Flexi-liner Afcl, ALK User Manual

Page 1
IMPORTANT: FLEXI-LINER HAS BEEN TESTED AND LISTED, USING ALL THE SUPPORTS,
SECTIONS, ETC., DESCRIBED HEREIN. DELETION OR MODIFICATION OF ANY OF THE REQUIRED PARTS OR MATERIALS MAY SERIOUSLY IMPAIR THE SAFETY OF YOUR INSTALLATION AND VOID THE CONDITIONS OF CERTIFICATION AND/OR WARRANTY OF YOUR LINER.
Flexi-Liner
®
Installation Instructions
1
Aluminum Flexible Chimney Liner
and Gas Vent Connector
IT IS OF THE UTMOST IMPORTANCE THAT THIS CHIMNEY LINER BE INSTALLED ONLY IN ACCORDANCE WITH THESE INSTRUCTIONS. PLEASE READ ALL INSTRUCTIONS BEFORE BEGINNING YOUR INSTALLATION. FAILURE TO INSTALL THIS SYSTEM IN ACCORDANCE WITH THESE INSTRUCTIONS WILL VOID THE CONDITIONS OF CERTIFICATION AND THE MANUFACTURER’S WARRANTY. KEEP THESE INSTRUCTIONS IN A SAFE PLACE FOR FUTURE USE.
For Installation into Masonry Chimneys
READ INSTRUCTIONS CAREFULLY BEFORE STARTING THE PROJECT. REMEMBER THAT SAFETY COMES FIRST.
OUR FLEXI-LINER®SYSTEM IS DESIGNED FOR INSTALLATION BY A QUALIFIED PERSON IN ACCORDANCE WITH LOCAL BUILDING CODES.
Types of Appliance
Flexi-Liner®is designed for use in existing masonry or listed factory-built chimneys and vents as a chimney liner for Category 1 listed gas-fired appliances equipped with draft hoods and other gas appliances listed for use with Type B Gas Vent that burn natural gas or propane, under neutral or negative draft.
CAUTION: THIS ALUMINUM LINER IS NOT INTENDED FOR
SOLID OR LIQUID FUEL-BURNING APPLIANCES!
Sizes, Location & Clearances
Ensure your installation will conform with all federal and municipal building code requirements. Before commencing installation, CONTACT LOCAL GAS UTILITY OR LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION IN YOUR AREA. Obtain any necessary building permits. Authorities require that the masonry chimney extend not less than three feet above the highest point where it passes through the roof of a building and not less than two feet above any portion of the building within ten feet. (See Figure 1.)
Close attention should be given to determine the correct connector size. Be sure to choose a size of
liner that is not less than that specified in the appliance manufacturer’s instructions. Vent size recommendations
are detailed in the CAN/CSA-B149.100 in Canada or the National Fuel Gas Code NFPA-54 in the USA. As per the above Fuel Gas Codes, all flexible
metallic chimney liners are to be sized using Type B Gas Vent sizing tables, with maximum capacities reduced by 20%. We have included sizing information in the back of this instruction book for flexible chimney liners.
Consult the appliance manufacturer’s installation instructions regarding the maximum venting run allowed.
Model ALK/AFCL
UL1777 CAN/ULC-S635
Page 2
2
Aluminum Flexible Chimney Liner and Gas Vent Connector Installation Instructions
Flexi-Liner
®
Your liner has been listed for installation at zero clearance to the inside masonry surface of an existing masonry or factory-built chimney and with zero clearance between the outside surface of the masonry chimney and surrounding combustibles.
Do not fill the airspace between the liner and chimney with loose fill insulation or cement.
The Flexi-Liner and any Type B Gas Vent may be used in any combination desired to complete the system.
When used as a Vent Connector, install with 1" (25mm) minimum airspace clearance to combustibles.
At no time should an exposed portion of the Flexi-Liner be enclosed or pass through any combustible area or materials, such as walls, ceilings, floors, roofs, attics, crawl spaces or joist areas, as this product is not listed as Type B Gas Vent.
Use Type B Gas Vent or Flexi-Sleeve (sold separately) to minimize condensation and down-drafting, particularly if: a) The flue gas temperature is below 280°F at the entry
point into the liner.
b) Flexible Liner is to be installed in an exterior or
oversized chimney. An exterior chimney has one or more sides exposed to the outdoors.
c) The liner system is venting only fan-assisted
appliances.
d) The masonry chimney contains solid or liquid fuel
residue from prior heating appliances.
e) The appliance is equipped with a vent damper.
Liner Components
The following parts are available for liner installation.
15' Flexible Liner Kit (3" to 5" only) 25' Flexible Chimney Liner Kit
35' Flexible Chimney Liner Kit Kits include applicable length of Flexible Liner, Support/Flashing assembly, Round Top, Mortar Guard, screws and Installation Instructions.
Note: The 5.5" flex kit also includes a 5.5" to 6" Flexible
Connector.
The following additional parts are available.
Guide Cone (pull-down)
10' Extension Kit
Flexible Connector
B-Vent Adapter
Flexible Sleeve Insulation
Tools and Materials
The following tools and materials are needed.
Safety gloves Eye protection Ladder or scaffolding to reach the roof Masonry drill bit ½" or
3
/8"
High speed drill bit
3
/
8"
Drill Hacksaw Screwdriver Hammer Pliers Cold chisel Tin snips Caulking, exterior grade Small bag of mortar mix Trowel Mortar pan Piece of rope 10 feet longer than the chimney
CAUTION: Always wear gloves and eye protection
during installation to avoid personal injury.
Chimney Inspection and Cleaning
Make sure the masonry chimney is sound in construction, clean, and free from all loose and potentially flammable debris. If you find any cracked, loose, or missing bricks or tiles, have them repaired or replaced.
Before the installation of the liner, it is recommended that the chimney be cleaned by a certified chimney sweep.
Since chimneys are usually very sooty and dusty, it is advisable to remove or cover your furniture, rugs, etc., for the duration of the cleaning and installation of the liner.
Chimney Preparation
PREPARING FOR A STAND-ALONE APPLIANCE INSTALLATION
If no opening currently exists, determine the location of the point where the vent system will penetrate the masonry wall, and prepare an opening through the masonry and any existing clay liner (with a masonry drill bit, cold chisel and hammer) large enough to accommodate the Mortar Guard, allowing for the Flexible Liner to exit the chimney opening. The opening must be located above the appliance outlet as high as possible to maximize connector rise yet maintain the proper clearances (see Figure 2a). It is recommended to install an inspection/ clean-out door on the opposite side if conditions permit.
Page 3
PREPARING FOR AN INSERT
Before installing the venting system, ensure that the damper plate is locked into the open position and secured or removed to prevent any damage to the liner (see Figure 2b).
Note: Due to possible snagging, which may result in
some surface damage, caution must be observed when lowering Liner lengths into the masonry flue.
PREPARING TOP OF CHIMNEY
Your chimney may have a clay-tile liner that protrudes above the brick chimney. There is no need to remove the top portion of the clay tile liner if it is in good condition. You may want, at this time, to do any repairs to the chimney crown if any cracks or deterioration are showing. Once the repairs are done, follow the Flashing/Support Installation - Masonry Chimney section on page 5. If, on the other hand, the clay tile liner is not in good condition, you will need to make it flush by chipping away at the excess with a hammer, and cold chisel (see Figure 3). Make sure that pieces of the clay tile liner don’t fall into the flue. When you have finished making the top of the chimney flush, fill in any cracks and uneven surfaces with mortar.
Liner Preparation
DETERMINING LINER LENGTH
Determine the required length of the liner by measuring the distance from the prepared opening to the top of the chimney, allowing for a 90-degree bend at the inlet. If the flexible liner will extend directly to the appliance, add the distance from the appliance exhaust collar to the prepared opening in the chimney flue, allowing for any required bends. Multiple lengths may be joined, using the Flexible Connector (see Figure 4).
3
Aluminum Flexible Chimney Liner and Gas Vent Connector Installation Instructions
Flexi-Liner
®
Page 4
4
Aluminum Flexible Chimney Liner and Gas Vent Connector Installation Instructions
Flexi-Liner
®
TRIMMING THE LINER
Select the length(s) necessary to accommodate the required distance determined above. Stretch the Flexible Liner to the desired length (requires 2 people) by placing both hands around the circumference of the ends of the liner and gently pulling. If any Flexible Liner requires cutting, use a sharp fine-toothed hacksaw.
CAUTION: Do not attach the Flexible Connector and use
it to stretch the liner. This may result in damage to the Flexible Liner.
GUIDE CONE (PULL-DOWN ASSEMBLY)
A Guide Cone (Pull-Down) is available as an optional installation aide. When attached to a rope, it is used to pull and guide the end of the Flexible Liner through the chimney. With one end of the rope, simply tie a knot around the band of the Guide Cone. Attach the Guide Cone to the flex by sliding it over the Flexible Liner and inserting screws through the prepunched holes (see Figure 5). Once the Flexible Liner has been lowered in its final position, remove the Guide Cone.
Installing the Liner
STAND-ALONE APPLIANCE
Gather all necessary component parts and locate them near the termination of the chimney. This should consist of a Support/Flashing assembly, a Round Top, and the prepared length of Flexible Liner complete with Guide Cone and rope. Feed the Guide Cone and rope down the chimney flue (see Figure 6). While an assistant gently pulls on the rope from below, start lowering the Flexible Liner down into the chimney flue. If additional lengths of flex are required, join the sections together as the Flexible Liner progresses down the chimney.
Note: Due to possible snagging, which may result in
some surface damage, caution must be observed when lowering Liner lengths into the masonry flue. After feeding the liner down the chimney to the bottom, form a 90-degree bend and bring the Flexible Liner through the prepared opening of the chimney wall (see Figure 6).
For the liner to extend directly to the appliance, continue to pull through the required amount of liner to allow a proper connection to the appliance exhaust collar. Any portion of liner used as a connector in a nearly horizontal orientation should include a minimum slope of ¼" per foot upward from the appliance toward the chimney.
Page 5
5
Aluminum Flexible Chimney Liner and Gas Vent Connector Installation Instructions
Flexi-Liner
®
GAS FIREPLACE INSERT
Follow the Liner Preparation - Guide Cone (Pull-Down Assembly section on page 4. Feed the liner down the
chimney until it exits through the masonry fireplace opening (see Figure 7). Most gas fireplace inserts are equipped with a removable draft hood for easy flex to insert connection. Check the insert manufacturer’s instructions for correct connection. Remove the Guide Cone from the Flexible Liner.
Attach the Flexible Liner over the collar of the gas fireplace insert (check the appliance manufacturer’s instructions for proper attachment). Once the insert is in its proper place, pull the excess Flexible Liner from the top of the chimney.
Flashing/Support Installation - Masonry Chimney
Position the Flashing and center the flat plate on top of the clay tile. Mark the outline of the clay tile on the underside of the flashing plate. There should be a minimum of 2" (50mm) of overhang on each side of the clay tile. Cut off each corner at 45° (see Figure 8), and bend over the excess at the marked line, using a pair of hand folders.
Round Top Installation - Masonry
Pull enough of the Flexible Liner through the Flashing/ Support assembly to be able to slide the Round Top into the Flexible Liner (see Figures 9 and 10).
Slide the Round Top and Liner back through the Flashing/Support assembly until the skirt of the Round Top comes in contact with the collar of the Flashing/ Support assembly. Install the four (4) ¾" sheet metal screws (provided) through the prepunched holes in the Flashing collar (see Figure 9).
Note: For 5.5" Flex, the Round Top installs to the outside of Flex, and must be fastened with screws.
Page 6
6
Aluminum Flexible Chimney Liner and Gas Vent Connector Installation Instructions
Flexi-Liner
®
Place a wide bead of high-temperature silicone along the entire top surface of the clay tile. Slide the Flex and Flashing assembly back into the chimney opening until the flashing plate comes to rest on the clay tile. Press the flashing firmly into the silicone to create a good seal (see Figure 10).
Round Top Installation - Existing Factory-Built Chimney
One method is offered for the installation of Flexi-Liner in an existing factory-built chimney.
Flexible Liner Kit with Liner Round Top
1. Remove existing chimney top and discard.
2. Center the Flashing/Support on the factory-built
chimney. Mark the outline of the factory-built chimney on the underside of the Flashing/Support plate (see Figure 11a). The flashing is then trimmed flush with the outline, and secured in place from the top with sheet metal screws once it is siliconed in place, as per step 6.
3. As an alternative to step 2, to have an overhang, the
flashing/support is trimmed approximately 2" larger in diameter than the marked outline (see Figure 11b). It is then slit and folded to fit down over the chimney. The screws are installed from the side once it is siliconed in place, as per step 6.
4. Lower the flexible liner down through the factory-built
chimney to the desired position.
5. Place a wide bead of high-temperature silicone along
the entire top surface of the factory-built chimney.
6. Place the trimmed Flashing/Support over the Flexible
Liner. Lower the Flashing/Support so that the plate comes to rest on the factory-built chimney. Press the plate firmly into the silicone to create a good seal, and secure into place with #8 x
3
/8" stainless sheet metal
screws, as per Figure 11b or 12.
7. Slide the Liner Round Top and the Flexible Liner back
through the Flashing/Support assembly until the skirt of the Round Top comes in contact with the collar of the Flashing/Support. Install the four (4) sheet metal screws (provided), using the prepunched holes in the flashing collar and through the flex and Round Top. Apply silicone sealant to any exposed lances, holes or screws.
Page 7
7
Aluminum Flexible Chimney Liner and Gas Vent Connector Installation Instructions
Flexi-Liner
®
Mortar Guard Installation
Back at the appliance, if you have not done so previously, slide the Mortar Guard over the end of the Flexible Liner protruding from the prepared opening. Position the Mortar Guard within the prepared opening, such that it will provide a protective barrier between the Liner and any required filler material. Refer to the Installation Completion section on page 8. Ensure that the end of the mortar Guard, with the Listing Label attached, extends into the room a minimum of 2" so that the label is visible for inspection.
Appliance Connection
Final connection of the flexible liner to the appliance may be made in a number of ways and will depend on specific conditions.
TYPE B VENT CONNECTOR
If Type B Vent is recommended as a connector (if clearances to combustibles or sizing guidelines suggest), the Flexible Liner should extend at least 2" (50mm) beyond the Mortar Guard.
FLEXIBLE LINER B-VENT ADAPTER
The Flexi-Liner universal B-Vent adapter connects Flexible Liner pipe to all brands of Type B Gas Vent pipe. To install:
1. Prior to installation, a Mortar Guard should be installed
within the prepared opening, such that it will provide a protective barrier between the liner and any required filler material. Ensure that the end of the Mortar Guard, with the listing label attached, extends into the room a minimum of 2" so that the label is visible for inspection (refer to main instructions for additional details).
Page 8
8
Aluminum Flexible Chimney Liner and Gas Vent Connector Installation Instructions
Flexi-Liner
®
2. The Flexible Liner should be installed such that it
extends at least 2" beyond the Mortar Guard, allowing sufficient length for attaching the universal B Vent adapter to the flex (see Figures 14 and 15).
3. Engage the outlet end of the universal B Vent adapter
with the flex pipe. Once fully engaged, secure the flex to the adapter using four (4) self-tapping sheet metal screws. Install the screws so that they penetrate through the flexible liner and the inner liner of the adapter (see Figure 16).
4. Engage the type B vent pipe with the universal B vent
adapter. Once fully engaged, tighten the machine screw so that the adapter clamps down and secures the B vent pipe in place (see Figure 17).
5. Refer to main instructions to complete installation.
SINGLE-WALL VENT CONNECTOR PIPE
Trim the Flexible Liner flush with the Mortar Guard. Insert the end of a single-wall vent connector pipe (by others) into the Flexible Liner. Secure into place with four (4) evenly spaced screws through the Mortar Guard and into the Flexible Liner and the vent connector (see Figure 18).
Note: The 5.5"-6" Flexible Connector is required when
connecting 6" single-wall pipe to the 5.5" flexible liner.
When used as a single-wall vent connector, and if it is acceptable, the Flexible Liner system may be extended all the way to the appliances and installed with 1" (25mm) airspace clearance to combustibles. Remember to include a minimum of ¼" per foot rise in any horizontal sections (from the appliance to the chimney) and keep turns to a minimum (see Figure 18).
Installation Completion
After the appliance is correctly positioned and all the venting connections are completed and checked for proper installation (clearances to combustibles, proper support and component parts), fill the void area around the penetration hole with mortar. High-temperature ceramic sealant or other noncombustible filler material may be used as a substitute instead of mortar.
Final Inspection
Ensure all gas piping, electrical, and vent connections are complete and up to code requirements. After adjusting the appliance and lighting the main burner, allow a couple of minutes for warm-up. Check the vent operation by holding a lighted match or smoking material just under the rim of the draft hood relief opening.
Proper venting will draw the flame or smoke into the draft hood. Improper venting, indicated by escape or spillage of burned gas, will cause smoke to move away from the draft hood and a flame to flicker or go out.
Liner Maintenance
The Flexible Liner should be inspected by a qualified heating or chimney technician before each heating season to ensure it is free of debris and condensation and that all components are in good condition. This can be accomplished by removing the vent connector and looking into the liner at its base.
The Round Top can be removed for inspection purposes by removing the fastening screws. Again, have it inspected by a qualified heating or chimney technician.
Reference
Upon completion of the installation, fill in the information below and keep in a safe place for future reference.
Chimney Model: ________________________________
Installation Date: ________________________________
Dealer Name: __________________________________
Address: ______________________________________
City, Province/State: _____________________________
Technician`s Name: _____________________________
Technician`s Certification Number: ____________________________
Address: ______________________________________
City, Province/State: _____________________________
Page 9
“H”
15’
25’
30’
35’
45’
FLEXI-LINE R SIZER
®
Cor ruga ted Chimn ey Line r fo r Ga s F ired Appliances
SINGL E APPLIANCE
t, Ft h g
i e
H
Double
Double
Double
Double
Double
r o
t c e n n o
C
“C”
Single
Single
Single
Single
Single
r o
e
l
l
b
l
u
a
o
W
D
e
l g n
i
Type:
S
Offset
Lateral
“L”
2’ 5’
10’
2’ 5’
10’
2’ 5’
10’
2’ 5’
10’
2’ 5’
10’
2’ 5’
10’
2’ 5’
10’
2’ 5’
10’
2’ 5’
10’
2’ 5’
10’
FLEXI-LINER Diameter “D” (inches)
3” 4” 5” 5.5” 6” 7” 8”
Appliance Input Rating Limits (x1000 BTU/h)
FAN
Min Max
11
55
22
52
29
47
38
55
51
50
NA
NA
10
62
21
59
28
54
37
62
50
57
NA
NA
9
65
21
62
27
56
37
64
49
59
NA
NA
9
66
21
63
27
57
37
65
49
60
NA
NA
8
68
20
65
26
60
36
66
48
63
NA
NA
Reduced 20% from Type B Vent Tables
NAT
FAN
NAT
FAN
NAT
181 175 165
180 173 161
213 207 196
212 204 191
226 220 210
225 217 204
234 227 217
232 224 211
249 242 232
247 239 226
Max
120 114 108
119 112 105
140 134 128
139 132 126
148 141 137
146 138 134
152 146 141
151 143 138
161 155 148
160 153 145
FAN
Min Max
21
226
44
220
58
208
98
225
123
217
155
204
18
268
42
261
55
249
94
267
119
258
149
244
16
286
41
278
54
267
93
284
117
275
147
261
16
296
40
289
53
277
92
294
116
285
145
271
15
317
39
309
51
298
90
315
114
306
142
291
Max
38 36 33
38 35 31
43 41 38
42 40
NA
45 43 40
45 42
NA
46 NA NA
46 NA NA
48 NA NA
48 NA NA
Min Max
15
109
30
104
40
97
57
109
75
102
95
93
14
126
29
120
38
113
56
125
73
119
92
109
13
133
28
128
37
120
55
131
72
126
91
115
13
136
28
131
37
124
55
135
72
129
91
118
12
143
27
138
36
131
54
141
71
136
90
125
Max
74 70 66
74 69 63
85 82 76
84 80 74
90 86 82
89 85 78
92 89 84
91 87
NA
96 93 89
95 91
NA
Min Max
20 39 51
80 102 128
16
37
49
77
99 124
14
36
48
76
98 122
14
36
47
75
97 121
14
35
46
74
95 119
NAT
Max
150 144 137
149 143 134
176 170 162
175 168 159
186 180 173
185 178 170
192 186 178
190 184 175
203 197 190
201 195 186
FAN
Min Max
22
271
49
264
64
252
115
270
144
261
182
246
19
324
46
315
61
302
111
322
139
312
174
296
18
346
45
337
59
324
109
343
136
334
171
318
17
359
45
350
58
337
108
356
135
347
169
330
16
385
44
376
57
364
105
383
132
373
164
356
NAT
Max
180 174 166
179 174 162
212 206 196
211 204 192
224 218 209
223 217 206
231 225 216
230 224 213
244 239 231
243 237 227
FAN
Min Max
38
380
64
370
84
356
148
378
182
367
228
350
30
458
60
448
79
432
142
455
175
444
218
424
27
490
58
480
77
464
139
488
171
476
213
456
26
511
57
500
76
484
138
508
169
496
211
476
23
552
56
541
74
525
135
549
166
537
206
517
NAT
Max
253 240 230
251 238 227
296 289 277
294 286 273
315 308 297
314 306 294
325 319 308
324 316 304
346 340 330
344 337 325
FAN
Min Max
45
506
76
496
99
480
187
505
231
493
284
474
37
615
71
603
93
585
179
612
220
599
271
577
33
661
69
649
91
630
175
658
215
645
265
622
31
691
68
679
90
660
173
688
212
674
262
651
28
750
66
738
87
719
170
747
207
733
256
709
NAT
Max
331 322 309
330 320 305
402 394 380
400 391 375
428 419 406
426 417 401
444 435 422
442 433 417
476 468 455
474 465 450
MULTIPLE APPLIANCES
r o
t
l
l
c
r
e n n o
C
“C”
o e
l b u o
Type
D
a W
Combined Appliance Input Rating Limits (x1000 BTU/h)
e
l g n
i S
FAN
Only
100
“H”
t, Ft h g
i e
H
Double
15’
Single
Double
97
116
25’
Single
Double
111
122
30’
Single
Double
116
125
35’
Single
Double
119
131
45’
Single
See Rigid Connector Sizing Table below for Multiple Appliance Systems
124
FLEXI-LINER Diameter “D” (inches)
Reduced 20% from Vertical Common Vent
NAT
FAN
NAT&
90
86
104
100
110
106
113
109
119
114
Only
73
70
88
84
94
90
97
93
104
99
FAN
Only
156
151
184
178
195
189
202
195
216
208
FAN
NAT&
131
127
157
152
168
162
175
168
188
180
NAT
Only
115
112
138
135
148
144
154
150
165
161
FAN
Only
191
186
227
220
242
235
252
243
271
261
FAN
NAT&
157
152
189
183
203
196
212
204
230
220
NAT
Only
140
136
168
163
181
175
188
182
202
195
FAN
Only
226
220
270
262
289
280
301
291
325
314
FAN
NAT&
182
177
221
214
238
229
249
239
271
260
165
160
198
192
213
206
222
214
239
229
NAT
Only
7”4” 5” 5.5” 6” 8”
FAN
FAN
Only
NAT&
342
282
333
274
409
341
398
332
438
367
426
357
457
385
444
374
494
420
480
407
NAT
Only
224
219
268
261
288
279
301
291
326
316
FAN
Only
445
435
537
524
576
562
603
588
656
640
FAN
NAT&
355
347
434
423
468
456
492
479
541
526
NAT
Only
292
286
350
342
376
367
392
382
424
413
Flexi-Liner® 9
Page 10
Aluminum Flexible Chimney Liner and Gas Vent Connector Installation Instructions
RIGID CONNECTOR - SIZING INFORMATION
VENT CONNECTOR CAPACITIES
FOR MULTIPLE CATEGORY 1 APPLIANCES CONNECTED TO A COMMON VENT
System Height,
Ft
15
25
30
35
45
Connector
Type:
Double or
Single Wall
Double
Single
Double
Single
Double
Single
Double
Single
Double
Single
3"
Connector
Rise, Ft
1 21 50 30 33 89 53 47 142 83 64 220 120 2 22 53 35 35 96 63 49 153 99 66 235 142 3 24 55 40 36 102 71 51 163 111 68 248 160 1 NA NA 29 79 87 52 116 138 81 177 214 116 2 NA NA 34 83 94 62 121 150 97 185 230 138 3 NA NA 39 87 100 70 127 160 109 193 243 157 1 21 58 32 32 106 58 46 169 90 61 267 130 2 22 61 38 34 112 68 48 179 107 63 279 154 3 23 63 43 35 117 77 49 187 120 65 290 173 1 48 58 31 78 104 56 114 164 87 172 258 125 2 52 61 37 82 109 66 119 174 104 180 271 148 3 55 63 41 86 113 74 124 183 117 188 282 168 1 20 62 33 31 113 59 45 181 93 60 288 134 2 21 64 39 33 118 70 47 190 110 62 299 158 3 22 66 44 34 123 79 48 198 124 64 309 178 1 47 60 31 77 110 57 112 175 89 169 278 129 2 51 62 37 81 115 67 117 185 106 177 290 152 3 54 64 42 85 119 76 122 193 120 185 300 172 1 20 64 34 31 118 60 45 190 95 59 303 137 2 21 66 40 33 123 72 47 198 112 61 314 162 3 22 68 45 34 128 81 48 206 127 63 323 182 1 47 62 32 77 115 58 111 183 91 167 293 131 2 51 64 38 81 119 68 116 193 108 175 304 155 3 54 66 43 85 123 78 121 200 121 183 313 176 1 19 69 35 30 128 63 44 207 99 58 334 142 2 21 71 42 32 132 75 46 215 117 60 343 169 3 22 73 47 33 137 84 47 221 132 62 352 190 1 46 67 33 76 124 59 110 199 94 164 322 135 2 50 69 39 80 128 71 115 208 111 172 331 161 3 53 70 44 84 132 81 120 214 122 180 340 183
Fan Fan Fan
Min Max Max Min Max Max Min Max Max Min Max Max
Nat Nat Nat Nat
4" 5"
6"
Fan
NA means "Not Allowed"
10
Flexi-Liner®
Page 11
SINGLE APPLIANCE
D
= Diameter
C
= Connector
H
= Height
L
= Lateral
D
MULTIPLE APPLIANCES
L = Manifold Lateral
M
(Shall be less than or equal to 18 x )D
D
H
Appliance
H
L
C
Appliance
C
Appliance
1
L
M
2
G EN ERAL VEN TIN G REQ UIREMEN TS
A1 . The a ir spa ce a round an installe d Flexi- Liner System must not be used to vent other
appliances.
Fle xi- Liner
A2 . A System venting more tha n one a ppliance sha ll not be smalle r in dia me ter
than the outlet of the largest appliance being served.
A3 . For single a pplia nce installa tions, the System may be sma ller in diameter tha n
the outlet of the a pplia nce be ing served, pr oviding:
a) the vent height is at lea st10ft. b) the liner size is not more tha n one size sma ller. c) the "FAN M AX" is reduced by 10 %if the a pplia nce is "fan assisted". d) the outlet is la rger than 4" if the appliance is "natura l draft".
A4 . Reduce capa city for e lbows (turns) a s follows:
Fle xi- Liner
A4 .1. Single Appliance (
In U SA
a) - for ea ch additional elbow up to 45 º, reduce ca pacity by 5%.
two 90º elbows for tota l vent system a re factored into cha rt)
- for e a ch a dditiona l elbow 45 º- 90º, reduce ca pacity by 10 %.
In C DA
b) - for e a ch a dditiona l elbow 90 º reduce capacity by 1 0% for N AT a nd 1 5%
for FAN .
A4 .2. Multiple Appliances (
In U SA
a) - for each elbow in the common vent up to 45º, r educe capacity by 5%.
90º turn at the bottom of liner is fa ctored into cha rt)
- for each elbow 4 5 º - 9 0 º , reduce ca pacity by 1 0 %.
In C DA
b) - for each 90 º elbow in the common vent, reduce capa city by 1 0% for N AT
and 1 5% for FAN .
Common Vent manifold fitting is part of the connector sizing coming to it.
A5 . D o not use these tables if the ve nt system contains a ny device (such a s a vent damper,
dra ft regula tor or hea t recla imer, etc.), which retards the flow of vent gases. Refer to instructions provide d by the ma nufa cturer of the device for vent instructions.
A6 . I nterpola tion betwee n the table entries is permitted, extrapolation beyond the table
entries is not permitted.
A7 . Vent connector sizes for multiple appliances are derived from tables included in the following national gas codes: N FPA 54 (USA) and B149.1 (CDA).
These tables are derived from the National Fuel Gas Code (NFPA 54 & CSA-B149). Current
A8.
code data and information will supercede these sizing instructions if there is any discrepency between them.
Fle xi- Liner
Flexi-Liner®
AD D ITIO N AL C O MMEN TS
Fle xi- Liner
B1 . System is U L/ULC Listed for relining existing masonry or fa ctory-built chimneys
and vents serving C ategory I na tural ga s or propane fired appliances.
B2 . Insula ting of System is a benefit to the insta llation but not a lways e ssential to
effective operation of this venting system. Consult the Flexi- Sleeve installa tion instructions for application guide lines.
B3 . The use of a "Y" fitting rather than a "T" fitting is re comme nded when common venting into
a manifold system.
B4 . AVO ID C O NDEN SATIO N and/ or SPILLAG E O F FLUE G AS ES :
a) Install as per insta llation instructions.
b) Set up applia nces a s per a ppliance installation instructions. B5 . C onta ctloca l authorities for restrictions and re gula tions in your a re a . B6 . Ve nting ga s fire d a ppliances into ma sonry chimneys is prohibited, unle ss a Listed liner
such a s or a tile liner conforming to C ode is utilized. O versized, misa ligned and/ or cra cked tile s DO N OT constitute a C ode line r.
Fle xi- Liner
Fle xi- Liner
Fle xi- Liner,
Printed in C an ada
11
Page 12
Aluminum Flexible Chimney Liner and Gas Vent Connector Installation Instructions
Index
Types of Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Sizes, Location & Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Liner Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Tools and Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Chimney Inspection and Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Chimney Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Preparing for a Stand-Alone Appliance Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Preparing for a Insert . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Preparing Top of Chimney . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Liner Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Determining Liner Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Trimming the Liner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Guide Cone (Pull-Down Assembly) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Installing the Liner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Stand-Alone Appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Gas Fireplace Insert . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Flashing/Support Installation - Masonry Chimney . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Round Top Installation - Masonry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Round Top Installation - Existing Factory-Built Chimney . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Mortar Guard Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Appliance Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Type B Vent Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Flexible Liner B-Vent Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Single-Wall Vent Connector Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Installation Completion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Final Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Reference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Sizing Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-11
12
©2009 Flexi-Liner All rights reserved Form No. 851419 10/20/2009 Printed in U.S.A
Loading...