Double Check Valve Installation Instructions
Models DCV 2-1/2” – 10”
Basic Installation Instructions:
CAUTION: Installation of Double Check Valves must be performed by qualified, licensed personnel.
Faulty installation could result in an improperly functioning assembly.
The installer should be sure the proper assembly has been selected for the particular installation.
Danfoss Flomatic Model DCV Double Check Valves are for use on potable water lines where a health hazard would not
exist in the event of a backflow situation.
Proper performance is dependent upon following these installation instructions and prevailing govern m ental and industry
standards and codes. Failure to do so, according to Danfoss Flomatics limited Warranty "releases Danfoss Flomatic of
any liability that it might otherwise have with respect to that assembly". Such failure could also result in an improperly
functioning assembly.
Damage to the assembly could result wherever water hammer and/or water thermal expansion could create excessive
line pressure. Where this could occur, shock arrestors and/or pressure relief valves should be installed downstream of
the assembly.
1. Before installing a Model DCV Double Check Valve, flush the lines thoroughly to remove all debris, chips and other
foreign matter. If required a strainer should be placed upstream of the Double Check Valve. CAUTION : Do not use a
strainer in seldom used emergency water lines such as fire lines.
2. Provide adequate space around the installed unit so that the testcocks will be accessible for testing and servicing.
3. Always consult local codes for installation methods, approvals and guidelines.
Outdoor Installation
Model DCV Double Check Valve may be installed outdoors only if the assembly is protected against any freezing
conditions. Exposure to freezing conditions will result in improper function or damage to the assembly. The installation
location must be kept above 32
Indoor Installation
Indoor installation is preferred in areas that are subject to freezing conditions. All the basic installation instructions apply
to such installations.
Parallel Installation
Where uninterrupted service from a single meter connection must be maintained, two or more Double Check Valves
may be connected in parallel. All the basic installation instructions apply to a parallel installation. Be sure to allow
adequate room between the units for testing and repair.
Placing the Assembly in Service
After the installation of a Model DCV unit has been completed, place the unit in service as follows:
1. Start with both shut-off valves closed. Slowly open the inlet shut-off valve until the backflow preventer is completely
pressurized.
2. After the assembly has been pressurized, vent all trapped air by slightly opening each of the four testcocks.
3. Slowly open the downstream shut-off valve. The Model DCV Double Check Valve is now in service.
4. After the backflow preventer has been properly installed, test the assembly (see Test Procedures). If the assembly
fails the test, remove the first and second check valves and thoroughly flush the assembly. Clean rubber seats of all
debris and place unit back in service.
o
F. All the basic installation instructions apply.
Danfoss Flomatic
Danfoss Flomatic Corp, 15 Pruyn’s Island, Glens Falls, New York 12801
Phone: 518-761-9797 Fax: 518-761-9798 www.flomatic.com
June 2006 Rev. B (8/08)
DCV
Double Check Valve Installation Instructions
Models DCV 2-1/2” – 10”
MAINTENANCE INSTRUCTIONS
1. GENERAL
A. Clean all parts thoroughly with water after disassembly.
B. Carefully inspect silicone discs, and o-rings for damage.
C. Test unit after reassembly for proper operation.
2. SERVICING CHECK VALVES
A. Close inlet and outlet shut-off valves.
B. Open No. 2, 3, and 4 test cocks to release pressure from valve.
C. Remove the cover bolts valve cover.
D. Remove check valve spring clip and check valve assembly.
E. Inspect check valve seat and o-ring for debris and damage.
F. To remove silicone disc, unscrew check valve stem from disc
holder.
G. Remove disc retainer and disc from the disc holder and inspect
for cuts or embedded debris.
H. The silicone disc may be inverted if the reverse side is
undamaged.
I. Inspect the valve cavity and seat area for damage and debris.
J. Reverse the above procedures to reinstall the check valve assemblies.
NOTE: Check valves can only be installed in one configuration,
they are not reversible.
TEST PROCEDURES – Refer to local codes and prevailing test methods.
Method #1 – Two-hose method
EQUIPMENT REQUIRED:
Fittings (if required) and Test Kit
Danfoss Flomatic
SPRING RETAINER
SPRING
O-RING
SEAT RING
STEM
DO NOT REMOVE THE SPRING
RETAINER FROM THE STEM
ASSEMBLY. Remove the disc
holder from the stem assembly.
DO NOT DISASSEMBLE
DISC RETAINER
DISC
DISC HOLDER
HIGH SIDE HOSE
BY PASS HOSE
HIGH SIDE BLEED
NEEDLE VALVE
(BEHIND BODY)
LOW SIDE BLEED
NEEDLE VALVE
(BEHIND BODY)
LOW SIDE HOSE
VALVES
FILTERS
BLEED TUBE