range S: 0.5 to 4 in. (15 ~ 100mm)
Mounting Method ‘V’ method: Suitable for pipe sizes 16 in. (400mm) or
Display Alphanumeric 2 x 20 digit backlight LCD Keyboard 4 x 4 keypad Mounting Wall Mount or optional Panel Mount Output 4-20mA or 0-20mA analog output, frequency output
Power Wall Mount: 120VAC & 24VDC
Dimension Wall Mount: 9.9 x 3.6 x 3.2 in. (251 x 92 x 80mm) Weight 7 lbs. (3kg) Wall Mount Temperature Flow Computer: -4 to 158º F (-20 to 70º C)
Humidity Flow Computer: 85% RH at 104º F (40º C)
Accuracy ±1.0% of reading above ±1 fps Repeatability ±0.2% at 1 to 53 fps (0.3 ~ 16m/s) Linearity 0.5%
10D upstream, 5D downstream (required length may be longer depending on site conditions)
Smaller than 10,000ppm(mg/l) with a low level of air
bubble content
M: 2 to 40 in. (50 ~ 1000mm) L: 12 to 236 in. (300 ~ 6000mm)
smaller ‘Z’ method: Suitable for pipe sizes 10 in. (250mm) or larger
(12-9999Hz), relay, serial output.
Panel Type : 120VAC
Transducer: -4 to 140º F (-20 to 60º C)
Transducer: 98% RH at 104º F (40º C) (Able to operate immersed in water depth smaller than 3m)
7. Power Connection
Attention: Meter can be badly damaged if a different power from what was specified is supplied. Careful
attention is advised.
The meter can use standard 120VAC or 24VDC power supply. By default, the meter is provided with the standard 120VAC power type. Therefore, should the user want 24VDC model, such should be indicated when ordering.
Flomotion Systems, Inc. ~ FlomotionSystems.com
9
Page 10
BE6000 Ultrasonic Flow Meter O&M Manual
8. Cables
Cables should never be spliced or cut. Please use the following cables;
(1) Power Cable
3-core or 2-core rubber insulated cable (outer diameter 11mm)
(2) Output Signal Cable
2-core or many-core rubber insulated cable (11mm)
(3) Cable between transducer and processor
10
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 11
9. Wire Connections
(1) Wall Mount
BE6000 Ultrasonic Flow Meter O&M Manual
Flomotion Systems, Inc. ~ FlomotionSystems.com
11
Page 12
BE6000 Ultrasonic Flow Meter O&M Manual
II. Installation and Operation
The clamp-on type ultrasonic flow meter allows for the simplest and the easiest installation of all types of flow meters, though careful attention in selecting the measurement point, inputting pipe parameters, fixing the transducers onto pipe, etc. in order to ensure accurate and reliable measurement of flow is needed. In this chapter, you’ll be introduced to how to select the measurement point, input parameters, select mounting method, etc.
1. Selecting the Measurement Point
Selecting the right measurement point is the most important factor for ensuring the accuracy and should be done according to the following steps;
(1) Make sure the pipe to be measured is full.
(2) Select a location where it allows for straight pipe run of 10D upstream and 5D downstream. In case there’s a pump or a bending section in the upstream, increase the upstream run to 30D in order to allow the flow to fully develop into stable flow profile.
(3) Ensure the temperature at the measuring point is within the specified range.
(4) Avoid sections where the inner wall of the pipe is scaled or rusted that can negatively affect the performance of the meter.
2. Setting the Parameters
In order to get the correct transducer mounting distance (the distance between the front edges of both transducers), verify and set the following parameters;
(1) Pipe outer diameter (2) Pipe inner diameter (3) Pipe material (4) Liner (5) Fluid type (6) Transducer type (7) Transducer mounting method type
When the above parameters are properly set, the correct transducer mounting distance is calculated and displayed in menu M25. Then the machine searches for proper amplifier gain. After S1, S2, S3 and S4 steps, the machine enters into the normal operation state.
12
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 13
3. Rapid Setup Procedure
BE6000 Ultrasonic Flow Meter O&M Manual
(1) Press [MENU] [1] [1] to enter M11 window, input pipe outer diameter, press [ENT]. (2) Press [] to enter M12 window, input wall thickness and press [ENT]. (3) Press [▼] [▼] to enter M14 window and [ENT] [] [] to select pipe material, and press [ENT]. (4) Press [] to enter M16 window and [ENT] [▼] [▲] to select liner material, and press [ENT]. (5) Press [] to enter M20 window and [ENT] [▼] [▲] to select fluid type, and press [ENT]. (6) Press [] to enter M23 window and [ENT] [▼] [▲] to select the transducer type, and press [ENT]. (7) Press [] to enter M24 window and [ENT] [▼] [▲] to select the transducer mounting method, and
press [ENT].
(8) Press [] to enter M25 window, which will display the correct transducer mounting distance(the
distance between the front edges of the transducers).
(9) Press [MENU] [0] [1] [ENT], the flow rate and the velocity of the flow will be displayed upon
completion of the gain adjusting process.
4. How to Go into a Specific Window
The user can enter into specific windows using the [MENU] key followed by a 2-digit code. So, for example, in order to go to window M13, which is the window for inputting the inner diameter of the pipe, press [MENU] [1] [3] [ENT].
5. Transducer Mounting Distance
The distance is measured between the front edges of both transducers. After all the parameters have been set, the distance is shown in M25.
Flomotion Systems, Inc. ~ FlomotionSystems.com
13
Page 14
BE6000 Ultrasonic Flow Meter O&M Manual
6. Transducer Mounting Methods
Clamp-on Sensors
There are 2 mounting methods, ‘V’ and ‘Z’. Usually V method is used as standard because it provides longer signal path and therefore more accurate measurement of flow velocity. It is recommended for pipes sizes between 25~6000mm. Special attention should be given when mounting transducers to ensure that sensors are aligned in direct line and along the center of the pipe and the transducer mounting line should be aligned.
Z method is recommended when the flow condition is bad because of scale built up inside the pipe, entrained air bubbles, too thick liner, etc. which can induce a lot of noise into signal. Using this method, the signal is dispersed in a straight path reducing the possibility of noise induction.
The user can verify whether the mounting is done correctly or not by checking the received signal strength, total travel time, time difference and rate of travel time, which are described below;
14
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 15
BE6000 Ultrasonic Flow Meter O&M Manual
(1) Signal Strength & Quality (M90)
The signal strength is indicated by a number between 0.00 ~ 9.99. 0.00 means no signal received and 99.9 means the signal strength is at the maximum. It should be larger than 60.0 for normal operation. The signal quality Q is indicated by a number between 0.00 ~ 9.99. 0.00 indicates that the signal is at its lowest level and 9.99 the highest. It should be at least 60.00 for normal operation.
(2) Total Travel Time and Time Difference (M93)
The measurement is taken based on the total travel time and the time difference. They are also indicative of the condition of the installation of the transducers. Under normal condition, the time difference should be smaller than 10%. If the pipe size is very small or the flow velocity is very low, the wave may be a little bigger. When the wave is too big, so are the flow and the velocity. This is said to be of bad signal quality, which may result from bad pipe condition, incorrect installation of the transducers or incorrect parameters set.
(3) Time Rate (TOM/TOS* 100, M91)
This is used to confirm whether the transducers are located with the correct interval. This should indicate 100 ±3%.
Flomotion Systems, Inc. ~ FlomotionSystems.com
15
Page 16
BE6000 Ultrasonic Flow Meter O&M Manual
6. Selecting a Location for Transducer Mounting
1. Locate the transducers downstream from the center of the longest available straight run. A location ten pipe diameters or greater downstream from the nearest bend will provide the best flow profile conditions.
2. Do not install the transducers downstream from a throttling valve, a mixing tank, the discharge of a positive displacement pump or any other equipment that could possibly aerate the liquid. The best location will be as free as possible from flow disturbances, vibration, sources of heat, noise, or radiated energy.
3. Avoid mounting the transducers on a section of pipe with any external scale. Remove all scale, rust, loose paint etc., from the location. Do not mount the transducers on a surface aberration (e.g., pipe seam, etc.).
4. Do not mount transducers from different ultrasonic flow meters on the same pipe. Also, do not run the transducer cables in common bundles with cables from communication equipment, other electronic systems or any type of ultrasonic equipment. You can run these cables through a common conduit ONLY if they originate at the same flowmeter.
5. Never mount transducers under water, unless you order submersible units and you install them in accordance with factory instructions.
6. Avoid mounting transducers on the top or bottom of a pipe. The ideal placement is either the nine o’clock or three o’clock position for Reflect Mode, or one transducer at nine o’clock and the other at three o’clock for Direct Mode. Mounting on a vertical pipe is recommended only if flow is in the upward direction.
Preparing the Pipe Surface
1. Pick a mounting location with the longest straight run. You must have easy access to at least one side of your pipe. The mounting location must remain full, even at zero flow.
2. Decide on your mounting mode (Z or V). Use V Mode whenever possible.
3. After receiving the spacing dimensions from the Installation Menu, prepare the pipe surface. Degrease the surface, if necessary, and remove any grit, corrosion, rust, loose paint, etc. Use abrasive material provided to create a clean contact surface for the transducers.
4. Refer to the next sections for illustrated instructions on how to locate each area to be cleaned and how to use each mounting option.
Please note that the instructions show vertical mounting for clarity purposes only. Do not install transducers on the top of a pipe. NOTE: In the following paragraphs, references to the 9 o’clock
position indicate the section of the pipe that is closest to you.
1. Install transducers in accordance with instructions in the manual and the appropriate installation drawings.
2. Apply a 1/4” wide bead of couplant edge-to-edge down the center of the emitting surface of the transducers.
3. Follow the instructions in the manual for installing the transducers.
4. For permanent applications allow the RTV type couplant to cure. It cures at room temperature upon exposure to moisture in the air. During the cure, it releases acetic acid (a vinegar like odor). It reaches full cure within 24 hours.
TRANSDUCERS
Apply 1/4” bead of couplant
to emitting surface.
16
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 17
BE6000 Ultrasonic Flow Meter O&M Manual
III. Display Windows
1. Summary
All display windows of BE6000 and their descriptions will be discussed in this chapter. The user can enter display windows following the instruction given in Chapter II, i.e. [MENU] [#] [#] to realize the communication between the user and the machine.
The followings are the display menus, which are defined by 2 numbers on the left column
Flow Totalizer/Display
Menu
00 Flow Rate/Net Totalizer 01 Flow Rate/Velocity 02 Flow Rate/POS Totalizer 03 Flow Rate/NEG Totalizer 04 Date Time/Flow Rate 05 Energy Flow Rate/Totalizer 06 AI1, AI2 (Analog Input) 07 AI3, AI4 08 System Error Code 09 Net Flow Today
Initial Setup Menu
10 Pipe Outer Perimeter 11 Pipe Outer Diameter 12 Pipe Wall Thickness 13 Pipe Inner Diameter 14 Pipe Material 15 Pipe Sound Velocity 16 Liner Material 17 Liner Sound Velocity 18 Liner Thickness 19 Inside ABS Thickness 20 Fluid Type 21 Fluid Sound Velocity 22 Fluid Viscosity 23 Transducer Type 24 Transducer Mounting 25 Transducer Spacing 26 Parameter Setups 27 Current Section Area 28 Holding for Poor Signal 29 Empty Pipe Setup
Flow Unit Setup
30 Measurement Unit in 31 Flow Rate Unit 32 Totalizer Unit 33 Totalizer Multiplier 34 NET Totalizer
35 POS Totalizer 36 NEG Totalizer 37 Totalizer Reset 38 Manual Totalizer 39 Language Selection
Option Setup Menu
40 Damping 41 Low Flow Cutoff 42 Set Zero 43 Reset Zero 44 Manual Zero Point 45 Scale Factor 46 Network IDN 47 System Lock 48 Keypad Lock Code
Output/Input Setup Menu
50 Logger Option 51 Logger Time Setups 52 Print only to RS-232C 53 Analog Input AI5 54 AI5 Value Range 55 CL Mode Select 56 CL 4mA Output Value 57 CL 20mA Output Value 58 CL Checkup 59 CL Current Output 60 Date and Time 61 Software Version and ESN 62 RS-232C Setup 63 AI1 Value Range 64 AI2 Value Range 65 AI3 Value Range 66 AI4 Value Range 67 FO Frequency Range 68 Low FO Flow Rate 69 High FO Flow Rate 70 LCD Backlight Option 71 LCD Contrast 72 Working Timer
73 Alarm #1 Low Value 74 Alarm #1 High Value 75 Alarm #2 Low Value 76 Alarm #2 High Value 77 Buzzer Setup 78 OCT Output Setup 79 Relay Output Setup
Energy Meter Menu
80 Flow Batch Control Source 81 Flow Batch Controller 82 Date Totalizer 83 Automatic Amending 84 Energy Unit Select 85 Temperature Select 86 Specific Heat 87 Energy Totalizer ON/OFF 88 Energy Multiplier 89 Reset Energy Totalizer
Diagnostics Menu
90 Signal Strength and Quality 91 TOM/TOS*100 92 Fluid Sound Velocity 93 Total Time and Delta Time 94 Reynolds No. and Factor
Others
+ 0 Power ON/OFF Time + 1 Total Working Time + 2 Last Power Time + 3 Last Flow Rate + 4 ON/OFF Times + 5 Calculator + 6 Velocity Changing + 7 Protocol Select + 8 Receive Shape + 9
Flomotion Systems, Inc. ~ FlomotionSystems.com
17
Page 18
BE6000 Ultrasonic Flow Meter O&M Manual
2. Descriptions
(1) Flow/Totalizer Displays
Flow Rate/Net Totalizer(M00)
Flow -10.023 m3/h *R NET 1342 x 0.01 m
3
This window is only for display. The selection of the unit is made in M31 and M32 windows. If the NET totalizer is unselected, the value shown in the window is replaced by the totalizer last time. Add the negative totalizer to the positive totalizer to get the net totalizer.
Flow Rate/Flow Velocity(M01)
Flow -10.023 m3/h *R
VEL -0.3215 m/s
This window is only for display. The selection of the unit is made in M31 and M32 windows.
Flow Rate/Positive Totalizer(M02)
Flow -10.023 m3/h *R
POS +1342 x 0.01 m
3
This window is only for display. The selection of the unit is made in M31. If the POS totalizer is unselected, the value shown in the window is replaced by the POS totalizer last time.
Flow Rate/Positive Totalizer(M03)
Flow -10.023 m3/h *R NEG -1342 x 0.01 m
3
This window is only for display. The selection of the unit is made in M31. If the POS totalizer is unselected (M36), the value shown in the window is replaced by the NEG totalizer last time.
Date and Time/Flow Rate(M04)
05-10-20 10:10 *R
Flow 10.023 m
This window is for displaying current date, time and flow rate. The time and date can be entered in M60.
18
3/h
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 19
BE6000 Ultrasonic Flow Meter O&M Manual
Energy/Total Energy(M05)
EFR +253.27 0kc/s *R
E.T +12213414EO GJ
This window shows energy flow and the totalizer. Details on measuring energy are described in “Energy Measurement”.
Analog Input AI1 and AI2(M06)
AI1= 4.0000:20.000 AI2= 8.0000:40.000
This window shows analog inputs AI1 and AI2 in currents that represent temperature, pressure or liquid level, etc.
Analog Input AI3 and AI4(M07)
AI3= 4.0000:20.000 AI4= 8.0000:40.000
This window shows analog inputs AI3 and AI4 in currents that represent temperature, pressure or liquid level, etc.
System Error Codes(M08)
*R System Normal
It shows the status of operation and corresponding status (or error) code. There are several error codes, whose implications and solutions are discussed in “ERROR SEARCHING”.
Net Flow Today(M09)
Net Flow of Today
358.34m
This window displays the net totalizer of the day.
3
Flomotion Systems, Inc. ~ FlomotionSystems.com
19
Page 20
BE6000 Ultrasonic Flow Meter O&M Manual
(2) Initial Setup
Pipe Outer Perimeter(M10)
Input the Outer Perimeter of Pipe
518.363mm
Input the outer perimeter of the pipe. If the outer diameter is available, please ignore this value and input the outer diameter of the pipe in M11.
Pipe Outer Diameter(M11)
Input the Outer Diameter of Pipe
165mm
Input the outer diameter directly or input the outer perimeter in M10. The value should be between 10mm and 6,000mm.
Attention: Either outer diameter or outer perimeter is ok.
Pipe Wall Thickness(M12)
Pipe Wall Thickness
5mm
Input the pipe wall thickness, if available, or skip this and go into M13.
Inner Diameter(M13)
Pipe Inner Diameter
155mm
Input the inner diameter. If you have input other diameter or outer perimeter and wall thickness, skip this window.
Either the wall thickness or the inner diameter is ok.
Pipe Material(M14)
Pipe Material
0. Carbon Steel
You can select one of the following materials from the list provided;
0. Carbon Steel 5. PVC
1. Stainless Steel 6. Aluminum
2. Cast Iron 7. Asbestos
3. Ductile Iron 8. Fiber Glass- Epoxy
4. Copper 9. Other
20
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 21
BE6000 Ultrasonic Flow Meter O&M Manual
If ‘9. Other’, you must input the corresponding sound velocity of the material in M15.
Pipe Sound Velocity(M15)
Pipe Sound Velocity
1300.5 m/s
Use this menu only when ‘9. Other’ is selected in M14. This menu is not activated if ‘9. Other’ is not selected in M14.
Liner Material(M16)
Liner Material
0. No Liner
You can select one of the following materials from the list provided;
0. No Liner 6. Polystyrene
1. Tar Epoxy 7. Polyester
2. Rubber 8. Polyethylene
3. Mortar 9. Ebonite
4. Polypropylene 10. Teflon
5. Polystrol 11. Other
If ‘11. Other’, you must input the corresponding sound velocity of the material in M17.
Liner Sound Velocity(M17)
Liner Sound Velocity
3300.5 m/s
Use this menu only when ‘11. Other’ is selected in M16.
Liner Thickness(M18)
Liner Thickness
10mm
Only when a liner is selected in M16, this menu will be activated.
Inside ABS Thickness(M19)
Inside ABS Thickness
0
Input ABS roughness coefficient. Not used. Reserved for future use.
Fluid(M20)
Flomotion Systems, Inc. ~ FlomotionSystems.com
21
Page 22
BE6000 Ultrasonic Flow Meter O&M Manual
Fluid Type
0. Water
You can select one of the following fluids from the list provided;
0. Water 8. Other
1. Sea Water 9. Diesel Oil
2. Kerosene 10. Caster Oil
3. Gasoline 11. Peanut Oil
4. Fuel Oil 12. Gasoline #90
5. Crude Oil 13. Gasoline #93
6. Propane (-45°C) 14. Alcohol
7. Butane (0°C) 15. Water (125°C)
If ‘8. Other’ is selected; input the corresponding sound velocity of the fluid in M21.
Fluid Sound Velocity(M21)
Fluid Sound Velocity
1600.0m/s
Enter the sound velocity of the fluid you chose in M20. This is activated only when ‘8. Other’ is selected in M20.
Fluid Viscosity(M22)
Fluid Viscosity
1.0054 cSt
Enter the viscosity of the fluid you chose in M20. This is activated only when ‘8. Other’ is selected in M20.
Transducer Type(M23)
Transducer Type
0. Standard – M
Select one of the transducer types from the list provided;
0. Standard – M 4. Standard - B
1. Plug-in Type c 5. Plug-in Type B45
2. Standard – S 6. Standard – L
3. User’s Own Type
If you select ‘3. User’s Own Type, you should enter a group of transducer parameters such as sound wedge angle, sound wedge velocity, ultrasonic delay and distance between the edge of the transducer and sound.
Transducer Mounting Method(M24)
Transducer Mounting
0. V
22
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 23
Select one of the transducer mounting types from the list provided;
0. V Method 2. N Method (for small pipes)
1. Z Method 3. W Method (for very small pipes)
Transducer Distance(M25)
Transducer Spacing
50.00mm
BE6000 Ultrasonic Flow Meter O&M Manual
This window is only for display of the transducer mounting distance that was calculated based on the parameters input in the foregoing menus. The distance is between the front edges of the transducers.
Parameter Save/Load(M26)
Parameter Setups
0. Entry SAVE
The pipe parameter data can be saved and loaded for a quick set up. A total of 18 sets of setup data can be stored and loaded. The following menus are provided;
0. Entry SAVE 1. Entry LOAD 2. Browse
When 0 is pressed and then ENTER is pressed, the window will show the address number and the data stored in that address. The data can be browsed using up and down keys and edited. Press ENTER to save the data. If a set of parameter data is loaded, the system will calculate the parameters and show the sensor distance in M25 window.
Current Section Area(M27)
Current Section Area
1963.5 mm2
The section area of the flow will be displayed.
Data Holding(M28)
Holding With Poor Signals
Yes
Select “Yes” to hold the last good flow signal displayed if the flow meter experiences a poor signal condition. This function will allow continued data calculation without interruption.
Empty Pipe Setup(M29)
Empty Pipe Setup
0
This value is used to solve the problem of the empty pipe. Even when the pipe is empty, the flow meter will show “Normal Working” for the signals that are transmitted and reflected through the pipe wall. In order to
Flomotion Systems, Inc. ~ FlomotionSystems.com
23
Page 24
BE6000 Ultrasonic Flow Meter O&M Manual
avoid this, set the lowest signal strength threshold to about 30~40, below which the system stop measurement because the pipe is deemed to be empty.
Measurement Unit (M30)
Measurement Units In
0. Metric
The following options are provided;
0. Metric 1. English
The default is Metric.
Flow Rate Units(M31)
Flow Rate Units
m3/h
The following flow units and time units are available;
Flow Units
0. Cubic Meters (m
1. Liters (l) 6. (American) Barrels
2. (American) Gallons 7. Imperial Barrels
3. Imperial Gallons 8. Oil Barrels (ob)
4. Million Gallons
Time Units /hour /day /min /sec
3) 5. Cubic Feet (cf)
Totalizer Units(M32)
Totalizer Units
Cubic Meters (m3)
Select totalizer units. The available unit options are the same as those found in M31. The user can select units as required. Factory default is cubic meters.
Totalizer Multiplier Options(M33)
Totalizer Multiplier
m3/h
The totalizer multiplier acts as the function to increase the totalizer indicating range. Meanwhile, the totalizer multiplier can be applied to the positive totalizer, negative totalizer and net totalizer at the same time. The followings options are available;
0. X 0.001 (1E-3) 4. X10
24
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 25
1. X 0.01 5. X100
2. X0.1 6. X1000
3. X1 7. X10000 (1E+4)
Factory default factor is x1.
ON/OFF Net Totalizer (M34)
Net Totalizer
ON
BE6000 Ultrasonic Flow Meter O&M Manual
On/off net totalizer. “ON” indicates that the totalizer is turned on, while “OFF” indicates it is turned off. When it is turned off, the net totalizer display in M00 will not change. Factory default is “ON”.
ON/OFF Positive Totalizer (M35)
POS Totalizer
ON
On/off positive totalizer. “ON” indicates the flowmeter starts to totalize the value. When it is turned off, the positive totalizer displays M02 won’t change. Factory default is “ON”.
ON/OFF Negative Totalizer (M36)
NEG Totalizer
ON
On/off negative totalizer. “ON” indicates the flowmeter starts to totalize the value. When it is turned off, the negative totalizer displays M03 won’t change. Factory default is “ON”.
Totalizer Reset(M37)
Totalizer Reset?
Selection
Totalizer reset; all parameters are reset. Press [ENTER]; move UP or DOWN arrow to select “YES” or “NO”. After “YES” is selected, the following operations are available;
None All NET POS NEG
If it is necessary to recover the factory default, press displayed on the screen.
Manual Totalizer(M38)
[.][Å] keys after the above-mentioned characters are
Flomotion Systems, Inc. ~ FlomotionSystems.com
25
Page 26
BE6000 Ultrasonic Flow Meter O&M Manual
Manual Totalizer
Press ENT when ready
The manual totalizer is a separate totalizer. Press [ENTER] to start, and press [ENTER] to stop it. It is used for flow measurement and calculation.
Damping(M40)
Damping
10 sec
The damping factor ranges from 0~999 seconds. 0 indicates no damping; 999 indicate the maximum damping. Damping functions to display the data smoothly. Its principle is the same as that in a single-section RC filter. The damping factor value corresponds to the circuit time constant. Usually a damping factor of 3 to 10 is recommended in applications.
Low Flow Cutoff Value(M41)
Low Flow Cutoff Val.
0.01 m/s
Low Flow Cutoff is used to make the system display as “0” value at lower and smaller flows to avoid any inefficiency in totalizing. For instance, if the cutoff value is set as 0.03, system will take all the measured flow values of ±0.03 as “0”. Usually 0.03 is recommended in most applications.
Set Zero(M42)
Set Zero[42
Press ENT to go
When the fluid is in the static state, the displayed value is called “Zero Point”. When “Zero Point” is not at zero in the flowmeter, the difference is going to be added into the actual flow values and measurement differences will occur in the flow meter.
Set Zero must be carried out after the transducers are installed and the flow inside the pipe is in the absolute static state (no liquid movement in the pipe). Thus, the “Zero Point” resulting from different pipe mounting locations and parameters can be eliminated. The measuring accuracy at low flow is enhanced consequently.
Press [ENT], wait for the processing instructions at the bottom right corner to reach 0. Set zero within the existing flow may cause the flow to be displayed as “0”. If so, it can be recovered via M43.
Reset Zero(M43)
Reset Zero [43
No
Select “YES”; reset “Zero Point” which was set by the user.
Manual Zero Point(M44)
26
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 27
Manual Zero Point [44
0m3/h
BE6000 Ultrasonic Flow Meter O&M Manual
This method is not commonly used. It is only suitable for experienced operators to set zero under conditions where it is not preferable to use other methods. Enter the value manually to add to the measured value to obtain the actual value.
For instance:
Actual Measured Value = 250 m Value Deviation = 10 m Displayed Value = 240 m Normally, set this value as “0”.
3/h
3/h
3/h
Scale Factor(M45)
Scale Factor [45
1
The scale factor is used to modify the measurement results. Factory default is 1. The user can enter a numerical value other than “1” according to calibration results.
Network IDN(M46)
Network IDN [46
88
Input system identifying code, these numbers can be selected from 0 ~ 65535 except that 13 (0DH ENTER), 10(0AH New Line), 42(2AH *) and 38(26H&). System IDN is used to identify a unit in network.
System Lock(M47)
System Lock [47
= Unlock
Lock the flowmeter.
Once the system is locked, any modification is prohibited in the system. However, the parameter is readable, so as to protect proper operation of the instrument. “Unlock” by the password only. The password is
composed of 1 to 4 numbers. (Please contact us if the password is forgotten)
Keypad Lock Code (M48)
Low Flow Cutoff Val.
0.01 m/s
The Keypad Lock function is used to avoid any operation errors by unauthorized personnel.
(Please contact us if the password is forgotten)
Logger Option (M50)
Flomotion Systems, Inc. ~ FlomotionSystems.com
27
Page 28
BE6000 Ultrasonic Flow Meter O&M Manual
Logger Option [50
OFF
Sets the printer on/off. When “ON” is selected. The following options will be displayed for further options(Use
key to move to next item);
0. Date and Time (OFF) 8. Signal Strength (OFF)
1. System Status (OFF) 9. Energy Flow Rate (OFF)
2. Current Window (OFF) 10. Energy Totalize (OFF)
3. Flow Rate (ON) 11. AI1 (OFF)
4. Velocity (OFF) 12. AI2 (OFF)
5. NET Totalize (OFF) 13. Working Timer (OFF)
6. POS Totalize (OFF) 14. Flow Today (OFF)
7. NEG Totalize (OFF)
Press ENT to select and set the setting.
Logger Time Setups(M51)
Logger Time Setups [51
Start Time = 00:00:00
Input Start Time, Interval and Duration. If you set the Start Time as **:**:**, the instrument will start logging on from now on. If you set it to 23:10:10, it will start logging from 23:10:10. If the Interval is set to **:**:**, the logging will never stop. The minimum logging interval is 1 second and the maximum is 24 hours.
Print to RS-232C(M52)
Print to RS-232C [52
This menu is fixed. That means the logging data will always be available at RS-232C port.
Display AI5(M53)
Analog Input AI5 [53
AI5=4.0000:20.00
Displays the electric current of AI5 and its corresponding parameters such as temperature, pressure or level.
AI5 Range(M54)
AI Value Range [54
10-100
To input scale range of temperature, pressure or level for the analog input of 4-20mA. For example, the value 10 in the above box represents 4mA and 100 20mA.
Current Output Selection(M55)
28
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 29
BE6000 Ultrasonic Flow Meter O&M Manual
CL Mode Select [55
0.4-20mA
0. 4-20mA 5. 0-4-20mA
1. 0-20Ma 6. 20-0-20mA
2. 0-20mA Via RS-232 7. 4-20mA vs. Vel.
3. 4-20mA vs. Flow 8. 4-20mA vs. Energy
4. 20-4-20mA
The serial port controls the output according to the command and parameter entered in the RS232 to output a definite current value through the current loop. The command formats are narrated in the command explanations to Serial Port controls. For instance, if it is necessary to output a 6mA current through the current loop, it can be realized by setting M56 to mode “0-20mA Via RS232” and giving a command “AO6(CR)”. This function is able to make the flowmeter operate a control valve conveniently.
4mA or 0mA Output Value(M56)
CL 4mA Output Value[56
0 m3/h
Use this window to set the flow value to 4mA or 0mA. The flow unit is the same that was set at M31.
20mA Output Value(M57)
CL 20mA Output Value[57
1200 m3/h
Use this window to set the flow value to 20mA. The flow unit is the same that was set at M31.
CL Check Verification(M58)
CL Checkup [58
Verification
Check if the current loop has been calibrated before leaving the factory. Press ENT, move 5or 6separately to display 0mA, 4mA till 24mA, and at the same time, check with an ammeter to verify that CL output terminals No. 31 and 32 agree with the displayed values. It is necessary to re-calibrate the CL if over the permitted tolerance. For more information, refer to Chapter 3- Operating Instructions. Section 3.29-Analog Output Calibration.
CL Current Output(M59)
CL Current Output [59
0.0000mA
Display CL current output. The display of 10.0000mA indicates that CL current output value is 10.0000mA. If the difference between displaying value and CL output value is too large, the current loop then needs to be re-calibrated accordingly.
Flomotion Systems, Inc. ~ FlomotionSystems.com
29
Page 30
BE6000 Ultrasonic Flow Meter O&M Manual
Date and Time Settings(M60)
YY-MM-DD HH:MM:SS
04-05-05 11:05:05
Date and time modifications are made. The format for setting time setting is 24hours. Press ENT, wait until “>” appears. The modification can then be made.
ESN(M61)
Ultrasonic Flowmeter
ESN = 35800003
Displays the electronic serial number (ESN) of the instrument. This ESN is the only one assigned to each BE6000 series flow meter ready to leave the factory. The factory uses it for files setup and for management by the user.
Serial Port Setup(M62)
RS-232C Setup [62
9600, 8, None
To set RS232 port property. The first information is bit rate and can be 110, 150, 300, 600, 1200, 240, 4800 or 9600. The second information is data bit and it can be either 7 or 8. The third information is parity and can be either None, Even or Odd. And the fourth information is stop bit and can be 1, 1.5 or 2.
AI1 Range(M63)
AI Value Range [63
10-100
To input scale range of temperature, pressure or level for the analog input of 4-20mA. For example, the value 10 in the above box represents 4mA and 100 20mA.
AI2 Range(M64)
AI Value Range [64
10-100
To input scale range of temperature, pressure or level for the analog input of 4-20mA. For example, the value 10 in the above box represents 4mA and 100 20mA.
AI3 Range(M65)
AI Value Range [65
10-100
To input scale range of temperature, pressure or level for the analog input of 4-20mA. For example, the value 10 in the above box represents 4mA and 100 20mA.
30
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 31
AI4 Range(M66)
AI Value Range [66
BE6000 Ultrasonic Flow Meter O&M Manual
10-100
To input scale range of temperature, pressure or level for the analog input of 4-20mA. For example, the value 10 in the above box represents 4mA and 100 20mA.
Frequency Output Signal Frequency Range(M67)
FO Frequency Range [67
1-1001
To input low(12-9999Hz) and high(12-9999Hz) frequency for the output. Make sure to set OCT to output frequency signal in order to output frequency signal.
Flow Value of Low Frequency Output(M68)
Low FO Flow Rate [68
0 m3/h
To input flow rate value for the low frequency point.
Flow Value of High Frequency Output(M69)
High FO Flow Rate [69
0 m3/h
To input flow rate value for the high frequency point.
LCD Back Light Controller (M70)
LCD Backlit Option [70
1. Always On
LCD can be controlled using this window. “Always On” means the back light will be always on. “Always Off” means always off. “Light for nn” means it will turn on when a key is pressed and will stay on for nn seconds after the keys have been pressed. This option is provided for power saving.
LCD Contrast Controller (M71)
LCD Contrast [71
9
To control the LCD contrast. Press ENT and adjust the number using up or down keys, and press ENT again to confirm.
Working Timer (M72)
Flomotion Systems, Inc. ~ FlomotionSystems.com
31
Page 32
BE6000 Ultrasonic Flow Meter O&M Manual
Working Timer [72
0000054:34:23
Display the totalized working hours of the unit since last reset. It is displayed by HH:MM:SS. If it is necessary to reset it, press ENT and select “YES”.
#1 Alarm Low Value (M73)
Alarm #1 Low Value [73
0 m3/h
Input the low value of alarm. When the value falls under this value, it will cause the alarm to be output using hardware OCT or relay as set in M78 and M79.
#1 Alarm High Value (M74)
Alarm #1 High Value [74
1600 m3/h
Input the high value of alarm. When the value exceeds this value, it will cause the alarm to be output using hardware OCT or relay as set in M78 and M79.
#2 Alarm Low Value (M75)
Alarm #2 Low Value [75
0 m3/h
Input the low value of alarm. When the value falls under this value, it will cause the alarm to be output using hardware OCT or relay as set in M78 and M79.
#2 Alarm High Value (M76)
Alarm #2 High Value [76
1600 m3/h
Input the high value of alarm. When the value exceeds this value, it will cause the alarm to be output using hardware OCT or relay as set in M78 and M79.
Beeper Setup (M77)
Beeper Setup [77
15. Key Stroking On
The following sources can be selected to set off the buzzer;
0. No Signal 9. POS into Pulse
1. Poor Signal 10. NEG into Pulse
2. Not Ready(No*R) 11. NET into Pulse
32
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 33
3. Reverse Flow 12. Energy Pulse
4. AO over 100% 13. On/Off via RS232
5. FO over 120% 14. Fluid Changed
6. Alarm #1 15. Key Stroking On
7. Alarm #2 16. Not Using
8. Batch Control
OCT Output Setup (M78)
OCT Output Setup [78
17. Not Using
BE6000 Ultrasonic Flow Meter O&M Manual
Set the system to put hardware OCT output when one of the following sources occurs;
0. No Signal 9. POS into Pulse
1. Poor Signal 10. NEG into Pulse
2. Not Ready(No*R) 11. NET into Pulse
3. Reverse Flow 12. Energy Pulse
4. AO over 100% 13. FO
5. FO over 120% 14. FO via RS232
6. Alarm #1 15. On/Off via RS232
7. Alarm #2 16. Fluid Changed
8. Batch Control 17. Not Using
Relay Output Setup (M79)
Relay Output Setup [79
15. Not Using
Set the system to put Relay output when one of the following sources occurs;
0. No Signal 8. Batch Control
1. Poor Signal 9. POS into Pulse
2. Not Ready(No*R) 10. NEG into Pulse
3. Reverse Flow 11. NET into Pulse
4. AO over 100% 12. Energy Pulse
5. FO over 120% 13. On/Off via RS232
6. Alarm #1 14. Fluid Change
7. Alarm #2 15. Not Using
Flow Batch Control Setup (M80)
Flow Batch CTRL in
0. Key Input
Select the batch control type. Available options are as follows;
0. Key Input 4. AI2 Down Edge
1. AI1 Up Edge 5. AI3 Up Edge
2. AI1 Down Edge 6. AI3 Down Edge
3. AI2 Up Edge 7. AI4 Up Edge
Flomotion Systems, Inc. ~ FlomotionSystems.com
33
Page 34
BE6000 Ultrasonic Flow Meter O&M Manual
Flow Batch Controller (M81)
Flow Batch Controller
10000 x 1m3
The internal batch controller in the system is able to control the input signals through keypad or analog input. Output signals can be transmitted through OCT or relay. The flow batch value can be modified in this window. The screen will enter the batch control display as soon as the modification is completed.
Date Totalizer (M82)
Date Totalizer [82
0. Day
In this window, it is possible to review the historical flow data totalizer for any day for the last 64 days, any month for last 64 months and any year for last 5 years. Press ENT, use UP or DOWN key to review totalizer in days, months and years. Use UP or DOWN key to review the flow total for a specific day, month or year.
For instance, to display the flow total for May 17, 2005, the display “-----------“ at the upper right corner of the screen indicates that it was working properly the whole day. On the contrary, if “G” is displayed, it indicates that the instrument gain was adjusted at least once. Probably it was offline once on that day. If “H” is displayed, it indicates that poor signal was detected at least once. Also, it indicates that the operation was interrupted or problems occurred in the installation.
For details, please refer to Chapter 5 – Error Diagnoses
0. Day
1. Month
2. Year
Automatic Flow Correction (M83)
Automatic Correction
ON
With the function of automatic flow correction, the flow lost in an offline session can be estimated and automatically adjusted. The estimate is based on the average value, which is obtained from flow rate before going offline and flow measured after going online the next time, multiplied times the time period that the meter was offline. Select “No” to cancel this function.
Energy Unit Selection (M84)
Energy Unit Select [84
0. Giga Joule(GJ)
Select GJ or K.C as energy unit. The default is GJ.
Energy Temperature Source Selection (M85)
34
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 35
Temperature Select
0. From AI1, AI2
BE6000 Ultrasonic Flow Meter O&M Manual
Select the sources for temperature signals when measuring energy. The following 2 options are provided;
0. From AI1, AI2 1. Fixed Difference
If “Fixed Difference” is selected the value should be entered manually through keypad.
Specific Heat (M86)
Specific Heat Select
0.0041868 GJ/m3oC
Select one of the following 2 kinds of specific heat;
0. GB 1. Fixed Specific Heat
Normally, 0.004186 GJ/ m
3o
C(=1000 kcal/ m3o C). Use M+9 to check the current temperature and calorie.
Energy Totalizer Switch (M87)
Energy Totalizer ON/OFF
ON
Turn on/off the energy totalizing function.
Energy Totalize Multiplier (M88)
Energy Multiplier [88
4. xl
Select the energy totalize multiplier. 10
-4
– 10
6
(E-4 – E-6)
Reset Energy Totalize (M89)
Reset Energy Totalize
NO
Select YES to reset energy accumulation.
Signal Strength and Signal Quality (M90)
Strength+Quality [90
UP:00.0 DN:00.0 Q=00
Display the measured signal strength and signal quality Q value upstream and downstream. Signal strength is indicated from 00.0~99.9. A reading of 00.0 indicates no signal detected, while 99.9 indicates maximum signal strength. Normally the signal strength should be > 60.0. Signal Quality Q is indicated 00~99.
Flomotion Systems, Inc. ~ FlomotionSystems.com
35
Page 36
BE6000 Ultrasonic Flow Meter O&M Manual
Therefore, 00 indicates the poorest signal while 99 indicates the best signal. Normally signal quality Q value should be better than 60.
TOM/TOS*100 (M91)
TOM/TOS*100 [91
0.0000
Display the ratio between the actual measured transmit time and the calculated transmit time according to customer’s requirement. Normally the ratio should be 100 ±3%. If the difference is too large, the user should check if the parameters are entered correctly, especially the sound velocity of the fluid and the installation of
the transducers. This data is of no use before the system is ready.
Fluid Sound Velocity (M92)
Fluid Sound Velocity
0.0000 m/s
Display the measured fluid sound velocity. Normally this value should be approximately equal to the entered value in M21. If the difference is too large, it probably results from an incorrect value entered in M21 or improper installation of the transducers.
Total Time and Delta Time (M93)
Total Time, Delta Time
8.9149uS, -171.09nS
Display the measured ultrasonic average time (unit: μS) and delta time of the upstream and downstream (unit: nS) time. The velocity calculation in BE6000 ultrasonic flowmeter is based on the two readings; especially the delta time will best indicate if the instrument is running steadily.
Normally the fluctuation in the ration of the delta time should be lower than 20%; otherwise, the system may not run steadily. It is, then, necessary to check if the transducers are installed properly or if the parameters have been entered correctly.
Reynolds Number and Factor (M94)
Reynolds Number [94
0.0000 1.0000
Displays the Reynolds number that is calculated by the system and the factor that is set currently by the system. Normally this scaling factor is the average of line and surface velocity factor inside the pipe.
Print Commands
(M97, M98, M99, M9.)
Press [MENU] [9] [7]. Prints the following working parameters as set by the user at the initial set up;
- Outer Diameter
- Wall Thickness
36
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 37
BE6000 Ultrasonic Flow Meter O&M Manual
- Inner Diameter
- Pipe Material
- Liner Material
- Fluid Type
- Sensor Type
- Sensor Mounting Type
- Sensor Spacing
Press [MENU] [9] [8]. Prints diagnostic data.
Press [MENU] [9] [9]. Prints contents of the current window.
Press [MENU] [9] [.]. Make the printer to pull the paper at 1 row distance.
Power On/Off Time [MENU] + 0
Power On/Off Time M+0
Press ENT when ready
To view the power on/off time and flow rate for the last 64 update times to obtain the offline time period and the corresponding flow rate. Enter the window, press ENT to display the last update before the last 64 times of on/off time and flow rate values. “ON” on right hand indicates that time power is on; “00” on the upper left corner indicates “00-07-18 12:40:12” the date time; flow rate is displayed in the lower right corner.
Total Working Hours [MENU] + 1
Total Work Hours [+1]
00000115:12:08
With this function, it is possible to view the total working hours since the flowmeter left the factory. The figure in the above indicates that the total working hours since the flowmeter left the factory is 115 hours 12 minutes and 8 seconds.
Last Power Off Time [MENU] + 2
Last Power Off Time
04-07-12 10:12:02
Display the last power off time.
Last Flow Rate [MENU] + 3
Last Flow Rate [+3
100.43 m3/h
Displays the last flow rate.
Calculator [MENU] + 5
Flomotion Systems, Inc. ~ FlomotionSystems.com
37
Page 38
BE6000 Ultrasonic Flow Meter O&M Manual
X=? M=0
0
This window is a calculator which has the ability of functional operation. How to use: Input the first parameter X, then select an operator. If this operation has a second parameter, then input the second parameter Y and put the result of the operation in X. For example, To calculate 1+2, press [MENU] [+] [5] [1] [ENT]. After selecting “+” operator by using [UP/+] key, press [ENT] [2] [ENT].
This calculator also has register function, which can be selected by operator selection.
Note: The calculator can be used even when the meter is operating. The measurement result of the meter will not be affected by the calculation.
Fluid Sound Changed [MENU] + 6
Velocity Changing
1 m/s
Displays the threshold value of the sound velocity that will trigger the alarm. Namely if the measured sound velocity should be different from the sound velocity stored in the instrument by more than this threshold value. An alarm signal will be generated and transmitted as OCT or relay output.
Compatible Communication Protocol Selection [MENU] + 7
Protocol Select [+7
0. Protocol 0(*Adxx)
Select one of two different communications protocols.
Receive Wave Shape [MENU] + 8
Receive
Shape
To display the wave shape of ultrasonic signals received by the flow meter. In normal conditions, the displayed wave shape should be constant without fluctuations.
38
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 39
BE6000 Ultrasonic Flow Meter O&M Manual
III. Trouble Shooting
With highly reliable design, the BE6000 ultrasonic flowmeter has a low failure rate. However, problems may occur as a result of unskillful handling, setting errors or working in an extremely undesirable working condition. For this reason, the meter is equipped with a self-diagnostic function. Problems detected are displayed in time order in code form on the upper right corner of the LCT screen. Hardware malfunctions, though generally checked after power is on, can also be detected (part of them) while the device is working normally. Information about “stop working” problems caused by wrong settings or undesirable working conditions can also be displayed, so users can locate the problems quickly and solve the problems according to the solutions offered in the following two tables in time.
There are two kinds of error displayed in BE6000:
- Error messages are displayed during self-test after the power is switched on. After entering the measurement mode, if there is an error, “*F” will be displayed at the top left corner of the screen. Check the information being displayed and take specific steps according to the following tables. If problems persist, contact your BE6000 distributor.
- Errors about the specific signal received or wrong settings can be displayed by the M08 window in error code form. Errors and solutions are listed in the following tables;
Power-On self-test information, Causes and Solutions
LCD Display Causes Solution
ROM Parity Error System ROM illegal or in error Contact the manufacturer.
Stored Data Error Stored Data Error
Handshaking Error
SCPU Fatal Error Fatal error in sub CPU circuit Restart or contact the manufacturer.
Timer Slow Error Timer Fast Error
CPU or Interruption error, retry
System RAM Error System RAM has problems. Restart or contact the manufacturer.
Time or Batt Error System time chip error Restart or contact the manufacturer.
When pressing the keys, no response from screen, no display or disorderly display
PRN Time Over Printer wrong or wrong connection. Examine printer or cable.
Hardware handle wrong, system will reset.
System clock is wrong. Contact the manufacturer.
Main CPU is wrong. Restart
Mis-operation, poor cable contact on the panel
Restart the instrument or contact the manufacturer.
Restart.
Soft Reset. Check whether the cables on the panel are contacted well.
Flomotion Systems, Inc. ~ FlomotionSystems.com
39
Page 40
BE6000 Ultrasonic Flow Meter O&M Manual
Error Code Causes and Solutions
Code Corresponding display M08 Causes Solution
*R System Normal System operates normally. Contact the manufacturer.
*J SCPU Fatal Error Hardware failure Contact the manufacturer.
*I Signal Not Detected
* No signal received * Make sure the sensor is
close to the pipe. Use sufficient couplant.
* A poor contact between sensor and the pipe, or too little couplant applied.
* The sensor has not been installed properly. * Too much scale formation in the inside wall.
* Make sure no rust, stain, no oil paint on the pipe surface. Use flat file clean to clean the pipe surface.
* Check the original settings.
* You can clean the couplant or change the pipe. But under normal conditions, you can try to change the measuring point.
Low Signal Strength Poor Signal
*H
Quality
Current loop over 20mA (Ignore it if the measuring process don’t use current output)
*E
*F See above Table
Adjusting Gain=>S1 Adjusting Gain=>S2 Adjusting Gain=>S3 Adjusting Gain=>S4 (Displayed in M00, M01, M02, M03 windows)
*G
Empty pipe, M29 menu settings
*K
* New Liner * Wait until the liner is
saturated and solidified.
* Poor Signal Quality * The above mentioned causes are applicable here, too.
* 4-20mA current loop overflow over 120% * Wrong current loop output settings
* Self-checking error * Restart the device and
* Perpetual hardware failure * Contact the company. * These all 4 steps means that the machine is going through the gain adjustment process, preparing for the normal measurement. If the machine stops on S1 or S2, or shifts between S1 and S2, it means that the received signal is too low or the waveform is not so good. The reasons may include all the above­mentioned causes. No liquid in the pipe or wrong settings
* The same as above column
* Recheck the settings(see M58 in the manual) or make sure the actual flow is not too big.
observe the information displayed on the screen. If the problem persists, contact the
company
If there is liquid in the pipe, input “0” in the M29 menu.
40
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 41
BE6000 Ultrasonic Flow Meter O&M Manual
Appendix 1. RS-232 Command Protocol
COMMAND
PC->METER
DQD(CR) Flow rate, everyday M@(CR)
DQH(CR) Flow rate, every hour LCD(CR) Current LCD display
DQM(CR) Flow rate, every minute C1(CR) OCT combined
DQS(CR) Flow rate, every second C0(CR) OCT separate
DV(CR) Flow velocity R1(CR) RELAY combined
DI+(CR) Positive total R0(CR) RELAY separated
DI-(CR) Negative total F0n(CR)
DIN(CR) Net flow total A0a(CR)
DIE(CR) Energy total BA1(CR) Binary value of A1 input
DATA RETURNED
METER -> PC
COMMAND
PC -> METER
DATA RETURNED
METER -> PC
Simulates key pressing on the
instrument.
To make frequency output as “n”
value
To make current loop output as
“a” value
DL(CR) Signal strength BA2(CR) Binary value of A1 input
DS(CR) A0 output in percentage AI1(CR) Value of A1 input
DC(CR) Current Error Code AI2(CR) Value of A2 input
DA(CR) OCT or RELAY alarms ESN Electronic Serial Number
DT(CR) Current date and time
Flomotion Systems, Inc. ~ FlomotionSystems.com
41
Page 42
BE6000 Ultrasonic Flow Meter O&M Manual
Appendix 2. Sound Velocity and Viscosity of Liquids
Liquid
Water 20oC 1482 1.0 Glycerin 1923 1180
Water 50oC 1543 0.55 Gas 1250 0.80
Water 75oC 1554 0.39 66# Gas 1171
Water 100oC 1543 0.29 80# Gas 1139
Water 125oC 1511 0.25 0# Gas 1385
Water 150oC 1466 0.21 Benzene 1330
Water 175oC 1401 0.18 Ethyl benzene 1340
Water 200oC 1333 0.15 Toluene 1170 0.69
Water 225oC 1249 0.14 Tetra chloromethane 938
Acetone 1190
Carbinol 1121
Ethanol 1168
Alcohol 1440 1.5 Ketone 1310
Acetaldehyde 1180
Arachis oil 1472
Sound
Velocity(m/s)
Viscosity
(mm2/s)
Liquid
Sound
Velocity(m/s)
Viscosity
(mm2/s)
Petroleum 1290
Pine oil 1280
Cloroethylene 1050 0.82
Glycol 1620
Castor oil 1502
42
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 43
BE6000 Ultrasonic Flow Meter O&M Manual
Appendix 3. Sound Velocity for Various Common Materials
Pipe Material
Pipe Material Sound Velocity(m/s)
Steel 3206
ABS 2286
Aluminum 3048
Brass 2270
Cast Iron 2460
Bronze 2270
Fiber, Glass-Epoxy 3430
Glass 3276
Polyethylene 1950
PVC 2540
PTFE 1450
Rubber 1600
Liner Material
Liner Material Sound Velocity(m/s)
PTFE 1225
Titanium 3150
Cement 4190
Bitumen 2540
Porcelain Enamel 2540
Glass 5970
Plastic 2280
Polyethylene 1600
Flomotion Systems, Inc. ~ FlomotionSystems.com
43
Page 44
BE6000 Ultrasonic Flow Meter O&M Manual
Appendix 4. Sound Velocity in Water (1 ATM) at different temperatures
Unit: t(oC), v(m/s)
t v t v t v t v
0 1402.3 25 1496.6 50 1542.5 75 1555.1
1 1407.3 26 1499.2 51 1543.5 76 1555.0
2 1412.2 27 1501.8 52 1544.6 77 1544.9
3 1416.9 28 1504.3 53 1545.5 78 1554.8
4 1421.6 29 1506.7 54 1546.4 79 1554.6
5 1426.1 30 1509.0 55 1547.3 80 1554.4
6 1430.5 31 1511.3 56 1548.1 81 1554.2
7 1434.8 32 1513.5 57 1548.9 82 1553.9
8 1439.1 33 1515.7 58 1549.6 83 1553.6
9 1443.2 34 1517.7 59 1550.3 84 1553.2
10 1447.2 35 1519.7 60 1550.9 85 1552.8
11 1451.1 36 1521.7 61 1551.5 86 1552.4
12 1454.9 37 1523.5 62 1552.0 87 1552.0
13 1458.7 38 1525.3 63 1552.5 88 1551.5
14 1462.3 39 1527.1 64 1553.0 89 1551.0
15 1465.8 40 1528.8 65 1553.4 90 1550.4
16 1469.3 41 1530.4 66 1553.7 91 1549.8
17 1472.7 42 1532.0 67 1554.0 92 1549.2
18 1476.0 43 1533.5 68 1554.3 93 1548.5
19 1479.1 44 1534.9 69 1554.5 94 1547.5
20 1482.3 45 1536.3 70 1554.7 95 1547.1
21 1485.3 46 1537.7 71 1554.9 96 1546.3
22 1488.2 47 1538.9 72 1555.0 97 1545.6
23 1491.1 48 1540.2 73 1555.0 98 1544.7
24 1493.9 49 1541.3 74 1555.1 99 1543.9
Please refer to the sound velocity of other fluids and materials, please contact the factory.
Calculation of Sound Velocity (C
=1557 - 0.0245(74-t)2(m/s) where, "t" is water temperature (oC)
C
o
Calculation of Sound Velocity (C
+1.39S where, “C0“ is the sound velocity in fresh water, “S” is the salinity of the sea water (%)
C
1=C0
0) in Fresh Water:
1) in Sea Water:
44
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 45
Appendix 5. Pipe Dimensions and Weights
Nominal
pipe size
(inch)
1/8 .0405 10
1/4 0.540 10
3/8 0.675 10
1/2
3/4
1 1.315 5
1-1/4 1.660
1-1/2
2
2-1/2 2.875 5
3
3-1/2 4.000 5
OD
Inch
0.840 5
1.050 5
1.900 5
2.375 5
3.500 5
Schedule
designations
STD XS
STD XS
STD XS
10 STD XS 160 XX
10 STD XS 160 XX
10 STD XS 160 XX 5 10 STD XS 160 XX
10 STD XS 160 XX
10 STD XS 160 XX
10 STD XS 160 XX
10 STD XS 160 XX
10 STD XS XX
40 80
40 80
40 80
40 80
40 80
40 80
40 80
40 80
40 80
40 80
40 80
40 80
10S 40S 80S 10S 40S 80S 10S 40S 80S
5S 10S 40S 80S
5S 10S 40S 80S
5S 10S 40S 80S
5S 10S 40S 80S
5S 10S 40S 80S
5S 10S 40S 80S
5S 10S 40S 80S
5S 10S 40S 80S
5S 10S 40S 80S
Wall inch
0.049
0.068
0.095
0.065
0.088
0.119
0.065
0.091
0.126
0.065
0.083
0.109
0.147
0.188
0.294
0.065
0.083
0.113
0.154
0.219
0.308
0.065
0.109
0.133
0.179
0.250
0.358
0.065
0.109
0.140
0.191
0.250
0.382
0.065
0.109
0.145
0.200
0.281
0.400
0.065
0.109
0.154
0.218
0.344
0.436
0.083
0.120
0.203
0.276
0.375
0.552
0.083
0.120
0.216
0.300
0.438
0.600
0.083
0.120
0.226
0.318
0.636
ID
inch
0.307
0.269
0.215
0.410
0.364
0.302
0.545
0.493
0.423
0.710
0.674
0.622
0.546
0.464
0.252
0.920
0.884
0.824
0.742
0.612
0.434
1.185
1.097
1.049
0.957
0.815
0.599
1.530
1.442
1.380
1.278
1.160
0.896
1.770
1.682
1.610
1.500
1.338
1.100
2.245
2.157
2.067
1.939
1.687
1.503
2.709
2.635
2.469
2.323
2.125
1.771
3.334
3.260
3.068
2.900
2.624
2.300
3.834
3.760
3.548
3.364
2.728
Nominal
pipe size
(inch)
4 4.500 5
4-1/2 5.000 STD
5 5.563 5
6
7
8
9
10
11
BE6000 Ultrasonic Flow Meter O&M Manual
OD
Inch
6.625 5
7.625 STD
8.625
9.625 STD
10.750
11.750
Schedule
Designations
10
STD XS 120 160 XX
XS XX
10 STD XS 120 160 XX
10
STD XS 120 160 XX
XS XX
10 20 30 STD 60 XS 100 120 140 XX 160
XS XX
20 30 STD XS 80 100 120 140 160 STD XS XX
40 80
40 80
40 80
40 80
40 80
40
80
40 80
40 80
40 80
Wall inch
5S
0.083
5S
5S
5S
5S
0.120
0.156
0.188
0.237
0.337
0.438
0.531
0.674
0.247
0.355
0.710
0.109
0.134
0.258
0.375
0.500
0.625
0.750
0.109
0.134
0.188
0.280
0.432
0.562
0.719
0.864
0.301
0.500
0.875
0.109
0.148
0.250
0.277
0.322
0.406
0.500
0.594
0.719
0.812
0.875
0.906
0.342
0.500
0.875
0.134
0.165
0.188
0.250
0.307
0.365
0.500
0.594
0.719
0.844
1.000
1.125
0.375
0.500
0.875
10S
40S 80S
40S 80S
10S 40S 80S
10S
40S 80S
40S 80S
10S
40S
80S
40S 80S
10S
40S 80S
40S 80S
ID
inch
4.334
4.260
4.188
4.124
4.026
3.826
3.624
3.438
3.152
4.506
4.290
3.580
5.345
5.295
5.047
4.813
4.563
4.313
4.063
6.407
6.357
6.249
6.065
5.761
5.501
5.187
4.897
7.023
6.625
5.875
8.407
8.329
8.125
8.071
7.981
7.813
7.625
7.437
7.187
7.001
6.875
6.813
8.941
8.625
7.875
10.482
10.420
10.374
10.250
10.136
10.020
9.750
9.562
9.312
9.062
8.750
8.500
11.000
10.750
10.000
Flomotion Systems, Inc. ~ FlomotionSystems.com
45
Page 46
BE6000 Ultrasonic Flow Meter O&M Manual
Nominal
pipe size
(inch)
12
14
16 16.000
18 18.000
20
OD
Inch
12.750
14.000
20.000
Schedule
designations
20 30 STD 40 XS 60 80 100 120 140 160
10 20 STD 40 XS 60 80 100 120 140 160
10 20 STD XS 60 80 100 120 140 160
10 20 STD 30 XS 40 60 80 100 120 140 160
10 STD XS 40 60 80 100 120 140 160
5S 10S
40S
80S
10S
40S
30
30 40
10S
40
80S
10S
40S 80S
40S
80S
10S
40S 80S
Wall inch
0.156
0.180
0.250
0.330
0.375
0.406
0.500
0.562
0.688
0.844
1.000
1.125
1.312
0.188
0.250
0.312
0.375
0.438
0.500
0.594
0.750
0.938
1.094
1.250
1.406
0.188
0.250
0.312
0.375
0.500
0.656
0.844
1.031
1.219
1.438
1.594
0.188
0.250
0.312
0.375
0.438
0.500
0.562
0.750
0.938
1.156
1.375
1.562
1.781
0.218
0.250
0.375
0.500
0.594
0.812
1.031
1.281
1.500
1.750
1.969
ID
inch
12.438
12.390
12.250
12.090
12.000
11.938
11.750
11.626
11.374
11.062
10.750
10.500
10.126
13.624
13.500
13.376
13.250
13.124
13.000
12.812
12.500
12.124
11.812
11.500
11.188
15.624
15.500
15.376
15.250
15.000
14.688
14.312
13.938
13.562
13.124
12.812
17.624
17.500
17.376
17.250
17.124
17.000
16.876
16.500
16.124
15.688
15.250
14.876
14.438
19.564
19.500
19.250
19.000
18.812
18.376
17.938
17.438
17.000
16.500
16.062
Nominal
pipe size
(inch)
22
24
26
28
30
32
34
36
42
48
OD
Inch
22.000
24.000
26.000
28.000
30.000
32.000
34.000
36.000
42.000
48.000
Schedule
designations
STD XS 60 80 100 120 140 160 10 STD XS 30 40 60 80 100 120 140 160
STD XS
STD XS
STD
STD
STD
STD XS STD XS
STD XS
10S
10
40S
20
80S
30
10S 40S
20
80S
10
40S 80S
10
40S
20
80S 30 10
40S 20
80S 30 10
20 30 40 10
20 30 40 10
40S
80S
40S
80S 30 40
40S
80S
Wall inch
0.218
0.250
0.375
0.500
0.875
1.125
1.375
1.625
1.875
2.125
0.250
0.375
0.500
0.562
0.688
0.969
1.219
1.531
1.812
2.062
2.344
0.312
0.375
0.500
0.312
0.375
0.500
0.625
0.312
0.375
0.500
0.625
0.312
0.375
0.500
0.625
0.688
0.312
0.375
0.500
0.625
0.688
0.312
0.375
0.500
0.375
0.500
0.625
0.750
0.375
0.500
ID
inch
21.564
21.500
21.250
21.000
20.250
19.750
19.250
18.750
18.250
17.750
23.500
23.250
23.000
22.876
22.624
22.062
21.562
20.938
20.376
19.876
19.312
25.376
25.250
25.000
27.376
27.250
27.000
26.750
29.376
29.250
29.000
28.750
31.376
31.250
31.000
30.750
30.624
33.376
33.250
33.000
32.750
32.624
35.376
35.250
35.000
41.250
41.000
40.750
40.500
47.250
47.000
46
Flomotion Systems, Inc. ~ FlomotionSystems.com
Page 47
DUCTILE IRON PIPE
Standard Classes (Inside Diameters)
3 4 6 8
Outside
Diameter
(in.)
3.96 --- 3.46 3.40 3.34 3.28 3.22 3.16
4.80 --- 4.28 4.22 4.16 4.10 4.04 3.98
6.90 6.40 6.34 6.28 6.22 6.16 6.10 6.04
9.05 8.51 8.45 8.39 8.33 8.27 8.21 8.15
11.10 10.52 10.46 10.40 10.34 10.28 10.22 10.16
13.20 12.58 12.52 12.46 12.40 12.34 12.28 12.22
15.30 14.64 14.58 14.52 14.46 14.40 14.34 14.26
17.40 16.72 16.66 16.60 16.54 16.48 16.42 16.36
19.50 18.60 18.74 18.68 18.62 18.56 18.50 18.44
21.60 20.88 20.82 20.76 20.70 20.64 20.58 20.52
25.80 25.04 24.98 24.92 24.86 24.80 24.74 24.68
32.00 31.22 31.14 31.06 30.98 30.90 30.82 30.74
38.30 37.44 37.34 37.06 37.14 37.04 36.94 36.84
44.50 43.56 43.44 43.32 43.20 43.08 42.96 42.84
50.80 49.78 49.64 49.50 49.36 49.22 49.08 48.94
57.10 55.96 55.80 55.64 55.48 55.32 55.16 55.00
(in.)
10 12
14 16 18 20 24
30 36 42 48 54
** Reduce I. D. by dimension shown. These figures also apply to cast iron pipe.
Class
50
Class
51
Class
52
Class
53
Class
54
Class
55
Class
56
BE6000 Ultrasonic Flow Meter O&M Manual
Cement Lining Size
**Std.
Thickness
**Dbl.
Thickness
.125 .250
.1875 .375
.250 .500
CAST IRON PIPE
Standard Classes
CLASS A CLASS B CLASS C CLASS D CLASS E CLASS F CLASS G CLASS H Nom. Pipe Size
(in.)
O.D.
(in.)
3 3.80 3.02 3.96 3.12 3.96 3.06 3.96 3.00 --- --- --- --- --- --- --- --- 4 4.80 3.96 5.00 4.10 5.00 4.04 5.00 3.96 --- --- --- --- --- --- --- --- 6 6.90 6.02 7.10 6.14 7.10 6.08 7.10 6.00 7.22 6.06 7.22 6.00 7.38 6.08 7.38 6.00
8 9.05 8.13 9.05 8.03 9.30 8.18 9.30 8.10 9.42 8.10 9.42 8.10 9.60 8.10 9.60 8.00 10 11.10 10.10 11.10 9.96 11.40 10.16 11.40 10.04 11.60 10.12 11.60 10.00 11.84 10.12 11.84 10.00 12 13.20 12.12 13.20 11.96 13.50 12.14 13.50 12.00 13.78 12.14 13.78 12.00 14.08 12.14 14.06 12.00 14 15.30 14.16 15.30 13.98 15.65 14.17 15.65 14.01 15.98 14.18 15.98 14.00 16.32 14.18 16.32 14.00 16 17.40 16.20 17.40 16.00 17.80 16.20 17.80 16.02 18.16 16.20 18.16 16.00 18.54 16.18 18.54 16.00 18 19.50 18.22 19.50 18.00 19.92 18.18 19.92 18.00 20.34 18.20 20.34 18.00 20.78 18.22 20.78 18.00 20 21.60 20.26 21.60 20.00 22.06 20.22 22.06 20.00 22.54 20.24 22.54 20.00 23.02 20.24 23.02 20.00 24 25.80 24.28 25.80 24.02 26.32 24.22 26.32 24.00 26.90 24.28 26.90 24.00 27.76 24.26 27.76 24.00 30 31.74 29.98 32.00 29.94 32.40 30.00 32.74 30.00 33.10 30.00 33.46 30.00 --- --- --- --- 36 37.96 35.98 38.30 36.00 38.70 35.98 39.16 36.00 39.60 36.00 40.04 36.00 --- --- --- --- 42 44.20 42.00 44.50 41.94 45.10 42.02 45.58 42.02 --- --- --- --- --- --- --- --- 48 50.50 47.98 50.80 47.96 51.40 47.96 51.98 48.00 --- --- --- --- --- --- --- --- 54 56.66 53.96 57.10 54.00 57.80 54.00 58.40 53.94 --- --- --- --- --- --- --- --- 60 62.80 60.02 63.40 60.06 64.20 60.20 64.82 60.06 --- --- --- --- --- --- --- --- 72 75.34 72.10 76.00 72.10 76.88 72.10 --- --- --- --- --- --- --- --- --- --- 84 87.54 84.10 88.54 84.10 --- --- --- --- --- --- --- --- --- --- --- ---
I.D. (in)
O.D.
(in.)
I.D. (in)
O.D.
(in.)
I.D. (in)
O.D.
(in.)
I.D. (in)
O.D.
(in.)
I.D. (in)
O.D.
(in.)
I.D. (in)
O.D. (in.)
I.D. (in)
O.D.
(in.)
I.D. (in)
Flomotion Systems, Inc. ~ FlomotionSystems.com
47
Loading...