FLIR i7 Operating Manual

User’s manual – Benutzerhandbuch Manual del usuarioManuel de l’utilisateur – Manuale dell’utente – Manual do utilizador – Felhas-
ználói kézikönyv – Käyttäjän opas –
Betjeningsvejledning – Brukerveiledning – Instrukcja obsługi – Bruksanvisning – Kullanım
Kılavuzu – Uživatelská příručka –
Gebruikershandleiding
FLIR i5 FLIR i7
T559382Publ. No. a358Revision English (EN)Language June 23, 2009Issue date
User’s manual
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
Legal disclaimer
All products manufactured by FLIR Systemsarewarranted against defectivematerialsandworkmanship for aperiodof one(1)year from the delivery date of the original purchase, provided such products have been under normal storage, use and service, and in accordance with FLIR Systems instruction.
All products not manufactured by FLIR Systems included in systemsdelivered by FLIRSystems to the original purchaser carrythe warranty, if any, of the particular supplier only and FLIR Systems has no responsibilitywhatsoever for such products.
The warranty extends only to the original purchaser and is not transferable. It is not applicable to any product which has been subjected to misuse, neglect, accident or abnormal conditions of operation. Expendable parts are excluded from the warranty.
In the case of adefect inaproduct coveredbythis warrantytheproduct must notbe furtherusedin order toprevent additional damage.The purchaser shall promptly report any defect to FLIR Systems or this warranty will not apply.
FLIR Systems will, at its option, repair or replace any such defective product free of charge if, upon inspection, it proves to be defective in material or workmanship and provided that it is returned to FLIR Systems within the said one-year period.
FLIR Systems has no other obligation or liability for defects than those set forth above. No other warranty is expressed or implied. FLIR Systems specifically disclaims the implied warranties of merchantability and fitness for a
particular purpose. FLIR Systems shall not be liable for any direct, indirect, special, incidentalor consequential loss or damage, whether basedon contract, tort
or any other legal theory.
Copyright
© FLIR Systems,2009. All rights reservedworldwide. No parts ofthesoftware including source codemaybe reproduced, transmitted, transcribed or translated into any language or computer language in any form or by any means, electronic, magnetic, optical, manual or otherwise, without the prior written permission of FLIR Systems.
This manual must not, in whole or part, be copied, photocopied, reproduced,translated ortransmitted to any electronic medium or machine readable form without prior consent, in writing, from FLIR Systems.
Names and marks appearing on the products herein are eitherregistered trademarksor trademarksof FLIR Systems and/or its subsidiaries. All othertrademarks,trade names or companynames referenced herein areusedfor identification only andarethe property of theirrespective owners.
Quality assurance
The Quality Management System under which these products are developed and manufactured has been certified in accordance with the ISO 9001 standard.
FLIR Systems is committed to a policy of continuous development; therefore we reserve the right to make changes and improvements on any of the products described in this manual without prior notice.
Patents
One or several of the following patents or design patents apply to the products and/or features described in this manual: 0002258-2; 000279476-0001;000439161;000499579-0001; 000653423; 000726344; 000859020;0101577-5; 0102150-0; 0200629-4; 0300911-
5; 0302837-0; 1144833;1182246;1182620; 1188086; 1263438; 1285345; 1287138; 1299699;1325808;1336775;1678485;200530018812.0; 2106017; 235308; 3006596; 3006597; 466540; 483782; 484155; 518836; 60004227.8; 60122153.2; 602004011681.5-08; 6707044; 68657; 7034300; 7110035; 7154093; 7157705; 7237946; 7312822; 7332716; 7336823; 75530; D540838; D549758; DI6702302-9; DI6703574-4; DM/057692; DM/061609;ZL00809178.1;ZL01823221.3; ZL01823226.4; ZL02331553.9; ZL02331554.7;ZL200530120994.2; ZL200630130114.4; ZL200730151141.4.
EULA Terms
You have acquired a device (“INFRARED CAMERA”) that includes software licensed by FLIR Systems AB from Microsoft Licensing, GP
or its affiliates (“MS”). Those installed software products of MS origin, as well as associated media, printed materials, and “online” or electronic documentation(“SOFTWARE”)are protected by internationalintellectualproperty laws and treaties.TheSOFTWARE is licensed, not sold. All rights reserved.
IF YOU DO NOTAGREE TO THISENDUSER LICENSE AGREEMENT(“EULA”), DO NOTUSETHE DEVICE ORCOPYTHESOFTWARE.
INSTEAD, PROMPTLY CONTACT FLIR Systems AB FOR INSTRUCTIONS ON RETURN OF THE UNUSED DEVICE(S) FOR A REFUND.
ANY USE OF THE SOFTWARE, INCLUDING BUT NOT LIMITED TO USE ON THE DEVICE, WILL CONSTITUTE YOUR AGREEMENT TO THIS EULA (OR RATIFICATION OF ANY PREVIOUS CONSENT).
GRANT OF SOFTWARE LICENSE. This EULA grants you the following license:
You may use the SOFTWARE only on the DEVICE.
NOT FAULT TOLERANT. THE SOFTWARE IS NOT FAULT TOLERANT. FLIR Systems AB HAS INDEPENDENTLY DETERMINED
HOW TOUSE THE SOFTWAREIN THE DEVICE,AND MS HASRELIED UPON FLIRSystems AB TOCONDUCT SUFFICIENT TESTING TO DETERMINE THAT THE SOFTWARE IS SUITABLE FOR SUCH USE.
iv Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
NO WARRANTIES FOR THE SOFTWARE. THE SOFTWARE is provided “AS IS” and with all faults. THE ENTIRE RISK AS TO SAT-
ISFACTORY QUALITY, PERFORMANCE, ACCURACY, AND EFFORT (INCLUDING LACK OF NEGLIGENCE) IS WITH YOU. ALSO, THERE ISNO WARRANTY AGAINSTINTERFERENCE WITH YOURENJOYMENT OF THESOFTWAREOR AGAINST INFRINGEMENT.
IF YOU HAVE RECEIVED ANY WARRANTIES REGARDING THE DEVICE OR THE SOFTWARE, THOSE WARRANTIES DO NOT ORIGINATE FROM, AND ARE NOT BINDING ON, MS.
No Liability for Certain Damages. EXCEPT AS PROHIBITED BY LAW, MS SHALL HAVE NO LIABILITY FOR ANY INDIRECT,
SPECIAL, CONSEQUENTIAL OR INCIDENTAL DAMAGES ARISING FROM OR IN CONNECTION WITH THE USE OR PERFOR­MANCE OF THE SOFTWARE. THIS LIMITATION SHALL APPLY EVEN IF ANY REMEDY FAILS OF ITS ESSENTIAL PURPOSE. IN NO EVENT SHALL MS BE LIABLE FOR ANY AMOUNT IN EXCESS OF U.S. TWO HUNDRED FIFTY DOLLARS (U.S.$250.00).
Limitations on Reverse Engineering, Decompilation, and Disassembly. Youmay not reverse engineer, decompile, ordisassemble
the SOFTWARE, exceptand only to the extentthat such activity isexpresslypermitted by applicable lawnotwithstandingthis limitation.
SOFTWARE TRANSFER ALLOWED BUT WITH RESTRICTIONS. Youmaypermanentlytransferrights under this EULA only aspart
of a permanent sale or transfer of the Device, and only if the recipient agrees to this EULA. If the SOFTWARE is an upgrade, any transfer must also include all prior versions of the SOFTWARE.
EXPORT RESTRICTIONS. You acknowledge that SOFTWARE is subject to U.S. export jurisdiction. You agree to comply with all
applicable international andnationallawsthatapplytotheSOFTWARE, includingthe U.S. Export Administration Regulations,aswell as end-user, end-use and destination restrictions issued by U.S. and other governments. For additional information see http://www.microsoft.com/exporting/.
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
vi Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

Table of contents

11 Warnings & Cautions .....................................................................................................................
32 Notice to user ..................................................................................................................................
43 Customer help ................................................................................................................................
54 Documentation updates .................................................................................................................
65 Important note about this manual .................................................................................................
76 Quick Start Guide ...........................................................................................................................
97 Packing list ......................................................................................................................................
108 Camera parts ..................................................................................................................................
139 Screen elements ............................................................................................................................
1510 Connectors and storage media ....................................................................................................
1611 Using the camera ............................................................................................................................
1611.1 Installing the battery .............................................................................................................
1711.2 Charging the battery .............................................................................................................
1911.3 Saving an image ...................................................................................................................
2011.4 Recalling an image ...............................................................................................................
2111.5 Opening the image archive ..................................................................................................
2211.6 Deleting an image .................................................................................................................
2311.7 Deleting all images ...............................................................................................................
2411.8 Measuring a temperature using a spotmeter .......................................................................
2511.9 Measuring a temperature using an area ..............................................................................
2611.10 Marking all areas above or below a set temperature level ..................................................
2711.11 Changing the color palette ...................................................................................................
2811.12 Changing the settings ..........................................................................................................
2911.13 Changing the image mode ...................................................................................................
3011.14 Setting the surface properties ..............................................................................................
3111.15 Changing the emissivity .......................................................................................................
3211.16 Changing the reflected apparent temperature ....................................................................
3311.17 Resetting the camera ............................................................................................................
3411.18 Finding the serial number of the camera .............................................................................
3512 Cleaning the camera ......................................................................................................................
3512.1 Camera housing, cables, and other items ...........................................................................
3612.2 Infrared lens ..........................................................................................................................
3713 Technical data .................................................................................................................................
3713.1 Camera data .........................................................................................................................
4013.2 Additional data ......................................................................................................................
4213.3 Accessories data ..................................................................................................................
4314 Dimensions ......................................................................................................................................
4314.1 Camera (front) ......................................................................................................................
4414.2 Camera (side) .......................................................................................................................
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 vii
16.2.1.2 Guidelines for moisture detection, mold detection & detection of
water damages ..................................................................................
16.3.8 Excerpt from Technical Note ‘Assessing thermal bridging and insulation
continuity’ (UK example) ......................................................................................
4515 Application examples .....................................................................................................................
4515.1 Moisture & water damage ....................................................................................................
4615.2 Faulty contact in socket ........................................................................................................
4715.3 Oxidized socket ....................................................................................................................
4815.4 Insulation deficiencies ..........................................................................................................
4915.5 Draft ......................................................................................................................................
5016 Introduction to building thermography ........................................................................................
5016.1 Important note ......................................................................................................................
5016.2 Typical field investigations ....................................................................................................
5016.2.1 Guidelines .............................................................................................................
5016.2.1.1 General guidelines ............................................................................
51
5116.2.1.3 Guidelines for detection of air infiltration & insulation deficiencies ...
5216.2.2 About moisture detection .....................................................................................
5216.2.3 Moisture detection (1): Low-slope commercial roofs ..........................................
5216.2.3.1 General information ...........................................................................
5316.2.3.2 Safety precautions ............................................................................
5416.2.3.3 Commented building structures .......................................................
5516.2.3.4 Commented infrared images ............................................................
5716.2.4 Moisture detection (2): Commercial & residential façades ..................................
5716.2.4.1 General information ...........................................................................
5716.2.4.2 Commented building structures .......................................................
5916.2.4.3 Commented infrared images ............................................................
5916.2.5 Moisture detection (3): Decks & balconies ..........................................................
5916.2.5.1 General information ...........................................................................
6016.2.5.2 Commented building structures .......................................................
6216.2.5.3 Commented infrared images ............................................................
6216.2.6 Moisture detection (4): Plumbing breaks & leaks ................................................
6216.2.6.1 General information ...........................................................................
6316.2.6.2 Commented infrared images ............................................................
6516.2.7 Air infiltration .........................................................................................................
6516.2.7.1 General information ...........................................................................
6516.2.7.2 Commented building structures .......................................................
6716.2.7.3 Commented infrared images ............................................................
6816.2.8 Insulation deficiencies ..........................................................................................
6816.2.8.1 General information ...........................................................................
6816.2.8.2 Commented building structures .......................................................
7016.2.8.3 Commented infrared images ............................................................
7216.3 Theory of building science ...................................................................................................
7216.3.1 General information ..............................................................................................
7316.3.2 The effects of testing and checking .....................................................................
7416.3.3 Sources of disruption in thermography ................................................................
7616.3.4 Surface temperature and air leaks .......................................................................
7616.3.4.1 Pressure conditions in a building .....................................................
8216.3.5 Measuring conditions & measuring season .........................................................
8216.3.6 Interpretation of infrared images ..........................................................................
8416.3.7 Humidity & dew point ...........................................................................................
8416.3.7.1 Relative & absolute humidity ............................................................
8516.3.7.2 Definition of dew point ......................................................................
85
viii Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
8516.3.8.1 Credits ...............................................................................................
8616.3.8.2 Introduction .......................................................................................
8616.3.8.3 Background information ...................................................................
8716.3.8.4 Quantitative appraisal of thermal anomalies ....................................
9016.3.8.5 Conditions and equipment ...............................................................
9116.3.8.6 Survey and analysis ..........................................................................
9216.3.8.7 Reporting ...........................................................................................
9416.4 Disclaimer .............................................................................................................................
9416.4.1 Copyright notice ...................................................................................................
9416.4.2 Training & certification ..........................................................................................
9416.4.3 National or regional building codes .....................................................................
9517 Introduction to thermographic inspections of electrical installations ......................................
9517.1 Important note ......................................................................................................................
9517.2 General information ..............................................................................................................
9517.2.1 Introduction ...........................................................................................................
9617.2.2 General equipment data .......................................................................................
9717.2.3 Inspection .............................................................................................................
9717.2.4 Classification & reporting ......................................................................................
9817.2.5 Priority ...................................................................................................................
9817.2.6 Repair ....................................................................................................................
9917.2.7 Control ..................................................................................................................
10017.3 Measurement technique for thermographic inspection of electrical installations ...............
10017.3.1 How to correctly set the equipment .....................................................................
10017.3.2 Temperature measurement ...................................................................................
10217.3.3 Comparative measurement ..................................................................................
10317.3.4 Normal operating temperature .............................................................................
10417.3.5 Classification of faults ...........................................................................................
10617.4 Reporting ..............................................................................................................................
10817.5 Different types of hot spots in electrical installations ...........................................................
10817.5.1 Reflections ............................................................................................................
10817.5.2 Solar heating .........................................................................................................
10917.5.3 Inductive heating ...................................................................................................
10917.5.4 Load variations ......................................................................................................
11017.5.5 Varying cooling conditions ...................................................................................
11117.5.6 Resistance variations ............................................................................................
11117.5.7 Overheating in one part as a result of a fault in another ......................................
11317.6 Disturbance factors at thermographic inspection of electrical installations ........................
11317.6.1 Wind ......................................................................................................................
11317.6.2 Rain and snow ......................................................................................................
11417.6.3 Distance to object .................................................................................................
11517.6.4 Object size ............................................................................................................
11717.7 Practical advice for the thermographer ................................................................................
11717.7.1 From cold to hot ...................................................................................................
11717.7.2 Rain showers ........................................................................................................
11717.7.3 Emissivity ..............................................................................................................
11817.7.4 Reflected apparent temperature ...........................................................................
11817.7.5 Object too far away ...............................................................................................
11918 About FLIR Systems .......................................................................................................................
12018.1 More than just an infrared camera .......................................................................................
12018.2 Sharing our knowledge ........................................................................................................
12018.3 Supporting our customers ...................................................................................................
12118.4 A few images from our facilities ...........................................................................................
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 ix
12319 Glossary ...........................................................................................................................................
12720 Thermographic measurement techniques ...................................................................................
12720.1 Introduction ..........................................................................................................................
12720.2 Emissivity ..............................................................................................................................
12820.2.1 Finding the emissivity of a sample .......................................................................
12820.2.1.1 Step 1: Determining reflected apparent temperature .......................
13020.2.1.2 Step 2: Determining the emissivity ...................................................
13120.3 Reflected apparent temperature ..........................................................................................
13120.4 Distance ................................................................................................................................
13120.5 Relative humidity ..................................................................................................................
13120.6 Other parameters ..................................................................................................................
13221 History of infrared technology ......................................................................................................
13622 Theory of thermography ................................................................................................................
13622.1 Introduction ...........................................................................................................................
13622.2 The electromagnetic spectrum ............................................................................................
13722.3 Blackbody radiation ..............................................................................................................
13822.3.1 Planck’s law ..........................................................................................................
13922.3.2 Wien’s displacement law ......................................................................................
14122.3.3 Stefan-Boltzmann's law .........................................................................................
14222.3.4 Non-blackbody emitters .......................................................................................
14422.4 Infrared semi-transparent materials .....................................................................................
14623 The measurement formula .............................................................................................................
15224 Emissivity tables .............................................................................................................................
15224.1 References ............................................................................................................................
15224.2 Important note about the emissivity tables ..........................................................................
15324.3 Tables ....................................................................................................................................
x Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

1 Warnings & Cautions

This equipment generates, uses, and can radiate radio frequency energy and if
WARNING
not installed and used in accordance with the instruction manual, may cause in­terference to radio communications. It has been tested and found to comply with the limits for a Class A computing device pursuant to Subpart J of Part 15 of FCC Rules, which are designedto providereasonable protection againstsuch interfer­ence when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference in which case the user at his own expense will be required to take whatever measures may be required to correct the interference. (Applies only to cameras with laser pointer:) Do not look directly into the laser
beam. The laser beam can cause eye irritation. Applies only to cameras with battery:
Do not disassemble or do a modification to the battery. The battery contains
safety and protection devices which, if they become damaged, can cause the battery to become hot, or cause an explosion or an ignition. If there is a leak from the battery and the fluid gets into your eyes, do not rub
your eyes.Flush well withwater and immediatelyget medical care. Thebattery fluid can cause injury to your eyes if you do not do this. Do not continue to charge the battery if it does not become charged in the
specified charging time. If you continue to charge the battery, it can become hot and cause an explosion or ignition. Only use the correct equipment to discharge the battery. If you do not use the
correct equipment, you can decrease the performance or the life cycle of the battery. If you do not use the correct equipment, an incorrect flow of current to the battery can occur. This can cause the battery to become hot, or cause an explosion and injury to persons.
Make sure that you read all applicable MSDS (Material Safety Data Sheets) and
warning labelson containersbeforeyou usea liquid: theliquids can bedangerous.
Do not point theinfrared camera (withor without the lens cover)at intensive energy
CAUTION
sources, for example devices that emit laser radiation, or the sun. This can have an unwanted effect on the accuracy of the camera. It can also cause damage to the detector in the camera. Do not use the camera in a temperature higher than +50°C (+122°F), unless
specified otherwise in the technical data section. High temperatures can cause damage to the camera. (Applies only to cameras with laser pointer:) Protect the laser pointer with the
protective cap when you do not operate the laser pointer. Applies only to cameras with battery:
Do not attach the batteries directly to a car’s cigarette lighter socket, unless a
specific adapter for connecting the batteries to a cigarette lighter socket is provided by FLIR Systems. Do not connect the positive terminal and the negative terminal of the battery
to each other with a metal object (such as wire). Do not get water or salt water on the battery, or permit the battery to get wet.
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 1
1 – Warnings & Cautions
Do not make holes in the battery with objects. Do not hit the battery with a
hammer. Do not step on the battery, or apply strong impacts or shocks to it. Do not put thebatteries inor near a fire, orinto direct sunlight. When thebattery
becomes hot, the built-in safety equipment becomes energized and can stop the battery charging process. If the battery becomes hot, damage can occur to the safety equipment and this can cause more heat, damage or ignition of the battery. Do not put the battery on a fire or increase the temperature of the battery with
heat. Do not put the battery on or near fires, stoves, or other high-temperature loca-
tions. Do not solder directly onto the battery.
Do not use the battery if, when you use, charge, or store the battery, there is
an unusual smell fromthe battery,the battery feelshot, changes color, changes shape, or is in an unusual condition. Contact your sales office if one or more of these problems occurs. Only use a specified battery charger when you charge the battery.
The temperature range through which you can charge the battery is ±0°C to
+45°C (+32°F to +113°F). If you charge the battery at temperatures outof this range, it can cause thebattery to become hot or to break. It can also decrease the performance or the life cycle of the battery. The temperature range through which you can dischargethe battery is −15°C
to +50°C (+5°F to +122°F). Use of the battery out of this temperature range can decrease the performance or the life cycle of the battery. When the battery is worn, apply insulation to the terminals with adhesive tape
or similar materials before you discard it.
Do not apply solvents or similar liquids to the camera, the cables, or other items. This can cause damage. Be careful when you cleanthe infraredlens. The lens has a delicate anti-reflective coating. Do not clean the infrared lens too vigorously. This can damage the anti-reflective coating.
2 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

2 Notice to user

Typographical conventions
User-to-user forums
Calibration
Accuracy
Disposal of electronic waste
This manual uses the following typographical conventions:
Semibold is used for menu names, menu commands and labels, and buttons in
dialog boxes. Italic is used for important information.
Monospace is used for code samples.
UPPER CASE is used for names on keys and buttons.
Exchange ideas,problems, and infraredsolutions with fellowthermographers around the world in our user-to-user forums. To go to the forums, visit:
http://www.infraredtraining.com/community/boards/
(This notice only applies to cameras with measurement capabilities.) We recommend that you send in the camera for calibration once a year. Contact
your local sales office for instructions on where to send the camera.
(This notice only applies to cameras with measurement capabilities.) For very accurate results, we recommend that you wait 5 minutes after you have
started the camera before measuring a temperature. For cameras where the detector is cooled by a mechanical cooler, this time period
excludes the time it takes to cool down the detector (usually 5–7 minutes).
10742803;a1
As with most electronic products, this equipment must be disposed of in an environ­mentally friendlyway, and inaccordance with existingregulations for electronicwaste.
Please contact your FLIR Systems representative for more details.
Training
To read about infrared training, visit: http://www.infraredtraining.com
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 3

3 Customer help

General
Submitting a question
Downloads
For customer help, visit: http://flir.custhelp.com
To submit a question to the customer help team, you must be a registered user. It only takes a fewminutes to registeronline. If you only wantto search the knowledge­base for existing questions and answers, you do not need to be a registered user.
When you want to submit a question, makesure thatyou have the following informa­tion to hand:
The camera model
The camera serial number
The communication protocol, or method, between the camera and your PC (for
example, HDMI, Ethernet, USB™, or FireWire™) Operating system on your PC
Microsoft®Office version
Full name, publication number, and revision number of the manual
On the customer help site you can also download the following:
Firmware updates for your infrared camera
Program updates for your PC software
User documentation
Application stories
Technical publications
4 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

4 Documentation updates

General
Our manuals are updated several times per year, and we also issue product-critical notifications of changes on a regular basis.
To access the latest manuals and notifications, go to the Download tab at: http://flir.custhelp.com It only takes a few minutes to register online. In the download area you will also find
the latest releases of manuals for our other products, as well as manuals for our historical and obsolete products.
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 5

5 Important note about this manual

General
NOTE
FLIR Systems issues generic manuals that cover several cameras within a model line.
This means that this manual may contain descriptions and explanations that do not apply to your particular camera model.
FLIR Systemsreserves therightto discontinuemodels,software, parts oraccessories, and other items, or to change specifications and/or functionality at any time without prior notice.
6 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

6 Quick Start Guide

Procedure
Follow this procedure to get started right away:
Remove the protective film from the LCD.1
You must charge the battery inside the camera for four full hours (or until
2
the battery charging indicator displays a green light) before you use the camera for the first time.
Charge thebatteryby connecting thepowersupply to the powerconnector on the camera. Make sure that you use the correct AC plug.
Note: The first time you charge a factory-new battery you must turn on and then turn off the camera after you have connected the power supply to the
power connector on the camera.
T630175;a1
1 Battery charging indicator 2 Power supply cable
Insert a miniSD™ memory card into the card slot.
3
T630176;a1
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 7
6 – Quick Start Guide
Push the On/Off button to turn on the camera.
4
Note: If the camera does not start after you have charged thebattery, push
the reset button with a non-conductive tool. The reset button is located beside the battery connector, inside the battery compartment. Then press the On/Off button again.
The reset button:
T630179;a1
Open the lens cap by pushing the lens cap lever.
5
T630177;a1
Aim the camera toward your target of interest.6
Pull the Save trigger to save the image.7
To move the image to a computer, do one of the following:
8
T630178;a1
(Fig. 1 above) Remove the miniSD™ memory card and insert it into a
card readerconnected to a computer. A miniSD™ cardadapter is includ­ed with your camera. (Fig. 2 above) Connect a computer to the camera using a USB™ Mini-
B cable.
In Windows®Explorer, move the image from the card or camera using a
9
drag-and-drop operation.
8 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

7 Packing list

Battery (inside camera)
Contents
NOTE
Calibration certificate
FLIR QuickReport CD
Hand strap
Infrared camera
miniSD card (512 MB), with SD adapter
Power supply/charger with EU, UK, US and Australian plugs
Printed Getting Started Guide
USB cable
User documentation CD-ROM
Contact your local sales office if any item is damaged or missing. You can find
the addresses and telephone numbers of local sales offices on the back cover of this manual. FLIR Systems reserves the rightto discontinue models, parts or accessories, and
other items, or to change specifications at any time without prior notice.
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 9

8 Camera parts

Figure
10780903;a1
Explanation
This table explains the figure above:
Infrared lens1
Lever to open and close the lens cap2
Trigger to save images3
Cover to connectors and the miniSD™ memory card slot4
Cover to the battery compartment5
Attachment point for the hand strap6
10 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
8 – Camera parts
Figure
Explanation
10781003;a1
This table explains the figure above:
Archive button
1
Function: Push to open the image archive.
Left arrow button (on the navigation pad)
2
Function:
Push to go left in menus, submenus, and dialog boxes
Push to navigate in the image archive
Left selection button. This button is context-sensitive, and the current
3
function is displayed above the button on the screen.
+ button (on the navigation pad)
4
Function:
Push to go up in menus, submenus, and dialog boxes.
Push to display the image archive (after having pushed the Archive
button). Push to increase/change the value.
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 11
8 – Camera parts
Right arrow button (on the navigation pad)
5
Function:
Push to go right in menus, submenus, and dialog boxes.
Push to navigate in the image archive.
Right selection button. This button is context-sensitive, and the current
6
function is displayed above the button on the screen.
On/Off button
7
Function:
Push to turn on the camera.
Push and hold down for more than one second to turn off the camera.
– button (on navigation pad)
8
Function:
Push to go down in menus, submenus, and dialog boxes.
Push to decrease/change the value.
12 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

9 Screen elements

Figure
Explanation
10781203;a2
This table explains the figure above:
Menu system1
Measurement result2
Power indicator
3
MeaningIcon
One of the following:
The camera is powered using
the battery. The battery is being charged
(indicated by a refilling battery animation).
The battery is fullycharged and the camera is powered using the power supply.
Date and time4
Limit value for the temperature scale5
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 13
9 – Screen elements
Temperature scale6
Currently set emissivity value or material properties7
Current function for the right selection button8
Current function for the left selection button9
14 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

10 Connectors and storage media

Figure
Explanation
10780803;a1
This table explains the figure above:
miniSD™ memory card
1
We recommend that you do not save more than 5,000 images on the min­iSD™ memory card.
Although a memory card may have a higher capacity than 5,000 images, saving more than that number ofimages severelyslows down file manage­ment on the miniSD™ memory card.
Note: There is no upper limit to the memory size of the miniSD™ memory card.
Battery charging indicator:
2
No light: The power supply is not connected.
Orange light: The battery is being charged.
Green light: The charging of the battery is completed.
Power supply cable3
USB cable with USB Mini-B connector4
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 15

11 Using the camera

11.1 Installing the battery

Procedure
Follow this procedure to install the battery:
Remove the battery compartment cover.
1
T630174;a1
Connect the cable that is attached to the battery to the connector inside
2
the battery compartment. Note: Do not use conductive tools when doing this.
T630173;a2
Push the battery into place.3
Replace the cover to close the battery compartment.4
16 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

11.2 Charging the battery

You must charge the battery inside the camera for four full hours (or until the
NOTE
battery indicator displays a green light) before you use the camera for the first time. The first time you charge a factory-new battery you must turn on and then turn off
the camera after you have connected the power supply to the power connector on the camera. If the camera does not start after you have charged the battery, push the reset
button with a non-conductive tool. The reset button is located beside the battery connector, inside the battery compartment. Then press the On/Off button again. The reset button:
T630179;a1
Do not replace the battery on a frequent basis. Only replace the battery when it
is worn out.
11 – Using the camera
About the battery charging indicator
Procedure
The battery charging indicator is an LED beside the power connector. It displays the following signals:
No light: The power supply is not connected.
Orange light: The battery is being charged.
Green light: The charging of the battery is completed.
Follow this procedure to charge the battery:
Connect the power supply to the power connector on the camera.
1
T630175;a1
1 Battery charging indicator 2 Power supply cable
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 17
11 – Using the camera
Connect the power supply mains-electricity plug to a mains socket. Make
2
sure that you use the correct AC plug.
Disconnect thepower supply cableplug when thebattery charging indicator
3
displays a green light.
18 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

11.3 Saving an image

11 – Using the camera
General
Image capacity
Formatting memory cards
Naming convention
You can save multiple images to the miniSD™ memory card.
We recommend that you do not save more than 5,000 images on the miniSD™ memory card.
Although amemory card mayhave a highercapacity than 5,000images, saving more than that number of images severely slows down file management on the memory card.
Note: There is no upper limit to the memory size of the miniSD™ memory card.
For best performance, memory cards should be formatted to the FAT (FAT16) file system. Using FAT32-formatted memory cards may result in inferior performance. To format a memory card to FAT (FAT16), follow this procedure:
Insert the memory card into a card reader that is connected to your com-
1
puter.
In Windows®Explorer, select My Computer and right-click the memory
2
card.
Select Format.3
Under File system, select FAT.4
Click Start.5
The naming convention for images is IR_xxxx.jpg, where xxxx is a unique counter. When you select Restore, the cameraresets the counterand assigns thenext highest free file name for the new file.
Procedure
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 19
To save an image, pull the Save trigger.
11 – Using the camera

11.4 Recalling an image

General
Procedure
When you save an image, it is stored on the removable miniSD™ memory card. To display the image again, you can recall it from the miniSD™ memory card.
Follow this procedure to recall an image:
Push the Archive button.1
Do one of the following:
2
Push the navigation pad left/right to select the image you want to view.
Push the + button, use the navigation pad to selectthe image you want
to see, then push the right selection button (Open).
To return to live mode, do one of the following:
3
Push the Archive button.
Push the right selection button (Close).
20 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

11.5 Opening the image archive

11 – Using the camera
General
Procedure
The image archive is a thumbnail gallery of all the images on the miniSD™ memory card.
Follow this procedure to open the image archive:
Push the Archive button.1
Push the + button on the navigation pad.
2
This will display the image archive. You can now use the navigation pad to navigate in the archive.
To open a selected image, push the right selection button (Open).3
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 21
11 – Using the camera

11.6 Deleting an image

General
Alternative 1
Alternative 2
You can delete one or more images from the miniSD™ memory card.
Follow this procedure to delete an image:
Push the Archive button.1
Push the + button. This will display the image archive.2
Select the image you want to delete by using the navigation pad.3
Push the left selection button (Options).4
Use the navigation pad to select Delete image.5
Push the left selection button (Select).6
Push the right selection button to confirm (Delete).7
To return to live mode, do one of the following:
8
Push the Archive button.
Push the right selection button (Close).
Follow this procedure to delete an image:
Push the Archive button.1
Select the image you want to delete by using the navigation pad.2
Push the left selection button (Delete).3
Push the right selection button to confirm (Delete).4
To return to live mode, do one of the following:
5
Push the Archive button.
Push the right selection button (Close).
22 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

11.7 Deleting all images

11 – Using the camera
General
Procedure
You can delete all images from the miniSD™ memory card.
Follow this procedure to delete all images:
Push the Archive button.1
Push the + button. This will display the image archive2
Push the left selection button (Options).3
Use the navigation pad to select Delete all images.4
Push the left selection button (Select).5
Push the right selection button to confirm (Delete).6
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 23
11 – Using the camera

11.8 Measuring a temperature using a spotmeter

General
Procedure
You can measure a temperature using a spotmeter. This will display the temperature at the position of the spotmeter on the screen.
Follow this procedure:
Push the left selection button (Menu).1
Use the navigation pad to select Measurement.2
Push the left selection button (Select).3
Use the navigation pad to select Spot.4
Push the left selection button (Select).
5
The temperature at the position of the spotmeter will now displayed in the top left corner of the screen.
24 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

11.9 Measuring a temperature using an area

11 – Using the camera
General
Procedure
You can continuouslyindicate the highestor lowest temperature within anarea, using a continuously moving cursor.
Follow this procedure:
Push the left selection button (Menu).1
Use the navigation pad to select Measurement.2
Push the left selection button (Select).3
Use the navigation pad to select one of the following:
4
Area max.
Area min.
Push the left selection button (Select).
5
The highest or lowest temperature within the area will now be indicated by a continuously moving cursor.
The temperature will also be displayed in the top left corner of the screen.
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 25
11 – Using the camera

11.10 Marking all areas above or below a set temperature level

General
Procedure
You can mark all areas above or below a set temperature level.
Follow this procedure:
Push the left selection button (Menu).1
Use the navigation pad to select Measurement.2
Push the left selection button (Select).3
Use the navigation pad to select one of the following:
4
Detect above
Detect below
Push the left selection button (Select).5
To change the temperature level above or below which you want to mark
6
the areas, use the navigation pad.
26 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

11.11 Changing the color palette

11 – Using the camera
General
Procedure
You can change the color palette that the camera uses to display different tempera­tures. A different palette can make it easier to analyze an image.
Follow this procedure to change the color palette:
Push the left selection button (Menu).1
Use the navigation pad to go to Color palette.2
Push the left selection button (Select). This will display the Color palette
3
submenu.
Use the navigation pad to select the new color palette.4
Push the left selection button (Select) to confirm the choice and leave the
5
submenu.
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 27
11 – Using the camera

11.12 Changing the settings

General
Procedure
You can change a variety of settings for the camera. These include the following:
Auto shutdown
Display intensity
Language
Unit
Time format
Set time
Time stamp
Firmware (to download program updates for your camera. See http://flir.cus-
thelp.com for more information.)
Restore
Follow this procedure to change a setting:
Push the left selection button (Menu).1
Use the navigation pad to go to Settings.2
Push the left selection button (Select). This will display the Settings sub-
3
menu.
Use the navigation pad to select the setting you want to change.4
Push the left selectionbutton (Select), then usethe navigationpad to select
5
a new setting.
Push the left selection button (Select) to confirm the choice and leave the
6
submenu, or push the right selection button (Close) to leave the menu.
28 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

11.13 Changing the image mode

11 – Using the camera
General
When to use Locked mode
Procedure
The camera can operate in two different image modes:
ExplanationIconImage mode
[None]Auto
Locked
A typical situation when you would want to use Locked mode is when looking for temperature anomalies in two items of similar design or construction.
For example, if you are looking at two cables, where you suspect one is overheated, working inLocked mode willclearly show that oneis overheated. Thehighertemper­ature in that cable would create a lighter color for the higher temperature.
If you use Auto mode instead, the color for the two items will appear the same.
To switch between Auto mode and Locked mode, push the right selection button
(Auto/Locked). A padlock icon ( ) indicates the Locked mode.
In Auto mode, the cam­era is continuously auto­adjusted for best image brightness and contrast.
In Locked mode, the camera locksthe temper­ature span and the tem­perature level.
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 29
11 – Using the camera

11.14 Setting the surface properties

General
Procedure
SEE ALSO
To measure temperatures accurately, the camera must know what kind of surface you are measuring.
The easiest way to do this is to set the surface property on the Measure menu. You can choose between the following surface properties:
Matt
Semi-matt
Semi-glossy
Glossy
Follow this procedure to set the surface property:
Push the left selection button (Menu).1
Use the navigation pad to go to Measure.2
Push the left selection button (Select). This will display the Measure sub-
3
menu.
On the Measure menu, use thenavigation pad to select asurface property.4
Push the left selection button (Select) to confirm the choice and leave the
5
menu.
For more precise measurements, see the following sections:
Section 11.15 – Changing the emissivity on page 31
Section 11.16 – Changing the reflected apparent temperature on page 32
30 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

11.15 Changing the emissivity

11 – Using the camera
General
Procedure
For very precise measurements, you may need to set the emissivity, instead of se­lecting a surface property. You also need to understand how emissivity and reflectiv­ity affect measurements, rather than just simply selecting a surface property.
Emissivity is a property that indicates how much radiation originates from an object as opposed to being reflected by it. A lower value indicates that a larger proportion is beingreflected, while ahigh value indicates thata lower proportionis being reflect­ed.
Polished stainless steel, for example, has an emissivity of 0.14, while a structured PVC floor typically has an emissivity of 0.93.
Follow this procedure to set the emissivity:
Push the left selection button (Menu).1
Use the navigation pad to go to Measure.2
Push the left selection button (Select). This will display the Measure sub-
3
menu.
Use the navigation pad to select Advanced.4
Push the left selection button (Select). This will display the Advanced sub-
5
menu.
Use the navigation pad to do either of the following:
6
Set a value for emissivity
Select a material in the list of materials
Push the left selection button (Select) to confirm the choice and leave the
7
menu.
SEE ALSO
To read more about emissivity, see section 20 – Thermographic measurement tech­niques on page 127.
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 31
11 – Using the camera

11.16 Changing the reflected apparent temperature

General
Procedure
SEE ALSO
This parameter is used to compensate for the radiation reflected by the object. If the emissivity is low and the object temperature relatively far from that of the reflected temperature it will be important to set and compensate for the reflected apparent temperature correctly.
Follow this procedure to set the reflected apparent temperature:
Push the left selection button (Menu).1
Use the navigation pad to go to Measure.2
Push the left selection button (Select). This will display the Measure sub-
3
menu.
Use the navigation pad to select Advanced.4
Push the left selection button (Select). This will display the Advanced sub-
5
menu.
Use the navigation pad to set the reflected apparent temperature.6
Push the left selection button (Select) to confirm the choice and leave the
7
menu.
To read more about the reflected apparent temperature, see section 20 – Thermo­graphic measurement techniques on page 127.
32 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

11.17 Resetting the camera

11 – Using the camera
General
NOTE
Procedure
If you need toreset the camera,there is areset buttoninside the batterycompartment.
Do not use a metal or other conductive tool to reset the camera.
Follow this procedure to reset the camera:
Open the battery compartment cover.1
To locate the reset button, see the figure below.
2
T630179;a1
Use a non-conductive tool to push reset button. The camera will now be
3
reset.
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 33
11 – Using the camera

11.18 Finding the serial number of the camera

General
When you communicate with our service departments, you may need to state the serial number of the camera.
The serial number is printed on a label inside the battery compartment, behind the battery.
34 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

12 Cleaning the camera

12.1 Camera housing, cables, and other items

Liquids
Equipment
Procedure
CAUTION
Use one of these liquids:
Warm water
A weak detergent solution
A soft cloth
Follow this procedure:
Soak the cloth in the liquid.1
Twist the cloth to remove excess liquid.2
Clean the part with the cloth.3
Do not apply solvents or similar liquids to the camera, the cables, or other items. This can cause damage.
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 35
12 – Cleaning the camera

12.2 Infrared lens

Liquids
Equipment
Procedure
WARNING
CAUTION
Use one of these liquids:
96% isopropyl alcohol.
A commercial lens cleaning liquid with more than 30% isopropyl alcohol.
Cotton wool
Follow this procedure:
Soak the cotton wool in the liquid.1
Twist the cotton wool to remove excess liquid.2
Clean the lens one time only and discard the cotton wool.3
Make sure that you read all applicable MSDS (Material Safety Data Sheets) and warning labels on containers before you use a liquid: the liquids can be dangerous.
Be careful when you cleanthe infraredlens. The lens has a delicate anti-reflective
coating. Do not clean the infrared lens too vigorously. This can damage the anti-reflective
coating.
36 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

13 Technical data

13.1 Camera data

Imaging and optical data
Detector data
Image presentation
Measurement
Field of view (FOV) Dependent on the camera:
17° × 17° (FLIR i5 (2009 model))
25° × 25° (FLIR i7)
0.6 m (2 ft.)Minimum focus distance
3.71 mradSpatial resolution (IFOV)
< 0.1°C (0.18°F)Thermal sensitivity/NETD
9 HzImage frequency
Focus freeFocus
Detector type Focal plane array (FPA), uncooled microbolometer
7.5–13 µmSpectral range
IR resolution
Display 2.8 in. color LCD
Object temperature range
Dependent on the camera:
80 × 80 pixels (FLIR i5 (2009 model))
120 × 120 pixels (FLIR i7)
Automatic adjust/lock imageImage adjustment
0°C to +250°C (+32° to +482°F)
Accuracy
Measurement analysis
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 37
Spotmeter Center spot
Area
Isotherm
±2°C (±3.6°F)or ±2% ofreading, for ambienttemper­ature 10°C to 35°C (+50°F to 95°F)
Dependent on the camera:
Not applicable (FLIR i5 (2009 model))
Box with max./min. (FLIR i7)
Dependent on the camera:
Not applicable (FLIR i5 (2009 model))
Above/below (FLIR i7)
Variable from 0.1 to 1.0Emissivity correction
13 – Technical data
Emissivity table of predefined materialsEmissivity table
Automatic, based on input of reflected temperatureReflected apparent tem-
perature correction
Set-up
Storage of images
Data communication interfaces
Power system
Environmental data
Color palettes Black and white, iron and rainbow
Set-up commands
Local adaptation of units, language, date and time formats
Image storage type miniSD card
Standard JPEG, 14-bit measurement data includedFile formats
Interfaces USB Mini-B: Data transfer to and from PC
Battery type Rechargeable Li Ion battery
3.6 VBattery voltage
Battery operating time
Approx. 5 hours at +25°C (+77°F) ambient tempera­ture and typical use
Battery is charged inside the camera.Charging system
3 h to 90% capacityCharging time
Automatic shut-downPower management
AC adapter, 90–260 VAC input, 5 V output to cameraAC operation
Operating temperature
0°C to +50°C (+32°F to +122°F)
range
–40°C to +70°C (–40°F to +158°F)Storage temperature
range
IEC 60068-2-30/24 h 95% relative humidityHumidity (operating and
storage)
EMC
EN 61000-6-2:2005 (Immunity)
EN 61000-6-3:2007 (Emission)
FCC 47 CFR Part 15 Class B (Emission)
Camera housing and lens: IP 43 (IEC 60529)Encapsulation
25 g (IEC 60068-2-29)Bump
2 g (IEC 60068-2-6)Vibration
38 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
13 – Technical data
Physical data
Certifications
Scope of delivery
Camera weight, incl. bat-
0.34 kg (0.75 lb.)
tery
223 × 79 × 83 mm (8.8 × 3.1 × 3.3 in.)Camera size(L× W × H)
Material
Polycarbonate + acrylonitrile butadiene styrene (PC­ABS)
Thixomold magnesium Thermoplastic elastomer (TPE)
Blue and grayColor
Certification UL, CSA, CE, PSE and CCC
Packaging, type Hard case
Packaging, contents
FLIR QuickReport CD
Printed Getting Started Guide
User documentation CD-ROM
Calibration certificate
Hand strap
Battery (inside camera)
Power supply/charger with EU, UK, US and Aus-
tralian plugs USB cable
miniSD card (512 MB), with SD card adapter
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 39
13 – Technical data

13.2 Additional data

Field of view & distance (FLIR i5)
10780503;a1
Figure 13.1 Relationship between the fieldof viewand distance. 1: Distance to target; 2: VFOV =vertical field ofview; 3: HFOV =horizontal field of view, 4: IFOV = instan-
taneous field of view (size of one detector element).
This table gives examples ofthe field of view for different target distances. Note: The table does not take into account the minimum focus distance.
10781103;a1
40 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
Field of view & distance (FLIR i7)
13 – Technical data
10780503;a1
Figure 13.2 Relationship between the fieldof viewand distance. 1: Distance to target; 2: VFOV =vertical field ofview; 3: HFOV =horizontal field of view, 4: IFOV = instan-
taneous field of view (size of one detector element).
This table gives examples ofthe field of view for different target distances. Note: The table does not take into account the minimum focus distance.
T638201;a1
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 41
13 – Technical data

13.3 Accessories data

USB cable Std A ↔ Mini B, 2 m/6.6 ft.
Battery
Power supply/charger with EU, UK, US and AU plugs
Memory card, 512 MB miniSD
Cable length 2.0 m (6.6 ft.)
Standard USB-A to USB Mini-BConnector
Battery type Rechargeable Li Ion battery
3.6 VBattery voltage
Approximate lithium content: 0.7 gBattery note
Battery is charged inside the cameraCharging system
AC operation 100–240 V, 50/60 Hz output 5.0 VAC, 1.2 A
6 WPower
69.2 × 43.3 × 29.8 mm (2.7 × 1.7 × 1.2 in.)Size (L × W × H)
1.8 m (5.9 ft.)Cable length
Packaging, contents
Power supply/Battery charger
EU, UK, US and Australian plugs
512 MBMemory card, size
21.5 × 20 × 1.4 mm (0.85 × 0.79 × 0.06 in.)Size (L × W × H)
Packaging, contents
miniSD card
Adapter from miniSD Card to SD Memory Card
42 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

14 Dimensions

14.1 Camera (front)

Figure
10780603;a1
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 43
14 – Dimensions

14.2 Camera (side)

Figure
10780703;a1
44 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

15 Application examples

15.1 Moisture & water damage

General
NOTE
Figure
It is often possible to detect moisture and water damage in a house by using an in­frared camera. This ispartly becausethe damaged area has adifferent heat conduc­tion property and partly because it has a differentthermal capacity to storeheat than the surrounding material.
Many factors can come into play as to how moisture or water damage will appear in an infrared image.
For example,heating and coolingof these parts takes placeat different ratesdepend­ing on the material and the time of day. For this reason, it is important that other methods are used as well to check for moisture or water damage.
The imagebelow shows extensive waterdamage on anexternalwall where thewater has penetrated the outer facing because of an incorrectly installed window ledge.
10739503;a1
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 45
15 – Application examples

15.2 Faulty contact in socket

General
NOTE
Figure
Depending on the type of connection a socket has, an improperly connected wire can result in local temperature increase. This temperature increase is caused by the reduced contact area between the connection point of the incoming wire and the socket , and can result in an electrical fire.
A socket’s construction may differ dramatically from one manufacturer to another. For this reason, different faults in a socket can lead to the same typical appearance in an infrared image.
Local temperature increase can also result from improper contact between wire and socket, or from difference in load.
The image below shows aconnection ofa cable to a socket where improper contact in the connection has resulted in local temperature increase.
10739603;a1
46 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

15.3 Oxidized socket

15 – Application examples
General
NOTE
Figure
Depending on the typeof socket andthe environment in which thesocket is installed, oxides may occur on the socket's contact surfaces. These oxides can lead to locally increased resistance when the socket is loaded, which can be seen in an infrared image as local temperature increase.
A socket’s construction may differ dramatically from one manufacturer to another. For this reason, different faults in a socket can lead to the same typical appearance in an infrared image.
Local temperature increase can also result from improper contact between a wire and socket, or from difference in load.
The image below shows a series of fuses where one fuse has a raised temperature on the contact surfaces against the fuse holder. Because of the fuse holder’s blank metal, the temperature increase is not visible there, while it is visible on the fuse’s ceramic material.
10739703;a1
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 47
15 – Application examples

15.4 Insulation deficiencies

General
NOTE
Figure
Insulation deficiencies may result from insulation losing volume over the course of time and thereby not entirely filling the cavity in a frame wall.
An infraredcamera allowsyou to seethese insulation deficienciesbecause they either have a different heat conduction property than sections with correctly installed insu­lation, and/or show the area where air is penetrating the frame of the building.
When you are inspecting a building, the temperature difference between the inside and outside should be at least 10°C (18°F). Studs, water pipes, concrete columns, and similar components may resemble an insulation deficiency in an infrared image. Minor differences may also occur naturally.
In the image below, insulation in the roof framing is lacking.. Due to the absence of insulation, air has forcedits way into the roof structure, whichthus takes on a different characteristic appearance in the infrared image.
10739803;a1
48 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009

15.5 Draft

15 – Application examples
General
NOTE
Figure
Draft can be found under baseboards, around door and window casings, and above ceiling trim. This type of draft is often possible to see with an infrared camera, as a cooler airstream cools down the surrounding surface.
When youare investigating draftin a house,there should besub-atmosphericpressure in the house. Close all doors, windows, and ventilation ducts, and allow the kitchen fan to run for a while before you take the infrared images.
An infrared image of draft often shows a typical stream pattern. You can see this stream pattern clearly in the picture below.
Also keep in mind that drafts can be concealed by heat from floor heating circuits.
The image below shows a ceiling hatch where faulty installation has resulted in a strong draft.
10739903;a1
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 49
16 Introduction to building
thermography

16.1 Important note

All camera functions and features that are described in this section may not be sup­ported by your particular camera configuration.

16.2 Typical field investigations

16.2.1 Guidelines

As will be noted in subsequent sections there are a number of general guidelines the user should take heed of when carrying out building thermography inspection. This section gives a summary of these guidelines.
16.2.1.1 General guidelines
The emissivity of the majority of building materials fall between 0.85 and 0.95.
Setting the emissivity value in the camera to 0.90 can be regarded as a good starting point.
An infrared inspection alone should never be used as a decision point for further
actions. Always verify suspicions and findings using other methods, such as con­struction drawings, moisture meters, humidity & temperature datalogging, tracer gas testing etc.
Change level and span to thermally tune the infrared image and reveal more details.
The figurebelow shows the difference between a thermally untuned and a thermally tuned infrared image.
10552103;a2
Figure 16.1 LEFT: A thermally untuned infrared image; RIGHT: A thermally tuned infrared image, after having changed level and span.
50 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
16 – Introduction to building thermography
16.2.1.2 Guidelines for moisture detection, mold detection & detection of water damages
Building defects related to moisture and water damages may only show up when
heat has been applied to the surface, e.g. from the sun.
The presence of water changes the thermal conductivity and the thermal mass of
the building material. It may also change the surfacetemperature of building mate­rial due to evaporative cooling. Thermal conductivity is a material’s abilityto conduct heat, while thermal mass is its ability to store heat.
Infrared inspection does not directly detect the presence of mold, rather it may be
used to find moisture where mold may develop or has already developed. Mold requires temperatures between +4°C to +38°C (+40°F to +100°F), nutrients and moisture to grow. Humidity levels above 50% can provide sufficient moisture to enable mold to grow.
10556003;a1
Figure 16.2 Microscopic view of mold spore
16.2.1.3 Guidelines for detection of air infiltration & insulation deficiencies
For very accurate camera measurements, take measurements of the temperature
and enter this value in the camera.
It is recommended that there is a difference in pressure between the outside and
the inside of the building structure. This facilitates theanalysis of the infrared images and reveals deficiencies that would not be visible otherwise. Although a negative pressure of between 10 and 50 Pa is recommended, carrying out the inspection at a lower negative pressure may be acceptable. To do this, close all windows, doors and ventilation ducts and then run the kitchen exhaust fan for some time to reach a negative pressure of 5–10 Pa (applies to residential houses only).
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 51
16 – Introduction to building thermography
A differencein temperaturebetween the inside and the outside of 10–15°C (18–27°F)
is recommended.Inspections can be carried out at a lower temperature difference, but will make the analysis of the infrared images somewhat more difficult.
Avoid direct sunlight on a part of a building structure—e.g. a façade—that is to be
inspected from the inside. The sunlight will heat the façade which will equalize the temperature differenceson theinside and mask deficiencies in the building structure. Spring seasons with low nighttime temperatures (±0°C (+32°F)) and high daytime temperatures (+14°C (+57°F)) are especially risky.

16.2.2 About moisture detection

Moisture in a building structure can originate from several different sources, e.g.:
External leaks, such as floods, leaking fire hydrants etc.
Internal leaks, such as freshwater piping, waste water piping etc.
Condensation, which is humidityin the air falling out as liquid water due to conden-
sation on cold surfaces.
Building moisture, which is any moisture in the building material prior to erecting
the building structure.
Water remaining from firefighting.
As a non-destructive detection method, using an infrared camera has a number of advantages over other methods, and a few disadvantages:
DisadvantageAdvantage
The method is quick.
The methodis a non-intrusivemeansof investi-
gation. The method does not require relocation of the
occupants. The method features an illustrative visual pre-
sentation of findings. The method confirms failure points and mois-
ture migration paths.
The method only detects surface temperature
differentials and can not see through walls. The methodcan not detectsubsurfacedamage,
i.e. mold or structural damage.

16.2.3 Moisture detection (1): Low-slope commercial roofs

16.2.3.1 General information
Low-slope commercial roofing is one of the most common roof types for industrial building, such as warehouses, industrial plants, machinery shops etc. Its major ad­vantages over a pitched roof is the lower cost in material and building. However, due to its design where snow and ice will not fall off by itself—as is the case for the major­ity of pitched roofs—it must be strongly built to support the accumulated weight of both roof structure and any snow, ice and rain.
52 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
16 – Introduction to building thermography
Although a basic understanding of the construction of low-slope commercial roofs is desirable whencarrying outa roof thermography inspection, expert knowledge is not necessary. There is a large number of different design principles for low-slope com­mercial roofs—bothwhen itcomes tomaterial anddesign—and itwould beimpossible for the infrared inspection person to know them all. If additional information about a certain roof is needed, the architect or contractor of the building can usually supply the relevant information.
Common causesof rooffailure areoutlined in the table below (from SPIE Thermosense Proceedings Vol. 371 (1982), p. 177).
%Cause
47.6Poor workmanship
2.6Roof traffic
16.7Poor design
7.8Trapped moisture
8.0Materials
8.4Age & weathering
Potential leak locations include the following:
Flashing
Drains
Penetrations
Seams
Blisters
16.2.3.2 Safety precautions
Recommend a minimum of two people on a roof, preferably three or more.
Inspect the underside of the roof for structural integrity prior to walking on it.
Avoid stepping on blisters that are common on built up bitumen and gravel roofs.
Have a cell phone or radio available in case of emergency.
Inform local police and plant security prior to doing nighttime roof survey.
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 53
16 – Introduction to building thermography
16.2.3.3 Commented building structures
This section includes a few typical examples of moisture problems on low-slope commercial roofs.
CommentStructural drawing
10553603;a2
Inadequate sealing of roof membrane around conduit and ventilation ducts leading to local leakage around the conduit or duct.
10553703;a2
Roof membrane inadequately sealed around roof access hatch.
54 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
10553803;a2
16 – Introduction to building thermography
CommentStructural drawing
Drainage channels located too high and with too low an inclination. Some water will remain in the drainage channelafter rain, whichmay lead tolocal leakage around the channel.
10553903;a2
Inadequate sealing between roof membrane and roof outlet leading tolocal leakage aroundthe roof outlet.
16.2.3.4 Commented infrared images
How do you find wet insulation below the surface of the roof? When the surface itself is dry, including any gravel or ballast, a sunny day will warm the entire roof. Early in the evening, if the sky is clear, the roof will begin to cool down by radiation. Because of its higher thermal capacity the wet insulation will stay warmer longer than the dry and will be visible in the infrared camera (see photos below). The technique is partic­ularly effective on roofs having absorbent insulation—such as wood fiber, fiberglass, and perlite—where thermal patterns correlate almost perfectly with moisture.
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 55
16 – Introduction to building thermography
Infrared inspections of roofs with nonabsorbent insulations, common in many single­ply systems, are more difficult to diagnose because patterns are more diffuse.
This section includes a few typical infrared images of moisture problems on low-slope commercial roofs:
CommentInfrared image
10554003;a1
Moisture detection on a roof, recorded during the evening.
Since the building material affected by moisture has ahigher thermal mass,itstemperature decreas­es slower than surrounding areas.
10554103;a1
10554203;a1
Water-damaged roofing components and insula­tion identified from infrared scan from the under­side of the built-up roof on a structural concrete tee deck.
Affected areas are cooler than the surrounding sound areas, due to conductive and/or thermal capacitive effect.
Daytime survey of built-up low-slope commercial roof.
Affected areas are coolerthan the surroundingdry areas, dueto conductiveand/orthermal capacitive effect.
56 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
16 – Introduction to building thermography

16.2.4 Moisture detection (2): Commercial & residential façades

16.2.4.1 General information
Thermography has proven to be invaluable in the assessment of moisture infiltration into commercial and residential façades. Being able to provide a physical illustration of the moisture migration paths is more conclusive than extrapolating moisture meter probe locations and more cost-effective than large intrusive test cuts.
16.2.4.2 Commented building structures
This section includes a few typical examples of moisture problems on commercial and residential façades.
CommentStructural drawing
10554303;a2
Pelting rain penetrates the façade due to badly executed bed joints. Moisture builds up in the masonry above the window.
10554403;a2
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 57
Pelting rain hits the window at an angle. Most of the rain runs off the window edge flashing but some finds its way into the masonry where the plaster meets the underside of the flashing.
16 – Introduction to building thermography
10554503;a2
CommentStructural drawing
Rain hits the façade at an angle and penetrates the plaster through cracks. The water then follows the inside of the plasterand leadsto frost erosion.
10554603;a2
Rain splashes on the façade and penetrates the plaster andmasonryby absorption, whicheventu­ally leads to frost erosion.
58 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
16 – Introduction to building thermography
16.2.4.3 Commented infrared images
This sectionincludes afew typical infrared imagesof moisture problems on commercial & residential façades.
CommentInfrared image
10554703;a1
Improperly terminatedand sealed stone veneer to window frame and missing flashings has resulted in moisture infiltration into the wall cavity and inte­rior living space.
10554803;a1
Moisture migration into drywallfrom capillary drive and interior finish components from inadequate clearance and slope of grade from vinyl siding façade on an apartment complex.

16.2.5 Moisture detection (3): Decks & balconies

16.2.5.1 General information
Although there are differences in design, materials and construction, decks—plaza decks, courtyard decks etc—suffer from the same moisture and leaking problems as low-slope commercial roofs. Improper flashing, inadequately sealed membranes, and insufficient drainage may lead to substantial damage in the building structures below.
Balconies, although smaller in size, require the same care in design, choice of mate­rial, and workmanship as any other building structure. Since balconies are usually supported on one side only, moisture leading to corrosion of struts and concrete re­inforcement can cause problems and lead to hazardous situations.
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 59
16 – Introduction to building thermography
16.2.5.2 Commented building structures
This section includes a few typical examples of moisture problems on decks and balconies.
CommentStructural drawing
10555203;a2
Improper sealing of paving and membrane to roof outlet, leading to leakage during rain.
10555103;a2
No flashing at deck-to-wall connection, leading to rain penetrating the concrete and insulation.
60 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
10555003;a2
16 – Introduction to building thermography
CommentStructural drawing
Water has penetrated the concrete due to inade­quately sized drop apron and has led to concrete disintegration and corrosion of reinforcement.
SECURITY RISK!
10554903;a2
Water has penetrated the plaster and underlying masonry atthe pointwhere the handrailis fastened to the wall.
SECURITY RISK!
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 61
16 – Introduction to building thermography
16.2.5.3 Commented infrared images
This section includes a few typical infrared images of moisture problems on decks and balconies.
CommentInfrared image
10555303;a1
Improper flashing at balcony-to-wall connections and missing perimeter drainage system resulted in moistureintrusion into thewood framingsupport structure of the exterior walkway balcony of a loft complex.
10555403;a1
A missing composite drainage plane or medium on a below-grade parking garage plaza deck structure resulted in standing water between the structural concrete deck and the plaza wearing surface.

16.2.6 Moisture detection (4): Plumbing breaks & leaks

16.2.6.1 General information
Water from plumbing leaks can often lead to severe damage on a building structure. Small leaks may be difficult to detect, but can—over the years—penetrate structural walls and foundations to a degree where the building structure is beyond repair.
Using building thermography at an early stage when plumbing breaks and leaks are suspected can lead to substantial savings on material and labor.
62 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
16 – Introduction to building thermography
16.2.6.2 Commented infrared images
This section includes a few typical infrared images of plumbing breaks & leaks.
CommentInfrared image
10555503;a1
Moisture migration tracking alongsteel joistchan­nels inside ceiling of a single family home where a plumbing line had ruptured.
10555603;a1
Water from plumbing leak was found to have mi­grated farther than originally anticipated by the contractor duringremediation techniques ofcutting back carpet and installing dehumidifiers.
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 63
16 – Introduction to building thermography
10555703;a1
CommentInfrared image
The infrared image of this vinyl-sided 3-floor apartment house clearly shows the path of a seri­ous leak from awashing machine onthe third floor, which is completely hidden within the wall.
10555803;a1
Water leak due to improper sealing between floor drain and tiles.
64 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
16 – Introduction to building thermography

16.2.7 Air infiltration

16.2.7.1 General information
Due to the wind pressure on a building, temperature differences between the inside and the outside of the building, and the fact that mostbuildings useexhaust air terminal devices to extract used air from the building, a negative pressure of 2–5 Pa can be expected. When this negative pressure leads to cold air entering the building structure due to deficiencies in building insulation and/or building sealing, we have what is called air infiltration. Air infiltration can be expected at joints and seams in the building structure.
Due to the fact that air infiltration creates an air flow of cool air into e.g. a room, it can lead to substantial deterioration of the indoor climate. Air flows as small as 0.15 m/s (0.49 ft./s) are usually noticed by inhabitants, although these air flows may be difficult to detect using ordinary measurement devices.
On an infrared image air infiltration can be identified by its typical ray pattern, which emanates from the point of exit in the building structure—e.g. from behind a skirting strip. Furthermore, areas of air infiltration typically have a lower detected temperature than areas where there is only an insulation deficiency. This is due to the chill factor of the air flow.
16.2.7.2 Commented building structures
This section includes a few typical examples of details of building structures where air infiltration may occur.
CommentStructural drawing
10552503;a2
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 65
Insulation deficiencies at the eaves of a brickwall house due to improperly installed fiberglass insu­lation batts.
The air infiltration entersthe roomfrom behind the cornice.
16 – Introduction to building thermography
10552303;a2
CommentStructural drawing
Insulation deficiencies in an intermediate flow due to improperly installed fiberglass insulation batts.
The air infiltration entersthe roomfrom behind the cornice.
10552603;a2
Air infiltration in a concrete floor-over-crawl-space due to cracks in the brick wall façade.
The air infiltration enters the room beneath the skirting strip.
66 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
16 – Introduction to building thermography
16.2.7.3 Commented infrared images
This section includes a few typical infrared images of details of building structures where air infiltration has occurred.
CommentInfrared image
10552703;a1
Air infiltration from behind a skirtingstrip. Note the typical ray pattern.
10552803;a1
10552903;a1
Air infiltration from behind a skirtingstrip. Note the typical ray pattern.
The white area to the left is a radiator.
Air infiltration from behind a skirtingstrip. Note the typical ray pattern.
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 67
16 – Introduction to building thermography

16.2.8 Insulation deficiencies

16.2.8.1 General information
Insulation deficiencies do not necessarily lead to air infiltration. If fiberglass insulation batts are improperly installed air pockets will form in the building structure. Since these air pockets have a different thermal conductivity than areas wherethe insulation batts are properly installed, the air pockets can be detected during a building ther­mography inspection.
As a rule of thumb, areas with insulation deficiencies typically have higher temperatures than where there is only an air infiltration.
When carrying out building thermography inspections aimed at detecting insulation deficiencies, be aware of the following parts in a building structure, which may look like insulation deficiencies on the infrared image:
Wooden joists, studs, rafter, beams
Steel girders and steel beams
Water piping inside walls, ceilings, floors
Electrical installations inside walls, ceilings, floors—such as trunking, piping etc.
Concrete columns inside timber framed walls
Ventilation ducts & air ducts
16.2.8.2 Commented building structures
This section includes a few typical examples of details of building structures with in­sulation deficiencies:
CommentStructural drawing
10553203;a2
Insulation deficiencies (and air infiltration) due to improper installation of insulation batts around an electrical mains supply.
This kind of insulation deficiency will show up as dark areas on an infrared image.
68 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
10553103;a2
16 – Introduction to building thermography
CommentStructural drawing
Insulation deficienciesdue toimproper installation of insulation batts aroundan attic floor beam. Cool air infiltrates the structure and cools down the in­side of the ceiling.
This kind of insulation deficiency will show up as dark areas on an infrared image.
10553003;a2
Insulation deficienciesdue toimproper installation of insulation batts creating an air pocket on the outside of an inclined ceiling.
This kind of insulation deficiency will show up as dark areas on an infrared image.
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 69
16 – Introduction to building thermography
16.2.8.3 Commented infrared images
This section includes a few typical infrared images of insulation deficiencies.
CommentInfrared image
10553303;a1
Insulation deficiencies in an intermediate floor structure. The deficiency may be due to either missing insulation batts or improperly installed in­sulations batts (air pockets).
10553403;a1
Improperly installed fiberglass batts in a suspend­ed ceiling.
70 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
10553503;a1
16 – Introduction to building thermography
CommentInfrared image
Insulation deficiencies in an intermediate floor structure. The deficiency may be due to either missing insulation batts or improperly installed in­sulations batts (air pockets).
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 71
16 – Introduction to building thermography

16.3 Theory of building science

16.3.1 General information

The demand for energy-efficient constructions has increased significantly in recent times. Developments in the field of energy, together with the demand for pleasant indoor environments,have resulted in ever-greater significance having to be attached to both the function of a building’s thermal insulation and airtightnessand theefficiency of its heating and ventilation systems.
Defective insulation and tightness in highly insulated and airtight structures can have a great impact on energy losses. Defects in a building’s thermal insulation and airtight­ness do not merely entail risk of excessive heating and maintenance costs, they also create the conditions for a poor indoor climate.
A building’s degree of insulation is often stated in the form of a thermal resistance or a coefficient of thermal transmittance (U value) for the various parts of the building. However, the stated thermal resistance values rarely provide a measure of the actual energy losses in a building. Air leakage from joints and connectionsthat are not airtight and insufficiently filled with insulation often gives rise to considerable deviations from the designed and expected values.
Verification that individual materials and building elements have the promised prop­erties is provided by means of laboratory tests. Completed buildings have to be checked andinspected in order to ensure that their intended insulation and airtightness functions are actually achieved.
In its structural engineering application, thermography is used to study temperature variations over the surfaces of a structure. Variations in the structure’s thermal resis­tance can, under certain conditions, produce temperature variations on its surfaces. Leakage of cold (or warm) air through the structurealso affects the variation in surface temperature. This means that insulation defects, thermal bridges and air leaks in a building’s enclosing structural components can be located and surveyed.
Thermography itself does not directly show the structure’s thermal resistance or air­tightness. Where quantification of thermal resistance or airtightness is required, addi­tional measurementshave also to be taken. Thermographic analysis of buildings relies on certain prerequisites in terms of temperature and pressure conditions across the structure.
Details, shapesand contrasts in the thermal image can vary quite clearly withchanges in any of these parameters. The in-depth analysis and interpretation of thermal images therefore requires thorough knowledge of such aspects as material and structural properties, the effects of climate and the latest measuring techniques. For assessing
72 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
16 – Introduction to building thermography
the results of measurements, there are special requirements in terms of the skills and experience of those taking the measurements, e.g. by means of authorization by a national or regional standardization body.

16.3.2 The effects of testing and checking

It can be difficult to anticipate how well the thermal insulation and airtightness of a completed building will work. There are certain factors involved in assembling the various components and building elements that can have a considerable impact on the final result. The effects of transport, handling and storage at the site and the way the work is done cannot be calculated in advance. To ensure that the intended function is actually achieved, verification by testing and checking the completed building is required.
Modern insulation technology has reduced the theoretical heat requirement. This does mean, however, that defects that are relatively minor, but at important locations, e.g. leaking joints or incorrectly installed insulation, can have considerable conse­quences in terms both of heat and comfort. Verification tests, e.g. by means of ther­mography, have proved their value, from the point of view both of the designer and the contractor and of the developer, the property manager and the user.
For the designer, the important thing is to find out about the function of various
types of structures, so that they can be designed to take into account both working methods and functional requirements. The designer must also know how different materials and combinations of materials function in practice. Effective testing and checking, as well as experiential feedback, can be used to achieve the required development in this area.
The contractor is keen on more testing and inspection in order to ensure that the
structures keep to an expected function that corresponds to established require­ments in the regulations issued by authorities and in contractual documents. The contractor wants to know at an early stage of construction about any changes that may benecessary sothat systematic defects can be prevented. During construction, a check should therefore be carried out on the first apartments completed in a mass production project. Similar checking then follows as production continues. In this way systematic defects can be prevented and unnecessary costs and future problems can be avoided. This check is of benefit both to manufacturers and to users.
For the developer and the propertymanager itis essentialthat buildings are checked
with reference to heat economy, maintenance (damage from moisture or moisture infiltration) and comfort for the occupants (e.g. cooled surfacesand airmovements in occupied zones).
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 73
16 – Introduction to building thermography
For the user the important thing is that the finished product fulfills the promised
requirements in terms of the building’s thermal insulation and airtightness. For the individual, buying a house involves a considerable financial commitment, and the purchaser therefore wants to know that any defects in the construction will not in­volve serious financial consequences or hygiene problems.
The effects of testing and checking a building’s insulation and airtightness are partly physiological and partly financial.
The physiological experience of an indoor climatic environment is very subjective, varying according to the particular human body’s heat balance and the way the indi­vidual experiencestemperature. Theexperience ofclimate dependson boththe indoor air temperature and that of the surrounding surfaces. The speed of movement and moisture content of indoor air are also of some significance. Physiologically, a draft produces the sensation of local cooling of the body’s surface caused by
excessive air movements in the occupied zone with normal air temperature;
normal air movements in the occupied zone but a room temperature that is too
low;
substantial radiated heat exchange with a cold surface.
It is difficult to assess the quantitative effects of testing and checking a building’s thermal insulation.
Investigations haveshown that defects found in the thermal insulation and airtightness of buildings cause heat losses that are about 20–30% more than was expected. Monitoring energyconsumption before and after remedial measures in relatively large complexes of small houses and in multi-dwelling blocks has also demonstrated this. The figures quoted are probably not representative of buildings in general, since the investigation data cannot be said to be significant for the entire building stock. A cautious assessment however would be that effectively testing and checking a building’s thermal insulation and airtightness can result in a reduction in energy consumption of about 10%.
Research hasalso shown that increased energy consumption associated with defects is often caused by occupants increasing the indoor temperature by one or a few de­grees abovenormal to compensate for the effect of annoying thermal radiation towards cooled surfaces or a sensation of disturbing air movements in a room.

16.3.3 Sources of disruption in thermography

During a thermographic survey, the risk of confusing temperature variations caused by insulation defects with those associated with the natural variation in U values along warm surfaces of a structure is considered slight under normal conditions.
74 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
16 – Introduction to building thermography
The temperature changes associated with variations in the U value are generally gradual and symmetrically distributed across the surface. Variations of this kind do of course occur at the angles formed by roofs and floors and at the corners of walls.
Temperature changes associated with air leaks or insulation defects are in most cases more evident with characteristically shaped sharp contours. The temperature pattern is usually asymmetrical.
During thermography and when interpreting an infrared image, comparison infrared images can provide valuable information for assessment.
The sources of disruption in thermography that occur most commonly in practice are
the effect of the sun on the surface being thermographed (sunlight shining in
through a window);
hot radiators with pipes;
lights directed at, or placed near, the surface being measured;
air flows (e.g. from air intakes) directed at the surface;
the effect of moisture deposits on the surface.
Surfaces on which the sun is shining should not be subjected to thermography. If there is a risk of an effect by sunlight, windows shouldbe covered up (closing Venetian blinds). However, be aware that there are building defects or problems (typically moisture problems) that only show up when heat has been applied to the surface, e.g. from the sun.
For more information about moisture detection, see section 16.2.2 – About moisture detection on page 52.
A hot radiator appears as a bright light surface in an infrared image. The surface temperature of a wall next to a radiator is raised, which may conceal any defects present.
For maximum prevention of disruptive effects from hot radiators, these may be shut off a short while before the measurement is taken. However, depending on the con­struction of the building (low or high mass), these may need to be shut off several hours before a thermographic survey. The room air temperature must not fall so much as to affect the surface temperature distribution on the structure’s surfaces. There is little timelag with electric radiators, so they cool down relatively quickly once they have been switched off (20–30 minutes).
Lights placed against walls should be switched off when the infrared image is taken. During a thermographic survey there should not be any disruptive airflows (e.g.open
windows, open valves, fans directed at the surface being measured) that could affect the surfaces being thermographed.
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 75
16 – Introduction to building thermography
Any wet surfaces, e.g. as a result of surface condensation, have a definite effect on heat transfer at the surface and the surface temperature. Where there is moisture on a surface, there is usually some evaporation which draws off heat, thus lowering the temperature of the surface by several degrees. There is risk of surface condensation at major thermal bridges and insulation defects.
Significant disruptions of the kind described here can normally be detected and eliminated before measuring.
If during thermography it is not possible to shield surfaces being measured from disruptive factors,these mustbe takeninto accountwhen interpretingand evaluating the results. The conditions in which the thermography was carried out should be recorded in detail when each measurement is taken.

16.3.4 Surface temperature and air leaks

Defects in building airtightness due to small gaps in the structure can be detected by measuring the surface temperature. If there is a negative pressure in the building under investigation, air flows into the space through leaks in the building. Cold air flowing in through small gaps in a wall usually lowers the temperature in adjacent areas of the wall. The result is that a cooled surface area with a characteristic shape develops on the inside surface of the wall. Thermography can be used to detect cooled surface areas. Air movements at the wall surface can be measured using an air velocity indicator. If there is a positive pressure inside the building being investi­gated, warm room air will leak out through gaps in the wall, resulting in locally warm surface areas around the locations of the leaks.
The amountof leakagedepends partly on gaps and partly on the differential pressure across the structure.
16.3.4.1 Pressure conditions in a building
The most important causes of differential pressure across a structural element in a building are
wind conditions around the building;
the effects of the ventilation system;
temperature differences between air inside and outside (thermal differential pres-
sure).
The actualpressure conditions inside a building are usually caused by a combination of these factors.
The resultantpressure gradientacross the various structural elements can be illustrated by the figure on page 78. The irregular effects of wind on a building means that in practice the pressure conditions may be relatively variable and complicated.
76 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
In a steady wind flow, Bernoulli’s Law applies:
where:
16 – Introduction to building thermography
ρ
Air density in kg/m
Wind velocity in m/sv
Static pressure in Pap
3
and where:
denotes the dynamic pressure and p the static pressure. The total of these pressures gives the total pressure.
Wind load against a surface makes the dynamic pressure become a static pressure against the surface. The magnitude of this static pressure is determined by, amongst other things, the shape of the surface and its angle to the wind direction.
The portion of the dynamic pressure that becomes a static pressure on the surface (p
) is determined by what is known as a stress concentration factor:
stat
If ρ is 1.23 kg/m3(density of air at +15°C (+59°F)), this gives the following local pressures in the wind flow:
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 77
16 – Introduction to building thermography
10551803;a1
Figure 16.3 Distribution of resultant pressureson a building’senclosing surfaces dependingonwind effects, ventilation and internal/external temperature difference. 1: Wind direction;Tu: Thermodynamic air temper­ature outdoors in K; Ti: Thermodynamic air temperature indoors in K.
If the whole of the dynamic pressure becomes static pressure, then C = 1. Examples of stress concentration factor distributions for a building with various wind directions are shown in the figure on page 79.
The wind therefore causes an internal negative pressure on the windward side and an internal positive pressure on the leeward side. The air pressure indoors depends on the wind conditions, leaks in the building and how these are distributed in relation to the wind direction. If the leaks in the building are evenly distributed, the internal pressure may vary by ±0.2 p
. If most of the leaks are on the windward side, the
stat
internal pressure increases somewhat. In the opposite case, with most of the leaks on the leeward side, the internal pressure falls.
78 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
10551903;a1
16 – Introduction to building thermography
Figure 16.4 Stress concentration factor (C) distributions for various wind directions and wind velocities (v) relative to a building.
Wind conditions can vary substantially over time and between relatively closely situ­ated locations. In thermography, such variations can have a clear effect on the mea­surement results.
It has been demonstrated experimentally that the differential pressure on a façade exposed to an average wind force of about 5 m/s (16.3 ft/s) will be about 10 Pa.
Mechanical ventilation results in a constant internal negative or positive pressure (depending onthe direction of the ventilation). Research has showed that the negative pressure caused by mechanical extraction (kitchen fans) in small houses is usually between 5 and 10 Pa. Where there is mechanical extraction of ventilation air, e.g. in multi-dwelling blocks, the negative pressure is somewhat greater, 10–50 Pa. Where there is so-called balanced ventilation (mechanically controlled supply and extract air), this is normally adjusted to produce a slight negative pressure inside (3–5 Pa).
The differential pressure caused by temperature differences, the so-called chimney effect (airtightness differences of air at different temperatures) means that there is a negative pressure in the building’s lower part and a positive pressure in the upper
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 79
16 – Introduction to building thermography
part. At a certain height there is a neutral zone where the pressures on the inside and outside are the same, see the figure on page 81. This differential pressure may be described by the relationship:
Air pressure differential within the structure in PaΔp
2
g
ρ
u
u
i
9.81 m/s
Air density in kg/m
Thermodynamic air temperature outdoors in KT
Thermodynamic air temperature indoors in KT
Distance from the neutral zone in metersh
3
If ρu= 1.29 kg/m3(density of air at a temperature of 273 K and ≈100 kPa), this pro­duces:
With a difference of +25°C (+77°F) between the ambient internal and external tem­peratures, the result is a differential pressure difference within the structure of about 1 Pa/m difference in height (= 3.28 Pa/ft.).
80 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
10552003;a1
16 – Introduction to building thermography
Figure 16.5 Distribution of pressures on a building withtwo openingsand wherethe external temperature is lower than the internal temperature. 1: Neutral zone; 2: Positive pressure; 3: Negative pressure; h: Distance from the neutral zone in meters.
The position of the neutral zone may vary, depending on any leaks in the building. If the leaks are evenly distributed vertically, this zone will be about halfway up the building. If more of the leaks are in the lower part of the building, the neutral zone will move downwards. If more of the leaks are in the upper part, it will move upwards. Where a chimney opens above the roof, this has a considerable effect on the position of the neutral zone, and the result may be a negativepressure throughoutthe building. This situation most commonly occurs in small buildings.
In a larger building, such as a tall industrial building, with leaks at doors and any windows in the lower part of the building, the neutral zone is about one-third of the way up the building.
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 81
16 – Introduction to building thermography

16.3.5 Measuring conditions & measuring season

The foregoing may be summarized as follows as to the requirements with regard to measuring conditions when carrying out thermographic imaging of buildings.
Thermographic imaging is done in such a way that the disruptive influence from ex­ternal climatic factors is as slight as possible. The imaging process is therefore carried out indoors, i.e. where a building is heated, the structure’s warm surfaces are exam­ined.
Outdoor thermography is only used to obtain reference measurements of larger façade surfaces. In certain cases, e.g. where the thermal insulation is very bad or where there is an internal positive pressure, outdoor measurements may be useful. Even when investigating the effects of installations located within the building’sclimatic envelope, there may be justification for thermographic imaging from outside the building.
The following conditions are recommended:
The air temperature difference within the relevant part of the building must be at
least +10°C (+18°F) for a number of hours before thermographic imaging and for as long as the procedure takes. For the same period, the ambient temperature difference must not vary by more than ±30% of the difference when the thermo­graphic imaging starts. During the thermographic imaging, the indoor ambient temperature should not change by more than ±2°C (±3.6°F).
For a number of hours prior before thermographic imaging and as long as it con-
tinues, no influencing sunlight may fall upon the relevant part of the building.
Negative pressure within the structure ≈ 10–50 Pa.
When conducting thermographic imaging in order to locate only air leaks in the
building’s enclosing sections, the requirements in terms of measuring conditions may be lower. A difference of 5°C (9°F) between the inside and outside ambient temperatures ought to be sufficient for detecting such defects. To be able to detect air leaks, certain requirements must however be made with regard to the differential pressure; about 10 Pa should be sufficient.

16.3.6 Interpretation of infrared images

The main purpose of thermography is to locate faults and defects in thermal insulation in exterior walls and floor structures and to determine their nature and extent. The measuring taskcan also be formulated in such a way that the aim of thethermography is to confirm whether or not the wall examined has the promised insulation and air­tightness characteristics. The ‘promised thermal insulation characteristics’ for the wall according to the design can be converted into an expected surface temperature dis­tribution for the surface under investigation if the measuring conditions at the time when the measurements are taken are known.
82 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
16 – Introduction to building thermography
In practice the method involves the following: Laboratory or field tests are used to produce an expected temperature distribution in
the form of typical or comparative infrared images for common wall structures, com­prising both defect-free structures and structures with in-built defects.
Examples of typical infrared images are shown in section 16.2 – Typical field investi­gations on page 50.
If infrared images of structural sections taken during field measurements are intended for use as comparison infrared images, then the structure’s composition, the way it was built, and the measurement conditions at the time the infrared image was taken must be known in detail and documented.
In order, during thermography, to be able to comment on the causes of deviations from the expected results, the physical, metrological and structural engineering pre­requisites must be known.
The interpretation of infrared images taken during field measurements may be de­scribed in brief as follows:
A comparison infrared image for a defect-free structure is selected on the basis of the wall structure under investigation and the conditions under which the field mea­surement was taken. An infrared image of the building element under investigation is then compared with the selected infrared image. Any deviation that cannot be ex­plained by the design of the structure or the measurement conditions is noted as a suspected insulationdefect. Thenature and extent of the defect is normally determined using comparison infrared images showing various defects.
If no suitable comparison infrared image is available, evaluation and assessment are done on the basis of experience. This requires more precise reasoning during the analysis.
When assessing an infrared image, the following should be looked at:
Uniformity of brightness in infrared images of surface areas where there are no
thermal bridges
Regularity and occurrence of cooled surface areas, e.g. at studding and corners
Contours and characteristic shapes in the cooled surface area
Measured temperature differences between the structure’s normal surface temper-
ature and the selected cooled surface area
Continuity and uniformity of the isotherm curve on the surface of the structure. In
the camera software the isotherm function is called Isotherm or Color alarm, de­pending on camera model.
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 83
16 – Introduction to building thermography
Deviations and irregularities in the appearance of the infrared image often indicate insulation defects. There may obviouslybe considerable variations in theappearance of infrared images of structures with insulation defects. Certain types of insulation defects have a characteristic shape on the infrared image.
Section 16.2 – Typical field investigations on page 50 shows examples of interpreta­tions of infrared images.
When taking infrared images of the same building, the infrared images from different areas should be taken with the same settings on the infrared camera, as this makes comparison of the various surface areas easier.

16.3.7 Humidity & dew point

16.3.7.1 Relative & absolute humidity
Humidity can be expressed in two different ways—either as relative humidity or as absolute humidity. Relative humidity is expressed in percent of how much water a
certain volume of air can hold at a certain temperature, while absolute humidity is expressed in percent water by weight of material. The latter way to express humidity is common when measuring humidity in wood and other building materials.
The higher the temperature of air, the larger the amount of water this certain volume of air can hold. The following table specifies the maximum amounts of water in air at different temperatures.
Figure 16.6 A: Temperature in degrees Celsius; B: Maximum amount of water expressed in g/m3(at sea level)
BABABABA
4.860.09.4210.017.3320.030.4430.0
4.49-1.08.849.016.3419.028.8329.0
4.15-2.08.298.015.4018.027.2928.0
3.83-3.07.777.014.5117.025.8327.0
3.53-4.07.286.013.6616.024.4326.0
3.26-5.06.815.012.8615.023.1025.0
3.00-6.06.384.012.0914.021.8324.0
2.76-7.05.963.011.3713.020.6223.0
2.54-8.05.572.010.6912.019.4722.0
2.34-9.05.211.010.0411.018.3821.0
84 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
16 – Introduction to building thermography
Figure 16.7 A: Temperature in degrees Fahrenheit; B: Maximum amount of water in gr/ft3(at sea level)
BABABABA
2.1232.04.1250.07.5868.013.3086.0
1.9630.23.8648.27.1466.212.6084.2
1.8128.43.6246.46.7364.411.9382.4
1.6726.63.4044.66.3462.611.2980.6
1.5424.83.1842.85.9760.810.6878.8
1.4223.0.2.9841.05.6259.010.1077.0
1.3121.22.7939.25.2957.29.5475.2
1.2119.42.6137.44.9755.49.0173.4
1.1117.62.4435.64.6753.68.5171.6
1.0215.82.2833.84.3951.88.0369.8
Example:
The relative humidity of a certain volume of air at a temperature of +30°C (+86°F) is 40 % RH. Amount of water in 1 m3(35.31 ft3) of air at +30°C = 30.44 × Rel Humidity = 30.44 × 0.40 = 12.18 g (187.96 gr).
16.3.7.2 Definition of dew point
Dew point is the temperature at which the humidity in a certain volume of air will condense as liquid water.
Example:
The relative humidity of a certain volume of air at a temperature of +30°C (+86°F) is 40 % RH. Amount of water in 1 m3(35.31 ft3) of air at +30°C = 30.44 × Rel Humidity = 30.44 × 0.40 = 12.18 g (187.96 gr). In the table above, look up the temperature for which the amount of water in air is closest to 12.18 g. This would be +14.0°C (+57.2°F), which is the approximate dew point.

16.3.8 Excerpt from Technical Note ‘Assessing thermal bridging and insulation continuity’ (UK example)

16.3.8.1 Credits
This Technical Note was produced by a working group including expert thermogra­phers, and research consultants. Additional consultation with other persons and or­ganisations results in this document being widely accepted by all sides of industries.
The contents of this Technical Note is reproduced with kind permission from, and fully copyrighted to, United Kingdom Thermography Association (UKTA).
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 85
16 – Introduction to building thermography
UK Thermography Association c/o British Institute of Nondestructive Testing 1 Spencer Parade Northampton NN1 5AA United Kingdom
Tel: +44 (0)1604 630124 Fax: +44 (0)1604 231489
16.3.8.2 Introduction
Over the last few years the equipment, applications, software, and understanding connected with thermography have all developed at an astonishing rate. As the technology hasgradually becomeintegrated intomainstream practises,a correspond­ing demand for application guides, standards and thermography training has arisen.
The UKTA ispublishing this technical note in order to establish a consistent approach to quantifying the results for a ‘Continuity of Thermal Insulation’ examination. It is in­tended that specifiers should refer to this document as a guide to satisfying the re­quirement in the Building Regulations, therefore enabling the qualified thermographer to issue a pass or fail report.
16.3.8.3 Background information
Thermography can detect surface temperature variations as small as 0.1 K and graphic images can be produced that visibly illustrate the distribution of temperature on building surfaces.
Variations in the thermal properties of building structures, such as poorly fitted or missing sections of insulation, cause variations in surface temperature on both sides of the structure. They are therefore visible to the thermographer. However, many other factors such as local heat sources, reflections and air leakage can also cause surface temperature variations.
The professional judgement of the thermographer is usually required to differentiate between real faults and other sources of temperature variation. Increasingly, thermo­graphers are asked to justify their assessment of building structures and, in the ab­sence of adequate guidance, it can be difficult to set definite levels for acceptable or unacceptable variation in temperature.
The current Standard for thermal iamging of building fabric in the UK is BS EN 13187:1999 (BS EN 13187:1999, Thermal Performance of Buildings—Qualitative de­tection of thermal properties in building envelopes—Infrared method (ISO 6781:1983 modified). However, this leaves interpretation ofthe thermal image to the professional expertise of of the thermographer and provides little guidance on the demarcation between acceptable and unacceptable variations. Guidance on the appearance of a
86 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
16 – Introduction to building thermography
range ofthermal anomaliescan be found in BINDT Guides to thermal imaging (Infrared Thermography Handbook; Volume 1, Principles and Practise, Norman Walker, ISBN 0903132338, Volume 2, Applications, A. N. Nowicki, ISBN 090313232X, BINDT, 2005).
16.3.8.3.1 Requirements
A thermographic survey to demonstrate continuity of insulation, areas of thermal bridging and compliance with Building Regulations should include the following:
Thermal anomalies.
Differentiate between real thermal anomalies, where temperature differences are
caused by deficiencies in thermal insulation, and those that occur through con­founding factors such as localised differences in air movement, reflection and emissivity.
Quantify affected areas in relation to the total insulated areas.
State whether the anomalies and the building thermal insulation as a whole are
acceptable.
16.3.8.4 Quantitative appraisal of thermal anomalies
A thermographicsurvey willshow differencesin apparent temperature of areas within the field of view. To be useful, however, it must systematically detect all the apparent defects; assess them against a predetermined set of criteria; reliably discount those anomalies that are not real defects; evaluate those that are real defects, and report the results to the client.
16.3.8.4.1 Selection of critical temperature parameter
The BRE information Paper IP17/01 (Information Paper IP17/01, Assessing the Effects of Thermal Bridging at Junctions and Around Openings. Tim Ward, BRE, 2001) pro­vides useful guidance on minimum acceptable internal surface temperatures and appropriate values of Critical Surface Temperature Factor, f
. The use of a surface
CRsi
temperature factor allows surveys under any thermal conditions to show areas that are at risk of condensation or mould growth under design conditions.
The actual surface temperature will depend greatly on the temperatures inside and outside at the time of the survey, but a ‘Surface Temperature Factor’ (f
) has been
Rsi
devised that is independent of the absolute conditions. It is a ratio of temperature drop across the building fabric to the total temperature drop between inside and outside air.
For internal surveys: f
= (Tsi– Te)/(Ti– Te)
Rsi
Tsi= internal surface temperature Ti= internal air temperature Te= external air temperature
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 87
16 – Introduction to building thermography
A value for f
of 0.75 is considered appropriate across new building as the upper
CRsi
end usage is not a factor considered in testingfor ‘Continuity of Insulation’, or ‘Thermal Bridging’. However, when considering refurbished or extended buildings, for example swimming pools, internal surveys may need to account for unusal circumstances.
16.3.8.4.2 Alternative method using only surface temperatures
There arestrong argumentsfor basingthermographic surveys on surface temperatures alone, with no need to measure air temperature.
Stratification inside the building makes reference to air internal temperatures very
difficult. Is it mean air temperature, low level, high level or temperature at the level of the anomaly and how far from the wall should it be measured?
Radiation effects, such as radiation to the night sky, make use of of external air
temperature difficult. It is not unusual for the outside surface of building fabric to be below air temperature because of radiation to the sky which may be as low as –50 (–58). This can be seen with the naked eye by the fact that dew and frost often appear on building surfaces even when the air temperature does not drop below the dewpoint.
It should be noted that the concept of U values is based on ‘environmental temper-
atures’ on each side of the structure. This is neglected by many inexperienced analysts.
The two temperatures that are firmly related to the transfer of heat through building
fabric (and any solid) are the surface temperatures on each side.
Therefore, by referring to surface temperatures the survey is more repeatable.
The surface temperatures used are the averages of surface temperatures on the
same material in an area near the anomaly on the inside and the outside of the fabric. Together with the temperature of the anomaly, a threshold level can be set dependent on these temperatures using the critical surface temperature factor.
These arguments do not obviate the need for the thermographer to beware of re-
flections of objects at unusual temperatures in the background facing the building fabric surfaces.
The thermographer should also use a comparison between external faces facing
different directions to determine whether there is residual heat from solar gain af­fecting the external surfaces.
External surveys should not be conducted on a surface where T
– Tsoon the face
si
is more than 10% greater than Tsi– Tsoon the north or nearest to north face.
For a defect that causes a failure under the 0.75 condition of IP17/01 the critical
surface factors are 0.78 on the inside surface and 0.93 on the outside surface.
The table below shows the internal and external surface temperatures at an anomaly which would lead to failure under IP17/01. It also shows the deterioration in thermal insulation that is necessary to cause this.
88 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
16 – Introduction to building thermography
Failing areaGood areaExample for lightweight built-up cladding with defective
insulation
00Outside temperature in
15.019.1Inside surface temperature in
1.50.3Outside surface temperature in
0.750.95Surface factor from IP17/01
0.92Critical external surface temperature factor, after IP17/01
5.180Insulation thickness to give this level of performance, mm
1.920.35Local U value W/m2K
0.78UKTA TN1 surface factor
0.93UKTA TN1 surface factor outside
Notes to the table
1 Values of surface resistances taken from ADL2 2001, are:
Inside surface 0.13 m
Outside surface 0.04 m
2
K/W
2
K/W
These originatefrom BS EN ISO 6946 (BN EN ISO 6946:1997 Building components and building elements - Thermal resistance and thermal transmittance - Calculation method).
2 Thermal insulation used here is assumed to have a conductivity of 0.03 W/m K. 3 The difference in temperature between an anomaly and the good areas is 1.2 de-
grees on the outside and 4.1 degrees on the inside.
4 The UKTA TN1 surface temperature factor for internal surveys is:
Fsi= (T
– Tso)/(Tsi– Tso)
sia
where: T
= internal surface temperature at anomaly
sia
Tso= external surface temperature (good area) Tsi= internal surface temperature (good area)
5 The UKTA TN1 surface temperature factor for external surveys is:
Fso= (T where T
– Tsi)/(Tso– Tsi)
soa
= external surface temperature at anomaly
soa
16.3.8.4.3 Selecting maximum acceptable defect area
The allowable area of defect is a quality control issue. It can be argued that there should be no area on which condensation, mould growth or defective insulation will occur andany suchanomalies shouldbe includedin the report. However, a commonly
Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009 89
16 – Introduction to building thermography
used value of 0.1% of the building exposed surface area is generally accepted as the maximum combined defect area allowable to comply with the Building Regulations. This represents one square metre in every thousand.
16.3.8.4.4 Measuring surface temperature
Measurement of surface temperature is the function of the infrared imaging system. The trained thermographer will recognise, account for and report on the variation of emissivity and reflectivity of the surfaces under consideration.
16.3.8.4.5 Measuring area of the defects
Measurement of defect area can be performed by pixel counting in the thermal anal­ysis software or most spreadhseet packages provided that:
the distance from camera to object is accurately measured probably using a laser
measurement system,
the target distance should take into account the IFOV of the imaging system,
any angular change between the camera and the object surface from the perpen-
dicular is accounted for.
Buildings consist of numerous construction features that are not conducive to quan­titative surveys including windows, roof lights, luminaries, heat emitters, cooling equipment, service pipes and electrical conductors. However, the joints and connec­tions between these objects and the building envelope should be considered as part of the survey.
16.3.8.5 Conditions and equipment
To achieve best results from a thermal insulation survey it is important to consider the environmentalconditions andto usethe mostappropriate thermographictechnique for the task.
Thermal anomalies will only present themselves to the thermographer where temper­ature differences exist and environmental phenomena are accounted for. As a mini­mum, the following conditions should be complied with:
Temperature differences across the building fabric to be greater than 10℃ (18℉).
Internal air to ambient air temperature difference to be greater than 5℃ (9℉) for
the last twentyfour hours before survey.
External air temperature to be within ±3℃ (±5.4℉) for duration of survey and for
the previous hour.
External air temperature to be within ±10℃ (±18℉) for the preceding twentyfour
hours.
In addition, external surveys should also comply with the following:
90 Publ. No. T559382 Rev. a358 – ENGLISH (EN) – June 23, 2009
Loading...