Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all
safety information. Failure to comply with instructions could result in personal injury and/or property damage! Retain instructions for future reference.
1. LOCATION
Indoor Use Only
FW1101
0711
Supersedes
1008
Centrifugal
Constant Pressure
Installation Guide
Insure that a proper utility ground
rod is present and connected.
Mount the Artesian Drive
unit as close as possible
to the service entrance
panel.
Service Entrance
Panel
4”
Min.
Use a dedicated branch circuit for the Artesian
Drive. Wire directly from the service entrance
panel.
Min.
Mount unit to a sturdy
supporting structure (wall or
post)
Min.
4”
Min.
Allow a 4”
clearance around
the Artesian
Drive box for
cooling
DO NOT drill
holes in the
Artesian Drive
box
Use the holes and
guides provided
IL0737
Service
Entrance Panel
DO NOT wire to a sub panel
located in a home.
It is preferable to wire directly to
the service entrance panel.
IN HOME
Sub Panel
GND
GND
Motor
GND
IL0738
2. WIRE ROUTING
Service Entrance
Panel
GND
When possible, DO NOT run
Artesian Drive input power or
motor wires in parallel with
house wiring.
Avoid runing out-building wires
in parallel with motor wires.
Inlet
Motor Pump
GND
Outlet
IL0739
Keep input power and motor
wiring separated by at least 8”.
Input power Motor
GND
Satellite /
Antenna
Wire
Motor
MOTOR
If it is necessary to run wiring in paralell, keep
Artesian Drive input power and motor wires at least
8” from other house wiring.
8” Min.
Telephone
GND
Branch 3
Branch 2
8” Min.
DO NOT run input power and
motor wires together.
Keep separated by at least 8”
GND
GND
Service
Entrance Panel
Branch 1
8” Min.
GND
8” Min.
GND
IL0740
OK
8” Min.
Service Entrance
Panel
90º
Cross over other branch
circuits and house wiring
at 90º
GND
8” Min.
GND GND
IL0741
3. GROUNDING
Insure that a
proper utility
ground rod is
present and
connected.
Service Entrance
Panel
GND.
An input power ground wire from the supply panel
must be connected to the Artesian Drive.
Outlet
Inlet
A dedicated ouput ground
wire from the Artesian
Drive must be connected
to the motor (motor wires
and ground wires must be
bundled together).
Inlet
Motor
GND.
IL0742
Outlet
Pump
Service Entrance
Panel
Use the service
entrance panel
ground ONLY
GND.
ground wire separate.
Motor ground wire MUST be
bundled with motor wires.
GND.
DO NOT run
Inlet
Motor Pump
Outlet
IL0743
Service Entrance
Panel
GND.
GND.
GND.
GND.
Inlet
Motor
Outlet
Pump
Power to
Motor
Power Supply from Circuit
Breaker
Motor
IL0783
GND.
Avoid multiple ground paths
IL0744
022688
L1
L2
L3
U
V
W
PEPE
IL0731
4. WIRING
MOTOR LEADS
GND
GND
Feed motor leads
through the strain
relief (right side)
Connect
them to the
terminal block
U, V, W &
Output to
Motor
Connect them to the terminal
block marked L1, L3 & PE*.
*PE = Earth Potential (Ground)
Feed the 230V power leads through
the strain relief (left side).
Power Terminal
Connections
POWER AND PRESSURE
SENSOR LEADS
B2
B5
B4
L1 L2 L3 U V W
PE
PE
GND
Feed the pressure sensor wire through the strain
relief (center).
Pressure
Sensor Leads
Connect them to the terminal block “B2”
and “B5”.
IL0732
5. PLUMBING
TABLE 2: MINIMUM PRESSURE TANK
Rated Pump Flow Pressure Tank Size (Total
Volume)
Pump Capacity less than 12
GPM
Pump Capacity greater than
12 but less than 25 GPM
Pump Capacity greater than
25 GPM
The pressure tank pre-charge setting should be 70% of the
system pressure sensor setting.
Inlet
Motor
Pump
Outlet
4 Gallon (AT15)
8 Gallon (AT25)
14 Gallon (AT44)
Pressure
Gauge
Pressure Tank
Pressure
Relief
Required
Tank Precharge 70% of
system pressure
(i.e. 30 PSI for 50 PSI system)
6 ft.
max.
Pressure switch locate
on the house side of
the tank
IL0745
Position sensor with
threaded connection down.
Remove rubber end cap to
adjust pressure with 7/32”
Allen Wrench
Pressure Sensor
Turn clockwise to increase pressure setting.
Turn counterclockwise to decrease pressure
setting.
1/4 turn = 3 PSI
Factory preset to 50 PSI
Pressure Sensor
Boot
IL0730
Outlet
Inlet
Pump
Pressure
Gauge
Motor
Tank Precharge 70% of
system pressure
(i.e. 30 PSI for 50 PSI system)
Pressure Tank
6 ft.
max.
Pressure Relief Valve
Required
Tech Support
Pressure switch locate
on the house side of
the tank
IL1205
®
Toll Free Help Line
1-800-742-5044