1.3. System overview ..........................................................................................................................................5
1.3.1. System structure ....................................................................................................................................5
1.3.2. Ventilation unit's switching space ......................................................................................................6
1.3.3. Ventilation unit's control cabinet .......................................................................................................7
2.2.4. Set time/time channels .......................................................................................................................10
2.3. Adjust the setpoints for speeds and temperatures ............................................................................12
2.4. Service switch ............................................................................................................................................. 12
2.5. Extract air regulation ................................................................................................................................ 12
2.6. Change the unit for the flow display ......................................................................................................12
3. Menu tree ...................................................................................................................................................13
4. Backup and program updates
4.1. Save a configuration ................................................................................................................................ 25
4.2. Load a configuration ................................................................................................................................ 25
4.3. Loan an application or software ............................................................................................................ 25
5. General functions ...................................................................................................................................26
9.10. Support operation .................................................................................................................................... 42
9.10.1. To activate the function..................................................................................................................... 42
9.10.2. To configure the function .................................................................................................................. 42
10. Fan regulation
10.1. Select method of regulation ....................................................................................................................43
10.1.1. Selection fan regulation method ......................................................................................................43
10.2. Pressure control .........................................................................................................................................43
10.2.1. Configuration of the pressure sensors’ measuring ranges .........................................................43
10.3. External fan setpoint ............................................................................................................................... 44
10.3.1. Parameter settings for Comp. .......................................................................................................... 45
10.3.2. Parameter settings for Main ............................................................................................................. 45
10.4. External fan control via digital inputs ................................................................................................... 46
10.5. Fire fan ........................................................................................................................................................ 46
11. Connection of external equipment
11.1. Fire damper ................................................................................................................................................ 47
11.3. Air quality .................................................................................................................................................... 51
11.4. AUX Damper .............................................................................................................................................. 52
12. Web ..............................................................................................................................................................53
This document describes the main functions of the CS2000 automatic control and is divided into different sections for
different parts of the system. If you only want to make basic settings to start the ventilation unit, there is a special section
describing the startup procedure. If you require more detailed information, select the relevant section in the document.
All electrical connections must be made
by an expert.
1.2. Highlighted boxes
A number of different text boxes are used in the document to draw the user's attention to various things. This may be anything
from pure information text to particularly important details to ensure that the system is not used incorrectly. Here is a brief
description of the various boxes:
WARNING! When a text is highlighted like
this, it means that personal injury or serious
damage to the equipment may result if the
instructions are not followed.
NB! When a text is highlighted like
this, it means that the equipment may
be damaged or function poorly if the
instructions are not followed.
RESTART
> EXAMPLE
Italicised text boxes show examples
A table looks like this
with various valueswith various values
with various valueswith various values
4
Page 5
1.3. System overview
1.3.1.
The control system is divided into two subgroups:
1. One part that is located in the ventilation unit's switching space
2. One part that is located in a separate control cabinet on the outside of the ventilation unit
System structure
1.
Terminal blocks for incoming feed
Fuse for automatic control and fans (not electric
heating coil)
Modbus extender - a communication card that
connects the ventilation unit's components to
the regulator via data communication
Power supply board - a circuit board that
distributes the power supply to the ventilation
unit's components and makes it possible to
connect components to a water heating coil
1, 2
2.
Regulator - the overall control system of the
ventilation unit
Terminal board - a circuit board with terminal
blocks for connection of additional components
and accessories
HMI - the control panel used to communicate
with the regulator
12
L modelS model
5
Page 6
1.3.2.
Ventilation unit's switching space
Modbus extender
A3
123
P1
4
128
9
3410
11
P2
5612
13
714
125
6
P3
347
8
Q1Q2
USER
FACTORY
FP1FP2
1095
4
873
P8
2
61
P7
P6
P5
P4
It is a communication card that connects the ventilation
unit's components to the regulator.
The card has four dipswitches called 'USER' that are used
to configure the unit, depending on the type of heating coil
installed.
Dipswitch no.ONOFF
1Heating coilNo heating coil
2Electric heating coil Water heating coil
3-Must be OFF
4-Must be OFF
The other four dipswitches and the rotary switches marked
'FACTORY' are factory-set and must not be changed.
The board's components have the following functions.
ComponentFunction
P1Power supply
P2Control signals to heating coil
P3Control signals to rotor and temperature sensor
P4Communication connection
P5Communication connection
P6Communication connection
P7Communication connection
P8Control signals to fans
Q1Differential pressure monitor for flow
measurement on supply air fan
Q2Differential pressure monitor for flow
measurement on extract air fan
FP1Differential pressure monitor for supply air filter
FP2Differential pressure monitor for extract air filter
Power supply board
A4
18
29
310
411
P6P7
512
613
714
14
25
P5
36
13
P4
24
1 2 3 4 5 6 7 8 9
18
29
310
411
512
613
714
P3
34
12
P8
10 11 12 13 14
1 2345
P9
1 2345
P10
PE PE PE
P1P2
L1 L2 L3 N
It is a circuit board that distributes the power supply to the
components of the ventilation unit (not the electric heating
coil) and control cabinet.
There is also a terminal block for the components required to
regulate a water heating coil.
The board's components have the following functions.
ComponentFunction
P1Terminal block for power supply
P2Terminal block for protective earth (PE)
P3Terminal block for water heating coil
P4Power supply to modbus extender
P5Power supply to control cabinet
P6Control signals to heating coil
P7Control signals to heating coil
P8Power supply to rotor control
P9Power supply to supply air fan
P10Power supply to extract air fan
Terminal block P3 has the following signals:
Block no.Function
1Valve motor - G0
2Valve motor - 24 V+
3Valve motor - G0
4Valve motor - control signal 0-10 V
5G0 (for F10 or B5)
6Overheating thermostat F10
7Return water sensor B5
8No connection
9N
10Pump motor - relay contact
11Pump motor - relay contact
12L
13N
14L
6
Page 7
1.3.3.
Ventilation unit's control cabinet
Regulator
A1
X1MX2X3MX4X5MX6X7MX3+24V
0V
24V=
T1T2T3T4
T6T7T8T9
Q13
Q14
Q23
Q24
Q33
Q34
Q43
Q44
Q53
Q54
Q63
Q64
+24VY1M
CE -
CE+
Y2
REF
B -
A +
D1MD2D3MD4D5
M
The ventilation unit's control system. This is where the
control panel (HMI) and sensors and other components
of the ventilation unit are connected. It is also possible
to connect an SD memory card to back up or reload
configuration settings and parameters for the regulator.
HMI
The control panel on which all settings and readings take place.
It has an 8-line graphic display and you navigate the menu
tree using a dial that is turned. Selections are confirmed by
pressing the same button.
It is a circuit board that connects the components to
the regulator. External components such as dampers are
connected to this board via the terminal blocks on the board.
The board's components have the following functions.
ComponentFunction
P1Connection for power supply
P2Data communication
P3Data communication
P4Connection for external pressure sensor
(accessory)
P5Connection for external pressure sensor
(accessory)
P6Connection for 24 V transformer
P7Data communication
P8Connection for digital outputs
P9Connection for control signals
P10Terminal block for 230 V signals
P12Terminal block for control signals
P14Terminal block for protective earth (PE)
7
Page 8
Terminal board
Terminal block P10 has the following signals:
Block no.Function
1L
2N
3L (Outdoor air damper)
4L1 (Outdoor air damper ON/OFF)
5N (Outdoor air damper)
6L (Exhaust air damper)
7L1 (Exhaust air damper ON/OFF)
8N (Exhaust air damper)
9L (Fire damper)
10L1 (Fire damper ON/OFF)
11N (Fire damper)
12Buzzer alarm IN
13Buzzer alarm OUT
14DX cooling/cooling pump IN
15DX cooling/cooling pump OUT
16L
17Heating IN
18Heating OUT
19N
20Not used
Terminal block P12 has the following signals:
Block no.Function
21Cooling - 0-10 V [AO]
22Cooling - G0
23External control 1 [DI]
24External control 1 - G0
25External control 2 [DI]
26External control 2 - G0
27Fire/smoke [DI]
28Fire/smoke - G0
29Air quality - 0-10 [AI]
30Air quality - G0
31Heating - 0-10 V [AO]
32Heating - 24 V+
33Heating - G0
34Fire damper open [DI]
35Fire damper closed [DI]
36Fire damper - G0
37AUX damper - 0-10 V [AO]
38AUX damper - G0
39Return water sensor B5 [AI]/Overheating
thermostat F20 [DI]
40Return water sensor B5 [AI] - G0 /
Overheating thermostat F20 [DI] - G0
External setpoint, supply air fan 0-10 V [AI] - G0
41CE- [Data bus]
42CE+ [Data bus]
43External setpoint, supply air fan 0-10 V [AI]
44External setpoint, extract air fan 0-10 V [AI]
8
Page 9
2. Getting started
2.1. HMI
A central element in the system is the HMI (control panel), where you can adjust settings and take readings. The control panel
consists of an 8-line graphic display, indicator lamps and controls for the settings.
Here is a short introduction to the control panel showing how to enter the initial settings in the system.
Info button
Press to go to
Main Menu
• Off = Stop, cool down
• Green lamp, steady =
Normal operation
• Flashing green =
Starting, Night
operation test, Night
cooling or Night
heating/night cooling.
• Orange lamp, steady =
Emergency stop and
alarm with stop
• Flashing orange = Fire
damper in motion
• Alternating green/
orange = Manual
control
Alarm button
• Flashing red = alarm
• Red lamp, steady =
alarm acknowledged
but remaining
ESC button
• Returns to the
previous menu page
• Cancels current
editing
Display
Shows information
Dial
• Turn
counterclockwise/
clockwise to go up/
down in menus or to
change values
• Press the button
to enter a menu or
change a value
• Hold the button
down to go directly
to the login menu if
the value you want
to change
• requires login
2.2. Settings
2.2.1.
The first time the system is started, you need to go through
some simple steps to ensure that the system will function.
If a heating coil has been installed in the ventilation unit and
the associated settings have been made with dipswitches
in the switching space in the unit, the automatic control
system will be restarted automatically once to complete the
operation. No extra action needs to be taken. It is simply
necessary to wait until the system has restarted.
There is a quick menu to access the most commonly used
functions in the control panel, Language, Timing Program
and Setpoint Settings.
2.2.2.
To change the language on delivery:
Start page > Quick menu > Language selection >
HMI Language > English
Changes the menu language to English.
Introduction
Select language
2.2.3.
Login
In order to make changes to the system, it is normally necessary
to log in. There are four authority levels in the system, and three
of them are password protected. The level at which the user is
currently logged in is shown by the number of keys in the top
left hand corner of the display. The menus show more options or
fewer, depending on the level at which you are logged in.
The following actions are possible at the different levels:
Level 1: No restrictions, no password required.
• Read rights to all menus except system parameters,
configuration and detail menus.
• Read rights to alarm lists and alarm history.
Level 2: End user, password 1000.
• All rights as for level 1, plus:
• Read rights to all menus except configuration menus.
• Write rights to the most important setpoints (Setpoints/
Settings > Setpoints).
• Alarms and alarm history can be acknowledged and reset.
9
Page 10
Level 3: System administrator, password 2000.
• All rights as for level 2, plus:
• Rights to all menus except I/O configuration and system
settings.
Level 4: OEM, password given only in consultation with the
Flexit service organisation.
• All rights as for level 3, plus:
• Rights to all menus and system settings.
Start page > Main menu > Log in
2.2.4.
Set time/time channels
Start page > Quick menu > Timing program
ParameterFunction
Date and TimeThis is where you set the time and date
Continuous operation This is where you can override the
timing programs and switch the unit to
continuous operation
Current valueDisplays the current timing
(temperature and speed)
Monday to SundaySee explanation of week schedule
(2.2.4.2)
2.2.4.1.
Set the calendar and timing program
General
This section describes functions and settings for the timing
program and calendars.
When no object with higher priority (for example Manual
control <> Auto) is activated, the system can be switched off
or the steps changed via the timing program. A maximum of
six switch-over times can be specified per day.
The calendar stop overrides the calendar exception, which in
turn overrides the normal timing program (only in operating
mode). Up to 10 periods or exception days can be specified
for each calendar.
NB! Both setpoints for fan steps and temperature setpoints
(comfort /economy) are controlled by the timing program.
2.2.4.2.
ParameterValueFunction
Current value---Switching according to schedule
MondayShows current command when the
Copy schedule
TuesdaySame function as for Monday
......
SundaySame function as for Monday
ExceptionShows current command when the
Period: Start
Period: Start
Period: End
Period: Start
Week schedule
–Mon to
–Tu– Fr
–Tu– Su
current day is Monday. The latest
time that can be entered for a day
is 23:59. Go to the day switching
schedule for Mondays
Copies times for the timing
program from Monday to
Tuesday–Friday/Tuesday–Sunday.
– Passive (no copying).
– Copying starts. Return to the
display screen
current day is an exception day.
Go to the day switching schedule
for exception days
(Only Authority level 3.)
Start date for week schedule.
*,* *.00 means that the week
schedule is always activated. --->
Activate week schedule
(Only Authority level 3.)
Start date and start time for
deactivating week schedule
2.2.4.3.
Parameter ValueFunction
Current
value
Day
schedule
Time-1 Special case: This time must not
Value-1Switching command for Time-1
Time-2Switching time 2
Value-2 ...
Value-6
Time-3 ...
Time-6
Dayschedule
---Switching according to the
schedule when the current
weekday is the same as the
switching day
Status for current week or
exception day:
– Passive
– Active
– Current weekday (system day) is
not the same as the switching day.
– Current weekday (system day) is
the same as the switching day
be changed, and must always be
00:00
*: * ---> Time deactivated
Analogue value 1
Analogue time 2
10
Page 11
2.2.4.4.
Kalender (undantag och stopp)
Exception days can be defined in the calendar. These can
include specific days, periods or weekdays. Exception days
override the weekly schedule.
EXAMPLE: Val-x = Date
Only the time for (start) is relevant.
• -(Start)Date = *,01.01.16
Calendar exceptions
Switching follows the weekly schedule and the exceptions
specified in the day schedule when a switching time is
activated in the calendar exception.
Calendar stop
The system is turned off when the calendar stop is activated.
Parameters:
Start page > Main Menu > Unit > Operating
information > Timing program > Calendar exceptions
Start page > Main Menu > Unit > Operating
information > Timing program > Calendar stops
ParameterValueFunction
Current
value
– Passive
– Active
Val-x
– Date
– Interval
– Weekday
– Passive
-(Start)Date– Val-x = interval: Enter the start
-End dateVal-x = interval:
-WeekdayVal-x = only weekdays: Enter
Shows whether a calendar time
is activated:
– No calendar time activated
– Calendar time activated
Specification of exception type:
– A certain day (e.g. Friday)
– A period (e.g. holiday)
– A certain weekday
– Times are deactivated
This value must always be placed
last, after the date
date for the period
– (Val-x = date: Enter specific
date)
Enter the end date for the period
The end date must be later than
the start date
a weekday
Result: 1 January 2016 is an exception date.
• -(Start)Date = Mo,*.*.00
Every Monday is an exception day
• -(Start)Date = *,*.Even.00
All days in even months (February, April, June, August, etc.)
are exception days.
EXAMPLE: Val-1 = Interval
The times for (Start)Date and End date are adjusted.
• -(Start)Date = *,23.06.16 / -End date = *,12.07.16.
23 June 2016 until end of 12 July 2016 are exception days
(for example holidays).
• -(Start)Date = *,23.12.16 / -End date = *,31.12.16
23–31 December are exception days every year. Time End
date = *,01.01.16 will not work because 1 January comes
before 23 December.
• -(Start)Date = *,23.12.16 / -End date = *,01.01.17.
23 December 2016 up to and including 1 January 2017 are
exception days.
• -(Start)Date = *,*.*.17 / -End date = *,*.*.17
Warning! This means that the exception is always active!
The system is constantly in exception mode or turned off.
EXAMPLE: Val-1 = Weekday
Val-1 = Weekday
The times for weekdays are adjusted.
• Weekday = *,Fr,*
Every Friday is an exception day.
• Weekday = *,Fr,Even
Every Friday in even months (February, April, June, August,
etc.) is an exception day.
• Weekday = *,*,*
Warning! This means that the exception is always active!
The system is constantly in exception mode or turned off.
11
Page 12
2.3. Adjust the setpoints for speeds and
temperatures
Start page > Quick menu > Setpoints/Settings
ParameterFunction
All settings>
Timing program>
Setp.comf.heatIndicates the temperature setpoint
Setp.econ.heatIndicates the temperature setpoint
Setp.TF step 1Indicates the supply air flow
Setp.TF step 2Indicates the supply air flow
Setp.TF step 3Indicates the supply air flow
Setp.FF step 1Indicates the extract air flow
Setp.FF step 2Indicates the extract air flow
To adjust supply air temperature limits with extract air regulation.
Start page > Quick menu > Setpoints/Settings
ParameterFunction
Setpoint, min. supply
air temp.
Setpoint, max. supply
air temp.
Indicates the lowest permitted supply air
temperature
Indicates the highest permitted supply
air temperature
2.6. Change the unit for the flow display
Toggles between m3/h and l/s in the air flow rate display.
Start page > Main menu > Configuration >
Configuration 2 > Flow display
Setp.FF step 3Indicates the extract air flow
2.4. Service switch
The service switch is used to stop the unit for service.
Start page > SERVICE SWITCH
ParameterFunction
AutoThe unit is controlled via time channel
OffService mode, unit stopped
2.5. Extract air regulation
The unit is configured by default to regulate temperature via
the supply air. However, it can be reconfigured to regulate
via the extract air. To do this, go to the following menu:
Start page > Main menu > Configuration >
Configuration 1 > Temperature regulation type
ParameterFunction
Supply airTemperature regulation is controlled by
the supply air temperature
Extract airTemperature regulation is controlled by
the extract air temperature
After making a change in a configuration menu, a restart is
required.
ParameterFunction
NoNot used.
l/sDisplays flow in l/s
3
/hDisplays flow in m3/h
m
After making a change in a configuration menu, a restart is
required.
Start page > Main menu > Configuration >
Configuration 2 > Restart > Execute
RESTART
2.7. Alarm handling
If an alarm has been triggered, it will be shown by the flashing
alarm symbol. You can get more information by pressing the
alarm button. To reset the alarm, press the alarm button twice
and select Confirm/Reset and then Execute in the menu.
Alternatively, the alarm can be reset with the menu option:
Start page > Main menu > Alarm management >
Alarm reset > Execute
Start page > Main menu > Configuration >
Configuration 1 > Restart > Execute
RESTART
12
Page 13
3. Menu tree
Logging in gives you access to several menu options.
The menu tree reflects the default configuration.
It may be different in other configurations.
Level 1
•
Start page
• Quick menu
• Main menu
• Operating information
• SERVICE
SWITCH
Operating mode
Outdoor temperature
Supply air temp.
Extract air temp.
Number of unused XINumber of unused DINumber of unused AONumber of unused DO
Set IO to
• Line test/Auto
Save/Cancel
Overview, outputs
Analogue outputs
• Supply air fan
• Extract air fan
• Recovery
Digital outputs
• Supply air fan
• Extract air fan
• Outdoor air damper
• Exhaust air damper
• Alarm output 1
Inputs
+Temperatures
• Extract air
• Supply air
• Outside
+Pressure/Flows
• Supply air flow
• Extract air flow
• Supply air filter
• Extract air filter
+Digital alarm
• Supply air fan
• Extract air fan
• Recovery alarm
• Digital inputs
Integrations
• +Room unit
• Settings
• Inputs
• +Energy meter EM24
• Settings
• Inputs
• Flexit MB units
• Settings
• Restart
24
Page 25
4. Backup and program updates
When the system has been fully configured and the
parameters have been set, it can be backed up to an SD
memory card or reset using the data on the memory card.
Two different sets of parameters for a configured system
can be backed up or reset. For example, you can back up
the standard settings (Save factory settings) and adjusted
settings (Save startup settings).
The options below can be selected only with the relevant
authority level. This is done using menu option:
Start page > Main menu > System overview >
Save/Reset
4.2. Load a configuration
Procedure:
1. Insert the memory card into the regulator.
2. Load the values from the memory card.
Start page > Main menu > System overview >
Save/Reset > Load param. <-S = Execute
3. Wait until:
Start page > Main menu > System overview >
Save/Reset > Load param. done = Yes
4. Restart the process unit:
The regulator has a card slot for an SD memory card with
max 2 GB capacity.
4.1. Save a configuration
After initiation and adjustment, the parameters and
configurations can be saved to the SD card. For example,
you can load these values on another process unit with the
same basic configuration (operating system, application,
control panel, HMI4Web and language/communication).
Authority level 4 is required.
Location of SD
memory card
Start page > Main menu > System overview >
Save/Reset > Restart = Execute
RESTART
Standard settings (Factory settings) and adjusted settings
(Startup settings) are handled in the same way.
4.3. Loan an application or software
Preconditions:
• The (uncompressed) files must be in the root folder of
the SD memory card.
• The files must have the names shown in the screen below.
Files on SD card
Procedure
1. Insert a blank SD memory card into the regulator.
2. Backup the values to the memory card.
Start page > Main menu > System overview >
Save/Reset > Save param.->SD = Execute
3. Wait until:
Start page > Main menu > System overview >
Save/Reset > Save param. done = Yes
Standard settings (Factory settings) and adjusted settings
(Startup settings) are handled in the same way.
Procedure
1. Insert the memory card into the regulator.
2. Switch off the regulator.
3. Press the button in the hole next to the regulator's
status screen with a thin object so that a clicking sound
is heard, and keep the button pressed down.
4. Switch on the regulator.
5. Wait until the LED flashes red and green.
6. Release the button.
7. Wait until orange LED lights up.
8. Switch off the regulator.
9. Switch on the regulator.
25
Page 26
4.4. Error diagnosis - Snapshot
For troubleshooting, the status of the ventilation unit just
before the alarm was triggered can be studied afterwards by
means of export to an SD card. Authority level 4 is required.
Procedure:
1. Insert a blank SD memory card into the regulator.
2. Backup the error diagnosis to the memory card.
5. General functions
Operating modes - Change
The system can be put in different operating modes.
Start page > Main menu > Unit >
Operating functions > Continuous operation
Start page > Main menu > System overview >
Save/Reset > Save snapshot = Execute
3. Wait until:
Start page > Main menu > System overview >
Save/Reset > Save snapshot = Yes
A file has now been generated on the SD card that can be
read from a PC.
Continuous Operation
NoThe unit operates in timer mode
Econ.St1The unit operates at ‘Econ’ temperature and
‘Step 1’ speed
Comf.St1The unit operates at ‘Comf’ temperature and
‘Step 1’ speed
Econ.St2The unit operates at ‘Econ’ temperature and
‘Step 2’ speed
Comf.St2The unit operates at ‘Comf’ temperature and
‘Step 2’ speed
Econ.St3The unit operates at ‘Econ’ temperature and
‘Step 3’ speed
Comf.St3The unit operates at ‘Comf’ temperature and
‘Step 3’ speed
26
Page 27
6. Configuration
On delivery, the ventilation unit is configured and ready.
Normally, therefore, no adjustments need to be made to the configuration.
However, the addition of accessories and other equipment may require a change to the configuration.
Where necessary, there is a more detailed description in this manual or with the accessory.
This section is, therefore, intended more as general information.
The configuration includes the following four steps:
• Activate and choose type of after heater on circuit board A3
• Configuration 1
• Configuration 2
• Configuration with inputs and outputs
6.1. Configuration 1
If adjustments are needed, ‘Configuration 1’ is the first step in the configuration.
• Configuration is done sequentially, which means that it is not possible to skip any options.
• Configuration 1 must have been completed and the process unit have been restarted before you continue with Configuration 2.
Start:
If necessary: Enter the password for level 3:
Start page > Log in
Then:
Start page > Main menu > Configuration >
Configuration 1
After making a change in a configuration menu, a restart is required.
Start page > Main menu > Configuration >
Configuration 1 > Restart > Execute
NB! The ventilation unit is supplied fully configured
RESTART
ParameterValueFunction
General comment:
Expansion modulesNoOnly the process unit's inputs and outputs are used.
OneOne expansion module is connected via address 1. Dipswitches 5 and 6 on the module must be set
to On.
TwoTwo expansion modules are connected via addresses 1 and 2. Dipswitch 5 on module 1 and
dipswitches 4 and 6 on module 2 must be set to On.
Fire alarmNoNo fire alarm.
AlarmExternal fire alarm such as smoke detectors, thermostat, fire alarm control centre, etc.
TempInternal fire alarm via measurement of normal supply air and extract air temperature when both sensors
are accessible. A fire alarm is triggered when one of the two temperatures reaches a specific value.
Alarm+TempBoth fire alarms.
and does not normally need to be changed.
27
Page 28
ParameterValueFunction
Filter alarmNoNo filter alarm.
Comb.Supply air and extract air filter with common alarm input.
Supply airInput only for supply air filter alarm.
Extract airInput only for extract air filter alarm.
Supply+Extract
Filter alarm,
analogue
Emergency stopNoInput for emergency stop. If the signal on this input is TRUE, the system is switched off
Alarm reset inputNoInput for acknowledging or resetting an alarm. Open alarms are acknowledged; closed alarms are
SuWi inputNoInput for summer/winter switching. If the signal on this input is TRUE, summer compensation is
NoNo filter alarm.
Supply airAnalogue input only for supply air filter alarm.
Extract airAnalogue input only for extract air filter alarm.
Supply+Extract
Yes
Yes
Yes
No heatingNo heating in the summer.
No cooling.No cooling in the winter.
Two separate filter alarm inputs for supply air and extract air filters.
Two separate filter inputs for supply air and extract air filters.
immediately. No alarm is triggered.
reset.
selected.
Timing program
function
Timing program
step
External control
input
Buzzer alarm
output
Sensor:
BothNo heating in the summer and no cooling in the winter.
NoNo timing program.
StepTiming program with possible settings for fan steps (Off and Stx). The parameter Timing program
step determines the number of possible steps.
Step+TempTiming program with possible settings for fan steps and temperature regulation type (Off, Econ.x
and Comf.x). The parameter Timing program step determines the number of possible steps.
The temperature mode comfort or economy can be selected for each fan step. Comfort and
economy operation have separate setpoints for temperature regulation.
Activation of possible fan steps. This setting controls the number of setpoints for regulated fans.
1 Step Timing program function = Step ---> Possible settings for timing program: Off, St1.
Timing program function = Step+Temp ---> Possible settings for timing program: Off, Econ1, Comf1.
2 StepTiming program function = Step ---> Possible settings for timing program: Off, St1, St2.
Timing program function = Step+Temp ---> Possible settings for timing program: Off, Econ1,
Econ2, Comf1, Comf2.
3 StepTiming program function = Step ---> Possible settings for timing program: Off, St1, St2, St3.
Timing program function = Step+Temp ---> Possible settings for timing program: Off, Econ1,
Econ2, Econ3, Comf1, Comf2, Comf3.
NoNo external input for operating mode switching, timer, button, detector for external control, etc.
OneOne input (e.g. on/off).
TwoTwo inputs (e.g. Auto/Off/St1/St2).
NoNo alarm output.
OneOne output (for example for priority alarms).
TwoTwo outputs (for priority and non-priority alarms).
Sensor 1Inputs for room temperature sensors. Select max., min., average or individual value for regulation
Sensor 2
Unit 1
Unit 2
for one or more sensors in Configuration 2.
28
Page 29
ParameterValueFunction
Extract air temp.
sensor
Supply air temp.
sensor
Outdoor temp.
sensor
Functions:
DamperNoNo air damper.
Extract air fanExtract air fan (supply air fan is always available and cannot be deactivated).
Fan regulation typeDirectUp to three digital outputs each for direct-drive fans.
Temp. regulation
type
NoInput for extract air sensor.
Yes
Yes+MaxIf the system has been in operation for more than 5 minutes, the max. temperature is saved when
it is switched off; otherwise the actual temperature is saved.
The setting is meaningful only if there is no room sensor and nighttime operation (for example
nighttime cooling) without a temperature test is to be used. This setting should not be used with
support operation. (Temperature test: the system is started briefly to update the duct sensor
temperature.)
NoInput for supply air sensor.
Yes
NoInput for sensor for outdoor air temperature.
Yes
Yes+Min.If the system has been in operation for more than 5 minutes, the min. temperature is saved when
it is switched off; otherwise the actual temperature is saved.
The setting is meaningful only if a sensor is fitted in the duct and nighttime support operation
(for example nighttime cooling) is activated, or as a safety function for pump start at low outdoor
air temperatures.
Comb.Two air dampers with a common output.
OutsideOutdoor air damper, one output.
Outdoor+
Extract air
NoneNo extract air fan.
SeparateExtract air fan with separate output.
Comb.Extract air and supply air fans with common output.
Dir.froUp to three digital outputs each for frequency-regulated fans with fixed steps.
Fixed freq.One digital and analogue output each for frequency-regulated fans regulated via modulating
Pressure reg.One digital and analogue output and one analogue input each for frequency-regulated fans in
Flow reg.One digital and analogue output and one analogue input each for frequency-regulated fans
Supply air fan
slave
Extract air
fan slave
Select the regulation algorithm for temperature regulation.
Supply airTemperature regulation of supply air only.
Room casc.Cascade regulation of room and supply air temperature.
Extract air
casc.
Room SuWiCascade regulation of room and supply air temperature in summer; regulation of supply air
Extract air
SuWi
RoomRoom regulation only.
Extract airTemperature regulation of extract air only.
One digital and analogue output each and three analogue inputs for frequency-regulated fans in
pressure-regulated systems where the supply air fan is driven depending on the extract air fan.
One digital and analogue output each and three analogue inputs for frequency-regulated fans in
pressure-regulated systems where the extract air fan is driven depending on the supply air fan.
Cascade regulation of extract and supply air temperature.
temperature only in winter.
Cascade regulation of extract and supply air temperature in summer; regulation of supply air
temperature only in winter.
29
Page 30
ParameterValueFunction
Mixing damperHeat recovery regulation with mixing damper.
NoNo mixing damper.
NormalMixing damper with output signal 100% for full circulation.
InvertedMixing damper with output signal 0% for full circulation.
Heat recoverySelect heat recovery regulation with rotating heat exchanger, plate heat exchanger or water heat exchanger.
NoNo heat recovery.
RotorRotating heat exchanger. One analogue output for regulation of rotating heat exchanger.
PlatePlate heat exchanger. One analogue output for regulation of regulating air damper.
WaterWater heat exchanger. One analogue output for regulation of the valve.
RotorInvRotating heat exchanger. One analogue output for regulation of rotating heat exchanger.
Inverted output signal 100% force = 0 V.
PlateInvPlate heat exchanger. One analogue output for regulation of regulating air damper.
Inverted output signal 100% force = 0 V.
WaterInvWater heat exchanger. One analogue output for regulation of the valve.
Inverted output signal 100% force = 0 V.
HeatingNoNo heating circuit.
YesHeating register without preheating. Analogue heating valve output.
Yes+Preh.
Outdoor temp.
Yes+Preh.Frost
protection
temp.
Electric heatingElectric heating register and type of regulation.
NoNo electric heating register available.
AnalogueElectric heating register with regulation via one analogue output.
1Step1-step electric heating register with regulation via one analogue and one digital output.
2Step2-step electric heating register with regulation via one analogue and two digital outputs.
3stegBin3-step electric heating register with binary regulation via one analogue and two digital outputs.
3step3RelExtra 3-step electric heating register with 3 digital outputs.
CoolingSelect cooling register and type of regulation.
NoNo cooling register.
WaterOne analogue output for cooling valve output.
DX 1stepOne analogue and one digital output for 1-step regulation of DX cooling unit.
DX 2stepOne analogue and two digital outputs for 2-step regulation of DX cooling unit.
DX 3stepOne analogue and two digital (binary) outputs for 3-step regulation of DX cooling unit.
Extra heatingNoNo extra heating register.
YesExtra heating register without preheating. Analogue heating valve output.
Yes+Preh.
Outdoor temp.
Yes+Preh.Frost
protection
temp.
Heating register with preheating. Analogue heating valve output.
Heating register with preheating based on frost protection temperature.
Extra heating register with preheating. Analogue heating valve output.
Heating register with preheating based on frost protection temperature.
30
Page 31
ParameterValueFunction
Extra electric
heating
Extra coolingExtra cooling register and type of regulation.
Fire damperFire damper.
Fire fanNoFire fan control deactivated.
External setpointNoNo analogue input for connection of external setpoint or compensation for external setpoint.
Configuration 1With this parameter, the system is activated after parameter settings have been set, i.e. when Configuration 1,
Restart
Extra electric heating register and type of regulation.
NoNo extra electric heating register available.
AnalogueExtra electric heating register with regulation via one analogue output.
1StepExtra 1-step electric heating register with regulation via one analogue and one digital output.
2StepExtra 2-step electric heating register with regulation via one analogue and two digital outputs.
3stepBinExtra 3-step electric heating register with binary regulation via one analogue and two digital outputs.
NoNo extra cooling register.
WaterOne analogue output for extra cooling valve output.
DX 1stepOne analogue and one digital output for 1-step regulation of extra DX cooling unit.
DX 2stepOne analogue and two digital outputs for 2-step regulation of extra DX cooling unit.
DX 3stepOne analogue and two digital (binary) outputs for 3-step regulation of extra DX cooling unit.
NoNo fire damper.
YesOne digital output and input each for fire damper regulation.
Yes+FollUnitOne digital output and input each for fire damper regulation. The fire damper is opened when the
unit starts and closed when the unit stops.
2Same as ‘Yes’ but with 2 fire dampers.
2+FollUnitSame as ‘Yes+FollUnit’ but with 2 fire dampers.
3Same as ‘Yes’ but with 3 fire dampers.
3+FollUnitSame as ‘Yes+FollUnit’ but with 3 fire dampers.
4Same as ‘Yes’ but with 4 fire dampers.
4+FollUnitSame as ‘Yes+FollUnit’ but with 4 fire dampers.
YesFire fan control activated.
VoltInput for 0-10 V DC signal.
OhmInput for 0-2500 ohm signal.
QAA27Input for QAA27.
BSG21Input for BSG21 setpoint compensation.
Configuration 2 and Config. Inputs/Outputs have been set (value Ready).
Not readyThe system is locked and cannot be started.
ReadyThe system is unlocked after the parameter settings have been set (value Ready for Configuration
2 and Config.In/Outputs), i.e. the system can be started.
Passive
Execute
The system must be restarted after parameter settings have been set in Configuration 1.
Changed presets in Configuration 2 are implemented.
After restart, the value is changed automatically from Execute to Passive.
31
Page 32
6.2. Configuration 2
If there is a need for adjustments, subfunctions for some parts of the system can be set in Configuration 2.
Preconditions:
Configuration 1 must have been completed, including restart of the regulator.
• Configuration is done sequentially, which means that it is not possible to skip any options.
• Configuration 2 must have been completed, including restart of the process unit, before you continue with Config.In/Outputs.
Start
If necessary: Enter the password for level 3:
Start page > Log in
Then:
NB! The ventilation unit is supplied fully configured
Main menu > Configuration > Configuration 2
ParameterValue Function
Nighttime cooling
Support operationStarts nighttime support operation.
BoostOptimum start of the system with heating and cooling via separate setpoints.
Support operation/
Osstp block
Damper return
NoThe function is not available.
YesFree cooling.
Precondition: Nighttime cooling can be selected only if a sensor for outdoor air temperature and
a room or extract air sensor are available.
Temperature motion is activated automatically if only one extract air sensor, which is set to not
hold the values, is available. If the extract air sensor holds the values, the temperature is used to
start nighttime cooling.
Precondition: The function can be selected only if a room or extract air sensor is available.
Temperature motion is activated automatically if only one extract air sensor which holds the values is available.
If the extract air sensor holds the values, the temperature is used for start.
NoThe function is not available.
HeatingThe function is available only for heating.
CoolingThe function is available only for cooling.
HeatingCooling
NoThe function is not available.
HeatingThe function is available only for heating.
CoolingThe function is available only for cooling.
HeatingCooling
NoneNo blocking.
DamperAir dampers remain closed.
Dam+FanAir dampers remain closed and only the supply air fan is started.
NoNo damper return.
OneReturn for supply air damper (or common return for both dampers). Digital input for return.
TwoSeparate return for supply air and extract air dampers. Two digital inputs for return.
The function is available for heating and cooling.
Precondition: The function can be selected only if a room or extract air sensor is available.
The function is available for heating and cooling.
Block the air damper or extract air fan when the system is started optimally or via temperature delta.
NB! This function is intended to be used in an emergency situation.
Warning! A regulating air damper must be in place and be open when the function is selected.
Otherwise, the system may suffer damage.
and does not normally need to be changed.
32
Page 33
ParameterValue Function
Dig.step freq.con.1 stepDigital output for activation of frequency-controlled fans (always activated).
2 stepAn extra digital output for alternative connection that is dependent on fan step 2.
3 stepTwo extra digital outputs for alternative connection that is dependent on fan step 3.
Flow displayNoThe function is not available.
l/sDisplays flow in litre/second.
3
/hDisplays flow in m3/hour.
m
Fan step typeNecessary fan regulation output that concerns settings for Fan regulation type, Timing program step and Dig.step
freq.conv.
SeparateDigital output for each step.
Example:
Fan regulation type = Direct / Timing program step = 2 / Extract air fan = Yes
---> 4 digital outputs: 2 each for step 1 and step 2, separated for supply air and extract air fans.
Sep.Comb.Separate outputs for the first step, common outputs for subsequent steps.
Example:
Fan regulation type = Pressure reg. / Timing program function = Step+Temp / Timing program step = 3 /
Extract air fan = Yes / Dig.step freq.conv = 3.
---> 4 digital outputs: Step 1 as separate activation of frequency-regulated fans, two extra
outputs that can be used (Dig.step freq.conv) for step 2 and step 3.
BinaryThe outputs for steps are binarily coded. The setting can be used for Fan regulation type = Direct
or Dir.fro.
Example:
Fan regulation type = Direct / Timing program function = Step+Temp / Timing program step = 3 /
Extract air fan = Yes
---> 4 digital outputs: 2 digital outputs each per fan (Step 1 = DO1 TRUE, Step 2 = DO2 TRUE,
Step 3 = DO1 and DO2 TRUE).
Fan alarmInputs for fan alarm (e.g. thermojunction). Logical 1 = alarm.
NoNo alarm.
Comb.Digital input for common alarm.
Supply airDigital input for supply air fan alarm.
Extract airDigital input for extract air fan alarm.
Supply+Extract Two digital inputs for supply air and extract air fan alarms.
Fan returnInputs for operating messages from fans (e.g. pressure current guard or relay contact). Logical 1 = activated fan.
NoNo return.
Comb.Digital input for common operating messages.
Supply airDigital input for operating messages for supply air fan.
Extract airDigital input for operating messages for extract air fan.
Supply+Extract Two digital inputs for operating messages for supply air and extract air fans.
Fan deviation alarmSetpoint or actual value for monitoring pressure or flow. The alarm is triggered in the event of a deviation that
remains for a certain period of time.
NoNo monitoring.
Supply airMonitoring of supply air only.
Extract airMonitoring of extract air only.
Supply+Extract Monitoring of supply and extract air.
Room temp. fan
comp.
Air qual. fan comp.
NoRoom temperature-dependent fan compensation.
Yes
Precondition: Room or extract air sensor activated.
NoAir quality-dependent fan compensation. Activation of analogue sensor input.
Yes
33
Page 34
ParameterValue Function
Outdoor temp. fan
comp.
Fan heating/coolingThe fan is used as heating or cooling sequence.
Ext. Setpoint, fanNoFunction deactivated.
Ext. setpoint
function SF
Ext. setpoint
function EF
Temp. setpoint typePredefined settings for temperature setpoints:
Temp. deviation
alarm
Summer/Winter
comp. temp.
Recovery frost
protection
Pump/command,
recovery
NoOutdoor air temperature-dependent fan compensation.
Yes
NoNo sequential fan activation.
HeatingFan activation only in connection with heating sequence.
CoolingFan activation only in connection with cooling sequence.
HeatingCooling
SFThe supply air fan is regulated via an external setpoint.
EFThe extract air fan is regulated via an external setpoint.
SF + EFBoth the supply air and extract air fans are regulated via an external setpoint.
Comp.Setpoint compensation.
MainMain setpoint.
Comp.Setpoint compensation.
MainMain setpoint.
Heating+DzEnter heating setpoint and dead zone. Setpoint for cooling = heating setpoint + dead zone.
HeatingCooling
Setpoint+
HalfDz
Cooling DzEnter setpoint for cooling and dead zone.
Monitors setpoint/current value for temperature.
The alarm is triggered in the event of a deviation that remains for a certain period of time.
NoNo monitoring
Supply airMonitoring of supply air only.
Room/Extract
air
Supply+Room Monitoring of supply air and room temperature.
NoSummer/winter compensation of temperature setpoint.
Yes
NoNo frost protection for heat recovery.
Guard Frost protection via guard. Digital input for frost guard.
Temp.Frost protection via sensor. One analogue input for regulated frost protection via setpoint.
Temp+GuardFrost protection via sensor and guard. One analogue input for regulated frost protection and one
PressureFrost protection via pressure sensor. One analogue input for regulated frost protection via setpoint.
Pressure+
Guard
NoNo pump.
YesPump without.
Yes+MotionThe extract air fan is regulated via an external setpoint.
Precondition: Outdoor air sensor activated.
Fan activation in connection with both sequences.
Setpoints for heating and cooling are entered directly.
Enter base setpoint and dead zone.
Heating setpoint = base setpoint – half dead zone.
Setpoint for cooling = base setpoint + half dead zone.
Heating setpoint = setpoint for cooling – dead zone.
Room and extract air temperature.
Precondition: Sensor for outdoor air temperature must be available.
Rotating heat exchanger and plate heat exchanger: extract air sensor, water heat exchanger:
water sensor.
digital input for frost guard.
Frost protection via pressure sensor and guard. One analogue input for regulated frost
protection and one digital input for frost guard.
34
Page 35
ParameterValue Function
Recovery alarmNoNo alarm.
AlarmAlarm: activation of one digital alarm input: Logical 1 = alarm.
Return.Return signal. A digital input for return. Pulse in connection with operation.
Alarm+Return Pump with alarm and return. Two digital inputs for pump alarm and return.
Cold recoveryType of cold recovery.
NoNo cold recovery.
TempCooling recovery via difference between outdoor and indoor temperatures.
Outdoor
enthalpy
Recovery efficiencyCalculation of heat recovery efficiency.
Precondition: Heat recovery (e.g. rotating heat exchanger) must be activated and there must be a sensor for
both outdoor air temperature and extract air.
NoNo calculation of heat recovery efficiency.
Exhaust airFor calculation with extract air sensor:
Supply airFor calculation with the supply air sensor located immediately behind the heat exchanger:
Aux. input
Aux. temp. sensor
Aux. timing program
Aux. output signalNoNo extra analogue output.
Aux. operating mode
input
Configuration 2With this parameter, the system is activated after parameter settings have been set, i.e. when Configuration 1,
RestartExecute
NoNo aux input.
InputExtra digital input for display only.
AlarmExtra digital input with alarm.
Inp.+AlarmTwo extra digital inputs; one for display and one with alarm.
NoNo extra analogue input.
YesExtra analogue input for connection of temperature display.
NoNo extra digital output.
YesOne digital aux. output with separate timing program.
FanAnalogue output that generates a 0-10 V signal, depending on current fan step.
Flow deviceAnalogue output that generates a 0-10 V signal, depending on temperature.
NoNo extra digital output.
YesAn extra digital output, the status of which depends on the current operating mode (e.g. Comfort
Configuration 2 and Config. Inputs/Outputs have been set (value Ready).
ReadyThe system is unlocked after the parameter settings have been set (value Ready for
Not readyThe system is locked and cannot be started.
Passive
Cooling recovery via difference between outdoor and indoor enthalpies.
One analogue input for the extract air sensor unless the frost guard has been activated.
One analogue input for extra supply air sensor.
or Off).
Configuration 2 and Config.In/Outputs), i.e. the system can be started.
The system must be restarted after parameter settings have been set in Configuration 2.
Changed presets in Config. Inputs/Outputs are applied.
After restart, the value is changed automatically from Execute to Passive.
35
Page 36
6.3. Configuration of inputs and outputs
If there is a need for adjustments, subfunctions for some parts
of the system can be set in Configuration 1, Configuration 2
and Configuration of inputs and outputs.
In Config.In/Outputs, a physical location is assigned to the inputs
and outputs specified in Configuration 1 and Configuration 2.
Parameter settings are also set for the relevant sensor
conversion (e.g. Ni1000, Pt1000, 0-10 V = 0-1,000 Pa).
Positions in regulator and expansion modules
•
Regulator: All single-digit positions, for example X1.
• Modbus extender: xxxxx
• Expansion module 1: All positions X1x, DI1x, DO1x, AO1x,
for example X11, DO14.
• Expansion module 2: All positions X2x, DI2x, DO2x, AO2x,
for example X21, DO24.
Preconditions
Configuration 1 and Configuration 2 must be ready (the process
unit must be restarted after each configuration).
Start
If necessary: Enter the password for level 3:
NB! The ventilation unit is supplied fully configured
and does not normally need to be changed.
Start page > Log in
Then:
Start page > Main menu > Configuration >
Config. lnputs/Outputs
ParameterValue Function
TemperaturesGo to the hardware configuration page for all temperature sensors.
Pressure/FlowsGo to the hardware configuration page for all pressure and flow sensors.
Digital inputsGo to the hardware configuration page for all digital inputs without alarm function.
Digital alarmGo to the hardware configuration page for all digital inputs with alarm function.
Damper outputsGo to the hardware configuration page for supply air, extract air and fire dampers.
Fan outputsGo to the hardware configuration page for fans.
Temp. control outputs
Alarm outputsGo to the hardware configuration page for both alarm outputs.
Config. lnputs/
Outputs
RestartPassive
Activation of the system after parameter settings have been set, i.e. when Configuration 1, Configuration 2 and
Config. Inputs/Outputs have been set (value Ready).
ReadyThe system is unlocked after the parameter settings have been set and can be started.
Not readyThe system is locked and cannot be started.
Execute
Go to the hardware configuration page for heating, cooling, heat recovery, etc.
The system must be restarted after parameter settings have been set in Config. Inputs/Outputs.
Changed presets in Config.In/Outputs are implemented. After restart, the value is automatically
changed back.
NB! The inputs and outputs in the expansion
modules can be used if the module has been
activated in Configuration 1.
36
Page 37
7. Cooling
21 22 23
DX cooling one step or liquid
The unit is equipped by default to control liquid cooling or
one DX step. If another two steps are required, expansion
module SP90 must be installed. Cooling control according
to the following instructions.
7.1. Installation
7.3. For activation of circulation pump
(only applies to liquid cooling)
Start page > Main menu > Configuration >
Configuration 2 > Pump/cooling
Now use the control panel to configure the unit for DX
cooling control or liquid.
Start page > Main menu > Configuration >
Configuration 1 > Cooling
YesPump control activated
Yes + MotionPump control activated +
maintenance operation
To perform parameter settings, use the menus below via the
control panel.
7.4. Blocking in connection with outdoor
temperature
Start page > Main menu > Unit > Temperature regulation >
Cooling > Block in connection with outdoor temperature
ParameterFunction
-64.0 to 64.0Indicates the lowest permitted outdoor
temperature for cooling operation
7.5. Operating times (only applies to
DX cooling)
Start page > Main menu > Unit >
Temperature regulation > Cooling >
Direct expansion > Min. operating time
ParameterFunction
NoCooling control deactivated
WaterCooling control via liquid battery
DX 1stepCooling control via DX machine, one step
DX 2stepCooling control via DX machine, two
steps, requires expansion module SP90
DX 3stepCooling control via DX machine, three
steps, requires expansion module SP90
After making a change in a configuration menu, a restart is
required.
Start page > Main menu > Configuration >
Configuration 1 > Restart > Execute
RESTART
ParameterFunction
0 to 3,600Indicates the minimum OPERATING TIME
of the DX machine after start
Start page > Main menu > Unit >
Temperature regulation > Cooling >
Direct expansion > Min. idle time
ParameterFunction
5 to 600Indicates the minimum IDLE TIME of the
DX machine after stop
37
Page 38
7.6. Cooling restriction depending on fan
speed (only applies to DX cooling)
8. Temperature regulation
Start page > Main menu > Unit > Temperature
regulation > Cooling > Max. signal, fan control
ParameterFunction
Fan step 1 > 0-100%Permitted DX cooling output signal when
the unit operates on step 1 or uses the
setpoint for step 1
Fan step 2 > 0-100%Permitted DX cooling output signal when
the unit operates on step 2 or uses the
setpoint for step 2
Fan step 3 > 0-100%Permitted DX cooling output signal when
the unit operates on step 3 or uses the
setpoint for step 3
> EXAMPLE OF COOLING RESTRICTION
Fan step 1 = 30% The automatic control limits the
cooling force to 30% at fan step 1.
Fan step 2 = 60%The automatic control limits the
cooling force to 60% at fan step 2.
Fan step 3 = 100%No cooling force restriction at fan
step 3.
8.1. Extract air regulation
The unit is configured by default to regulate temperature via
the supply air. However, it can be reconfigured to regulate
via the extract air. To do this, go to the following menu.
Start page > Main menu > Configuration >
Configuration 1 > Temperature regulation type
ParameterFunction
Supply airTemperature regulation is controlled by
the supply air temperature.
Extract airTemperature regulation is controlled by
the extract air temperature.
After making a change in a configuration menu, a restart is
required.
Start page > Main menu > Configuration >
Configuration 1 > Restart > Execute
RESTART
7.7. Setting of temperature setpoint
Start page > Quick menu > Setpoints/Settings
ParameterFunction
Setp.comf.coolingIndicates the temperature setpoint for
comfort operation
Setp.econ.coolingIndicates the temperature setpoint for
economy operation
8.2. To adjust supply air temperature limits
with extract air regulation.
Start page > Quick menu > Setpoints/Settings
ParameterFunction
Setpoint, min. supply
air temp.
Setpoint, max. supply
air temp.
Indicates the lowest permitted supply air
temperature
Indicates the highest permitted supply
air temperature
38
Page 39
9. Summer/winter compensation
Summer compensation:
Adjusts the fan/temperature setpoint (in relation to
regulation, supply air or extract air) in relation to regulation
for high outdoor air temperature in the summer.
9.3. Adjustment of temperature setpoint in
connection with high/low outdoor temperature
Start page > Main menu > Configuration >
Configuration 2 > SuWi comp.temp
Winter compensation:
Adjusts the fan/temperature setpoint (in relation to
regulation, supply air or extract air) in relation to regulation
for low outdoor air temperature in the winter.
9.1. Adjustment of fan setpoint in
connection with high/low outdoor temperature
Start page > Main menu > Configuration >
Configuration 2 > Fan comp., outdoor temp.
ParameterFunction
NoFunction deactivated
YesFunction activated
After making a change in a configuration menu, a restart is
required.
Start page > Main menu > Configuration >
Configuration 2 > Restart > Execute
RESTART
9.2. Parameter settings for fan compensation
Start page > Main menu > Unit > Fan control >
Summer/Winter compensation
ParameterFunction
Outdoor temperature
start
Outdoor temperature
finish
DeltaSetpoint offset in %.
Outdoor temperature when the
compensation is activated
Outdoor temperature when the highest
(summer) or lowest (winter) fan setpoint
is achieved
Example with flow regulation and summer
compensation:
Fan setpoint start = 500 l/s
Outdoor temperature start = 20 degrees
Outdoor temperature finish = 30 degrees
Delta = 20%
Fan setpoint finish (at 30 degrees) =
600 l/s
ParameterFunction
NoFunction deactivated
YesFunction activated
After making a change in a configuration menu, a restart is
required.
Start page > Main menu > Configuration >
Configuration 2 > Restart > Execute
RESTART
9.4. Parameter settings for temperature
compensation
Start page > Main menu > Unit >
Temperature regulation > Temperature setpoint >
Summer/Winter compensation
ParameterFunction
Outdoor temperature
start
Outdoor temperature
finish
DeltaSetpoint offset in degrees.
Outdoor temperature when the
compensation is activated
Outdoor temperature when the highest
(summer) or lowest (winter) fan setpoint
is achieved
Example with temperature regulation
and summer compensation:
Temperature setpoint start
(at 20 degrees) = 22 degrees
Outdoor temperature start = 20 degrees
Outdoor temperature finish = 30 degrees
Delta = -5 degrees
Temperature setpoint finish
(at 30 degrees) = 17 degrees
39
Page 40
9.5. Settings for switching between summer
34 3 23
and winter operation
Switches between extract air regulation in the summer and
supply air regulation in the winter.
Start page > Main menu > Configuration >
Configuration 1 > Temp. regulation type
ParameterFunction
Extract air SuWiExtract air regulation in summer and
supply air regulation in winter
Room SuWiRoom regulation in summer and supply
air regulation in winter. NB! Requires
room sensors
9.6. Switch between summer and winter
via signal
The function can be changed via three factors: physical input,
date or outdoor temperature.
If D1 is selected, the external speed control function must be
deactivated.
Physical input:
Start page > Main menu > Configuration >
Configuration 1 > SuWi input
ParameterFunction
NoFunction deactivated
YesSwitches between summer and winter
operation.
1 = Summer & 0 = Winter
No heatingYes + Heating deactivated in the summer
No cooling.Yes + Cooling deactivated in the winter
BothYes + Heating deactivated in the
summer & Cooling deactivated in the
winter
After making a change in a configuration menu, a restart is
required.
Start page > Main menu > Configuration >
Configuration 1 > Restart > Execute
Start page > Main menu > Configuration >
Configuration 1 > External control input > No
After making a change in a configuration menu, a restart is
required.
Start page > Main menu > Configuration >
Configuration 1 > Restart > Execute
RESTART
RESTART
A physical input must then be connected to the function.
There are various inputs to choose between, fire damper
return (fire damper is installed) and external speed control.
If the fire damper return is activated, the input for speed
control is used, and vice versa.
Start page > Main menu > Configuration >
Config. Inputs/Outputs > Digital inputs > SuWi input
40
Page 41
9.7. Switch between summer and winter via
date/outdoor temperature
Start page > Main menu > General functions >
Summer/winter mode
After making a change in a configuration menu, a restart is
required.
Start page > Main menu > Configuration >
Configuration 2 > Restart > Execute
ParameterFunction
StatusDisplay of current operating mode
Outdoor temperature
reduced
Date/Time, summerDate/time for switching to summer
Date/Time, winterDate/time for switching to winter
Time constantTime constant for calculation of Outdoor
Outdoor temp.
Summer
Outdoor temp. Winter Outdoor temperature for switching
Average outdoor air temperature over
given time constant
operation. If * is indicated instead of
date/time, switching is on Outdoor
temperature reduced
operation. If * is indicated instead of
date/time, switching is on Outdoor
temperature reduced
temperature reduced. Set to 0 for ten
seconds for reset of reduced outdoor
temperature. Set constantly to 0 for
switching on current outdoor temperature
Outdoor temperature for switching
to summer operation
to winter operation
RESTART
> EXAMPLE OF NIGHTTIME COOLING
Room setpoint = 22
Hysteresis = 2
Delta = 5
Min. outdoor air temp. = 10
Min. operating time = 30
When a temperature test is carried out, the room/extract air
is >24 degrees and the outdoor temperature is between 10
and 17 degrees.
The system starts and stops only when the room/extract air is
22 degrees and at least 30 minutes have passed since the start.
Configure as follows.
Start page > Main menu > Unit > Operating functions >
Nighttime operation temp. test
ParameterFunction
Motion timeTime of temperature test
9.8. Temperature test for nighttime operation
A temperature test starts the system after an extended
period of inactivity to update the duct sensor’s temperature.
This temperature is used as the criterion for starting
nighttime cooling or support operation and must always be
kept up to date.
The function is activated automatically when the following
conditions are met:
There is no room sensor:
Start page > Main menu > Configuration >
Configuration 1 > Room sensor temp. = No
Nighttime cooling or support operation is activated:
Start page > Main menu > Configuration >
Configuration 2 > Nighttime cooling > Yes
Or:
Start page > Main menu > Configuration >
Configuration 2 > Support operation > No
Interval timeHow often the temperature test is required
Pulse timeOperating time for temperature test.
NB! not shorter than 180 seconds
> EXAMPLE OF TEMPERATURE TEST
Motion time = 23:00
Interval time = 3
Pulse time = 300
The system is switched on for 300 seconds if it has been
switched off for at least three hours from 23:00
NB! Motion time = *:* and interval time = 0.0 =
No temperature test is carried out.
41
Page 42
9.9. Nighttime cooling
Configure as follows:
Start page > Main menu > Configuration >
Configuration 2 > Nighttime cooling
ParameterFunction
YesFunction activated
NoFunction deactivated
Start page > Main menu > Unit > Operating functions >
Nighttime cooling
ParameterFunction
Room setpointDisplays the current setpoint for room/
extract air
HysteresisHysteresis for power up (Power up =
Room setpoint + Hysteresis).
DeltaMinimum difference between room/
extract air and outdoor temperature
Min. outdoor temp.Lowest permitted outdoor temperature
to activate nighttime cooling
Min. operating timeShortest operating time in minutes after
start of nighttime cooling has been
activated
9.10. Support operation
Nighttime support operation prevents the building from
being heated or cooled too much. This is regulated via
a separate setpoint for heating and cooling.
9.10.1.
ParameterFunction
NoFunction deactivated
HeatingFunction activated for heating
CoolingFunction activated for cooling
HeatingCoolingThe function is activated for both
To activate the function
Start page > Main menu > Configuration >
Configuration 2 > Support operation
heating and cooling
After making a change in a configuration menu, a restart is
required.
Start page > Main menu > Configuration >
Configuration 2 > Restart > Execute
RESTART
9.10.2.
To configure the function
Start page > Main menu > Operating functions >
Support operation
ParameterFunction
Start coolingStart temperature for cooling, extract air >
Start cooling
Setpoint for coolingSupply air setpoint for activated support
operation cooling
Start heatingStart temperature for heating, extract
air > Start heating
Setpoint for coolingSupply air setpoint for activated support
operation cooling
HysteresisHysteresis for power down:
For cooling: Extract air < Start cooling Hysteresis
For heating: Extract air < Start heating +
Hysteresis
Min. restart time Shortest power down time after heating
or cooling has been activated
Min. operating timeShortest operating time after start
> EXAMPLE OF SUPPORT OPERATION COOLING
Start cooling = 25 degrees
Setpoint for cooling = 16 degrees
Hysteresis = 3 degrees
Min. restart time = 30 min.
Min. operating time = 15 min.
When a temperature test is carried out, the extract air is
26 degrees. The unit then switches to support operation
cooling and regulates the supply air to 16 degrees.
The system stops when the extract air has fallen to
22 degrees (Start cooling – Hysteresis), but no earlier
than after 15 minutes. Support operation starts again at
the earliest after 30 minutes after the last stop.
42
Page 43
10. Fan regulation
Now use the control panel to configure the unit for pressure
control.
10.1. Select method of regulation
10.1.1.
All fan regulation functions are selected under the menu option:
'Flow regulation' is selected by default.
10.1.1.1. Fixed frequency
Frequency-controlled fans controlled with fixed steps via
analogue outputs [%].
After making a change in a configuration menu, a restart is
required.
Selection fan regulation method
Start page > Main menu > Configuration >
Configuration 1 > Fan regulation type
NB! The options 'Direct' and 'Dir. fro' must not
be used!
Start page > Main menu > Configuration >
Configuration 1 > Restart > Execute
Start page > Main menu > Configuration >
Configuration 1 > Fan regulation type
ParameterFunction
Pressure reg.Requires 2 pressure sensors. The fans
are adjusted individually to their
respective setpoints
Supply air fan slave
Requires 1 pressure sensor for the extract
air fan. The supply air fan follows the extract
air fan with an adjustable slave offset
Extract air fan slave
Requires 1 pressure sensor for the supply
air fan. The extract air fan follows the supply
air fan with an adjustable slave offset
After making a change in a configuration menu, a restart is
required.
Start page > Main menu > Configuration >
Configuration 1 > Restart > Execute
RESTART
RESTART
Set parameters in the menu option:
Start page > Main menu > Unit > Setpoints/Settings
10.2. Pressure control
Before pressure control is selected, one or two pressure
sensors must be installed and connected to the unit.
If pressure sensors from Flexit are used, they must be
connected to P5 and P4. See the manual for the accessory.
If other makes are used, they must be connected to block
P12. See table.
Start page > Main menu > Configuration > Config.
Inputs/Outputs > Pressure/Flows > Supply air pressure
ParameterFunction
X6 500 PaX6 = Physical input (must not be
changed). 500 Pa = Max. set value of
connected pressure sensor.
Type 0-10 VType of signal. Must not be changed.
Start page > Main menu > Configuration > Config.
Inputs/Outputs > Pressure/Flows > Extract air pressure
ParameterFunction
X7 500 PaX7 = Physical input (must not be
changed). 500 Pa = Max. set value of
connected pressure sensor.
Type 0-10 VType of signal. Must not be changed.
43
Page 44
10.2.2.
43
4
Pressure setpoint adjustment.
If SF or EF is selected to operate as a slave, only three
setpoint steps are displayed.
Start page > Quick menu > Setpoints/Settings
ParameterFunction
Setp.TF step 1Supply air fan setpoint speed 1
Setp.TF step 2Supply air fan setpoint speed 2
Setp.TF step 3Supply air fan setpoint speed 3
Setp.FF step 1Extract air fan setpoint speed 1
Setp.FF step 2Extract air fan setpoint speed 2
Setp.FF step 3Extract air fan setpoint speed 3
If SF slave or EF slave is selected for the fan regulation type,
an offset must be set against which the fan selected is regulated.
The supply air/extract air fan is pressure-regulated. The
supply air/extract air flow is calculated and regulated against
the slave offset. See example.
Start page > Main menu > Unit >
Fan control > Slave offset
Explanation: The offset indicates the difference between the
master fan and the slave fan.
> EXAMPLE OF OFFSET
Example 1: If the offset is 0 l/s, the slave fan
operates with the same flow as the
master fan.
Example 2:If the offset is -100 l/s, the slave fan
operates with 100 l/s lower flow than
the master fan.
Example 3:If the offset is 100 l/s, the slave fan
operates with 100 l/s higher flow than
the master fan.
10.3. External fan setpoint
The fans can be controlled directly via an analogue 0-10 V
input on the automatic control. Min. and max. speeds/flows
are defined, which correspond to 0 V and 10 V on the input.
127
4
2
5
P6
3
6
123
P5
4
123
P4
4
P7
P14
P1P3 P2
1 2 3 4 5
1312
1 2 3 4 5 6 7 8 9
Block no.
40Earth signal G0
43Supply air fan 0-10 V
829310411
16
5623144155978
P8
10 11 12 13 14 15 16 17 18 19 20
Function
44Extract air fan 0-10 V
Activated via the following menu option:
Start page > Main menu > Configuration >
Configuration 2 > Ext. Setpoint, fan
ParameterFunction
NoNot activated
SFExternal control of supply air fan
EFExternal control of extract air fan
SF + EFExternal control of both supply air
and extract air fans
After making a change in a configuration menu, a restart is
required.
Start page > Main menu > Configuration >
Configuration 2 > Restart > Execute
1. Comp. A basic flow via step 1, 2 or 3 on which
the fan operates + comp.
2. Main. The fan is controlled only via the 0-10 V input
and steps 1, 2 and 3 are inactive.
Start page > Main menu > Configuration >
Configuration 2 > Ext. setpoint function SF/EF
After making a change in a configuration menu, a restart is
required.
Start page > Main menu > Configuration >
Config. Inputs > Restart > Execute
RESTART
ParameterFunction
Comp.Example of Comp.
Comp. is set to 0 V = 0 l/s and 10 V = 500 l/s
Step 1 is set to 100 l/s and the input
for the external setpoint is 0 V. The fan
operates at 100 l/s
Step 2 is set to 300 l/s and the input
for the external setpoint is 10 V. The fan
operates at 800 l/s
MainExample of Main.
Main is set to 0 V = 100 l/s and 10 V =
1,000 l/s
The input for the external setpoint is 0 V.
The fan operates at 100 l/s
The input for the external setpoint is 5 V.
The fan operates at 500 l/s
After making a change in a configuration menu, a restart is
required.
Start page > Main menu > Configuration >
Configuration 2 > Restart > Execute
RESTART
10.3.1.
Parameter settings for Comp.
Start page > Quick menu > Setpoints/Settings >
All settings > Fan control >
Supply air fan/Extract air fan
ParameterFunction
Current setpoint
supply air/extract air
Step 1Supply air/extract air fan setpoint speed 1
Step 2Supply air/extract air fan setpoint speed 2
Step 3Supply air/extract air fan setpoint speed 3
Ext. setpoint curve Y1Scaling of the 0-10 V signal,
Ext. setpoint curve Y2 Scaling of the 0-10 V signal,
External setpoint
SF/EF
Displays the current setpoint for the
supply air/extract air fan, including
compensation.
speed/flow at 0 V
speed/flow at 10 V
Displays the current setpoint for the
0-10 V input
10.3.2.
Parameter settings for Main
After the restart, the unit starts with an alarm:
‘External SF/EF setpoint config. error’. This means that one
or two physical inputs must be defined for the function.
This is done via:
Start page > Main menu > Configuration >
Config. Inputs/Outputs > Other > Ext. Setpoint, SF
ParameterFunction
X6Defines the input to which the function
must be connected
Start page > Main menu > Configuration >
Config. Inputs/Outputs > Other > Ext. Setpoint, EF
ParameterFunction
X7Defines the input to which the function
must be connected
Start page > Quick menu > Setpoints/Settings >
All settings > Fan control >
Supply air fan/Extract air fan
ParameterFunction
Current setpoint
supply air/extract air
Step 1Not active
Step 2Not active
Step 3Not active
Ext. setpoint curve Y1Scaling of the 0-10 V signal, speed/flow
Ext. setpoint curve Y2 Scaling of the 0-10 V signal, speed/flow
External setpoint
SF/EF
Displays the current setpoint for the
supply air/extract air fan
at 0 V
at 10 V
Displays the current setpoint for the
0-10 V input
Connection of signal(s) for controlling fan speeds from
external components. It is possible to connect various
types of switch/sensor that have pulse or fixed positions.
By default the regulator is set for switches with fixed values.
> EXAMPLE OF EXTERNAL CONTROL
Control 1 ON = Speed 1
Control 2 ON = Speed 2
Controls 1 & 2ON = Speed 3
Speed 3 can be configured to Stop. This is done via:
Start page > Main menu > Unit > Operating functions >
External control > Fan step
ParameterFunction
OffExternal inputs 1 and 2 ON produce stop
10.5. Fire fan
The unit has a potential-free output to control an external
fire fan. This requires the expansion module SP90 to be
installed.
46
Page 47
11. Connection of external
equipment
After making a change in a configuration menu, a restart is
required.
11.1. Fire damper
The unit can control fire dampers and operate them for
maintenance. Fire dampers can be included in the system
control, either via autotest or always open. Defined limit
positions are monitored. The current status and operating
mode of the dampers are displayed.
To activate the function.
Start page > Main menu > Configuration >
Configuration 1 > Fire damper
ParameterFunction
NoFunction deactivated
YesFunction activated. One digital output
and input each for fire damper regulation
Yes + FollUnitFunction activated. One digital output
and input each for fire damper regulation.
The fire damper is opened when the unit
starts and closed when the unit stops.
2-4Same as ‘Yes’ but with 2-4 fire dampers
2-4 + FollUnitSame as ‘Yes+FollUnit’ but with 2-4 fire
dampers
After making a change, a restart is required.
Start page > Main menu > Configuration >
Configuration 1 > Restart > Execute
RESTART
Start page > Main menu > Configuration >
Configuration 2 > Restart > Execute
RESTART
Connection description for fire damper indication with
combined signal for open and closed.
Continue to configure the return of the fire damper.
Start page > Main menu > Configuration >
Configuration 2 > Fire damper return
ParameterFunction
ClosedOnly one return for closed damper.
Clo + OpTwo separate returns for open and
closed positions.
CombiReturns for open and closed modes,
but only one signal/input with
sequence as below:
1 (closed) ---> 0 (closes/opens)
---> 1 (open)
The fire dampers must be connected according to the above
diagram to ensure correct operation.
47
Page 48
Configure as follows.
Start page > Main menu > Unit > Damper control >
Fire damper
ParameterValue Function
OperationOffCurrent status of outdoor air damper.
OnGo to the page for all settings for digital outputs.
Return open modeOKActive return if the damper is open. The parameter is activated automatically after 115% of the
time in open mode if return for open mode is not activated in Configuration 2.
1 / 2 / 3 / 4
+ all possible
combinations
Return closed modeOKActive return if the damper is closed. This must always be set.
1 / 2 / 3 / 4
+ all possible
combinations
No movementOK
Alarm
StatusN/APossible only in connection with configuration.
ClosedClosed.
Cl/OpCloses/opens.
OpenOpen. See example below.
Operating modeN/APossible only in connection with configuration.
OKOK.
TestTest mode.
AlarmAlarm mode.
Open time1…600 [s]Time for damper opening (see product sheet for damper actuator).
Close time1…600 [s]Time for damper closing (see product sheet for damper actuator).
Start manual testPassive
Active
MotionTime, Weekday,
Date
Test interval0...36000 [h]Time interval for automatic damper test.
The figures indicate which damper has an error.
The figures indicate which damper has an error.
No reaction to the alarm message for both returns if the damper operation has been changed.
See example below.
The time for automatic start of the damper test. Autotest is deactivated for Configuration 1 >
Fire damper = Yes+FollUnit.
See example below.
The time for automatic start of the damper test.
Autotest is deactivated for Configuration 1 > Fire damper = Yes+FollUnit.
See example below.
See example below.
48
Page 49
> EXAMPLE OF DAMPER OPERATION 0 -> 1:
After 15% of the time in open mode, return must be ClosedOtherwise an alarm is triggered for no movement.
After 115% of the time in open mode, return must be OpenOtherwise a return alarm is triggered for open mode
Damper operation 1 -> 0.
> EXAMPLE OF DAMPER OPERATION 1 -> 0:
After 15% of the time in closed mode, return must be OpenOtherwise an alarm is triggered for no movement.
After 115% of the time in closed mode, return must be ClosedOtherwise a return alarm is triggered for closed mode.
An automatic test can be carried out at a certain time (day, time) and/or at a certain interval.
> EXAMPLE OF TEST INTERVAL:
Motion = *:* *,*.* / Test interval = 24A test is carried out every 24 hours, regardless of the time
Motion = 23:* Mo,*.* / Test interval = 47 hA test is carried out every month at 23:00, with the previous test
having been carried out at least 47 hours earlier.
Motion = *:* *,*:* and Autotest interval = 0No automatic test is carried out.
Test sequence = 1
Test mode; the entire unit stops. After the Power down delay period, the outdoor air and extract air dampers are closed and a
fire damper test is initiated.
> EXAMPLE OF SWITCH TO 1 -> 0:
After 15% of the time in closed mode, return must be OpenOtherwise an alarm is triggered for no movement.
After 115% of the time in closed mode, return must be ClosedOtherwise a return alarm is triggered for closed mode.
If everything works as intended:
> EXAMPLE OF SWITCH TO 0 -> 1:
After 15% of the time in open mode, return must be closedOtherwise an alarm is triggered for no movement.
After 115% of the time in open mode, return must be OpenOtherwise a return alarm is triggered for open mode.
The unit confirms OK and starts.
49
Page 50
2
11.2. Fire/smoke detector
For selection of Alarm or Alarm+Temp, the fan regulation is
configured as follows:
Start page > Main menu > Configuration >
Configuration 1 > Fire alarm
ParameterFunction
NoNo fire alarm.
AlarmExternal fire alarm such as smoke
detectors, thermostat, fire alarm
control centre, etc.
TempInternal fire alarm via measurement
of normal supply air and extract air
temperature when both sensors are
accessible. A fire alarm is triggered
when one of the two temperatures
reaches a specific value.
Alarm+TempBoth fire alarms.
After making a change in a configuration menu, a restart is
required.
Start page > Main menu > Configuration >
Configuration 1 > Restart > Execute
RESTART
Start page > Main menu > Unit > Fan control > Fire
function
ParameterFunction
StopThe fans stop in the event of fire.
SF operationThe supply air fan operates on the set
max. step. The extract air fan stops.
EF operationThe extract air fan operates on the set
For selection of Temp or Alarm+Temp, the alarm limits for the
temperatures are configured as follows:
Start page > Quick menu > Setpoints/Settings >
All settings > Alarm limits
ParameterFunction
Supply air temp. fire
limit
Extract air temp.
fire limit
Alarm limit for high supply air
temperature.
Alarm limit for high extract air
temperature.
The input is normally open (NO) and produces an alarm if it
closes. This can be reconfigured to normally closed (NC) via:
Start page > Main menu > Unit > Inputs > Fire >
Contact function
ParameterFunction
NONormally open = produces an alarm
if the input closes.
NCNormally closed = produces an
alarm if the input opens.
50
Page 51
29 30
11.3. Air quality
Fans (see Fan compensation) are regulated based on air
quality. The outdoor air volume increases when the carbon
dioxide content exceeds a certain value (the fan speed
increases and the circulation volume decreases). The
outdoor air volume decreases when the carbon monoxide
content exceeds a set value (the fan speed decreases and
the circulation volume increases).
Start page > Main menu > Configuration >
Configuration 2 > Fan comp. air quality = Yes
After making a change in a configuration menu, a restart is
required.
Start page > Main menu > Configuration >
Configuration 1 > Restart > Execute
RESTART
Start page > Main menu > Unit >
Air quality regulation
Scaling of the CO2 sensor
Start page > Main menu > Configuration >
Config. Inputs/Outputs >
FunctionThe output signal must be selected based on
current requirements:
NormalNormal for CO2
InvertedInverted for carbon monoxide.
Setpoint0…3000 [ppm]Setpoint for air quality
regulation.
> EXAMPLE OF CO2 REGULATION
The setpoint is set to 800 ppm and the CO2 sensor detects
an actual value of 1,000 ppm. The unit switches up to speed
3 and remains at this speed until the CO2 sensor detects an
actual value below 800 ppm, at which time the unit switches
down to the speed set in the current time channel.
51
Page 52
11.4. AUX Damper
The output signal is affected by the speed of the ventilation
unit. The function can be used, for example, to open
a damper when the unit switches to a higher speed.
The function must be activated in the control system.
This is done via the following menu option.
Start page > Main menu > Configuration >
Configuration 2
Parameter Value Function
Aux. output
signal
After making a change in a configuration menu, a restart is
required.
NoAnalogue aux. output that
generates a 0-10 V signal,
depending on current fan step.
FanAn output signal can be set for
each fan step. For example 10%
at step 1 and 60% at step 2.
Flow deviceThe output signal here depends
on the difference between the
supply air temperature and the
room temperature. Adjustable
to the difference that produces
0 V and 10 V. For example
supply air temperature-room
temperature = 5 degrees
produces a 7 V output signal.
Start page > Main menu > Unit > Auxiliary
Parameter Value Function
Fan step 00…100 [%]Aux. output signal when unit is
Start page > Main menu > Configuration >
Configuration 2 > Restart
RESTART
52
Page 53
12. Web
The unit can be controlled via the web. This is done by the
control panel being mirrored in a web browser. If you want to
have flow charts showing the current values for temperatures,
flows, etc., a web module (accessory) must be installed.
To configure the function, go to the following menu:
Start page > Main menu > System overview >
Communication > TCP/IP > DHCP
ParameterFunction
ActiveThe regulator is assigned an
IP address from the network
PassiveA fixed IP address is set in the regulator
Information on other settings under the communication
menu is available from the staff in charge of the network.
After making a change, a restart is required.
You can now navigate using the arrow keys and ESC to go in
and out of menus.
Start page > Main menu > System overview >
Communication > TCP/IP > Restart
RESTART
After restart, go to:
Start page > Main menu > System overview >
Communication > TCP/IP
and make a note of the Current IP.
Then go to Other settings further down the same menu.
Make a note of the User name and Password.
Then open your web browser, go to the IP address you noted
down and log in with the User name and Password you
noted down.
53
Page 54
13. ModBus TCP/IP
14. DX heating/cooling
The unit can be controlled via ModBus TCP/IP as a default
function in the regulator. If you want to have ModBus with
RS485 serial communication, a communication module
(accessory) must be installed.
To configure the function, go to the following menu:
Start page > Main menu > System overview >
Communication > Modbus> TCP/IP > DHCP
ParameterFunction
ActiveThe regulator is assigned an
IP address from the network
PassiveA fixed IP address is set in
the regulator
Information on other settings under the communication
menu is available from the staff in charge of the network.
After making a change, a restart is required.
Start page > Main menu > System overview >
Communication > Modbus > Restart
This function is only available on software V3.07 and later.
To see the current version for the unit:
Main menu > System overview > Versions > Flexit AHU
If the function is needed on older versions, contact Flexit.
The control system is able to control a heat pump for
heating and cooling, which is connected to ducted coils. It
can be used both as a free-standing unit or in sequence
ahead of the internal electric-powered coils, which can then
be used as peak heating and/or as reserve heating while the
heat pump is defrosting.
For the function to operate, I/O module SP90 must
be installed and configured. See Manual 112548.
If you wish to use the internal electric-powered
coils, these must be installed/configured as shown in
the manual supplied with the coils.
14.1. Configuration of control system
Start page > Main menu > Configuration >
Configuration 1 > Additional heating
RESTART
Connect here.
The parameter list for ModBus can be downloaded at
www.flexit.com.
ParameterFunction
NoAdditional heating deactivated
YesAdditional heating activated
Yes+Preh+Outd.Additional heating with preheating
based on outdoor air temperature.
Analogue heating valve output.
Yes+Preh.Frost
protection temp.
Select Yes to activate the function.
Start page > Main menu > Configuration >
Configuration 1 > Additional cooling
ParameterFunction
NoAdditional cooling deactivated
WaterAdditional cooling via 0-10V signal
DX 1stepAdditional cooling Off/On 1 step
DX 2stepAdditional cooling Off/On 2 step
DX 3stepAdditional cooling Off/On 3 step
Additional heating with preheating
based on frost protection temperature.
Select Water to activate the 0-10V output signal for the
function. After making a change in a configuration menu,
RESTART.
54
Page 55
RESTART
Start page > Main menu > Configuration >
Configuration 2 > Additional cooling regulation
The unit will show an alarm on startup. This can be removed
by the configuration shown further down.
Start page > Main menu > Configuration >
Configuration 2 > Pump, additional heating
ParameterFunction
NoNo Off/On signal to pump
YesOff/On signal to pump
Yes+ExerciseNo Off/On signal to pump +
exercise operation
Select Yes. Used to signal a heating/cooling requirement to
the heating pump. Closes a circuit in the event of a heating
requirement.
After restarting, toggle between open and closed contact
using the following menu:
Start page > Main menu > Unit > Outputs > Pump
Add. heat > Contact function = NO /NC
Start page > Main menu > Configuration >
Configuration 2 > Heat pump defrosting
ParameterFunction
StandaloneRegulation seeks its own temperature
target value
SequenceRegulation uses the sequence before
or after ordinary cooling regulation
Select Sequence to force the regulation to operate in
sequence with heat recovery and heating.
Start page > Main menu > Configuration >
Configuration 2 > E.g. Combi Coil
ParameterFunction
NoFunction deactivated
1outputFunction activated shared output
2outputsFunction activated two different
outputs
Select 1output to send the same signal (0-10V) to the heat
pump for both heating and cooling.
After making a change in a configuration menu, RESTART.
RESTART
ParameterFunction
NoDefrosting function deactivated
YesDefrosting function activated
Select Yes. Used to lock the output signal to the heat pump
and if necessary activate electric heating (if connected)
when defrosting the heat pump.
Start page > Main menu > Configuration >
Configuration 2 > Additional heating regulation
ParameterFunction
StandaloneRegulation seeks its own
temperature target value
Sequence HeatingAdditional heating
Sequence Additional
heating-Heating
Regulation uses the sequence heat
pump - electrical heating
Regulation uses the sequence
electrical heating - heat pump
Select Sequence Additional heating - Heating to force
the regulation to operate using the sequence Heat pump
first and electrical heating second.
After restarting, an alarm will appear on the regulator
requiring configuration of which input is connected to the
heat pump defrosting function.
Start page > Main menu > Configuration >
Config. In/Outputs > Digital inputs > Heat pump
defrosting
ParameterFunction
D4Block P12-35
Select D4. This will connect block P12-35 on the A2 circuit
board to the function. The input is also used for resetting the
fire damper. If both functions are used, contact Support to
configure a new input.
The function works in such a way that when the heat pump is
defrosting (signal in on block P12-35), the control system is
automatically started up
from the regulator to the heat pump until defrosting plus an
extra period has elapsed, when it will start to regulate again.
If internal electrical coils have been installed and configured,
these will attempt to maintain the supply air temperature
during the defrosting period. This is to prevent the heating
sequence switching over when the heat pump has finished
defrosting.
To adjust the function’s locking time:
Start page > Main menu > Unit > Temperature
regulation > Additional heating > Heat pump
defrost. Lock electrics