3
1.1 UNI 3
Water heating element art.no. 110948 has the highest
capacity of Flexit’s water heating elements. It is designed
for systems with air flow rates of more than 280 m3/h, and
where outdoor temperatures can go below -20°C.
For other conditions, use art.no 110863.
High capacity element: example 1
Air flow rate: 350 m³/h
Power consumption: 1,28kW
Temperature, incoming water °C 60 50
Temperature, outgoing water °C 36,56 35,22
Water flow l/h 44 69
Water speed m/s 0,26 0,4
Pressure drop, water side kPa 1,39 3,18
Valve presssure drop kPa 3 7,6
Capacity kW 1,28 1,28
Pipe connection thread DN15 DN15
Valve KVS 0,25 0,25
Normal capacity element: example 2
Air flow rate: 216
m³/h
Power consumption: 0,58kW
Temperature, incoming water °C 80 70 60 50
Temperature, outgoing water °C 57,64 53,3 49 44,7
Water flow l/h 23 31 47 96
Water speed m/s 0,14 0,18 0,27 0,56
Pressure drop, water side kPa 0,25 0,42 0,91 3,44
Valve presssure drop kPa 0,33 0,6 1,38 5,76
Capacity KW 0,58 0,58 0,58 1,28
Pipe connection thread DN15 DN15 DN15 DN15
Valve KVS 0,4 0,4 0,4 0,4
Normal capacity element: example 3
Air flow rate: 350 m³/h
Power consumption: 1,28kW
Temperature, incoming water °C 80 70
Temperature, outgoing water °C 66,38 63,03
Water flow l/h 84 164
Water speed m/s 0,49 0,96
Pressure drop, water side kPa 2,47 8,47
Valve presssure drop kPa 4,41 16,8
Capacity kW 1,28 1,28
Pipe connection thread DN15 DN15
Valve KVS 0,4 0,4
Water heating element installation manual
1.2 UNI 4
Air flow rate: 470 m3/h
Power consumption: 1,72kW
Temperature,
incoming water
°C 80 70 60 50
Temperature,
outgoing water
°C 41 40,4 39,73 38,98
Water flow l/h 39 52 75 138
Water speed m/s 0,23 0,3 0,44 0,81
Pressure drop, water
side
kPa 1,09 1,8 3,58 10,77
Valve presssure drop kPa 0,9 1,7 3,5 11,9
Capacity kW 1,75 1,75 1,75 1,75
Pipe connection Gjenger DN15 DN15 DN15 DN15
Valve KVS 0,4 0,4 0,4 0,4