Flomec F116-P Owner's Manual

Page 1
Page 1
FL_F116P_v1702_01_EN
Signal input flowmeter: pulse, Namur and coil
Output: (0)4-20mA / 0-10V ref. flow rate, pulse ref. total and negative
flow
F-Series - Field mounted indicators for safe and hazardous areas.
Page 2
Page 2
FL_F116P_v1702_01_EN
Page 3
Page 3
FL_F116P_v1702_01_EN
SAFETY INSTRUCTIONS
Any responsibility is lapsed if the instructions and procedures as described in this manual
are not followed.
LIFE SUPPORT APPLICATIONS: The F116-P is not designed for use in life support
appliances, devices, or systems where malfunction of the product can reasonably be expected to result in a personal injury. Customers using or selling these products for use in such applications do so at their own risk and agree to fully indemnify the manufacturer and supplier for any damages resulting from such improper use or sale.
Electro static discharge does inflict irreparable damage to electronics! Before installing or
opening the F116-P, the installer has to discharge himself by touching a well-grounded object.
The F116-P must be installed in accordance with the EMC guidelines (Electro Magnetic
Compatibility).
Do connect a proper grounding to the metal enclosure as indicated if the F116-P has an
incoming power line which carries a 115-230V AC. The Protective Earth (PE) wire may never be disconnected or removed.
Intrinsically safe applications: follow the instructions as mentioned in Chapter 0 and
consult “Fluidwell F1..-..-XI - Documentation for Intrinsic safety
DISPOSAL OF ELECTRONIC WASTE
The WEEE Directive requires the recycling of disposed electrical and electronic
equipment in the European Union. When the WEEE Directive does not apply to your region, we support its policy and ask you to be aware on how to dispose of this product.
The crossed out wheelie bin symbol as illustrated and found on our products tells that this
product shall not be disposed of into the general waste system or into a landfill.
At the end of its life, equipment shall be disposed of according to the local regulations
regarding waste of the electrical and the electronic equipment.
Please contact your local dealer, national distributor or the manufacturer’s Technical
helpdesk for information on the product disposal.
SAFETY RULES AND PRECAUTIONARY MEASURES
The manufacturer accepts no responsibility whatsoever if the following safety rules and
precautions instructions and the procedures as described in this manual are not followed.
Modifications of the F116-P implemented without preceding written consent from the
manufacturer, will result in the immediate termination of product liability and warranty period.
Mounting, electrical installation, start-up and maintenance of this device may only be
carried out by trained persons authorized by the operator of the facility. Persons must read and understand this manual before carrying out its instructions.
This device may only be operated by persons who are authorized and trained by the
operator of the facility. All instructions in this manual are to be observed.
Check the mains voltage and information on the manufacturer's plate before installing the
unit.
Check all connections, settings and technical specifications of the various peripheral
devices with the F116-P supplied.
Open the enclosure only if all leads are free of potential. Never touch the electronic components (ESD sensitivity). Never expose the system to heavier conditions than allowed according the classification
of the enclosure (see manufacture's plate and chapter 4).
If the operator detects errors or dangers, or disagrees with the safety precautions taken,
then inform the owner or principal responsible.
The local labor and safety laws and regulations must be adhered to.
Page 4
Page 4
FL_F116P_v1702_01_EN
ABOUT THE MANUAL
This manual is divided into two main sections:
The daily use of the F116-P is described in chapter 2 Operational. These instructions are
meant for users.
The following chapters and appendices are exclusively meant for electricians/technicians. These
provide a detailed description of all software settings and hardware installation guidance.
This manual describes the standard unit as well as the available options. For additional information, please contact your supplier.
A hazardous situation may occur if the F116-P is not used for the purpose it was designed for or is used incorrectly. Please carefully note the information in this manual indicated by the pictograms:
A "warning !" indicates actions or procedures which, if not performed correctly, may lead to personal injury, a safety hazard or damage of the F116-P or connected instruments.
A "caution !" indicates actions or procedures which, if not performed correctly, may lead to personal injury or incorrect functioning of the F116-P or connected instruments.
A "note !" indicates actions or procedures which, if not performed correctly, may indirectly affect operation or may lead to an instrument response which is not planned.
Hardware version : 03.01.xx Software version : 03.01.xx Manual : FL_F116-P_v1702_01_EN © Copyright 2017 : Fluidwell B.V. - The Netherlands.
Information in this manual is subject to change without prior notice. The manufacturer is not responsible for mistakes in this material or for incidental damage caused as a direct or indirect result of the delivery, performance or use of this material.
© All rights reserved. No parts of this publication may be reproduced or used in any form or by any means without written permission of your supplier.
Page 5
Page 5
FL_F116P_v1702_01_EN
CONTENTS MANUAL
SAFETY INSTRUCTIONS .................................................................................................................... 3
DISPOSAL OF ELECTRONIC WASTE ............................................................................................... 3
SAFETY RULES AND PRECAUTIONARY MEASURES .................................................................... 3
ABOUT THE MANUAL ......................................................................................................................... 4
CONTENTS MANUAL .......................................................................................................................... 5
1 INTRODUCTION ...................................................................................................................... 6
1.1 System description ...................................................................................................................6
2 OPERATIONAL ....................................................................................................................... 7
2.1 Control panel ............................................................................................................................7
2.2 Operator information and functions ..........................................................................................8
3 CONFIGURATION ................................................................................................................... 9
3.1 How to program the F116-P .....................................................................................................9
3.1.1 Setup menu – Settings .......................................................................................................... 11
3.1.2 Explanation of SETUP-menu 1 - Total-A............................................................................... 12
3.1.3 Explanation of SETUP-menu 2 - Flow rate-A ........................................................................ 13
3.1.4 Explanation of SETUP-menu 3 - Total-B............................................................................... 14
3.1.5 Explanation of SETUP-menu 4 - Flow rate-B ........................................................................ 14
3.1.6 Explanation of SETUP-menu 5 - Display .............................................................................. 14
3.1.7 Explanation of SETUP-menu 6 - Power management .......................................................... 15
3.1.8 Explanation of SETUP-menu 7 - Flowmeter ......................................................................... 16
3.1.9 Explanation of SETUP-menu 8 - Analog output .................................................................... 16
3.1.10 Explanation of SETUP-menu 9 - Pulse ................................................................................. 18
3.1.11 Explanation of SETUP-menu A - Communication (option) ................................................... 18
3.1.12 Explanation of SETUP-menu B - Others ............................................................................... 18
4 INSTALLATION ..................................................................................................................... 19
4.1 General directions ................................................................................................................. 19
4.2 Installation / surrounding conditions ...................................................................................... 19
4.3 Dimensions- Enclosure.......................................................................................................... 20
4.4 Installing the hardware .......................................................................................................... 22
4.4.1. General installation guidelines .............................................................................................. 22
4.4.2. Aluminum enclosure - Field mounted .................................................................................... 23
4.4.3. Aluminum enclosure - Panel mounted .................................................................................. 23
4.4.4. Plastic (GRP) enclosure ........................................................................................................ 24
4.4.5. Terminal connectors .............................................................................................................. 25
5 INTRINSICALLY SAFE APPLICATIONS.............................................................................. 32
5.1 General information and safety instructions .......................................................................... 32
5.2 Terminal connectors Intrinsically safe applications ............................................................... 34
5.3 Configuration examples Intrinsically safe applications .......................................................... 36
6 MAINTENANCE ..................................................................................................................... 38
6.1 General directions ................................................................................................................. 38
6.2 Instructions for repair ............................................................................................................. 38
6.3 Battery replacement .............................................................................................................. 39
6.3.1 Safety instructions ................................................................................................................. 39
6.3.2 Replace the battery (hazardous area) ................................................................................... 39
6.3.3 Disposal of batteries .............................................................................................................. 39
TECHNICAL SPECIFICATION ................................................................................. 40
PROBLEM SOLVING ............................................................................................... 43
COMMUNICATION ................................................................................................... 44
DECLARATION OF CONFORMITY ......................................................................... 48
INDEX OF THIS MANUAL.................................................................................................................. 49
LIST OF FIGURES IN THIS MANUAL ............................................................................................... 49
Page 6
Page 6
FL_F116P_v1702_01_EN
1 INTRODUCTION
1.1 SYSTEM DESCRIPTION Functions and features
The flow rate / totalizer model F116-P is a microprocessor driven instrument designed to show the flow rate, the total and the accumulated total as well as for the calculation of differential flow measurement and to sum two separate flows. This product has been designed with a focus on:
two multi-purpose pulse inputs; ultra-low power consumption to allow long-life battery powered applications (type PB/PC), Intrinsic safety for use in hazardous applications (type XI); several mounting possibilities with aluminum or GRP enclosures for harsh industrial
surroundings;
ability to process all types of flowmeter signals; transmitting possibilities with analog / pulse and communication outputs.
Flowmeter and temperature input
This manual describes the unit with a pulse input from the flowmeter. Other versions are available to process (0)4-20mA signals. Two flowmeters with a passive or active pulse, Namur or sine wave (coil) signal output can be connected to the F116-P. To power the sensor, several options are available.
Standard output
Pulse output to transmit a pulse that represents a totalized quantity as programmed.  Linear (0)4-20mA or 0-10V analog output to represent the actual calculated differential flow rate
as programmed. The (0)4-20mA or 0-10V signal limits can be tuned.
Fig. 1: Typical application
Page 7
Page 7
FL_F116P_v1702_01_EN
Configuration
The F116-P is designed for use in many types of applications. For that reason, a setup menu is available to program the F116-P according to your specific requirements.
The setup includes several important features, such as K-Factors, engineering units, signal selection, power management (to extend battery life-time), etc. All settings are stored in a non­volatile memory and therefore kept in the event of a power failure or an exhausted battery.
Display information
The unit has a LCD with (optional) backlight to show the process information, status and alarm messages. The display refresh rate is programmed in the setup menu.
At a key press, the display refresh rate will switch to FAST for 30 seconds. When 'OFF' is selected, the display goes off after 30 seconds after the last key press. The display temporarily comes on after a key press.
A backup of the total and accumulated total in EEPROM memory is made every minute.
Backlight
A backlight is available as an option. The brightness can be tuned as desired (requires power supply type PD/PF/PM). For battery and loop powered applications the backlight will not function.
Options
The following options are available: isolated or active (0)4-20mA / 0-10V analog output, full Modbus communication RS232/485/TTL (also battery powered), Intrinsic safety, mechanical relay or active output, power- and sensor-supply options, panel-mount, wall-mount and weather-proof enclosures, flame proof enclosure and LED backlight.
2 OPERATIONAL
This device may only be operated by persons who are authorized and trained by the
operator of the facility. All instructions in this manual are to be observed.
Take careful notice of the "Safety rules, instructions and precautionary measures" in the
front of this manual.
This chapter describes the daily use of the F116-P. This instruction is meant for users / operators.
2.1 CONTROL PANEL
The control panel has three keys. The available keys are:
Fig. 2: Control panel
Functions of the keys
This key is used to program and save new values or settings. The PROG/ENTER key is also used to gain access to the setup menu (read
chapter 3).
This key is used to select the differential or sum accumulated total, flow rate A and B and accumulated total A and B
The SELECT/ key is also used to increase a value after the PROG/ENTER key has been pressed (read chapter 3)..
This key is used to reset the total. The CLEAR/ key is also used to select a digit or an option after the PROG/ENTER
key has been pressed (read chapter 3).
Page 8
Page 8
FL_F116P_v1702_01_EN
2.2 OPERATOR INFORMATION AND FUNCTIONS
In general, the F116-P operates in the operator mode. The shown information depends on the settings which are made in the setup menu.
The signal from the connected sensor is processed by the F116-P in the background, independent from the selected display refresh rate.
Fig. 3: Process information (typical)
For the Operator, the following functions are available:
Display (differential or summed) total/rate
Total/rate is the main display of the F116-P. After the selection of any other information, it will always return to this main display automatically. Total is shown on the upper line of the display and flow rate on the bottom line. When selected in the setup menu, the display shows the flow rate only or all. When the SELECT/ key is pressed, the other information shows momentarily.
When "-------" is shown, then the flow rate value is too high to be shown. The arrows indicate the increase/decrease of the flow rate trend. If the consumption is very low, it might be that a stable low flow rate and total is shown; this is due to the settings of the F116-P.
Clear total
The value for total can be reset. To do so, press the CLEAR/ key twice. When the key is pressed once, the text "PUSH CLEAR" is shown. To avoid a reset at this stage, press another key other than the CLEAR/ key or wait for 20 seconds. A reset of the total does not influence the accumulated total.
Display accumulated total
When the SELECT/ key is pressed, total and accumulated total are shown. The accumulated total cannot be reset. The value will count up to 99,999,999,999. The unit and number of decimals are shown according to the settings for the total.
Display Flow rate-A, Flow rate-B, (accumulated) total-A, (accumulated) total-B
The setting All shows the (differential or summed) flow rate. When the SELECT/ key is pressed again, the total/accumulated total, the flow rate A, the accumulated total A, the flow rate B and the accumulated total B are shown temporarily.
Low-battery alarm
Only use original batteries. Original batteries can be ordered at the manufacturer. The use of unapproved batteries will void the warranty.
At the end of the battery’s life-time, the voltage starts to drop. When the voltage becomes too low, the battery indicator comes on. When the battery indicator is on, install a
new and fresh battery as soon as possible.
Fig. 4: Low-battery alarm (typical)
Alarm
When the alarm indicator is shown, refer to Appendix B: Problem Solving.
RUN
Page 9
Page 9
FL_F116P_v1702_01_EN
3 CONFIGURATION
This and the following chapters are exclusively meant for electricians and non-operators. In these, an extensive description of all software settings and hardware connections are provided.
Mounting, electrical installation, start-up and maintenance of this device may only be
carried out by trained persons authorized by the operator of the facility. Persons must read and understand this manual before carrying out its instructions.
This device may only be operated by persons who are authorized and trained by the
operator of the facility. All instructions in this manual are to be observed.
Make sure, the measuring system is correctly wired up according to the wiring diagrams.
Protection against accidental contact is no longer assured when the housing cover is removed or the panel cabinet has been opened (danger from electrical shock). The housing may only be opened by trained persons authorized by the operator of the facility.
Take careful notice of the "Safety rules, instructions and precautionary measures" in the
front of this manual.
The SETUP menu is used to program the F116-P The SETUP menu is accessible at all times while the F116-P remains fully operational. Be aware
that in this case any change to the settings may have an influence on the operation.
It is possible to prevent access to the SETUP menu with a password. A password may be required to enter the SETUP menu. Without this password, access to SETUP is denied.
3.1 HOW TO PROGRAM THE F116-P
The setup menu has different submenus. Each submenu has an unique number which is shown in front of the menu name.
Each setting has an unique two­digit number which is shown in front of the setting. The first digit refers to the submenu and the second digit refers to the setting.
Note that sometimes the name of the setting is shown on the upper line of the display.
How to enter the setup menu
When the setup menu is protected by a password, the F116-P asks for a password to access the setup menu. When in the operator mode, press and hold the PROG/ENTER key for 7 seconds to access the setup menu.
How to navigate in the setup menu
The setup menu has different submenus to program the F116-P. For navigation, the submenus and the settings are identified with numbers (for the submenu: e.g. 1; for the setting: e.g. 12.).
The CLEAR/► key and the PROG/ENTER key are used for navigation. The explanation
assumes that you are in the submenu TOTAL.
Action
Result
Remark
1
Press the CLEAR/► key to
select the next submenu.
The submenu FLOW
RATE shows
-
2
Press again to go to the next submenu.
The submenu DISPLAY
shows.
-
3
Momentarily, press the PROG/ENTER key to select the previous submenu.
The submenu FLOW
RATE shows
The PROG/ENTER key is used as a key. 4
Press again to go to the previous submenu.
The submenu TOTAL
shows
The PROG/ENTER key is used as a key.
Page 10
Page 10
FL_F116P_v1702_01_EN
The SELECT/▲ key and the CLEAR/► key are used for navigation. The explanation assumes that you are in the submenu TOTAL. When you are: in the first setting and you navigate to the previous setting, the F116-P goes back to the related
main menu.
in the last setting and you navigate to the next setting, the F116-P goes to the related main
menu.
Action
Result
Remark
1
Press the SELECT/▲ key
to select the first setting.
The setting UNIT shows.
-
2
Press the SELECT/▲ key
again to go to the next setting.
The setting DECIMALS
shows.
­3
Press the CLEAR/► key to
select the previous setting.
The setting UNIT shows.
-
4
Press the CLEAR/►key
again to go to the previous setting.
The submenu TOTAL
shows
This is normal behavior because the setting UNIT is the first setting of the submenu TOTAL.
How to make a setting
Changes are only saved when you press the PROG/ENTER key.
The explanation assumes that you are in the submenu TOTAL and the setting UNIT. When you do not want to save the change, wait for approximately 20 seconds or press and hold the PROG/ENTER key for approximately 3 seconds.
Action
Result
Remark
1
Momentarily, press the PROG/ENTER key.
The PROG indicator blinks. The engineering unit L shows.
To access the setting.
2
Press the SELECT/▲ key to
select the next engineering unit.
The PROG indicator blinks. The engineering unit m3 shows.
If you wait too long, the program mode goes off and changes are not saved, this is normal behavior.
3
Press the SELECT/▲ key to
select the next engineering unit.
The PROG indicator blinks. The engineering unit US GAL
shows.
-
4
Press the CLEAR/► key to
select the previous engineering unit
The PROG indicator blinks. The engineering unit m3 shows.
-
5
To confirm the changes: Momentarily, press the PROG/ENTER key.
The PROG indicator goes off. The change is saved. The engineering unit m3 shows.
If you do not press the PROG/ENTER key to confirm, your selection is not saved.
To discard the changes: Press and hold the PROG/ENTER key for approximately 3 seconds.
The PROG indicator goes off. The change is discarded. The engineering unit L shows.
-
Page 11
Page 11
FL_F116P_v1702_01_EN
3.1.1 SETUP MENU – SETTINGS
1
TOTAL-A
11
unit
L; m3; kg; lb; GAL; USGAL; bbl; no unit
12
decimals
0000000; 111111.1; 22222.22; 3333.333
13
K-factor
0.000010 - 9999999
14
decimals K-factor
0 - 6
2
FLOW RATE-A
21
unit
mL; L; m3; mg; g; kg; ton; gal; bbl; lb; cf; rev; - - - - (no unit); scf; nm3; nL; p
22
time
/sec; /min; /hour; /day
23
decimals
0000000; 111111.1; 22222.22; 3333.333
24
K-factor
0.000010 - 9999999
25
decimals K-factor
0 - 6 26
filter
0 - 99
27
period
0.1 - 99.9 seconds
3
TOTAL-B
31
K-factor:
0.000010 - 9999999
32
decimals K-factor
0 - 6
4
FLOW RATE-B
41
K-factor
0.000010 - 9999999
42
decimals K-factor
0 - 6
5
DISPLAY
51
function
total; rate; all
52
light
0% (off); 20%; 40%; 60%;- 80%; 100% (full brightness)
53
calculate
add; differ
54
measurement
bi-direct; not negative; threshold; stationary
55
stationary flow rate
0000.000 - 9999999
56
stationary total
0000.000 - 9999.999
6
POWER MANAGEMENT
61
LCD new
fast; 1 sec; 3 sec; 15 sec; 30 sec; off
62
battery mode
operational; shelf
7
FLOWMETER
71
signal A
npn; npn-lp; reed; reed-lp; pnp; pnp-lp; namur; coil-hi; coil-lo; 8-1 DC; 12 DC; 24 DC
72
signal B
npn; npn-lp; reed; reed-lp; pnp; pnp-lp; namur; coil-hi; coil-lo; 8-1 DC; 12 DC; 24 DC
8
ANALOG
81
output
disable; enable
82
rate-min
000.000 - 999999
83
rate-max
000.000 - 999999
84
cut-off
0.0 - 9.9%
85
tune-min
0 - 9999
86
tune-max
0 - 9999
87
filter
01 - 99
9
PULSE
91
mode
signed; not negative; separated
92
width
0.001 – 9
93
decimals
0000000; 111111.1; 22222.22; 3333.333
94
amount
0.001 – 9999999
Page 12
Page 12
FL_F116P_v1702_01_EN
A
COMMUNICATION
C1
speed
1200; 2400; 4800; 9600
C2
address
1 - 247
C3
mode
bus-rtu; bus-asc; off
D
OTHERS
D1
model
F116-P
D2
software version
nn:nn:nn
D3
serial no.
nnnnnnn
D4
password
0000 - 9999
D5
tag-nr
0000000 - 9999999
3.1.2 EXPLANATION OF SETUP-MENU 1 - TOTAL-A
1
TOTAL-A
11
unit
This setting is used to select the engineering unit for the indication of the total (A and B), the accumulated total (A and B), and the pulse output.
When you change the engineering unit, you must recalculate and reprogram the K-factor for the (accumulated) total. When you recalculate and reprogram the K-Factor, the history for (accumulated) total is not correct anymore, because the (accumulated) total is not recalculated. For future reference, best practice is to make a note of the accumulated total before you program the recalculated K-Factor.
12
decimals
This setting is used to set the amount of digits behind the decimal point for the (accumulated) total indication (A and B).
13
K-factor
This setting is used to set the K-Factor for the total (A). With the K-Factor, the flowmeter pulse signals are converted to a quantity. The K-Factor is based on the number of pulses generated by the flowmeter per selected engineering unit, for example per m3. A more accurate K-Factor (more decimals, as set in decimals K-Factor) allows for a more accurate operation of the system.
Example 1: Calculating the K-Factor.
The flowmeter generates 2.4813 pulses per liter and the selected unit is m3. A cubic meter consists of 1000 liter which gives 2.4813 pulses*1000 liter=2481.3 pulses per m3. So, the K-Factor is 2481.3. Enter for the Flowmeter K-Factor: 24813 and for the flowmeter K-Factor decimals: 1.
Example 2: Calculating the K-Factor.
The flowmeter generates 6.5231 pulses per gallon and the selected engineering unit is gallons. So, the K-Factor is 6.5231. Enter for the Flowmeter K-Factor: 65231 and for the Flowmeter K-Factor decimals: 4.
When you recalculate and reprogram a new K-Factor, the history for (accumulated) total is not correct anymore, because the (accumulated) total is not recalculated. For future reference, best practice is to make a note of the accumulated total before you program the recalculated K-Factor.
14
decimals K-factor
This setting is used to set the amount of digits behind the decimal point for the K-Factor (A).
Page 13
Page 13
FL_F116P_v1702_01_EN
3.1.3 EXPLANATION OF SETUP-MENU 2 - FLOW RATE-A
The settings for total and flow rate are entirely separate. In this way, different engineering units can be used for each e.g. cubic meters for total and liters for flow rate.
2
FLOW RATE-A
21
unit
This setting is used to select the engineering unit for the indication of the flow rate (A and B).
Alteration of the engineering unit will have consequences for operator and setup values, they will not be automatically recalculated to the value of the new selected unit. The K-Factor has to be adapted as well; the calculation is not done automatically.
22
time
This setting is used to set the time unit for the flow rate calculation (A and B). Note that the flow rate is given in engineering unit/time unit, e.g. liters/minute (l/min).
When you change this setting, also recalculate and change the settings for the analog rate-min and analog rate-max.
23
decimals
This setting is used to set the amount of digits behind the decimal point for the flow rate indication (A and B).
24
K-factor
This setting is used to set the K-Factor for the flow rate (A). With the K-Factor, the flowmeter pulse signals are converted to a quantity. The K-Factor is based on the number of pulses generated by the flowmeter per selected engineering unit, for example per m3. A more accurate K-Factor (more decimals, as set in decimals K-Factor) allows for a more accurate operation of the system.
25
decimals K-factor
This setting is used to set the amount of digits behind the decimal point for the K-Factor (A).
26
filter
This setting is used to stabilize the output signal. With the help of this digital filter a more stable but less actual representation of the flow rate can be obtained.
The filter principal is based on three input values: the filter level (01-99), the last calculated flow rate and the last average value. The higher the filter level, the longer the response time on a value change will be.
27
period
This setting is used to calculate the flow rate by counting the number of pulses within a certain time, for example 1 second. The longer the time the more accurate the flow rate will be.
This setting does influence the update time for the analog output directly. If the
output response is too slow, decrease the number of pulses.
The shorter the update time, the higher the power consumption of the unit will
be (important for battery powered applications).
Page 14
Page 14
FL_F116P_v1702_01_EN
3.1.4 EXPLANATION OF SETUP-MENU 3 - TOTAL-B
The engineering units are the same as used in SETUP-menu 1 - Total-A.
3
TOTAL-B
31
K-factor
This setting is used to set the K-Factor for the total (B). With the K-Factor, the flowmeter pulse signals are converted to a quantity. The K-Factor is based on the number of pulses generated by the flowmeter per selected engineering unit, for example per m3. A more accurate K-Factor (more decimals, as set in decimals K-Factor) allows for a more accurate operation of the system.
32
decimals K-factor
This setting is used to set the amount of digits behind the decimal point for the (accumulated) total indication (B).
3.1.5 EXPLANATION OF SETUP-MENU 4 - FLOW RATE-B
The engineering units are the same as used in SETUP-menu 2 - Flow rate-A.
4
FLOW RATE-B
41
K-factor
This setting is used to set the K-Factor for the flow rate (B). With the K-Factor, the flowmeter pulse signals are converted to a quantity. The K-Factor is based on the number of pulses generated by the flowmeter per selected engineering unit, for example per m3. A more accurate K-Factor (more decimals, as set in decimals K-Factor) allows for a more accurate operation of the system.
42
decimals K-factor
This setting is used to set the amount of digits behind the decimal point for the K-Factor (B).
3.1.6 EXPLANATION OF SETUP-MENU 5 - DISPLAY
5
DISPLAY
51
function
This setting can be set to display total or rate.
When 'total' is selected, simultaneously, (differential or summed) total and
(differential or summed) flow rate is shown. When SELECT is pressed, the (differential or summed) accumulated total is shown temporarily.
When 'rate' is selected, only (differential or summed) flow rate is shown
together with its engineering unit. When SELECT is pressed, the (differential or summed) total and the (differential or summed) accumulated total are shown temporarily.
When ‘All’ is selected, only (differential or summed) flow rate is shown together
with its engineering unit. When SELECT is pressed again, the (differential or summed) total/accumulated total, the flow rate A, the accumulated total A, the flow rate B and the accumulated total B are shown temporarily.
52
light
The backlight brightness can be adjusted from 0% (off) to 100% (full brightness) in steps of 20%. When the F116-P is only loop powered, the backlight is disabled. An external power supply is required to supply the backlight.
53
measurement
To solve undesired display readings during low or even negative consumption situations, four different measurement methods have been implemented. Note that the selection does influence the analog output value (ref. flow rate) as well.
bi-directional
Shown flow rate: positive and negative. Shown total: increases or decreases.
not negative
Shown flow rate: only positive or zero. Shown total: increases or decreases.
Page 15
Page 15
FL_F116P_v1702_01_EN
threshold
Shown flow rate: as soon as the flow rate is lower than SETUP 54 or negative, zero flow rate is shown. Shown total: as soon as the flow rate is lower than SETUP 54 or negative, totalization will stop.
stationary
Shown flow rate: as soon as the flow rate is lower than SETUP 54 or negative, the stationary flow rate (SETUP 54) is shown. Shown total: as soon as the flow rate is lower as SETUP 54 or negative, stationary totalization (SETUP 55) will be activated. However, if the value of setting 54 is zero, totalization increases or decreases.
54
stationary flow rate
Enter here the flow rate according SETUP 53: threshold or stationary. The time and measuring units are according to flow rate SETUP 21 and 22.
threshold
Flow rate zero is shown as soon as the flow rate will be lower as this setting.
stationary
As soon as the flow rate is lower as this setting, this flow rate is shown.
If the flowmeters do not generate pulses, the flow rate shows zero.
55
stationary total
Enter here a flow rate per hour according to SETUP 53 – ‘stationary’. The measuring unit is according to TOTAL (A and B) - SETUP 11. This flow rate is converted to a total which will be used as long as the flow rate is lower as SETUP 54.
If the flowmeters do not generate pulses, the totalization will stop. This function is disabled if value zero has been entered.
3.1.7 EXPLANATION OF SETUP-MENU 6 - POWER MANAGEMENT
When used with the internal battery option (type PB/PC), the user can expect reliable measurement over a long period of time. The F116-P has several smart power management functions to extend the battery life time significantly. Two of these functions can be set.
6
POWER MANAGEMENT
61
lcd new
The calculation of the display-information influences the power consumption significantly. When the application does not require a fast display refresh rate, it is strongly advised to select a slow refresh rate. Please understand that NO information will be lost; every pulse will be counted and the output signals will be generated in the normal way. At a key press, the display refresh rate will switch to FAST for 30 seconds. When 'OFF' is selected, the display goes off after 30 seconds after the last key press. The display temporarily comes on after a key press.
Example battery life-time with a coil pick-up:
1kHz pulse and FAST update: about 2 years; 1kHz pulse and 1 sec update: about 5 years.
62
battery mode
The F116-P has two modes: operational or shelf. After "shelf" has been selected, the F116-P can be stored for several years; it will not process the sensor signal; the display is switched off but all settings and totals are stored. In this mode, power consumption is extremely low. To wake up the F116-P again, press the SELECT/ key two times.
Page 16
Page 16
FL_F116P_v1702_01_EN
3.1.8 EXPLANATION OF SETUP-MENU 7 - FLOWMETER
The F116-P is able to handle several types of input signal. The pickup / signal is selected with:
SETUP 71 (Input A), Read also chapter 4 SETUP 72 (Input B), Read also chapter 4.
The selections "active pulse" offer a detection level of 50% of the supply voltage.
7
FLOWMETER
71/72
SIGNAL
TYPE OF SIGNAL
EXPLANATION
RESISTANCE
FREQ. / mV
REMARK
NPN
NPN input
100 kΩ pull-up
max. 6 kHz.
(open collector)
NPN-LP
NPN with low pass filter
100 kΩ pull-up
max. 1.2 kHz.
(open collector)
less sensitive
REED
Reed-switch input
1 MΩ pull-up
max. 600 Hz.
REED-LP
Reed-with low pass filter
1 MΩ pull-up
max. 120 Hz.
Less sensitive
PNP
PNP input
100 kΩ pull-down
max. 6 kHz.
PNP-LP
PNP with low pass filter
100 kΩ pull-down
max. 1.2 kHz.
Less sensitive
NAMUR
NAMUR input
820 Ω pull-down
max. 4 kHz.
External power
required
COIL-HI
High sensitive coil input
-
min. 20 mVpp
Sensitive for interference!
COIL-HI (option ZF)
min. 10 mVpp
COIL-HI (option ZG)
min. 5 mVpp
COIL-LO
Low sensitive coil input
-
min. 80 mVpp
Normal sensitivity
8-1 DC
Active pulse input
detection level 8.2V DC
3.9
max. 10 kHz.
External power
required
12 DC
Active pulse input
detection level 12V DC
4
max. 10 kHz.
External power
required
24 DC
Active pulse input
detection level 24V DC
3
max. 10 kHz.
External power
required
3.1.9 EXPLANATION OF SETUP-MENU 8 - ANALOG OUTPUT
A linear 4-20mA signal (option AB: 0-20mA or option AU: 0-10V) output signal is generated that represents the flow rate. The settings for the flow rate influence the analog output directly. The relationship between the flow rate and the analog output is set with the following settings.
8
ANALOG OUTPUT
81
output
If the analog output is not used, select disable to minimize the power consumption (e.g. save battery life-time).
Option AP: When a power supply is available but the output is disabled, a 3.5mA signal will be generated.
82
rate-min
Enter here the flow rate at which the output should generate the minimum signal (0)4mA or 0V - in most applications at zero flow. The number of decimals shown depend upon setup 23. The engineering units/time (e.g. L/min) are dependent upon setup 21 and 22.
83
rate-max
Enter here the flow rate at which the output should generate the maximum signal (20mA or 10V) - in most applications at maximum flow. The number of decimals shown depend upon setup 23. The engineering units/time (e.g. L/min) are dependent upon setup 21 and 22.
Page 17
Page 17
FL_F116P_v1702_01_EN
84
cut-off
To ignore leakage of the flow for example, a low flow cut-off can be set as a percentage of the full range of 16mA, 20mA or 10V. When the flow is less than the required rate, the current will be the minimum signal (0)4mA or 0V.
Example: Calculate the cut-off. Rate-min: 0L/min [4mA], Rate-max: 100 L/min [16mA], Cut-off: 2%
Required rate [L/min]: (rate-max - rate-min)*cut-off: (100-0)*2%=2.0L/min Output [mA]: rate-min + (rate-max*cut-off): 4+(16*2%)=4.32mA
85
tune-min
The (0)4mA or 0V value can be tuned precisely with this setting. The initial minimum analog output value is (0)4mA or 0V. However, this value might differ slightly due to ambient influences such as temperature for example.
Before tuning the signal, make sure that the analog signal is idle (not used) for any application!
After pressing PROG, the current will be about 4mA (0mA or 0V). The current can be increased / decreased with the arrow keys and is directly active. Press ENTER to store the new value.
If required, you can program the analog output 'up-side-down'. The (0)4mA or 0V represents the maximum flow rate and the 20mA or 10V represents the minimum flow rate.
86
tune-max
The 20mA or 10V value can be tuned precisely with this setting. The initial maximum analog output value is 20mA or 10V However, this value might differ slightly due to ambient influences such as temperature for example.
Before tuning the signal, make sure that the analog signal is idle (not used) for any application!
After pressing PROG, the current will be about 20mA or 10V. The current can be increased / decreased with the arrow keys and is directly active. Press ENTER to store the new value.
If required, you can program the analog output 'up-side-down'. The (0)4mA or 0V represents the maximum flow rate and the 20mA or 10V represents the minimum flow rate.
87
filter
This setting is used to stabilize the output signal. With the help of this digital filter a more stable but less actual representation of the flow rate can be obtained. The filter principal is based on three input values: the filter level (01-99), the last calculated flow rate and the last average value. The higher the filter level, the longer the response time on a value change will be.
filter value
RESPONSE TIME ON STEP CHANGE OF ANALOG VALUE. TIME IN SECONDS
influence
01 02 03 05 10 20 30 50 75 99
50%
filter disabled
0.1 sec
0.3 sec
0.5 sec
0.9 sec
1.8 sec
2.6 sec
4.4 sec
6.5 sec
8.6 sec
75%
filter disabled
0.3 sec
0.5 sec
0.9 sec
1.8 sec
3.5 sec
5.1 sec
8.6 sec 13 sec 17 sec
90%
filter disabled
0.5 sec
0.8 sec
1.4 sec
2.8 sec
5.6 sec
8.5 sec 14 sec 22 sec 28 sec
99%
filter disabled
0.9 sec
1.5 sec
2.6 sec
5.5 sec 11 sec 17 sec 29 sec 43 sec 57 sec
Page 18
Page 18
FL_F116P_v1702_01_EN
3.1.10 EXPLANATION OF SETUP-MENU 9 - PULSE
9
PULSE
91
mode
The unit has three scaled pulse output modes. This functionality drives two pulse outputs which, depending on the mode, can be used as follows:
signed
On pulse output R1 a pulse will be send when the total has increased or decreased with the set quantity (SETUP 94). Pulse output R2 will send a 0 for increase or 1 for decrease.
not negative
On pulse output R1 a pulse will be sent when the total has increased with the set quantity (SETUP 94). On pulse output R2 the sign of the flow rate will be send (positive=0, negative=1).
separated
On pulse output R1 a pulse will be sent when the total has increased with the set quantity (SETUP 94). On pulse output R2 a pulse will be sent when the total has decreased with the set quantity (SETUP 94).
92
width
The pulse width determines the time that the output will be active; in other words the pulse duration. Value “zero” will disable the pulse output. The pulse signal always has a 50% duty cycle, hence the minimum time between the pulses is equal to the pulse width setting. If the frequency should go out of range – when the flow rate increases for example – an internal buffer will be used
to “store the missed pulses”: As soon as the flow rate slows down, the buffer will be “emptied”.
It might be that pulses will be missed due to a buffer-overflow, so it is advised to program this setting within its range!
93
decimals
This setting is used to set the amount of digits behind the decimal point for the amount.
94
amount
A pulse will be generated every time a certain quantity is added to the total. Enter this quantity here while taking the decimals for pulse into account.
3.1.11 EXPLANATION OF SETUP-MENU A - COMMUNICATION (OPTION)
This product is designed for the connection to a communication network. Products with a communication option do not include cyber security functions. Fluidwell cannot take any responsibility for the cyber security, omissions or errors in the communication safety. To maintain a secure operation, automation and control, it is the sole responsibility of the owner to install and manage the appropriate safety measures to protect the network, the product and the communication against any kind of security breaches.
The functions described below deal with hardware that is not part of the standard delivery. Programming of these functions does not have any effect if this hardware has not been installed. Consult Appendix C and the Modbus communication protocol description for a detailed explanation.
A
COMMUNICATION
A1
speed
This setting is used to set the Baudrate.
A2
address
This setting is used to set the communication address for the F116-P.
A3
mode
This setting is used to set the Modbus transmission mode. Select OFF to disable the communication.
3.1.12 EXPLANATION OF SETUP-MENU B - OTHERS
For support and maintenance it is important to have information about the characteristics of the F116-P. Your supplier will ask for this information when support is required.
B
OTHERS
B1
model
This setting shows the model name.
B2
software version
This setting shows the version number of the firmware (software).
B3
serial no.
This setting shows the serial number.
B4
password
This setting is used to set a password (pin code) to limit the access for the setup menu. Only persons who know the pin code can access the setup menu. The pin code 0000 disables the pin code to allow for access by any person.
B5
tag-nr
This setting is used to set a tag number for the F116-P.
Page 19
Page 19
FL_F116P_v1702_01_EN
4 INSTALLATION
4.1 GENERAL DIRECTIONS
Mounting, electrical installation, start-up and maintenance of this device may only be
carried out by trained persons authorized by the operator of the facility. Persons must read and understand this manual before carrying out its instructions.
This device may only be operated by persons who are authorized and trained by the
operator of the facility. All instructions in this manual are to be observed.
Make sure, the measuring system is correctly wired up according to the wiring diagrams.
Protection against accidental contact is no longer assured when the housing cover is removed or the panel cabinet has been opened (danger from electrical shock). The housing may only be opened by trained persons authorized by the operator of the facility.
Take careful notice of the "Safety rules, instructions and precautionary measures" at the
front of this manual.
4.2 INSTALLATION / SURROUNDING CONDITIONS
Take the relevant IP classification of the enclosure into account (see identification plate). Even an enclosure rated for IP67 / TYPE 4(X) should NEVER be exposed to strongly varying (weather) conditions.
When panel-mounted, the front panel of the F116-P is rated for IP65 / TYPE 4(X)!
When used in very cold surroundings or varying climatic conditions, inside the instrument case, take the necessary precautions against moisture.
Mount the F116-P onto a solid structure to avoid vibrations.
Page 20
Page 20
FL_F116P_v1702_01_EN
4.3 DIMENSIONS- ENCLOSURE
Fig. 5: Aluminum enclosures - Dimensions
75 mm (2.95")
130 mm (5.12")
112 mm (4.40")
1
2
0
m
m
(
4
.
7
2
)
M20 x 1,5
PG9
PG9
30mm 30mm
M20 x 1,5
M16 x 1,5 M16 x 1,5
30mm 30mm
M20 x 1,5
M20 x 1,5 M20 x 1,5
25mm 25mm
1/2"NPT
0
.
9
3x 1/2"NPT
0.12" 0.12"
HA
HM
HN
HO
HP
HT
HU
6 x M12
12mm
12mm
24mm 24mm
36mm
36mm
1
4
m
m
1
7
m
m
115 mm (4.53”)
HB
29.1 mm (1.15”)
31 mm
(1.22”)
HZ
4x M20 x 1,5
15 15
HV
23 23
1
6
mm
1/2"NPT 1/2"NPT
25mm 25mm
2
2
,
5
m
m
HL
2
2
,
5
m
m
2
2
,
5
m
m
2
2
,
5
m
m
2
2
,
5
m
m
0
.
9
1
5
6
0
m
m
(
2
.
3
6
)
9
8
m
m
(
3
.
8
6
)
Page 21
Page 21
FL_F116P_v1702_01_EN
Fig. 6: GRP enclosures - Dimensions
75 mm (2.95")
130 mm (5.12")
112 mm (4.40")
60 mm (2.36")
120 mm (4.72")
HD HK
HK back box:
(flat bottom)
HE
HF
HG
HH
D=12mm
12mm
12mm
24mm24mm
36mm
36mm
14mm
17mm
22,5mm
30mm 30mm
D=16mm
D=20mm
0.9"
D=22mm (0.866")
22,5mm
25mm 25mm
D=20mm D=20mm
D=16mm
HC
75 mm (2.95")
118 mm (4.65”)
104 mm (4.09”)
HJ
0.9
0.12” 0.12”
3x D=22mm (0.866”)
115 mm (4.53”)
98 mm (3.86”)
29.1 mm (1.15”)
31 mm
(1.22”)
Page 22
Page 22
FL_F116P_v1702_01_EN
4.4 INSTALLING THE HARDWARE
Electro static discharge does inflict irreparable damage to electronics! Before installing or
opening the F116-P , the installer has to discharge himself by touching a well-grounded object.
Do ground the aluminum enclosure properly as indicated. It is the responsibility of the
installer to install, connect and test the Protective Earth connections in accordance with the (inter)national Rules and Regulations.
This chapter shows general information regarding the electrical installation of the F116-P
. Chapter 5 gives additional specific information regarding Intrinsically safe installation and overrules the information given in this chapter.
When installed in an aluminum enclosure and a potentially explosive atmosphere
requiring apparatus of equipment protection level Ga and Da, the unit must be installed such that, even in the event of rare incidents, an ignition source due to impact or friction sparks between the enclosure and iron/steel is excluded.
4.4.1. GENERAL INSTALLATION GUIDELINES
In the F116-P , different types of bonding and earthing are used. The common (ground) is mostly
used for termination of the wire shields and the Protective Earth (PE) is used for electrical safety.
The F116-P that came with a power module type PM; 110V-230V AC or type PD/PF with an
option OR (the relays can handle 110V-230V AC) shall be connected to the Protective Earth (PE) stud which is installed in the metal back panel. The metal front panel is connected to the Protective Earth by the mounting screws and serrated washers.
For V AC applications, the terminal 00 shall not be connected to avoid earth loops.
For V DC applications, the terminal 00 shall be connected to the common (do NOT use for PE).
The wire screens (shield) are meant to prevent electromagnetic interference and shall be,
galvanic isolated, connected to the common ground terminals that belong to the specific sensor connection. The wire screens shall be terminated at one side to prevent wire loops. Inside of the Fluidwell unit, the different common ground terminals are connected to each other. It is advised, as illustrated, to terminate the wire screens in the vicinity of the sensor and to insulated the wire screen with a shrink tube at the Fluidwell unit side.
Separate cable glands with effective IP67 / TYPE 4(X) seals for all wires. Unused cable entries: ensure that you fit IP67 / TYPE 4(X) plugs to maintain rating. A reliable ground connection for both the sensor, and if applicable, for the metal enclosure
(above).
An effective screened cable for the input signal, and grounding of its screen to the “┴ “ terminal or
at the sensor itself, whichever is appropriate to the application.
Field mounted
Panel mounted
Page 23
Page 23
FL_F116P_v1702_01_EN
4.4.2. ALUMINUM ENCLOSURE - FIELD MOUNTED
Risk of damage to equipment!
Do not use the terminal 00 to connect the protective earth wire, the 00 and the common ground terminals are internally connected. Be careful, to prevent damage to equipment when you connect different power supplies (sensor, PLC, etc.). Inside the Fluidwell display, the common grounds are internally connected to each other.
The PE connection
The PE connection is made with the PE stud inside the back panel and the 4 mounting screws that attach the cover to the back panel.
Type PM (110-230V AC)
The PE connection in the metal back panel is made with a serrated washer, a terminal, a washer and a screw.
The PE connection to the metal cover is made with the serrated washers and the mounting screws.
Type PD-OR / PF-OR (8-24V AC)
Type PD-OR / PF-OR (8-30V DC)
4.4.3. ALUMINUM ENCLOSURE - PANEL MOUNTED
The PE connection
The PE connection is made with one of the mounting screws that attaches the front panel to the panel.
Type PM (110-230V AC)
The PE connection to the metal cover is made with the serrated washers and the mounting screws. The PE connection to the panel is made with the washer, the nut, the terminal, the washer and a lock nut.
Type PD-OR / PF-OR (8-24V AC)
Type PD-OR / PF-OR (8-30V DC)
Page 24
Page 24
FL_F116P_v1702_01_EN
4.4.4. PLASTIC (GRP) ENCLOSURE
The PE connection
The F116-P in a GRP enclosure meets the requirements of class 2 (double insulated). Therefore the incoming PE wire is terminated with an insulating end cap.
Type PM (110-230V AC)
Type PD-OR / PF-OR (8-24V AC)
Type PD-OR / PF-OR (8-30V DC)
Page 25
Page 25
FL_F116P_v1702_01_EN
4.4.5. TERMINAL CONNECTORS
For Intrinsically safe applications: read chapter 5.
Fig. 7: Overview of terminal connectors - Standard configuration and options
SENSOR SUPPLY For type PB/PC; PX; AP: There is no real sensor supply out available. Only a limited power supply
is available. This power supply MAY NOT be used to supply the flowmeters electronics, converters etc. as it will not provide adequate sustained power ! All energy used by the flowmeters pick-up will directly influence the battery life-time. It is strongly advised to use a "zero power" pickup such as a coil or reed-switch when operating without external power. It is possible to use some low power NPN or PNP output signals, but the battery life time will be significantly reduced (consult your distributor).
For type PD; PF; PM: It is possible to supply the sensor with different voltages. You can set the voltage with the switches. Internal power is only applicable for low power sensors (Coil, Reed). The sensor supply is fixed: 1.2V DC or 3V DC (set by the firmware). External power is only available when the main external power supply is connected. The sensor supply voltage is selectable: 8.2; 12 or 24V DC.
Page 26
Page 26
FL_F116P_v1702_01_EN
Set the sensor supply
1. Make the F116-P safe. If applicable, mind the battery power.
2. Open the F116-P and carefully remove the cable-connectors and the protective cover.
3. Find and set the switches and select the V
out
as required.
4. Close the protective cover and install the cable connectors.
5. Close the F116-P.
Risk of electrocution - High voltage!
Make sure, all the leads to the terminals are disconnected from the F116-P and NEVER connect the mains power supply to the unit when the protection cover has been removed!
Option PD
Power supply in: 8-24V AC / 8-30V DC
Switch location (Typical)
Sensor
V
out
selection
Sensor supply out
A
B
1 2 3
4
NOTE: Use an AC autotransformer (spartrafo) with galvanic isolation.
int
int
off
off
Coil 1.2V DC; <1mA Reed 3V DC; <1mA
ext
ext
on on off
on off off
8.2V DC; 50mA (max) 12V DC; 50mA (max) 24V DC; 50mA (max)
Option PF
Power supply in: 24V AC / 24V DC ±10%
Switch location (Typical)
Sensor
V
out
selection
Sensor supply out
A
B
1 2 3 4
int
int
off
off
Coil 1.2V DC; <1mA Reed 3V DC; <1mA
ext
ext
on on off
on off off
8.2V DC; 400mA (max) 12V DC; 400mA (max) 24V DC; 400mA (max)
Option PM
Power supply in: 115V AC - 230V AC ±10%
Switch location (Typical)
Sensor
V
out
selection
Sensor supply out
A
B
1 2 3 4
int
int
off
off
Coil 1.2V DC; <1mA Reed 3V DC; <1mA
ext
ext
on on off
on off off
8.2V DC; 400mA (max) 12V DC; 400mA (max) 24V DC; 400mA (max)
Fig. 8: Sensor supply voltage - Switch setting
Page 27
Page 27
FL_F116P_v1702_01_EN
Terminal 05-06 (R1) / 03-04 (R2, negative total); scaled pulse output
SETUP A (read chapter 3) determines the pulse output function. The maximum pulse frequency of this output is 500Hz. If a relay output option has been supplied, be sure that the output frequency does not exceed 5Hz or else the life-time of the relay will be reduced significantly.
Type OA
An active 24V DC pulse signal output is available with this option. Max. driving capacity 50mA@24V per output. (Requires power supply type PD/PF/PM).
Fig. 9: Terminal connections - Active output (typical)
Type OR
A mechanical relay output is available with this option. Max. switch power 240V 0,5A per output. (Requires power supply type PD/PF/PM). Be sure that the output frequency does not exceed 5Hz, else the relay life time will be reduced significantly.
Fig. 10: Terminal connections - Mechanical relay output (typical)
Type OT
A passive transistor output is available with this option. Max. driving capacity 300mA@50V DC.
Fig. 11: Terminal connections - Pulse output (typical)
Terminal 07-08; basic POWER SUPPLY - type AP - output loop powered
Connect an external power supply of 8-30VDC to these terminals or a (0)4-20mA loop. Do connect the "-" to terminal 7 and the "+" to terminal 8. When power is applied to these terminals,
the (optional) internal battery will be disabled / enabled automatically to extend the battery life time.
Terminal 07-08 analog output (SETUP 7) :
An analog output signal proportional to the (differential or summed) flow rate is available as standard.
Page 28
Page 28
FL_F116P_v1702_01_EN
Type AA
An active 4-20mA signal proportional to the (differential or summed) flow rate is available with this option. When the output is disabled, a 3.5mA signal will be generated on these terminals.
Max. driving capacity 1000 Ohm @ 24VDC. (Requires power supply type PD/PF/PM).
Fig. 12: Terminal connections - 4-20mA analog output (typical)
Type AB
An active 0-20mA signal proportional to the (differential or summed) flow rate is available with this option. Max. driving capacity 1000 Ohm @ 24VDC. (Requires power supply type PD/PF/PM).
Fig. 13: Terminal connections - Active 0-20mA analog output (typical)
Type AF
For the Intrinsically safe floating 4-20mA signal: please read Chapter 5.
Type AI
An isolated 4-20mA signal proportional to the (differential or summed) flow rate is available with this option. When the output is disabled, a 3.5mA signal will be generated on these terminals. Max. driving capacity 1000 Ohm @ 30VDC. This option can be used with a battery powered unit but the battery life time is about 2 -3 years.
Fig. 14: Terminal connections - Isolated 4-20mA analog output (typical)
Page 29
Page 29
FL_F116P_v1702_01_EN
Type AP
A passive 4-20mA signal proportional to the (differential or summed) flow rate is available with this option. When a power supply is connected but the output is disabled, a 3.5mA signal will be generated. Max. driving capacity 1000 Ohm. This output does loop power the unit as well.
Fig. 15: Terminal connections - Passive 4-20mA analog output (typical)
Type AU
A 0-10VDC signal proportional to the (differential or summed) flow rate is available with this option. Max. load 10mA @ 10VDC. (Requires power supply type PD/PF/PM).
Fig. 16: Terminal connections - Active 0-10V analog output (typical)
Terminal 09-11; Terminal 12-14; Flowmeter input A and B:
Three basic types of flowmeter signals can be connected to the unit: pulse, active pulse or coil. The connections for flowmeter A (Terminal 09-11) and B (Terminal 12-14) are the same. The screen of the signal wire must be connected to the related common ground terminal (unless earthed at the sensor itself) The maximum input frequency is approximately 10 kHz (depending on the type of signal). The input signal type has to be selected in the flowmeter setup (read chapter 3).
Sine-wave signal (Coil):
The F116-P is suitable for use with flowmeters which have a coil output signal. Two sensitivity levels can be selected:
COIL-LO: sensitivity from about 80mVpp;  COIL-HI: sensitivity from about 20mVpp;  type ZF, COIL-HI: sensitivity from about 10mVpp;  type ZG, COIL-HI: sensitivity from about 5mVpp.
Fig. 17: Terminal connections - Coil signal input (typical)
Page 30
Page 30
FL_F116P_v1702_01_EN
Pulse-signal NPN / NPN-LP:
The F116-P is suitable for use with flowmeters which have a NPN output signal. For reliable pulse detection, the pulse amplitude has to go below 1.2V. Signal setting NPN-LP employs a low-pass signal noise filter, which limits the maximum input frequency (read chapter 3).
Fig. 18: Terminal connections - NPN signal input (typical)
Pulse-signal PNP / PNP-LP:
The F116-P is suitable for use with flowmeters which have a PNP output signal. 3V is offered on terminal 11 which has to be switched by the sensor to terminal 10 (SIGNAL). For a reliable pulse detection, the pulse amplitude has to go above 1.2V. Signal setting PNP-LP employs a low-pass signal noise filter, which limits the maximum input frequency (read chapter 3).
A sensor supply voltage of 8.2, 12 or 24V DC can be provided with power supply type PD, PF, PM. For a signal detection level of 50% of the supply voltage: please refer to "active signals".
Fig. 19: Terminal connections - PNP signal input (typical)
Active signal 8.2V, 12V and 24V:
If a sensor gives an active signal (read chapter 3).The detection levels are 50% of the selected supply voltage; approx. 4V (8-1 DC) or 6V (12 DC) or 12V (24 DC). Active signal selection may well be desired in case of power supply type PD, PF, PM is available for sensor supply.
Fig. 20: Terminal connections - Active signal input (typical)
Reed-switch:
The F116-P is suitable for use with flowmeters which have a reed-switch. To avoid pulse bounce from the reed-switch, it is advised to select REED LP - low-pass filter (read chapter 3).
Page 31
Page 31
FL_F116P_v1702_01_EN
Fig. 21: Terminal connections - Reed-switch signal input (typical)
NAMUR-signal:
The F116-P is suitable for flowmeters with an NAMUR signal. The standard F116-P is not able to power the NAMUR sensor, as an external power supply for the sensor is required. However, a 8.2V sensor supply voltage (terminal 11) can be provided with type PD, PF, PM.
Fig. 22: Terminal connections - NAMUR signal input (typical)
Terminal 26-31: type CB / CH / CI / CT - communication RS232 / RS485 / TTL (option)
For connections, refer to figure: Overview of terminal connectors - Standard configuration and options
Full serial communications and computer control in accordance with RS232 (length of cable max. 15 meters) or RS485 (length of cable max. 1200 meters) is possible.
When using the RS232 communication option, terminal 27 is used for supplying the interface. Please connect the DTR (or the RTS) signal of the interface to this terminal and set it active (+12V).
If no active signal is available it is possible to connect a separate supply between terminals 26 and 27 with a voltage between 8V and 24V.
Terminal 00 - 01: type ZB backlight (option):
If the unit is supplied with a power supply:
type PD, PF or PM, the backlight supply is integrated. type PX, use the terminals 00 and 01 to supply the backlight.
The backlight intensity is set in the setup menu: Display.
Page 32
Page 32
FL_F116P_v1702_01_EN
5 INTRINSICALLY SAFE APPLICATIONS
5.1 GENERAL INFORMATION AND SAFETY INSTRUCTIONS
For the combined connection of the different supply, input and output circuits, the
instructions in this manual must be observed. From the safety point of view the circuits shall be considered to be connected to earth
Certificates, safety values, control drawing and declaration of compliance can be found in
the document named: Fluidwell F1..-..-XI - Documentation for Intrinsic safety
For installation under ATEX directive: this Intrinsically safe device must be installed in
accordance with the latest ATEX directive and product certificate KEMA 03ATEX1074 X.
For installation under IECEx scheme: this Intrinsically safe device must be installed in
accordance the product certificate IECEx DEK 11.0042X.
Exchange of Intrinsically safe battery FWLiBAT-0xx with certificate number
KEMA 03ATEX1071 U or IECEx KEM 08.0005U is allowed in Hazardous Area. Read chapter 6 for battery replacement instructions.
When the enclosure of the F116-P is made of aluminum alloy, when used in a potentially
explosive atmosphere requiring apparatus of EPL Ga, the indicator shall be installed so, that even in the event of rare incidents, an ignition source due to impact or friction sparks between the enclosure and iron/steel is excluded.
When two or more active Intrinsically safe circuits are connected to the indicator, in order
to prevent voltage and/or current addition, applicable to the external circuits, precautions must be taken to separate the Intrinsically safe circuits in accordance with EN 60079-11.
To maintain the degree of protection of at least IP65 in accordance with IEC 60529,
suitable cable entries and blanking elements must be used and correctly installed.
For enclosures and windows with a high surface resistance, potential charging hazard
exists. Do not rub these surfaces of the indicator. Clean window and enclosure only with a lint-free cleaning cloth made damp with a mild soap solution.
Chapter 4 shows general information regarding the electrical installation of your indicator.
This chapter gives additional specific information regarding Intrinsically safe installation and overrules the information given in chapter 4.
Mounting, electrical installation, start-up and maintenance of this device may only be
carried out by trained persons authorized by the operator of the facility. Persons must read and understand this manual before carrying out its instructions.
This device may only be operated by persons who are authorized and trained by the
operator of the facility. All instructions in this manual are to be observed.
Make sure, the measuring system is correctly wired up according to the wiring diagrams.
Protection against accidental contact is no longer assured when the housing cover is removed or the panel cabinet has been opened (danger from electrical shock). The housing may only be opened by trained persons authorized by the operator of the facility.
Take careful notice of the "Safety rules, instructions and precautionary measures" in the
front of this manual.
Special conditions for safe use mentioned in both the certificate and the installation
instructions must be observed for the connection of power to both input and / or output circuits.
When installing this device in hazardous areas, the wiring and installation must comply
with the appropriate installation standards for your industry.
Study the following pages with wiring diagrams per classification.
Page 33
Page 33
FL_F116P_v1702_01_EN
Serial number and year of production
This information can be looked-up in the setup menu: Others.
Fig. 23: Example serial number (typical)
Label information pulse input type – F1xx-..-..-XI (inside and outside the enclosure)
Fig. 24: Label information - Intrinsically safe application (typical)
Page 34
Page 34
FL_F116P_v1702_01_EN
5.2 TERMINAL CONNECTORS INTRINSICALLY SAFE APPLICATIONS
The unit is classified as group IIB/IIIC by default
Classification of the unit as group IIC is only possible under the following conditions: The indicator is either supplied by
the internal supply (type PC); the external supply connected to terminals 0 and 1 (type PD); the circuit supply connected to terminals 7 and 8 (type AP); The maximum values for any of those circuits are those as defined for group IIB/IIIC; No other active external Intrinsically safe circuits may be connected to the indicator, with
exception of circuits connected to terminals 3 and 4 and/or terminals 5 and 6; the maximum values for any of those circuits are those as defined for group IIB/IIIC.
Terminal connectors F116-P-XI:
Fig. 25: Overview terminal connectors - Intrinsically safe (typical)
Page 35
Page 35
FL_F116P_v1702_01_EN
Type AF - Intrinsically safe floating 4-20mA analog output - Terminal 7-8
A floating 4-20mA signal proportional to the flow rate is available with this option. When the output is disabled, a 3.5mA signal will be generated. Max. driving capacity 1000 Ohm @ 30V DC.
It is required to link the minus from the analog output - terminal 7 - with a ground terminal of the unit; terminal: 00, 03, 05, 09, 12 or 15.
Fig. 26: Terminal connections - Intrinsically safe floating 4-20mA analog output (typical)
For type PD-XI: It is possible to supply the sensor with different voltages. You can set the voltage
with the switches. Internal power is only applicable for low power sensors (Coil, Reed). The sensor supply is set by the firmware: 1.2V DC or 3V DC. External power is only available when the main external power supply is connected. The sensor supply voltage is fixed: 8.2V DC.
Set the sensor supply
1. Make the F116-P safe. If applicable, mind the battery power.
2. Open the F116-P and carefully remove the cable-connectors and the protective cover.
3. Find and set the switches and select the V
out
as required.
4. Close the protective cover and install the cable connectors.
5. Close the F116-P.
Risk of electrocution - High voltage!
Make sure, all the leads to the terminals are disconnected from the F116-P and NEVER connect the mains power supply to the unit when the protection cover has been removed!
Type PD-XI
Power supply in: 8-30V DC
Switch location (typical)
Sensor
Sensor supply out
A
B
1 2
off
off
Coil 1.2V DC; <1mA Reed 3V DC; <1mA
on
on
8.2V DC; 50mA (max)
Fig. 27: Switch position voltage selection type PD-XI
Page 36
Page 36
FL_F116P_v1702_01_EN
5.3 CONFIGURATION EXAMPLES INTRINSICALLY SAFE APPLICATIONS
Fig. 28: F116-P-(AP)-(CT)-(OT)-PC-XI - Battery powered - IIB/IIC – IIIC
Page 37
Page 37
FL_F116P_v1702_01_EN
Fig. 29: F116-P-AP-(CT)-OT-(PX)-XI - Output loop powered - IIB/IIC - IIIC
Page 38
Page 38
FL_F116P_v1702_01_EN
6 MAINTENANCE
6.1 GENERAL DIRECTIONS
Mounting, electrical installation, start-up and maintenance of this device may only be
carried out by trained persons authorized by the operator of the facility. Persons must read and understand this manual before carrying out its instructions.
This device may only be operated by persons who are authorized and trained by the
operator of the facility. All instructions in this manual are to be observed.
Make sure, the measuring system is correctly wired up according to the wiring diagrams.
Protection against accidental contact is no longer assured when the housing cover is removed or the panel cabinet has been opened (danger from electrical shock). The housing may only be opened by trained persons authorized by the operator of the facility.
Take careful notice of the "Safety rules, instructions and precautionary measures" in the
front of this manual.
The F116-P does not require special maintenance unless it is used in low-temperature applications or surroundings with high humidity (above 90% annual mean). It is the users responsibility to take all precautions to dehumidify the internal atmosphere of the F116-P in such a way that no condensation will occur, e.g. to put a dose of desiccant (drying agent) inside the enclosure just before closing it. Furthermore, it is required to replace the desiccant periodically as advised by its supplier.
Battery life-time:
It is strongly advised to disable the unused functions
It is influenced by several issues :
Type of sensor (read chapter 3): NPN and PNP inputs consume more energy than coil inputs;  Input frequency: the higher the frequency, the shorter the battery life-time;  Analog output signal; be sure that an external power supply is connected or that the function is
disabled if not in use; or else it will have a major influence on the battery life-time;
Display update: fast display update uses significantly more power;  Pulse output and communications;  Low temperatures; the available power will be less due to battery chemistry.
Check periodically:
The condition of the enclosure, cable glands and front panel.  The input/output wiring for reliability and aging symptoms.  The process accuracy. As a result of wear and tear, re-calibration of the flowmeter might be
necessary. Do not forget to re-enter any subsequent K-Factor alterations.
The indication for low-battery.  Clean window and enclosure only with a lint-free cleaning cloth made damp with a mild soap
solution.. Do not use any aggressive solvents as these might damage the coating.
6.2 INSTRUCTIONS FOR REPAIR
This product cannot be repaired by the user and must be replaced with an equivalent certified product. Repairs are only allowed to be carried out by the manufacturer or his authorized agent.
Page 39
Page 39
FL_F116P_v1702_01_EN
6.3 BATTERY REPLACEMENT
6.3.1 SAFETY INSTRUCTIONS
Handle the battery with care. A mistreated battery can become unsafe. Unsafe batteries
can cause (serious) injury to persons.
Only use batteries which are certified for use in hazardous areas. The use of standard
batteries in hazardous area's is not safe and prohibited. Batteries that are regarded as unsafe can cause (serious) injury to persons and damage to the property.
Mounting, electrical installation, start-up and maintenance of this device may only be
carried out by trained persons authorized by the operator of the facility. Persons must read and understand this manual before carrying out its instructions.
Only use batteries which are certified for use in hazardous areas. The use of standard
batteries in hazardous area's is not safe and prohibited. Batteries that are regarded as unsafe can cause (serious) injury to persons and damage to the property.
For use in hazardous areas we advise to apply FW-LiBAT batteries only.
6.3.2 REPLACE THE BATTERY (HAZARDOUS AREA)
The batteries are used to store electrical energy. The battery is a high power battery which must be treated carefully. When the battery is mistreated or damaged, there is a risk of a fire, an explosion and serious burns.
1. Mind that you cannot switch off a battery.
2. Make sure, it is safe to work on the battery system.
3. Handle the battery with the utmost care to prevent a short circuit and damage.
4. Do not recharge, crush, disassemble, incinerate, heat above its rated temperature or expose the contents to water.
5. Dispose of the battery in accordance with the (inter)national, the manufacturer’s and the plant owner’s standards and regulations.
6. Read and understand the instructions.
7. Get approval from the safety officer to do the work.
8. Lock-out/Tag-out the unit and related system.
9. Make sure, it is safe to do the work.
Remove the battery
1. If necessary, clean the housing with an anti-
static cloth made damp with a mild soap solution.
2. Let the enclosure dry onto the air.
3. Carefully, open the enclosure.
4. Keep the removed parts in a clean location.
5. Get access to the battery.
6. Find the battery connector and disconnect
the battery from the unit.
7. Remove and keep the battery from the unit.
8. Install an insulation tape over the battery
connector to prevent a short circuit.
Install the battery
1. Make sure, the new battery is certified for use in the unit.
2. Work as clean as possible, to prevent contamination to enter the unit.
3. Carefully, install the battery.
4. Make sure, the battery is correctly locked into the battery holder.
5. Install the battery connector.
6. Carefully assemble the unit and close the enclosure.
7. With the enclosure carefully closed, do a test of the unit.
8. If necessary, get access to the setup menu
and make any adjustments to obtain the correct settings.
6.3.3 DISPOSAL OF BATTERIES
Batteries pose an environmental hazard.  Do not dispose of as general waste or incinerate.  Return used batteries to a recycling point.
Page 40
Page 40
FL_F116P_v1702_01_EN
TECHNICAL SPECIFICATION
Display
Type
High intensity reflective numeric and alphanumeric LCD, UV-resistant.
Dimensions
90 x 40mm (3.5”x 1.6”)
Digits
Seven 17mm (0.67") and eleven 8mm (0.31"). Various symbols and measuring units.
Refresh rate
User definable: 8 times/sec - 30 secs.
Type ZB
LCD with LED backlight. Good readings in full sunlight and darkness. Power requirements: 12-24V DC + 10% or type PD, PF, PM. Power consumption max. 1 Watt.
Only available for safe area applications.
Enclosures
General
Control Keys
Painting
Die-cast aluminum or GRP (Glassfibre Reinforced Polyamide) enclosure with Polycarbonate window, silicone gaskets. UV stabilized and flame retardant material. Three industrial micro-switch keys. UV-resistant silicone keypad. Aluminum enclosure only: UV-resistant 2-component industrial painting.
Panel-mount enclosures
Classification Panel cut-out
Type HC Type HB
Dimensions: 130 x 120 x 60mm (5.10" x 4.72" x 2.38") – LxHxD. IP65 / TYPE 4(X) 115 x 98mm (4.53" x 3.86") LxH. GRP panel-mount enclosure Aluminum panel-mount enclosure
Field/wall-mount enclosures
Classification
Aluminum enclosures
Type HA
Type HL
Type HM
Type HN
Type HO
Type HP
Type HT Type HU Type HV
Type HZ
GRP enclosures
Type HD Type HE
Type HF
Type HG
Type HJ Type HH Type HK
Dimensions: 130 x 120 x 75mm (5.10” x 4.72” x 2.95”) – LxHxD. IP67 / TYPE 4(X)
Drilling: 2x PG9 – 1x M20. Drilling: 2x ½”NPT. Drilling: 2x M16 – 1x M20. Drilling: 1x M20. Drilling: 2x M20. Drilling: 6x M12.
Drilling: 1x ½”NPT. Drilling: 3x ½”NPT.
Drilling: 4x M20 No drilling.
No drilling.
Drilling: 2x 16mm (0.63”) – 1x 20mm (0.78”). Drilling: 1x 22mm (0.87”). Drilling: 2x 20mm (0.78”). Drilling: 3x 22mm (0.87”). Drilling: 6x 12mm (0.47”).
Flat bottom - no drilling.
Operating temperature
Operational
-40°C to +80°C (-40°F to +178°F).
Intrinsically safe
-40°C to +70°C (-40°F to +158°F).
Relative humidity
90%, no condensation allowed.
Power requirements
Type PB
Lithium battery - life-time depends upon settings - up to 5 years.
Type PC
Intrinsically safe lithium battery - life-time depends upon settings - up to 5 years.
Type PD
8-24V AC + 10%. / 8-30V DC Power consumption max. 10 Watt. Intrinsically safe: 16-30V DC; power consumption max. 0.75 Watt.
Type PF
24V AC / DC + 10%. Power consumption max. 15 Watt.
Type PL
Input loop powered from sensor signal 4-20mA (type A, non IS).
Type PM
115-230V AC + 10%. Power consumption max. 15 Watt.
Type PX
8-30V DC. Power consumption max. 0.5 Watt.
Type PX / ZB
10-30V DC. Power consumption max. 0.5 Watt.
Note PF / PM
The total consumption of the sensors`, backlight and outputs may not exceed 400mA@24V.
Note I.S. applications
For Intrinsically safe applications, consult the safety values in the certificate.
Page 41
Page 41
FL_F116P_v1702_01_EN
Sensor excitation
Type PB / PC / PX
3V DC for low power pulse signals and 1.2V DC for coil pick-up.
Type PD
1.2; 3; 8.2; 12; 24V DC - max. 50mA@24V DC
Type PD-XI
Intrinsically safe: Pulse signals: 1.2; 3; 8.2 - max. 7mA@8.2V DC.
Type PF / PM
1.2; 3; 8.2; 12; 24V DC - max. 400mA@24V DC.
Terminal connections
Type
Removable plug-in terminal strip. Wire max. 1.5mm2 and 2.5mm2
Data protection
Type
EEPROM backup of all settings. Backup of running totals every minute. Data retention at least 10 years.
Password
Configuration settings can be Password protected.
Hazardous area
Intrinsically safe Type XI
ATEX approval :
II 1 G Ex ia IIB/IIC T4 Ga II 1 D Ex ia IIIC T100°C Da
IECEx approval :
Ex ia IIB/IIC T4 Ga Ex ia IIIC T100°C Da
Explosion proof Type XF
ATEX approval ref: II 2 EEx d IIB T5. Weight appr. 15kg. Dimensions of enclosure: 350 x 250 x 200mm (13.7” x 9.9” x 7.9”) LxHxD.
Directives and Standards
EMC
EN 61326-1; FCC 47 CFR part 15
LVD
EN/IEC 61010-1
ATEX / IECEx
EN/IEC 60079-0; EN/IEC 60079-11
RoHS
EN 50581
IP & NEMA
EN 60529; NEMA 250
Inputs
Flowmeter
Type P
npn; npn-lp; reed; reed-lp; pnp; pnp-lp; namur; coil-hi; coil-lo; 8-1 DC; 12 DC; 24 DC
Frequency
Minimum 0 Hz – maximum 7 kHz for total and flow rate. Maximum frequency depends on signal type and internal low-pass filter. E.g. Reed switch with low-pass filter: max. frequency 120 Hz.
K-Factor
0.000010 - 9999999 with variable decimal position.
Low-pass filter
npn-lp; reed-lp; pnp-lp
Outputs
Analog output
Function
transmitting differential flow rate.
Accuracy
10 bit. Error < 0.05% - update 10 times a second. Software function to calibrate the 4.00mA and 20.00mA levels precisely within set-up.
Load
max. 1 kΩ
Type AA
Active 4-20mA output (requires type OA + PD, PF or PM).
Type AB
Active 0-20mA output (requires type OA + PD, PF or PM).
Type AF
Passive floating 4-20mA output for Intrinsically safe applications (requires PC or PD).
Type AI
Passive galvanic isolated output (requires PB, PD, PF, PL or PM).
Type AP
Passive 4-20mA output - output loop powered.
Type AU
Active 0-10V output (requires type OA + PD, PF or PM).
Switch outputs
Function
One pulse output - transmitting accumulated total.
Pulse output
Max. frequency 500Hz. Pulse length user definable between 0.001 up to 9.999 seconds.
Type OA
Active 24V DC transistor output; max. 50mA per output (requires type AA + PD, PF or PM).
Type OR
Isolated mechanic relay output; max. switch power 230V AC - 0,5A (requires type PF or PM).
Type OT
Passive transistor output - not isolated. Load max. 50V DC - 300mA.
Page 42
Page 42
FL_F116P_v1702_01_EN
Communication (option)
Protocol
bus-rtu; bus-asc
Speed
1200; 2400; 4800; 9600
Addressing
1 - 247
Type CB
RS232
Type CH
RS485 2-wire
Type CI
RS485 4-wire
Type CT
TTL Intrinsically safe communication.
Type CX
no communication.
Operational
Operator functions
Shown functions
calculated differential or sum total and/or flow rate. calculated differential or sum accumulated total. flow rate A total A flow rate B total B.
Total
Digits
7 digits.
Unit
L; m3; kg; lb; GAL; USGAL; bbl; no unit
Decimals
0000000; 111111.1; 22222.22; 3333.333
All totals can be reset to zero by pressing the CLEAR-key twice.
Accumulated total
Digits
11 digits.
Unit / decimals
According to selection for total.
Flow rate
Digits
7 digits.
Unit
mL; L; m3; mg; g; kg; ton; gal; bbl; lb; cf; rev; - - - - (no unit); scf; nm3; nL; p
Decimals
0000000; 111111.1; 22222.22; 3333.333
Time units
/sec; /min; /hour; /day
Page 43
Page 43
FL_F116P_v1702_01_EN
PROBLEM SOLVING
In this appendix, several problems are included that can occur when the F116-P is going to be installed or while it is in operation.
Flowmeter does not generate pulses:
Check:
Signal selection;  Pulse amplitude;  Flowmeter, wiring and connection of terminal connectors;  Power supply of flowmeter.
Flowmeter generates "too many pulses":
Check:
Settings for total and Flow rate;  Type of signal selected with actual signal generated;  Sensitivity of coil input;  Proper grounding of the F116-P;  Use screened wire for flowmeter signals and connect screen to terminal 9. (unless connected at
sensor).
Analog output does not function properly:
Check:
is the analog output enabled?  are the flow-levels programmed correctly?  connection of the external power-supply according to the specification.
Flow rate displays "0 / zero" while there is flow (total is counting):
Check:
SETUP 22 / 25 and 41-42: are the K-factor and time unit correct?  SETUP 26 / 27: The unit has to count the number of pulses according to SETUP 26 within the
time according to SETUP 27. Make sure that 27 is set to 10.0 seconds for example : the result is the unit has at least 10 seconds time to measure the number of pulses according to SETUP 26.
The password is unknown:
If the password is not 1234, there is only one possibility left: call your supplier.
ALARM
When the alarm flag starts to blink an internal alarm condition has occurred. Press the "select button" several times to display the error code. When multiple errors arise at the same time, their error codes are added and their sum is shown. The digital [d] codes are:
Not recoverable by the end user:
[d] 0 = no error; [d] 1 = display error; [d] 2 = data-storage error; [d] 3 = error 1 + error 2 simultaneously; [d] 4 =: initialization error.
For a not recoverable error, keep the error code at hand and contact your supplier.
Page 44
Page 44
FL_F116P_v1702_01_EN
COMMUNICATION
General
The product is fitted with the Modbus communication protocol and can be equipped with various physical interfaces like RS485 and RS232 (please see device datasheet for available options). The tables below show the various variables that can be accessed through the communication. Currently, the function codes supported are:
function code 3 “Read Holding Registers” (4x references);  function code 16 “Preset Multiple Registers” (4x references).
The table below shows the Modbus PDU addresses in a decimal format, followed by its hexadecimal representation (0x0000). When the PLC address range is required (4x references are typically used by PLCs), please add a value of 40001 to the Modbus PDU address. E.g. reading the serial number of the product with PLC-based addressing means: 165 + 40001 = register 40166.
The variables that consist of a multiple register must always read/write in 1 single action!
Refer to the illustration:
For this example it is assumed that the variable accumulated total has 3 registers (words) with address 566, 567 and 568. When a transmission is done, register 566, which acts as the MSW, arrives first with bit 15 which is the MSB of the lowest addressed word, but is also the MSB (bit 47) of the complete variable that represents the Accumulated total.
Although most Modbus Masters will support variables that span 2 registers, variables spanning more registers sometimes require you to manually calculate the resulting value.
For additional information regarding using your Modbus device, please read our ’General Modbus
Communication Protocol’ and ‘Modbus troubleshooting guide’ that are available through our website
or your distributor.
Runtime variables
PDU ADDRESS
REGISTER
VARIABLE RUN TIME
NO.
REGISTERS
R/W TYPE
VALUE / REMARKS
[d] 1596 [h] 0x63C
41597
(differential or sum) flow rate
2 r uint32
0…9999999 Representation: unit, time, decimals depending on variables 48, 49, 50
[d] 1590 [h] 0x636
41591
(differential or sum) total
3
r*
uint48
0…9999999999 Representation: unit, decimals depending on variables 32, 33
[d] 1584 [h] 0x630
41585
(differential or sum) accumulated total
3
r*
uint48
0…9999999999 Representation: unit, decimals depending on variables 32, 33
[d] 560 [h] 0x230
40561
accumulated total A
3
r*
uint48
0…99999999999999 Representation: unit, decimals depending on variables 32, 33
[d] 1072 [h] 0x430
41073
accumulated total B
3
r*
uint48
0…99999999999999 Representation: unit, decimals depending on variables 32, 33
[d] 572 [h] 0x23C
40573
Flow rate-A
2 r uint32
0…9999999; Representation: unit, time, decimals depending on variables 48, 49, 50
[d] 588 [h] 0x24C
40589
Flow rate-B
2 r uint32
0…9999999; Representation: unit, time, decimals depending on variables 48, 49, 50
[d] 516 [h] 0x204
40517
error status (bitfield)
1
R
uint16
[d] 0 = no error [d] 1 = display error [d] 2 = data-storage error [d] 3 = error 1 + error 2 simultaneously [d] 4 =: initialization error
Page 45
Page 45
FL_F116P_v1702_01_EN
Reading differential flow rate, total or accumulated total
The returned values are given including the decimals and represent the actual value. The given value may differ from the value that is shown on the display – this is due to the fact that the display is limited in the number of digits and may have a slower update rate set. For example when two decimals are selected for total and total has a value of 123456,78 the display will show 23456,78 while communication will read a “total” of 12345678 and a “total decimals” of 2.
* Clearing total
It is possible to clear the total counter by means of writing a value of 0 to all the 3 registers of total/flow rate in a single write action. Writing any other value will result in the reply of an error message because the registers of total/flow rate are during operation read-only.
Setup variables
PDU ADDRESS
REGISTER
VARIABLE TOTAL A
NO.
REGISTERS
R/W TYPE
VALUE / REMARKS
[d] 32 [h] 0x020
40033
unit (A and B)
1
r/w
uint16
0=none 1=L 2= m3
3=kg 4= lb 5=GAL
6= USGAL 7=bbl
[d] 33 [h] 0x021
40034
decimals (A and B)
1
r/w
uint16
0…3
[d] 34 [h] 0x022
40035
K-factor
2
r/w
uint32
1...9999999
Representation: 0.000010…9999999 depending
on variable 37: K-Factor decimals.
[d] 37 [h] 0x025
40038
decimals K-factor
1
r/w
uint16
0…6
PDU ADDRESS
REGISTER
VARIABLE FLOW RATE A
NO.
REGISTERS
R/W TYPE
VALUE / REMARKS
[d] 48 [h] 0x030
40049
unit (A and B)
1
r/w
uint16
0=mL 1=L 2= M3 3=mg
4=g 5=kg 6=ton 7=GAL
8=bbl 9=lb 10=cf 11=rev
12=none 13=scf 14=NM3 15=NL 16=P
[d] 49 [h] 0x031
40050
time unit (A and B)
1
r/w
uint16
0=/sec
1=/min
2=/hour
3=/day
[d] 50 [h] 0x032
40051
decimals (A and B)
1
r/w
uint16
0…3
[d] 51 [h] 0x033
40052
K-factor
2
r/w
uint32
1...9999999 Representation: 0.000010…9999999 depending on variable 54: decimals K-factor.
[d] 54 [h] 0x036
40055
decimals K-factor
1
r/w
uint16
0…6
[d] 62 [h] 0x03E
40063
filter 1 r/w
uint16
1...99
[d] 71 [h] 0x047
40072
period 1 r/w
uint16
1...999 Representation: 0.1 – 99.9 sec
PDU ADDRESS
REGISTER
VARIABLE TOTAL B
NO.
REGISTERS
R/W TYPE
VALUE / REMARKS
[d] 40 [h] 0x028
40041
K-factor
2
r/w
uint32
1...9999999
Representation: 0.000010…9999999 depending
on variable 43: decimals K-factor.
[d] 43 [h] 0x02b
40044
decimals K-factor
1
r/w
uint16
0…6
PDU ADDRESS
REGISTER
VARIABLE FLOW RATE B
NO.
REGISTERS
R/W TYPE
VALUE / REMARKS
[d] 227 [h] 0x0E3
40228
K-factor
2
r/w
uint32
1...9999999 Representation: 0.000010…9999999 depending on variable 230 decimals K-factor
[d] 230 [h] 0x0E6
40231
decimals K-factor
1
r/w
uint16
0…6
Page 46
Page 46
FL_F116P_v1702_01_EN
PDU ADDRESS
REGISTER
VARIABLE DISPLAY
NO.
REGISTERS
R/W TYPE
VALUE / REMARKS
[d] 64 [h] 0x040
40065
function
1
r/w
uint16
0: total
1: flow rate
2=all
[d] 67 [h] 0x043
40068
backlight brightness
1
r/w
uint16
0: off 1: 20%
2: 40% 3: 60%
4: 80% 5: 100%
[d] 140 [h] 0x08C
40141
calculate
0=differential
1=add
[d] 73 [h] 0x049
40074
measurement
1
r/w
uint16
0: bi-direct 1: not negative
2: threshold 3: stationary
[d] 77 [h] 0x04D
40078
stationary flow rate
2
r/w
uint32
0...9999999 Representation: 0.000000…9999999
[d] 44 [h] 0x02C
40045
stationary total
2
r/w
uint32
0...9999999 Representation: 0.000000…9999999
PDU ADDRESS
REGISTER
VARIABLE POWER MANAGEMENT
NO.
REGISTERS
R/W TYPE
VALUE / REMARKS
[d] 80 [h] 0x050
40081
LCD update time
1
r/w
uint16
0=fast 1=1sec
2=3sec 3=15sec
4=30sec 5=off
[d] 81 [h] 0x051
40082
power mode
1
r/w
uint16
0=operational
1=shelf
PDU ADDRESS
REGISTER
VARIABLE FLOWMETER
NO.
REGISTERS
R/W TYPE
VALUE / REMARKS
[d] 96 [h] 0x060
40097
flowmeter signal A
1
r/w
uint16
0: npn 1: npn lp 2: reed 3: reed lp
4: pnp 5: pnp lp 6: namur 7: coil-hi
8: coil-lo 9: act. 8.1V 10: act. 12V 11: act. 24V
[d] 97 [h] 0x061
40098
flowmeter signal B
1
r/w
uint16
0: npn 1: npn lp 2: reed 3: reed lp
4: pnp 5: pnp lp 6: namur 7: coil-hi
8: coil-lo 9: act. 8.1V 10: act. 12V 11: act. 24V
PDU ADDRESS
REGISTER
VARIABLE ANALOG OUTPUT
NO.
REGISTERS
R/W TYPE
VALUE / REMARKS
[d] 112 [h] 0x070
40113
analog output
1
r/w
uint16
0: disable
1: enable
[d] 113 [h] 0x071
40114
rate-min
2
r/w
uint32
0…9999999 Representation: unit, time, decimals depending on variables 48, 49, 50
[d] 116 [h] 0x074
40117
rate-max
2
r/w
uint32
0…9999999 Representation: unit, time, decimals depending on variables 48, 49, 50
[d] 119 [h] 0x077
40120
cut off 1 r/w
uint16
0...99 Representation: 0.0 – 9.9%
[d] 120 [h] 0x078
40121
tune-min
1
r/w
uint16
0...9999
[d] 122 [h] 0x07A
40123
tune-max
1
r/w
uInt16
0...9999
[d] 127 [h] 0x07F
40128
filter 1 r/w
uint16
1...99
PDU ADDRESS
REGISTER
VARIABLE PULSE
NO.
REGISTERS
R/W TYPE
VALUE / REMARKS
[d] 135 [h] 0x087
40136
mode 1 r/w
uint16
0: not negative
1: separated
2: signed
[d] 128 [h] 0x080
40129
pulse width
1
r/w
uint16
0…9999, (0=disabled) Representation: 0.000 – 9.999 sec
[d] 133 [h] 0x085
40134
decimals
1
r/w
uint16
0…3
[d] 130 [h] 0x082
40131
amount
2
r/w
uint32
1...9999999 Representation: 0.001 – 9999999 depending on variable 133
Page 47
Page 47
FL_F116P_v1702_01_EN
PDU ADDRESS
REGISTER
VARIABLE COMMUNICATION
NO.
REGISTERS
R/W TYPE
VALUE / REMARKS
[d] 144 [h] 0x090
40145
speed (baud rate)
1
r/w
uint16
0: 1200 1: 2400
2: 4800 3: 9600
[d] 145 [h] 0x091
40146
Modbus address
1
r/w
uint16
1…247
[d] 146 [h] 0x092
40147
Modbus mode
1
r/w
uint16
0: ASCII
1: RTU
2: OFF
PDU ADDRESS
REGISTER
VARIABLE OTHERS
NO.
REGISTERS
R/W TYPE
VALUE / REMARKS
[d] 173 [h] 0x0AD
40174
model number
1 r uint16
0…9999
[d] 160 [h] 0x0A0
40161
model suffix
1 r char
Representation: ASCII character
[d] 162 [h] 0x0A2
40163
firmware version
2 r uint32
0…999999 Representation: nn:nn:nn
[d] 165 [h] 0x0A5
40166
serial no
2 r uint32
0…9999999 Representation: nnnnnnn
[d] 168 [h] 0x0A8
40169
password
1 r uint16
0…9999
[d] 170 [h] 0x0AA
40171
tag-nr 2 r/w
uint32
0...9999999 Representation: nnnnnnn
Page 48
Page 48
FL_F116P_v1702_01_EN
DECLARATION OF CONFORMITY
Page 49
Page 49
FL_F116P_v1702_01_EN
INDEX OF THIS MANUAL
accumulated total 8 actual settings 50, 51 analog
floating output. 35 flow rate min. 16 intrinsically safe output. 35 tune / calibrate 17
Analog output 27
backlight
density 14
clear total 8 coil-signal 29 Coil-signal 29 communication 31 contents 5 dimensions 20
display
function 14
flowmeter
signal 16
Flowmeter input 29
flow rate calculation 13 functional description 6 hardware version 4 intrinsic safety 32 Intrinsic safety 32, 34, 35, 38 IP classification 19 maintenance 38 manual version 4 namur signal 31 operational 7, 9, 10, 19, 38 operator level 8
pulse output
pulse length / period time 18
Pulse output 27 pulse-signal NPN 30 pulse-signal PNP 30 rate / total 8 reed-switch: 30 software version 4 time/date 8
LIST OF FIGURES IN THIS MANUAL
Fig. 1: Typical application 6 Fig. 2: Control panel 7 Fig. 3: Process information (typical) 8 Fig. 4: Low-battery alarm (typical) 8 Fig. 5: Aluminum enclosures - Dimensions 20 Fig. 6: GRP enclosures - Dimensions 21 Fig. 7: Overview of terminal connectors - Standard configuration and options 25 Fig. 8: Sensor supply voltage - Switch setting 26 Fig. 9: Terminal connections - Active output (typical) 27 Fig. 10: Terminal connections - Mechanical relay output (typical) 27 Fig. 11: Terminal connections - Pulse output (typical) 27 Fig. 12: Terminal connections - 4-20mA analog output (typical) 28 Fig. 13: Terminal connections - Active 0-20mA analog output (typical) 28 Fig. 14: Terminal connections - Isolated 4-20mA analog output (typical) 28 Fig. 15: Terminal connections - Passive 4-20mA analog output (typical) 29 Fig. 16: Terminal connections - Active 0-10V analog output (typical) 29 Fig. 17: Terminal connections - Coil signal input (typical) 29 Fig. 18: Terminal connections - NPN signal input (typical) 30 Fig. 19: Terminal connections - PNP signal input (typical) 30 Fig. 20: Terminal connections - Active signal input (typical) 30 Fig. 21: Terminal connections - Reed-switch signal input (typical) 31 Fig. 22: Terminal connections - NAMUR signal input (typical) 31 Fig. 23: Example serial number (typical) 33 Fig. 24: Label information - Intrinsically safe application (typical) 33 Fig. 25: Overview terminal connectors - Intrinsically safe (typical) 34 Fig. 26: Terminal connections - Intrinsically safe floating 4-20mA analog output (typical) 35 Fig. 27: Switch position voltage selection type PD-XI 35 Fig. 28: F116-P-(AP)-(CT)-(OT)-PC-XI - Battery powered - IIB/IIC – IIIC 36 Fig. 29: F116-P-AP-(CT)-OT-(PX)-XI - Output loop powered - IIB/IIC - IIIC 37
Page 50
Page 50
FL_F116P_v1702_01_EN
LIST OF CONFIGURATION SETTINGS
SETTING
DEFAULT
DATE:
DATE:
1
TOTAL-A
Enter your settings here
11
unit
L
12
decimals
0000000
13
K-factor
0000001
14
decimals K-factor
0
2
FLOW RATE- A
21
unit
L
22
time unit
/min
23
decimals
0000000
24
K-factor
0000001
25
decimals K-factor
0
26
filter
1
27
period
1.0 sec.
3
TOTAL-B
31
K-factor
0000001
32
decimals K-factor
0
4
FLOW RATE- B
41
K-factor
0000001
42
decimals K-factor
0
5
DISPLAY
51
function
total
52
light
100%
53
calculate
differential
54
measurement
bi-directional
55
stationary flow rate
0 L/ min
56
stationary total
0 L/hr
6
POWER MANAGEMENT
61
LCD-new
1 sec.
62
battery mode
operate
7
FLOWMETER
71
signal A
coil-lo
72
signal B
coil-lo
Page 51
Page 51
FL_F116P_v1702_01_EN
LIST OF CONFIGURATION SETTINGS
SETTING
DEFAULT
DATE:
DATE:
8
ANALOG OUTPUT
Enter your settings here
81
output
disabled
82
rate-min
0000000
83
rate-max
9,999,999
84
cut-off
0.0
85
tune-min
0160
86
tune-max
6656
87
filter
1
9
PULSE
91
mode
signed
92
width
0 (off)
93
decimals 0
94
amount
1.000
A
COMMUNICATION
A1
speed
9600
A2
address 1
A3
mode
BUS-RTU
B
OTHERS
B1
model
F116-P
B2
software version
B3
serial no.
B4
password
0000
B5
tag-nr
0000000
Page 52
Page 52
Loading...