1.3 Heat recovery system (HR-R) .................................................................................................................4
1.4 Heating element (EB1) (for UNI 3 E) ........................................................................................................4
1.5 Temperature sensors (B1, B4) .................................................................................................................. 4
2 Operation of Handheld Terminal .....................................................................................5
2.1 Horizontally Wall-Mounted Unit ..............................................................................................................5
2.3 Horizontal Unit ............................................................................................................................................6
2.4 For Necessary Removal of Door ..............................................................................................................6
3 Cleaning and Maintenance ..............................................................................................7
3.5 Tightening of rotor belt ............................................................................................................................ 11
4 CI60 control unit overview ............................................................................................ 12
5 CI60 in use ...................................................................................................................... 13
5.1 General .........................................................................................................................................................13
5.2 Increasing/reducing air supply ...............................................................................................................13
5.3 Adjusting the air supply ............................................................................................................................13
5.4 Temperature adjustment .........................................................................................................................13
7 CI600 in use ................................................................................................................... 15
7.1 General ........................................................................................................................................................ 15
7.3 Menu navigation ....................................................................................................................................... 15
7.4 Start menu ................................................................................................................................................. 15
7.5 Operating status ....................................................................................................................................... 15
8 CI600 main menu ...........................................................................................................16
8.1 Fan speeds.................................................................................................................................................. 16
8.4 Temperature .............................................................................................................................................. 16
8.7 Time and date ............................................................................................................................................ 18
8.8 Language .................................................................................................................................................... 18
8.11 Operating information ............................................................................................................................. 18
9 CI600 advanced user menu ..........................................................................................19
9.2 Advanced user ........................................................................................................................................... 19
9.3 Temperature regulation .......................................................................................................................... 19
9.4 Fan control ................................................................................................................................................ 20
9.6 Operating time ......................................................................................................................................... 22
9.7 Service ....................................................................................................................................................... 22
9.8 Menu tree ...................................................................................................................................................23
12 CE Declaration of Conformity ........................................................................................25
Our products are subject to continuous development and we therefore reserve the right to make changes.
We also disclaim liability for any printing errors that may occur.
2
Page 3
!
UNI 3 User Manual
!
Important Safety Instructions:
It is the installer’s responsibility to carry out a full safety and function assessment of the appliance.
To reduce the risk of fire, electric shock or injury, read all the safety instructions and warning texts before using the unit.
• This unit is only designed for ventilation air in housings or commercial buildings
• It must not be used to extract combustible or flammable gases
• Disconnect the mains plug before commencing any service and maintenance work
• Before opening the door: switch off the heat, let the fans continue for three minutes to remove hot air, disconnect power from
the unit and wait 2 minutes before opening the doors.
• If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or a similarly qualified person, in
order to avoid hazard.
• The unit contains heating elements that must not be touched when they are hot
• The unit must not be operated without the filters in place
• Do not cook any combustible substances under the kitchen hood, if this is installed
• Do not leave a saucepan or frying pan containing oil or grease unsupervised when using a kitchen hood
• For the warranty to apply, the user manual instructions must be followed.
To maintain a good indoor climate, comply with regulations. To avoid condensation damage, the unit must never be
stopped apart from during service/maintenance or in connection with an accident.
Symbols Used
These products bear a number of symbols used for
labelling the actual product and in installation and user
documentation.
Supply air
Exhaust air
Extract airKitchen air
DANGER! ELECTRICITY
DANGER! DO NOT
TOUCH
CAUTION! When a text bears this symbol, it
means that personal injury or serious damage to
the equipment may result if the instructions are
not followed.
Outdoor air
NB! When a text bears this symbol, damage to
equipment or poor efficiency may be the consequence of not following the instructions.
EXAMPLE OF NIPPLE LOCATION
(shown as a right-hand model)
This appliance can be used by children aged from 8 years and above and
persons with reduced physical, sensory or mental capabilities or lack of
experience and knowledge if they have been given supervision or instruction
concerning use of the appliance in a safe way and understand the hazards
involved. Note that the product is not intended for use by children.
Children shall not play with the appliance. Cleaning and user maintenance
shall not be made by children without supervision.
Our products are subject to continuous development and we therefore
reserve the right to make changes.
We also disclaim liability for any printing errors that may occur.
3
Page 4
UNI 3 User Manual
1 Functional Description Balanced
Ventilation
1.1 Fans (M1, M2)
The fans ensure that air enters and leaves the building. These
can be individually adjusted for optimal operation. The unit
can be regulated at 3 different speeds using the operating
panel; Min, Normal and Max. See section 5.1 for more
information.
1.2 Filter (FI1, FI2)
Filters with a high filter grade (ePM1 55% F7) are used as
standard both for supply air and extract air, so that the air
which enters the building is clean. The filters also ensure that
the unit stays clean.
1.3 Heat recovery system (HR-R)
The air goes through the rotary wheel heat recovery system.
The rotor functions as a heat storage. The heat from the
extract air heats up one half of the rotor. When the heated
part comes over to the supply air side, the heat is transferred
to the supply air.
Fig. 1
M2
B4
FI1
K
EB1
HR-R
M4
M1
B1
F20
F10
FI2
1.4 Heating element (EB1) (for UNI 3 E)
If the heat recovery system cannot raise the temperature
enough, an electrical heating element will raise the
temperature to a set level. The heating element is protected
against overheating by the thermostat (F20), which switches
off at 60°C. As an additional safety measure, the F10
thermostat switches off at 85°C. The F10 thermostat must be
reset manually by pressing the reset button (see Fig. 2).
1.5 Temperature sensors (B1, B4)
The unit has two temperature sensors as standard. Supply air
sensor B1 registers the temperature of the heating battery.
The outdoor air sensor (B4) registers the temperature of the
outdoor air.
Fig. 2
reset button
4
Page 5
UNI 3 User Manual
2 Operation of Handheld Terminal
2.1 Horizontally Wall-Mounted Unit
1. 1he unit is opened by first unscrewing the screw in the top
(see Fig. 3).
2. Pull the handles out, and rotate to the side (see Fig. 4).
3. The door can now be opened to hang open at 180º (see
Fig. 5), or be hooked off (see point 2.4).
Fig. 3
Fig. 4
2.2 Sideways Wall-Mounted Unit
NB! A sideways mounted unit must have a strap
and end studs installed, so that the door does
not become damaged or fall off when opened.
1. Ensure that the end studs and strap are installed (Fig. 6
and Fig. 7).
2. Unscrew the top screw (see Fig. 3).
3. Pull the handles out, and rotate to the side (see Fig. 4).
4. The door can now be opened, but will have a maximum
swing of 105º (se Fig. 7).
Fig. 6
Fig. 5
Fig. 7
MAX 180°
MAX 105°
5
Page 6
UNI 3 User Manual
!
40-105°
MAX 105°
2.3 Horizontal Unit
1. Ensure that the end studs and strap are installed (see Fig.
6 and 7).
2. Unscrew the top screw (see Fig. 3).
3. Pull the handles out, and rotate to the side (see Fig. 4).
4. The door can now be opened, but will have a maximum
swing of 105º (se Fig. 8).
Fig. 8Fig. 9
MAX 105°
2.4 For Necessary Removal of Door
The door can be removed when it is open between 40º and
105º (see Fig. 9). If there is limited space in front of the unit,
the lock screw under the door can be temporarily unscrewed
(see Fig. 10), as well as the end studs if these are installed
(see Fig. 6). Then the door can be pushed out sideways (see
Fig. 11).
CAUTION! The door weighs 10kg, take care
when removing it.
40-105°
Fig. 10
Fig. 11
6
Page 7
UNI 3 User Manual
!
3 Cleaning and Maintenance
CAUTION! Before opening the door: switch off
the heat, let the fans continue for three minutes
to remove hot air, disconnect power from the
unit and wait 2 minutes before opening the doors.
3.1 Fans
The fans must be cleaned a minimum of once a year. Clean
the fan blades with detergent (for example methylated spirit)
on a cloth and compressed air if possible. NB! Do not use
water.
To take out the fans:
1. Loosen the screw on the fan door (see Fig. 12).
2. Pull out the electric quick-release contact for the motor
(see Fig. 13).
3. The fan can then be carefully pulled out of the unit (see
Fig. 14).
4. Loosen the screws and remove the fan cover to access
the fan blades.
Fig. 12Fig. 14Fig. 13
1
2
7
Page 8
!
UNI 3 User Manual
CAUTION! For safety reasons, always mount
the door screw when you’re finished
maintaining the ventilation unit!
8
Page 9
UNI 3 User Manual
3.2 Filter
The filters have a limited lifetime, and to preserve a
healthy indoor air quality it is important to change them
when they are dirty.
How often the filters need to be changed depends on the
degree of contamination in the air where they are installed.
In general, the filters need to be changed a minimum of once
a year, preferably in the autumn (after the pollen season). In
areas with a lot of dust and contamination, the filters should
be changed in the spring and autumn.
Dirty filters can, among other things, lead to:
• Reduced performance of the unit
• The unit becoming dirty
• Humidity damage in the bathroom
• Reduced indoor air quality
A filter subscription is recommended to ensure full benefit
from the system. The article number for a replacement filter
set is 110716.
To take out the filters:
1. Grip the handle and pull the filter cassette out (see Fig.15).
2. Push the filter out of the cassette (see Fig.16).
3. Insert a new filter.
Fig. 16
NB! Ensure that the filter is not damaged during
installation. Use the filter’s outer edge when you
push it in. A damaged filter reduces the unit’s
effect and the air’s purity.
When changing the filter, check that the whole unit is working
normally. Use the following checklist:
• Check that the rotor is rotating (see Fig. 17).
• The unit has filters both for outdoor air and extract air.
• Check that the fans are clean.
Fig. 15
NB! When inserting the filter cartridge into its
slot, push it properly to prevent air leakage.
Fig. 17
9
Page 10
UNI 3 User Manual
3.3 Replacing the brush strips
The brush strips become worn over time. If they do not
sit tightly against the rotary wheel-type heat exchanger,
it can be necessary to replace them
Alternatively, they can be moved closer to the rotor, where
the aluminium profile they are mounted in has two grooves.
Do the following:
1. Pull the rotor a little way out (see Fig. 18).
2. Unplug the quick-release contact fastened to the rotor
(see Fig. 19).
3. Pull the rotor out completely.
4. Remove the screw in the centre of the aluminium profile
and pull the profile out (see Fig.20).
5. Pull the brush strips out of the groove. Move them up
from level 1 to level 2 (see Fig. 21), or replace them with
new ones if they are completely worn out.
(art.no. 110894).
Fig. 18
Fig. 19
Fig. 20
Fig. 21
10
level 1
level 2
Page 11
UNI 3 User Manual
3.4 Rotor
As the unit has high impermeability, filters installed, it is not
usually necessary to clean the rotor. If, for various reasons,
it should still be necessary, dust can be removed with a soft
brush.
Further cleaning is possible if you remove the rotor, spray it
with fat-soluble detergent and then blow it clean from the
opposite side. Distance approximately 60 mm and max.
pressure 8 bar.
Ensure that the motor is not exposed to water during
cleaning. Ensure that all seals around the rotor are intact
and tight. Ensure that there is no damage to the rotor belt,
and that the rotor rotates freely.
3.5 Tightening of rotor belt
The rotor belt can be tightened by releasing 8 screws in order
to remove the rotor side plate (See Fig. 22).
Next release the screws (one on each side) holding the rotor
motor in place (see Fig. 23). This will allow the rotor motor
to be repositioned, thus tightening the belt (see Fig. 24).
Tighten all the screws again
Fig. 22
Fig. 23
3.6 External Cleaning
Many kitchen surface cleaners contain chemicals that
may damage the product’s plastic components. Therefore
use a soft cloth moistened with warm water and a neutral
detergent to clean the outside of the product.
NB! Do not use abrasive cleaners or scouring
powder, as such products can damage the
surfaces. Do not use cleaners containing citric
acids or ammonia. Products that give stainless steel
an anti-fingerprint coating must not be used either.
Fig. 24
11
Page 12
4 CI60 control unit overview
CI60 User Manual
8
3
4
*
1
2
5
6
7
No. Description
*
1
Switch for increased ventilation
2Switch for decreased ventilation
3
Indication of MAX speed
4
Indication of NORMAL speed
5
Indication of MIN speed
6
Indication of ALARM
7
Indication of FILTER REPLACEMENT
9
10
11
12
No. Description
8Potentiometer for adjusting extract air
at NORMAL speed
9Potentiometer for adjusting supply air at
NORMAL speed
10
Switch for additional heating OFF/ON
11Potentiometer for adjusting supply air
temperature
12Switch to reset the alarm
*The figures are used as references in subsequent descriptions
Nos. 8, 9 and 10 are used to adjust the unit before it
is used for the first time.
12
Page 13
5 CI60 in use
CI60 User Manual
5.1 General
The control unit consists of a touch panel with pushbuttons,
LEDs for indication and adjustment potentiometers and
switches for adjusting the ventilation unit. The control unit
communicates with the ventilation unit via a low-voltage
cable.
5.2 Increasing/reducing air supply
Use switches 1 and 2 to increase and reduce the fan speed
and thus the air flow. Different speeds depending on the
operating situation.
MIN
NORMAL
MAX
The different speeds are indicated with LEDs 3, 4 and 5.
Do not use during first year of operation, or
when the building is in use.
Used under normal conditions. In this
setting, the air supply must be adjusted
according to current regulations.
Used if there is a need for increased air
supply on account of increased occupancy
or a higher humidity level, for example
during showering or when clothes are being
dried. This setting is usually used for limited
periods of time.
5.3 Adjusting the air supply
At NORMAL speed level, the air flow must be adjusted
according to project data. Potentiometer 9 is used for the
supply air level and potentiometer 8 for the extract air level.
The adjustment range is 20-100% of the maximum level
according to the scale of the potentiometer.
Factory settings:
MIN
NORMAL
MAX
50% (fixed)
75% (variable)
100% (fixed)
9
8
5.4 Temperature adjustment
The temperature required in the supply air can be set with
potentiometer 11. The adjustment range is 10 - 30 °C. Using
the factory settings is recommended.
If necessary, the ventilation unit’s heating can also be
switched ON/OFF with switch 10. In this case only the rotating
heat exchanger is used as a source of heat. It is best to leave
it in ON position, as the unit will then respond automatically
when there is a need for additional heating.
ITEM 10
ON
OFF
5.5 Filter replacement
Every six months, LED 6 lights up to remind you that it is time
to replace the air filters in the unit. See section 3 for more
information on filter replacement.
After the activity has been carried out, the
indicator must be reset. See more under the
Reset section.
5.6 Alarm
If anything unforeseen occurs with the
ventilation unit, indicator 6 lights up.
The signal given by the indicator depends on the
reason for the indication.
A permanent light indicates:
!
• Fault return water detector (B5)
• Heat recovery fault (B)
A permanent light with indicator 5 (MIN speed) flashing
indicates:
• Fault supply air detector (B1)
• Fault extract air detector (B3)
• Fault outdoor air detector (B4)
1011
A flashing light indicates:
• Overheating thermostat fault (applies only to electric
heating)
• Fault in external fire/smoke detector (accessory)
• Heat recovery fault (A)
• Additional heating fault (applies only if the unit has a
water battery)
13
Page 14
CI600 User Manual
5.7 Reset
After the filter has been replaced or the cause of the
alarm repaired, the alarm must be reset. This is done by
pressing switch 12.
If the indicator goes out, the action has been carried out
correctly. If the indicator remains on, the fault has not
been repaired correctly.
6 CI600 control unit overview
NB! If thermostat F10 trips, the unit will have to be
opened up and physically reset before resetting on the
panel. If the alarm trips repeatedly, contact the service
company or distributor.
6
*
1
2
3
No. Description
*
1
UP/INCREASE switch
2
BACK/CANCEL/NO switch
3
DOWN/DECREASE switch
4
OK/YES switch
5
HELP switch
6Display
7
Indication of OPERATION/OK - Green light
8
Indication of FILTER REPLACEMENT - Yellow light
9
Indication of ALARM - Red light
7
8
9
45
*The figures are used as references in subsequent descriptions
14
Page 15
CI600 User Manual
45
04
07
09
7 CI600 in use
7.1 General
The control unit consists of a colour display, a touch panel
and indicators (LEDs). The unit communicates with the
ventilation unit via a low-voltage cable.
7.2 Idle mode
If the touch panel is not used, the control unit will, after a
certain period of time, enter idle mode, in which operating
information will be displayed.
A
13.08.2009
BC
If you select a function that has numerical values, the
current value is displayed with a light blue cursor. The value
is changed with buttons 1 and 3 and is then confirmed by
pressing button 4.
TIME AND DATE
TIME DAY MONTH YEAR
13 : 45 04.07.09
OK?
16:43
18°C 22°C
- NORMAL
DEF
A. Time and date
B. Outdoor air temperature
C. Room temperature
D. Current speed
E. Additional heating activated/deactivated
F. Daily/weekly timer active
7.3 Menu navigation
Buttons 1 and 3 are used to navigate through the menu lines.
The cursor is illustrated by the line being light blue. If it is
possible to make a selection on the current menu line, this
is displayed with OK? to the right of the line. A selection is
confirmed by pressing button 4.
If a menu line contains submenus, this is illustrated with a ‘>’
sign at the end of the line.
If several values can be changed, the cursor jumps to
the right when a selection is confirmed with button 4. The
procedure is repeated until all values have been changed to
the desired values.
If you want to cancel a function or return to the previous
menu screen, use button 2.
Button 5 activates a help text that briefly describes the
current menu screen.
7.4 Start menu
When the system is started, a start menu is opened.
START MENU
LANGUAGE
TIME AND DATE
MAIN MENU
OK?
>
>
SETTINGS
TEMPERATURE
TIMER
DAY/WEEK SET TINGS
TIME AND DATE
LANGUAGE
FILTER
ALARM
ADVANCED USER
OPERATING INFORMATION
>
>
OK?
>
>
>
>
>
>
The basic language and date settings are set in this menu.
When this activity has been carried out, you choose to go to
the main menu.
7.5 Operating status
In normal operation without problems, the green LED 7
lights up to confirm that everything is working normally. How
any problems affect the system is described in subsequent
sections.
15
Page 16
8 CI600 main menu
CI600 User Manual
8.1 Fan speeds
The main menu contains various choices. Most concern
fan speeds. The speed selected is indicated with large fan
symbols and bold font.
MAIN MENU
MIN
NORMAL
OK?
MAX
MAX TIMER
SETTINGS
To change the speed, move the cursor with buttons 1 and 3.
>
MAIN MENU
MIN
NORMAL
MAX
OK?
MAX TIMER
8.2 Max. timer
This menu item activates a function that increases the speed
to MAX for a limited period of time before subsequently
returning to the speed selected previously. The period of
time can be adjusted under the SETTINGS menu item.
MAIN MENU
MIN
NORMAL
OK?
MAX
MAX TIMER
SETTINGS
When the function is active, the time is counted down on the
display. If you select TIMER OFF, the function will be cancelled
and the speed will return to the previous selection.
8.3 Settings
Under the SETTINGS menu item, you can adapt the system
as you want.
>
SETTINGS
Then confirm your selection with button 4 and the speed
selected is highlighted with large fan symbols and bold font.
>
MAIN MENU
MIN
NORMAL
MAX
OK?
MAX TIMER
SETTINGS
MINMust not be used when the home is in use. Must
not be used in the first two heating seasons.
NORMAL Used under normal conditions. On this setting
the air supply must be adjusted according to
current regulations.
MAXUsed if there is a need for increased air supply
on account of higher occupancy or a raised
humidity level, for example during showering
or when clothes are being dried. This setting is
normally used for limited periods.
>
SETTINGS
TEMPERATURE
TIMER
DAY/WEEK SET TINGS
TIME AND DATE
LANGUAGE
FILTER
ALARM
ADVANCED USER
8.4 Temperature
Here you set the temperature for the air that enters the
building.
>
>
OK?
>
>
>
>
>
TEMPERATURE
18
°C
HEATING ELEMENT ON/OFF
OK?
>
16
Page 17
CI600 User Manual
We recommend adjusting the temperature to max 18° so
that the air is mixed optimally with the air already in the
building.
In the HEATING ELEMENT OFF/ON menu item, the additional
heating in the ventilation unit can be switched off. In such
case, only the rotating heat exchanger is used as a source of
heat.
If necessary, the ventilation unit’s heating can also be turned
off. In this case only the rotating heat exchanger is used as
a source of heat. It is best to leave it ON, as the unit will then
respond automatically when there is a need for additional
heating.
NB! This is not possible if the unit is installed with a water
battery.
If the heating element is switched off, this symbol is
displayed when the display enters idle mode.
HEATING ELEMENT ON/OFF
8.6 Daily/weekly timer
The programming of the timer begins by selecting the day.
DAY / WEEK SETTINGS
MONDAY
TUESDAY
WEDNESDAY
THURSDAY
FRIDAY
SATURDAY
SUNDAY
A new menu screen appears under each day.
TUESDAY
1 08
2 16
:
00
:
00
-
16
-
18
:
:
00
00
MIN
NORMAL
OK?
16°
18°
HEATING ELEMENT ON
8.5 Timer
Here you set the time you want for the MAX TIMER function.
This is used when the function is activated from the main
menu.
TIMER
min
60
To adjust the time interval for MAX TIMER, see chapter 9.4
under “Timer”.
OK?
OK?
:
3 18
4 19
Each day can be programmed with four different time
intervals. Adjust the start and stop times for each interval
and then adjust the desired speed and temperature. To
activate the interval, select a green tick. A red cross means
that the interval is not activated. If necessary, then select
another interval and repeat the procedure.
After you have finished programming a day, repeat the
procedure for other days.
If there is no new time interval registered after the finished
period, the speed and temperature return to the setting that
was previously active.
00
:
00
NB!
The following rules apply to the programming:
• An interval can never commence before a
previous one has been finished.
• The stop time can never appear before the
start time.
When the timer is active, this symbol is displayed
when the display enters idle mode.
-
19
-
24
:
:
00
00
MAX
NORMAL
16°
18°
17
Page 18
8.7 Time and date
45
04
07
09
The time and date can be adjusted in this dialog.
CI600 User Manual
The normal interval is 6 - 12 months, depending on the
environment.
TIME AND DATE
TIME DAY MONTH YEAR
13 : 45 04.07.09
OK?
8.8 Language
The language selected can be changed in this dialog.
LANGUAGE
NORSK
ENGLISH
SVENSKA
DEUTCH
NEDERLANDS
SUOMI
DANSK
OK?
When the filter alarm is triggered, the yellow indicator 8 lights
up and an information text appears. Follow the instructions
in the text. It is possible to go directly to this dialog from
the message or via the menu tree. After the alarm has been
reset, the countdown to the next filter replacement begins.
8.10 Alarm
If a problem occurs in the operation of the ventilation unit,
an alarm will be triggered. The red indicator 9 lights up
and an information text appears in the display. Follow the
instructions in the text. It is possible to go directly to this
dialog from the message or via the menu tree.
NB! If thermostat F10 trips, the unit will have to be opened
up and physically reset
alarm is tripped repeatedly, contact the service company or
distributor.
before resetting on the panel. If the
ALARM
RESET ALARM
OK?
8.9 Filter
A reminder appears regularly in the display. In this dialog,
the time interval can be adjusted and the filter alarm reset.
FILTER
INTERVAL CHANGE OF FILTER
RESET FILTER ALARM
>
OK?
INTERVAL CHANGE OF FILTER
8.11 Operating information
This general screen displays current temperature values,
whether the daily/weekly timer is active and activity as
0-100% for cooling, heat exchanger and additional heating.
OPERATING INFORMATION
SET TEMPERATURE
DAY / WEEK SETTINGS
SUPPLY AIR
EXTRACT AIR
OUTDOOR AIR
RETURN WATER
HEAT RECOVERY SYSTEM
COOLING
HEATING
22°
AKTIV
22°
21°
0°
35°
100%
0%
100%
6 MND
OK?
18
Page 19
9 CI600 advanced user menu
NB! For more information on the ”Advanced
User” menu, refer to the ”CI600 Reference Ma-
nual” on Flexit’s homepage.
CI600 User Manual
Regulation type
If supply air regulation is selected, no further settings can
be set here. If extract air regulation is selected, the max. and
min. supply air temperatures can also be specified.
9.1 PIN
To access the menu item, you need to enter the PIN 1 0 0 0.
PIN CODE
1 0 0 0
9.2 Advanced user
This menu contains functions for monitoring, configuration
and troubleshooting. Information to do with adjustment
can be found in the installation instructions. Complete
documentation of all menus, including configuration for
accessories and extras, etc., is described in the CI600
reference manual, which is available at www.flexit.no.
OK?
REGULATION TYPE
REGULATION
MAX SUPPLY AIR TEMP
MIN SUPPLY AIR TEMP
EXTR OK?
35°
15°
Cooling
NB! Flexit does not supply or project cooling
machines.
In this dialog, the cooling function is activated and the
parameters MIN OUTDOOR AIR TEMP for supply of cooling
and MIN SPEED for supply of cooling are specified. If a DX
cooling machine is used, the supply delay interval can be
specified.
ADVANCED USER
TEMPERATURE REGULATION
FAN REGULATION
CONFIGURATION
OPERATING TIME
FACTORY SETTINGS
SERVICE
9.3 Temperature regulation
In this menu screen, you configure the temperature
regulation and cooling functions.
>
OK?
>
>
>
>
TEMPERATURE REGULATION
REGULATION TYPE
COOLING
NEUTRAL ZONE
EXT. TEMP. CONTROL
>
>
OK?
>
COOLING
OK?
COOLING
MIN OUTDOOR TEMP
MIN SPEED
RESTART DELAY
COOLNESS RECOVERY
AV
18°
MIN
180 s
>
It is also possible to activate a function to recover cooling
in the building using the rotating heat exchanger. Enter
the desired difference between the outdoor and indoor air
temperatures for when the function is activated.
COOLNESS RECOVERY
COOLNESS RECOVERY
DIFF
OFF
1°
OK?
19
Page 20
CI600 User Manual
Neutral zones
To achieve more even temperature regulation, the
neutral zones can be set in this menu.
NEUTRAL ZONE
COOLNESS RECOVERY
HEAT RECOVERY SYSTEM
2°
OK?
1°
External temperature control
Control of the temperature settings from an overall
system must be entered in this menu. In this case, the
temperature settings in the control unit are overridden.
EXT. TEMP. CONTROL
EXT. TEMP. CONTROL
OFF
OK?
Adjustment (supply air and extract air)
This dialog is identical for the supply air and extract air fans.
The fans are adjusted individually to the desired capacity for
the respective speed.
SUPPLY AIR
MIN SPEED
NORMAL SPEED
MAX SPEED
Factory settings:
MIN
NORMAL
MAX
Timer
Settings are entered in this menu for the speed and time that
are to apply to the ‘MAX TIMER’ function in the main menu.
50%
75%
100%
OK?50%
75%
100%
9.4 Fan control
The fans are selected and configured in this menu screen.
FAN REGULATION
SUPPLY AIR
EXTRACT AIR
TIMER
AIR VOLUME COMP
>
>
OK?
>
TIMER
STANDARD SPEED
STANDARD TIME
Air flow rate compensation
This function can be activated via an input on the control
card. The speeds required for each fan are selected here. The
function can be used with a kitchen fan or other device that
requires additional supply air.
OK?MAX
30 m
AIR VOLUME COMPENSATION
SUPPLY AIR
EXTRACT AIR
OK?MAX
MIN
20
Page 21
CI600 User Manual
9.5 Configuration
The general configuration is set in this menu screen.
CONFIGURATION
SENSORS
FIRE/SMOKE
COMMUNICATION
START/STOP SEQUENCE
REST MODE
>
>
OK?
>
>
Sensors
The temperature sensors can be calibrated in this menu to
be better coordinated with the real situation, and a pressure
sensor is activated as a pressure guard instead of the
integrated time control.
SENSORS
SUPPLY AIR
EXTRACT AIR
OUTDOOR AIR
RETURN WATER
FILTER GUARD
>
>
OK?
>
>
Fire/Smoke
This function requires an external sensor to be connected to
the control card.
FIRE/SMOKE
MODE
ModeSupply air fanExtract air fan
1STOPSTOP
2MAXMAX
3STOPMAX
4MAXSTOP
OK?1
Communication
Proceed to the “HOME/AWAY”submenu. This function can
be used to make the unit run on other operating settings
using an external switch.
NB! The settings have no effect unless an external switch is
connected.
The menu screen is identical for all temperature sensors and
they can be adjusted within an interval of 5 °C.
SUPPLY AIR
CALIBRATION
If the pressure guard is activated, an external sensor must
be connected to the control card. The sensor replaces the
integrated filter time control.
OK?0
FILTER GUARD
ACTIVATION
OK?OFF
COMMUNICATION
HOME/AWAY
The settings are entered for the AWAY selection. Speed and
temperature can be selected, plus how long after activation
the new setting should take effect.
OK?
21
Page 22
CI600 User Manual
Standby mode
In this menu you can adjust the time it takes before the
display enters idle mode.
REST MODE
TIME DELAY
2 min OK?
9.6 Operating time
This menu screen displays the ventilation unit’s total
operating time and how much time has passed since the last
filter replacement.
OPERATIONS COUNTER
OPERATING TIME
FILTER
STOP
MIN
NORMAL
MAX
ROTOR
HEATING ELEMENT
459.7 TIM
459.7 TIM
0.0 TIM
123.0 TIM
161.4 TIM
178.0 TIM
0.4 TIM
0.3 TIM
De-icing
Activates/deactivates the function.
Start temperature
The start temperature for the defrosting function is set here.
The temperature in question is the outdoor temperature.
Period time
Period time for de-icing operation.
Frequency
Decides how many times the period shall be repeated per
hour.
Rotor speed
When the start temperature has been reached, the speed of
the drive motor of the rotating heat exchanger is reduced to
the specified RPM.
Start fan reduction
As an additional safety function, the speed of the supply
air fan can be reduced. This takes effect at the set outdoor
temperature.
Period time
Period time for de-icing operation.
Frequency
Decides how many times the period shall be repeated per
hour.
9.7 Service
Password given only in consultation with
the Flexit service organisation
.
De-icing
The integrated de-icing function is deactivated on delivery
of the ventilation unit.
The function can be configured or activated in this menu
screen.
Search path to menu screen:
MAIN MENU/SETTINGS/ADVANCED USER/SERVICE/DE-ICING
DE-ICING
DE-ICING
START TEMPERATURE
PERIOD TIME
FREQUENCY
ROTOR SPEED
START FAN REDUCTION
PERIOD TIME
FREQUENCY
FAN SPEED
OK?OFF
-9°
60 min
1/TIM
15
-14°
60 min
1/TIM
50%
Fan speed
As an additional safety function, the speed of the supply
air fan can be reduced. This takes effect at the set outdoor
temperature.
De-icing - Parameters
ParameterDefaultRangeUnit
De-icingOFFOFF/ON
Start temperature-9(-5)–(-45)°C
Period time601–60min
Frequency11–10no./hour
Rotor speed1515–180rpm
Fan reduction-14(-5)–(-45)°C
Period time601–60min
Frequency11–10no./hour
Fan speed5020–100%
22
Page 23
9.8 Menu tree
CI600 User Manual
MAIN MENU
TEMPERATURE
TIMER
DAY/WEEK SETTINGS
TIME AND DATE
LANGUAGE
FILTER
ALARM
ADVANCED USER
PIN
TEMPERATURE REGULATION
FAN CONTROL
CONFIGURATION
OPERATING TIME
FACTORY SETTINGS
SERVICE
HEATING ELEMENT ON/OFF
MONDAY
SUNDAY
RESET FILTER ALARM
FILTER CHANGE INTERVAL
REGULATION TYPE
COOLINGCOOLING RECOVERY
NEUTRAL ZONE
EXT. TEMPERATURE CONT.
SUPPLY AIR
EXTRACT AIR
TIMER
AIR FLOW RATE COMP.
SENSORS
FIRE/SMOKE
COMMUNICATIONHOME/AWAY
START/STOP SEQUENCE
IDLE MODE
SUPPLY AIR
EXTRACT AIR
OUTDOOR AIR
RETURN WATER
FILTER GUARD
SYSTEM INFORMATION
PRODUCTION DATA
TEST
ALARM
SPECIAL FUNCTIONS
DE-ICING
PARAMETERS
23
Page 24
UNI 3 User Manual
10 Maintenance Table
ComponentActionInterval
FiltersFilters must be replaced at least once a year. It is recommended to change them twice a year,
before and after the pollen season. Check that the filter seal is completely tight.
FansFans must be cleaned at least once a year to maintain fan efficiency.12 months
RotorCheck that the surfaces are clean. Check that the sealing strips face in towards the rotary
wheel-type heat exchanger. Check that the rotor belt is whole and not too slack.
Kitchen hood*Wash the grease filter. Check that the damper is clean and closes fully.2 weeks
SealsCheck that the seals in the unit are intact.12 months
ValvesTo be cleaned at least once a year.12 months
Air intakeCheck that no leaves or other items have caught in the grille.
In frost mist periods during winter the air intake can freeze up. If necessary it must be scraped
clean so that the air can pass through.
Roof cowlIf the unit has a roof cowl, this must be checked for leaves and the like. Also check that the
drain slots are open.
DuctsCheck that the ducts are clean.10 years
Brush stripsCheck that the brush strips are whole and sit tightly against the rotor. If they are worn they
can be moved to the next groove in the profile, so that they are closer to the rotor.
Inside unitA combination of a very low outside temperature and damp extract air can lead to the
formation of ice. Normally this will not be a problem - when normal operating conditions
return the ice crystals will be converted to damp and be removed from the unit via the
exhaust air. In the case of extreme cold over longer periods the unit should be checked for
ice.
6-12
months
12 months
12 months
12 months
3 years
*For units with extract air from the kitchen hood connected to the unit.
11 Troubleshooting
Type of faultRemedial action
Cold draughtsCheck which supply temperature has been selected. See operating panel.
Check that the rotor is rotating.
Check that heating comes on.
Needs new extract filter.
Fans not workingCheck that the power to the unit is connected.
Check that the thermostat has not cut out.
Reset by pressing the button. Must also be reset on the automatic panel.
Low air volumeCheck the speed the unit is set to.
Check that the filters are tight.
Check the intake grille.
24
Page 25
12 CE Declaration of Conformity
UNI 3 User Manual
This declaration confirms that the products meet the
requirements in the following Council Directives and
standards:
Compliance with valid versions of the following standards on
the date on which the declaration of conformity was signed:
Safety standard:EN 60335-1
EN 60335-2-80
EMF standard:EN 62233
EMC standard:EN 55014-1
EN 55014-2
EN 61000-3-2
EN 61000-3-3
The product is CE-marked: 2010
FLEXIT AS 29.11.2016
Frank Petersen
Adm. dir.
The right to give notice of lack of conformity applies to this product in
accordance with the existing terms of sale, provided that the product is correctly used and maintained. Filters are consumables.
The symbol on the product shows that this product must not be
treated as household waste. It must be taken to a reception station
for recycling of electrical and electronic equipment.
By ensuring correct disposal of the equipment, you will contribute
to preventing negative consequences for the environment and
health that incorrect handling may entail. For further information on
the recycling of this product, please contact your local authority, your refuse
collection company or the company from which you purchased it.
Notice of lack of conformity as a result of incorrect or defective installation must
be submitted to the installation company responsible. The right to give notice of
lack of conformity may lapse if the system is used incorrectly or maintenance is
grossly neglected.
25
Page 26
26
Page 27
27
Page 28
Flexit AS, Televeien 15, N-1870 Ørje www.flexit.no
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.