flex7 FNC3000X/U Installation Instructions

fns3400D(X, A)/U Dimming Sensor Kit
3400/U
The fns3400D(X, A)/U sensor kit plugs directly into any of the eZeBox range of connection units or
eZeBox connection unit
(not included)
a 7-pole single socket outlet to provide control of the connected mains rated luminaires. Control is ON/OFF/DIM, dependent on occupancy and or light level detection. The kit comprises a controller, sensor head, and sensor lead.
Three products are available:
fns3400D/U for DSI digital dimmable ballasts. fns3400X/U for DALI digital dimmable ballasts. fns3400A/U for Analogue ballasts 0-10V.
Please ensure the correct product is selected for the type of ballast being used as incorrect connection may damage the controller.
Sensor lead
Sensor head
Controller
Switch drop lead
This product should only be installed by a qualified electrician.
Switch
(not included)
Light level detection performance
The fnh400 sensor head detects both occupancy and light level. However, conditions for optimum light
sensing should always have priority over those for occupancy coverage. To achieve effective daylight linking control, select only an area where the daylight contribution, though changeable, is significant and remains consistent across the area.
As lamp output across the circuit must be common, it is not possible to provide the 'optimal' luminosity for all areas when some receive more daylight than others.
Flex Connectors Limited, Unit 8, The Gate Centre, Syon Gate Way, Brentford, Middlesex TW8 9DD, UK
Telephone: +44 (0) 20 8580 1066 Fax: +44 (0) 20 8580 1062
Website: www.flexconnectors.co.uk Email: info@flexconnectors.co.uk
Leaflet reference number: 22/035 issue 2 07/08/2012
Try to split into zones where the changes in daylight are reasonably consistent. Darker areas may then be controlled via alternative means such as on/off without consideration to
light level. You may even consider sufficient natural light reaches these areas to justify a second light level sensing circuit.
Note: Always fit the sensor head as close as possible to the centre of the group of lights under its control. Do not site where the sensor head could receive direct sunlight.
Configuring the controller and wiring the connection unit
Setting up your sensor
Link in position 1
Prise open lid 'C' using a screw driver. Position link as
C
1 2
Lights can remain ON during an emergency test. Wire connection unit as shown on page 6.
required.
Link in position 2
1 2
Lights will switch OFF during an emergency test. Wire connection unit as shown on page 6.
Rating
Supply Voltage : 230V~ 50Hz
Load
Fluorescent & Incandescent Lighting : 6A Compact Fluorescent Lighting : 3A
Maximum number of Ballast
fnc3000D/U (DSI Digital control) : 25 fnc3000D/U (DALI Digital control) : 25 fnc3000D/U (Analogue 0-10V control) : 25
Sensor head and occupancy detection performance
Fnh400 sensor head
LED
I.R.
receiver
Light cell
The sensor head has a rectangular occupancy detection range broadly 7.4m x 5.6m at a ceiling height of
Occupancy sensor
2.5m (Longest length of detection aligning with the spring clips). As the ceiling height increases so will the overall detection area but sensitivity to small movements will decrease. Note: Make sure that the sensor is not adjacent to circulating air, heaters or lamps.
31.3 mm
40.0 mm
The sensor head fits
19.5 mm
hole, with clips which
into a 32mm diameter
can grip ceiling panels down to 1.5mm thick
12.3 mm
.
Detection Zone
Max. 7.42m
3m
2
1
X X
1
2
3m
3 3
Y
Y
112 2
The X-Y cross-sectional diagram shows the detection area. The differences in the detection zone patterns indicate the projections of the 16 lenses with a single focal point. Movement of an object with higher than background temperature, between the detection zones, will be detected.
Detection Zone
Max. 5.66m
4m4m
5.0m
View X-X
2.5m
O
50
2.5m
0
5.0m 2.5m 2.5m
5.0m
XX
Y
O
50
O
41
0
View Y-Y
5.0m
O
41
Y
frc/set
frc/user
fnh/Slave
Fsl--
Fsw--
Fsy/a
Fsy/2e/2/0
Setup Remote Control - frc/set
Your sensor comes factory set with a 20 minute occupancy time out, however you will require an frc/set remote control (ordered separately) to set up daylight linking. You may also require one if another time out period is required (2,5,10,20 and 40 minutes) or other operational options are desired. Full instruction for setting up the sensor are supplied with the frc/set remote control.
Optional Extras/Spares
User Remote Control - frc/user
The frc/user remote control is a convenient method for the user to control the lighting
remotely. Lights can be temporarily overridden ON or OFF dimmed UP or DOWN. In addition, up to six preset light levels can be stored and recalled.
Note: Unlike the frc/set remote control the frc/user remote control can not be used to
setup or change occupancy time-out settings.
Increasing Occupancy Coverage -
Occupancy coverage can be increased by adding up to a maximum of five slave sensor
fnh/slave The fnh/slave comes complete with a
heads ( ) to your existing sensor head. 'Y' adaptor to facilitate connection.
A connecting lead may also be required, part number fslXX (XX = length /5m).
Increasing Occupancy Coverage -
Occupancy coverage can be increased by adding up to a maximum of five slave sensor heads ( ) to your existing sensor head.
fnh/slave The fnh/slave comes complete with a
'Y' adaptor to facilitate connection.
A connecting lead may also be required, part number fslXX (XX = length /5m).
PELV - Switch Drop
To add additional switches a PELV switch drop lead and a fsy/a will be required to connect the additional switch to the control unit.
Fsy/a
If your room requires additional sensor heads (fnh/slave) or additional switch drops you will require an fsy/a to link your additional cables into.
Fsy/2e/2/o
If your room requires 2-way switching you will require in addition: 1 x fsy/2e/2/0 - ‘Y’ adaptor for 2 x 2-way. 1 x fswXX - Switch drop lead. (XX = length in metres in multiples of 5m).
fnh/slave
fnh/slave
2 7
(Connection unit shown) fsu06
Switching Option 1
Absence + Manual dimming using a 3-position retractive Switch
Earth
Neutral
Em/L
Option B
Wiring
Fsl05
E
fnc3000D/U
E
5
6
3
4
Earth
2
Em/L
Neutral
1
Aux/L
Option A
Wiring
configuring link
for details on
See page 2
Circuit diagram for fnc3000(D,X or A)/U Controller
fnh400
Note:
For best operation it is advisable that occupancy coverage extends to cover the wall switch.
fnc3000X/U fnc3000A/U
E
Operation:
E
5
6
3
4
2
1
Dim
R1
12
*
(Orange) (White) (Brown) (Grn/Yel) (Blue) (Black)
Emergency
luminaire
Switch control:
ON pulse - turns the lights ON with daylight linking activated. OFF pulse - turns the lights OFF. A long ON pulse - brightens lights (eventually to maximum & daylight linking will be deactivated). A long OFF pulse - dims lights (eventually to minimum &daylight linking will be deactivated, but should the pulse exceed 15 secs the lights will switch OFF completely).
Absence detection: When occupancy is no longer detected, lights will switch OFF after a pre-selected time-out period (default 20 minutes).
Daylight linking: Provided daylight linking is activated (see switch control above) the light output will adjust to compensate for any changes in ambient light in order to maintain a constant light level under the sensor head - the target level.
Note: Alternative operational options not necessarily shown above are available using the frc/set
setup remote control.
Full instructions for setting up the sensor are supplied with the sensor head and the frc/set remote
control - both ordered separately.
Fsw10
3-position, centre off,
retractive switch
(not supplied)
Note: Multiple switches can be
connected in parallel. 'Y' connectors are available to enable two switch drop leads to be connected into one point.
(Part No. fsy/A - adaptor)
Switch wiring
3 Position Retracive
OFF/Dim Down
ON/Dim Up
*
(Orange) (White) (Brown) (Grn/Yel) (Blue)
D1/10V
Sw/L
D2/0V
6 3
Earth
Em/L
Neutral
Aux/L
Luminaire
Switching Option 2
Switching Option 3
Absence + Manual dimming using a 1-way Retractive Switch
Fsl05
fnc3000D/U
fnh400
Note:
For best operation it is advisable that occupancy coverage extends to cover the wall switch.
fnc3000X/U fnc3000A/U
Operation:
Switch control:
Pulse - turns the lights ON or OFF with daylight linking activated if turning ON. Long pulse - Alternates from brightening the light to dimming the light with each consecutive long pulse, deactivates daylight linking, (but should the pulse exceed 15 secs the lights will switch OFF completely).
Absence detection: When occupancy is no longer detected, lights will switch OFF after a pre-selected time-out period (default 20 minutes).
Daylight linking: Provided daylight linking is activated (see switch control above) the light output will adjust to compensate for any changes in ambient light in order to maintain a constant light level under the sensor head - the target level.
Note: Alternative operational options not necessarily shown above are available using the frc/set
setup remote control.
Full instructions for setting up the sensor are supplied with the sensor head and the frc/set remote
control - both ordered separately.
Fsw10
1-way,
retractive switch
(not supplied)
Note: Multiple switches can be
connected in parallel. 'Y' connectors are available to enable two switch drop leads to be connected into one point.
(Part No. fsy/A - adaptor)
Switch wiring
Toggle/Dim
Occupancy with override Switching
Fsl05
fnc3000D/U
fnh400
Note:
For best operation it is advisable that occupancy coverage extends to cover the wall switch.
fnc3000X/U fnc3000A/U
Operation:
Switch control:
Override OFF - turns the lights OFF (takes priority over sensing). Occupancy detection: Provided the wall switch is in the 'Sensor' position the lights will switch ON with daylight linking activated, whenever there is occupancy detected by the sensor head. When occupancy is no longer detected, lights will switch OFF after a pre-selected time-out period (default 20 minutes). Daylight linking: While lights are ON due to occupancy their light output will adjust to compensate for any changes in ambient light in order to maintain a constant light level under the sensor head - the target
level.
Note: Alternative operational options not necessarily shown above are available using the frc/set
setup remote control.
Full instructions for setting up the sensor are supplied with the sensor head and the frc/set remote
control - both ordered separately.
Fsw10
1-way,
retractive switch
(not supplied)
Note: If your room requires 2-way
switching, a special 'Y' connector is available to enable two switch drop leads to be connected.
(Part No. fsy/2e/2 - OFF control from
2 x 2-way switches)
Switch wiring
Cut back & insulate unwanted cores.
Sensor
Override OFF
Other switching options incorporating override ON
Note:
You may not be able to claim enhanced capital allowances under the Carbon Trust scheme if you incorporate local
Latched Option
Cut back & insulate unwanted cores.
Latched Option
Sensor
Override ON
or
Override OFF
'override ON' switches in your occupancy sensor scheme.
Cut back & insulate unwanted cores.
4
Override ON
5