Flomatic RPZ 2-1-2 Shematics

Page 1
Reduced Pressure Zone Specification Submittal Sheet
Model RPZ (2½” - 10”)
FEATURES: Sizes: 2 ½” 3” 4” 6” 8”
Max. working pressure: 175 PSI (1200 kPa) Max. working temperature: 140°F (60°C) Hydrostatic Test Pressure: 350 PSI (2400 kPa)
MATERIALS:
Valve Body: Ductile Iron Access Cover: Ductile Iron Polymers: Noryl Elastomers: Silicone Buna-n (FDA approved) Springs: Stainless Steel Coatings: FDA approved fusion epoxy
OPTIONS:
1 – less NRS gate valves
OSY – with OS&Y gate valves
STANDARDS COMPLAINCE:
TM,
NSF Listed
(ex B9215 replace 3rd number)
ASSE® Listed 1013
CSA® Listed
AWWA Compliant C511
City of Los Angeles Approved
Approved by the Foundation for Cross-Connection
Control and Hydraulic Research at the University of Southern California
FLOMATIC SPECIFICATIONS:
Reduced Pressure Principle backflow preventer shall protect against backflow by either backpressure or backsiphonage from a cross-connection between potable water systems and substances that are non­health and health hazards.
The device shall be constructed from Ductile Iron. It shall consist of two (2) mechanically independent, spring loaded, center stem guided check valves. It shall also have a hydraulically dependent differential pressure relief valve with the sensing passage set in an integral cast ductile iron body, with a single access cover. The assembly shall have four (4) vertical test cocks and two shut off valves which are quarter-turn, full-port, resilient seated and ball type which are constructed with low lead material, less than 0.25% lead content (ASTM C90500) or approved equal. Supplied with full ported gate valves.
The relief valve shall have removable stainless steel seat ring. The check valves shall be held into place by stainless steel clips and the check valve assemblies shall be non-interchangeable with silicone discs.
Size A B C D Width Wgt with GV Wgt less GV
Inch mm
2-1/2 65 B9205 31-1/4 794 16-1/4 413 16-7/16 418 11-3/8 289 8-1/32 204 164 74.5 60 27
3 80 B9206 32-1/4 819 16-1/4 413 17-7/16 443 12-3/8 314 10 254 186 84.5 60 27
4 100 B9207 39 991 21 533 22-13/32 569 14-3/4 375 10 254 314 142.5 120 54.5
6 150 B9209 44-5/8 1133 23-1/2 597 28-3/8 721 19 483 12-1/2 318 463 210 163 74
8 200 B92010 52-1/2 1334 29-1/2 749 32-7/16 824 22-1/2 572 15-3/16 386 710 322 300 136
10 250 B92011 61-1/8 1553 34-7/8 886 36-15/16 938 26-1/2 673 18 457 125 567 530 240
Part #
Inch mm Inch mm Inch mm Inch mm Inch mm lbs kg lbs kg
Danfoss Flomatic Corp, 15 Pruyn’s Island, Glens Falls, New York 12801
Phone: 518-761-9797 Fax: 518-761-9798 www.flomatic.com
Danfoss Flomatic
July 6,2004 Rev. 5
Page 2
Reduced Pressure Zone Specification Submittal Sheet
Model RPZ (2½” - 10”)
FLOW CHARACTERISTICS
i
a
s
P
p
S S O L
E R U S S E R P
k
138 20
110 16
83 12
855
428
0
FLOW CURVES w/ GATE VALVES
2-1/2" (65mm)
3" (80mm)
100
6.31
200
12.62
300
FLOW RATE
4" (100mm)
500400
600 gpm
25.2418.93
31.55
37.86 lps
(Established by Approval Agencies)
RATED FLOW
TYPICAL INSTALLATION
Model RPZ Reduced Pressure Backflow Preventers should be installed with adequate clearance and easy accessibility for testing and maintenance and must be protected from freezing. Local codes shall govern installation requirements. Unless otherwise specified, the assembly shall be mounted at a minimum clearance of 12” (305mm) between port and floor or grade. The assembly shall have a maximum of 30” (762mm) above adequate drains with sufficient side clearance for testing and maintenance. The installation shall be made so that no part of the unit can be submerged. Thermal water expansion can cause excessive pressure. Excessive pressure situations
i
a
s
P
p
S S O L
E R U S S E R P
k
138 20
110 16
83 12
855
428
0
FLOW CURVES w/ GATE VALVES
500
31.55
Capacity thru Schedule 40 Pipe (GPM)
Pipe size 5 ft/sec 7.5 ft/sec 10 ft/sec 15 ft/sec
2 ½”
3”
4”
6”
8”
75 112 149 224 115 173 230 346 198 298 397 595 450 675 900 1351 780 1169 1559 2339
should be eliminated to avoid possible damage to the system and assembly.
WARRANTY: Danfoss Flomatic valves are guaranteed against defects of materials or workmanship when used for
the services recommended. If in any recommended service, a defect develops due to material or workmanship, and the device is returned, freight prepaid, to Danfoss Flomatic within 12 months from the date of purchase, it will be repaired or replaced free of charge. Danfoss Flomatics’ liability shall be limited to our agreement to repair or replace the valve only.
Danfoss Flomatic Corp, 15 Pruyn’s Island, Glens Falls, New York 12801
Phone: 518-761-9797 Fax: 518-761-9798 www.flomatic.com
6" THRU 10"2-1/2" THRU 4"
6" (150mm)
1000
FLOW RATE
Danfoss Flomatic
8" (200mm)
1500
94.6463.10
10" (250mm)
2000
126.18
July 6,2004 Rev. 5
2500 gpm
157.73 lps