Flavel REGENT L.F.E Instruction

Page 1
REGENT L.F.E.
BATTERY IGNITION
LIVE FUEL EFFECT CONVECTOR GAS FIRE
Installation and Maintenance Instructions
Hand these instructions to the user
Model No’s FRLCP0EN & FRLCN0EN are for use on Natural Gas (G20) at a supply pressure of 20 mbar in G.B. / I.E.
Page 2
CONTENTS
Installation Instructions Page
Appliance Data 3
Section 1 1.1 Conditions of installation. 4
1.2 Flue & chimney suitability 4
1.3 Fireplace/surround suitability 5
1.4 Shelf position 5
1.5 Side clearance 5
1.6 Closure plate 5
1.7 Flue & chimney inspection 5-6
1.8 Chimney catchment space 6
1.8.1 Brick built chimney 6-7
1.8.2 Fitting to pre-fab. twin wall metal flueboxes 7
1.8.3 Fitting to pre-cast flue installations 8
1.9 Hearth fitting 8
1.10 Spillage monitoring system 8
Section 2 2.1 Packing check list 9
2.2 Installation of fire 9-10
2.3 Gas connection 11
2.4 Fitting the fuel-bed 11-12
2.5 Gas tightness 12
2.6 Fitting the battery 12-13
Section 3 3.1 Lighting the appliance 13
3.2 Checking for clearance of combustion products 14-15
3.3 Final checks 15
Section 4
Maintenance Instructions
4.1 General access for servicing 16
4.1.1 Removal of the upper canopy 16-17
4.2 Removal of the burner assembly 17-18
4.3 Removal of the control tap 18-19
4.4 Removal of the ODS 20
2
Page 3
APPLIANCE DATA
Main injector (1 off) Size 380, Cat 82 Pilot Type. Copreci Single Flame Type 21100 / 178
Max. Gross Heat Input : 6.1 kW Min. Gross Heat Input : 1.8 kW
Cold Pressure : 20.0 +/- 1.0 mbar (8.0 +/- 0.4 in w.g.)
IIgnition : Battery Ignition, 1.5V
Electrode Spark Gap : 4.0 mm
Weight (Packed) : 22.0kg
Firebox Dimensions (with case fitted)
Width : 710mm Height : (without feet fitted) 680mm Depth : 255mm Height to top of the flue spigot : 425mm (with feet fitted)
Gas Connection : 8mm compression
(Supplied with fire)
Efficiency Declaration
The efficiency of this appliance has been measured as specified in BS 7977-1 : 2002 and the result is 67%. The gross calorific value of the fuel has been used for this efficiency calculation. The test data from which it has been calculated has been certified by BSI. The efficiency value may be used in the UK Government’s Standard Assessment Procedure (SAP) for energy rating of dwellings.
3
Page 4
1.1 CONDITIONS OF INSTALLATION
In Great Britain :-
It is law that all gas appliances are installed only by a GAS SAFE registered installer in GB, in accordance with these installation instructions and the Gas Safety (Installation and use) Regulations 1998. Failure to install appliances correctly could lead to prosecution. It is in your own interest and that of safety to comply with the law. The installation must also be in accordance with all relevant parts of the Local and National Building regulations where appropriate, the Building Regulations (Scotland Consolidation) issued by the Scottish Development Department, and all relevant recommendations of the following British Standard Code of Practice.
1. B.S. 5871. Part 1. Installation of Gas Fires.
2. B.S. 5440.: 2000 Parts 1 & 2. Installation of Flues & Ventilation.
3. B.S. 6891. Installation of Gas Pipework.
4. B.S. 6461. Part 1. Installation of Chimneys & Flues.
5. B.S. 1251. Open Fireplace Components.
6. B.S. 715. Metal Flue pipes for Gas Appliances.
7. B.S. E.N. 1858 Clay Flue blocks and Terminals.
8. B.S. 7566 Installation of factory-made Chimneys.
Ventilation Requirements
For use in G.B. purpose built ventilation is not normally required for this appliance.
In Republic of Ireland
For use in I.E. this appliance must be installed in accordance with the rules in force by a competent person and used only in a sufficiently ventilated space. Please consult document I.S. 813 : 1996 Domestic Gas Installation, issued by the National Standards Authority of Ireland.
1.2 FLUE AND CHIMNEY SUITABILITY
The appliance is designed for use with conventional brick built chimneys or lined chimneys and pre – fabricated flues. It is also suitable for use with pre-cast flue blocks conforming to BS EN 1858 and metal flue boxes conforming to BS 715. All flues must conform to the following minimum dimensions.
Minimum diameter of circular flues 125 mm Minimum effective height of all flue types 3 metres
Minimum cross sectional area of Pre-cast Flues 122.7 cm
:-
2
4
Page 5
1.3 FIREPLACE / SURROUND SUITABILITY
The fire is suitable for hearth mounting only. It must not carpet or other combustible material. It must not be wall mounted. This fire is suitable for the following hearth / surround types :­Non-combustible hearths / surrounds. Purpose made proprietary hearths / surrounds with a minimum temperature rating
of 100oC.
If a heating appliance is fitted directly against a wall without the use of a fire­place or fire surround, soft wall coverings such as wallpaper, blown vinyl, etc. could be affected by the heat and may, therefore scorch or become discoloured. Please bear this in mind when installing or decorating.
1.4 SHELF POSITION
The fire may be fitted below a combustible shelf providing there is a minimum distance of 100 mm above the top of the fire and the shelf does not project more than 150 mm. If the shelf overhangs more than 150 mm the distance between the fire and the shelf must be increased by 25 mm for every 25 mm of additional overhang over 150 mm.
1.5 SIDE CLEARANCE
A minimum clearance of 100mm should be allowed on either side of the fire for servicing. Any fire surround uprights should not project forward by more than 100mm. NOTE. The fire must be installed so that no part of a combustible side wall when measured laterally is less than 500mm from the fuelbed ceramics.
be fitted directly onto a
1.6 CLOSURE PLATE
A closure plate is supplied with this fire and must be fitted. The closure plate must be sealed to the fireplace or surround opening with suitable adhesive tape. See section 2.2.2
1.7 FLUE / CHIMNEY INSPECTION
Before commencing installation, a flue or chimney should be inspected to ensure that all the following conditions are satisfied.
a) Check that the chimney / flue only serves one fireplace and is clear of
any obstruction. Any obstruction. Any dampers or register plates must be removed or locked in the open position.
5
Page 6
b) Brick / stone built chimneys and any chimney or flue which has been
used for an appliance burning fuel other than gas must be thoroughly swept. The base of the chimney/flue must also be thoroughly cleared of debris etc.
Any under floor air supply to the fireplace must be completely sealed off.
Ensure that the inside of the chimney/flue is in good condition along its length and check that there is no leakage of smoke through the structure of the chimney during and after the smoke pellet test.
With pre-cast flues it is especially important to check the inside of the flue for extruded cement / sealant protruding from the joints between the flue blocks. If present, these should be removed by rodding the flue before proceeding with the installation.
Using a smoke pellet, check that there is a positive up draught present in the chimney / flue and that the smoke can be seen issuing from the terminal / chimney pot outside. There must be no leakage of smoke through the structure of the chimney during or after the smoke pellet test and it is important to check inside upstairs rooms adjacent to the chimney / flue. Check the chimney pot / terminal and general condition of the chimney brickwork or masonry. If the chimney or flue is in poor condition or if there is no up draught do not proceed with the installation. If there is a history of down draught conditions with the chimney / flue, a tested and certified flue terminal or cowl suitable for the relevant flue type should be considered.
A spillage test must always be carried out during commissioning of the appliance.
1.8 CHIMNEY CATCHMENT SPACE.
1.8.1 Brick Built Chimneys.
The catchment space below the flue spigot should be as deep as possible, and must not be less than 250mm measured from the bottom of the flue spigot to the bottom of the catchment space, or to the top of any “bricking-up” of the fireplace, whichever is the least. See Fig. 1.
The flue spigot must pass through the closure plate at least 25mm and have a minimum clearance of 50mm between its open end and the nearest obstruction. There must be a minimum clearance of 165mm between the back of the closure plate and the back of the catchment space. See Fig. 1 overpage.
6
Page 7
The front opening of the fireplace must be between 305mm and 440mm wide, and between 525mm and 650mm high. If the opening is larger than this, then a surround must be constructed in a suitable non-com bustible material to create an opening to these limits. Allow a minimum flat surface of 20mm around the opening to ensure that the closure plate can be sealed to the fireplace. Any surround must be sealed to the fireplace to prevent leakage. The operation of the chimney should be tested a detailed as in section 1.7.
Note. A flue spigot extension of up to a maximum total length of 125mm may be fitted if necessary, providing that a minimum clearance 50mm between its open end and nearest obstruction is always maintained.
Fig.1. Chimney Catchment Space.
1.8.2 Fitting to Pre-Fabricated twin wall metal Flue Boxes.
The appliance may be fitted to a twin wall metal flue box conforming to the constructional requirements of BS 715, (for example the Selkirk LFE 125 box). The box must have a minimum flue diameter of 125mm internal and minimum internal dimensions of 160mm deep by 580mm high by 350mm wide. There are no maximum dimensional requirements for the box. The top face of the box must be insulated with a minimum thickness of 50mm of non-combustible mineral wool insulation or similar material. The flue box must stand on a non-combustible base of minimum thickness 12mm.
7
Page 8
1.8.3 Fitting to Pre-Cast Flue Installations.
The appliance is suitable for use with pre-cast flues conforming to B.S.
EN 1858. The pre-cast opening must be a minimum of 122.7cm2or equivalent cross-sectional area and have a minimum effective flue height of 3 metres. The flue spigot restrictor must be removed when installing into pre-cast flue applications
This appliance has been tested for use in a pre-cast flue block complying with BS EN 1858. In accordance with BS EN 1858, pre-cast flues built with directly plastered faces (front or rear) are not correctly installed as to ensure proper operation with any type of gas fire. In some instances of this flue construction, temperature cracking of surface plaster may occur through no fault of the appliance. An air gap or some form of insulation material should be installed to prevent normal flue temperatures from damaging wall surfaces.
1.9 HEARTH FITTING
This appliance must only be installed on to a level concrete or non­combustible hearth. The feet must not be removed when installing directly onto a hearth.The hearth material must be a minimum thickness of 13 mm with the top surface at least 50 mm above the floor level. The hearth must be fitted symmetrically about the fire opening and have a minimum width of 760 mm and a minimum projection of 300 mm forwards from the fire opening.
1.10 SPILLAGE MONITORING SYSTEM
This appliance is fitted with an atmosphere sensing spillage monitoring system in the form of an oxygen sensing pilot. This is designed to shut the fire off in the event of partial or complete blockage of the flue causing a build up of combustion products in the room in which the fire is operating. The following are important warnings relating to the
spillage monitoring system:
The spillage monitoring system must not be adjusted by the Installer. The spillage monitoring system must not be put out of action. When the spillage monitoring system is exchanged, only a complete original manufacturers part may be fitted. It is not possible to replace individual parts on the pilot system on the appliance, only a complete pilot assembly (including thermocouple) may be fitted.
8
Page 9
2.1 PACKING CHECK LIST
1 off Firebox / Burner Assembly 1 off Flue Spigot 1 off Efficiency Baffle 1 off Closure Plate 1 off AA Battery 1 off Literature / Loose Items Pack 1 off Fuelbed Pack
2.2 INSTALLATION OF FIRE
2.2.1 Preparation.
a) Remove the dress guard by springing the location wires out at the
bottom and lifting away. See Fig. 2. Take care not to scratch the trim.
Fig. 2 Remove the Dress Guard.
b) Fit the flue spigot to the back panel using four screws provided.
9
Page 10
Closure plate.
a) Fit the closure plate to the fireplace opening and ensure that it has a flat
sealing area of at least 10mm sealed on all sides. See Fig. 3 below Dimensions stated are for closure plate supplied
Fig. 3
Closure Plate
460mm
Dimensions
Fireplace Opening Dimensions
660mm
390mm to CTR
Spigot Opening
168 x 68mm
305mm Minimum 440mm Maximum
Air Relief Openings
525mm Minimum 650mm Maximum
Minimum 10mm Flat Sealing Area
Check the operation of the chimney as follows:-
Apply a smoke match to the flue spigot opening in the closure plate and observe the smoke. If there is a definite flow into the opening then proceed with the installation. If there is not a definite flow into the opening, pre-heat the chimney for about two minutes and retest for flow. If there still is no definite flow into the open­ing, the chimney may require attention. DO NOT FIT THE FIRE-SEEK EXPERT ADVICE.
10
Page 11
2.3 GAS CONNECTION
Note :
A means of isolation must be provided near to the appliance to facilitate servicing.
Ensure that the gas supply is turned off before commencing. The gas connection should be made to the appliance inlet elbow using 8 mm rigid tubing. The gas connection can be made left hand, right hand or rear. In line with current installation regulations, a restrictor should be fitted to the inlet pipework to isolate the appliance for servicing and repair purposes.
Before making the final gas connection, thoroughly purge the gas supply pipe work to remove all foreign matter, otherwise serious damage may be caused to the gas control valve on the fire.
2.4 FITTING THE FUELBED
a) Fit the rear fuelbed section to the combustion chamber, locating behind
the support bracket as indicated below in fig. 4
Fig. 4
Fit rear section of fuelbed behind support bracket as shown
b) Fit the front section of the fuelbed to the combustion chamber, locating
behind the front casting as shown overpage in fig. 5
11
Page 12
Fig. 5
Fuelbed front section fits behind the front casting as shown
c) Refit the dress guard.
2.5 GAS TIGHTNESS
a) Remove the pressure test point screw from the inlet elbow and fit a
manometer.
b) Turn on the main gas supply, fit the battery as described in section 2.6
then carry out a gas tightness test.
c) Check that the gas pressure is 20.0 mbar (± 1.0 mbar), 8.0 in w.g. +/-
0.4 in w.g. with the main burner running.
d) Turn off the fire, remove the manometer and refit the pressure test point
screw. Check the pressure test point screw for gas tightness with the appliance turned on using a suitable leak detection fluid or detector.
2.6 FITTING THE BATTERY
a) The battery holder is located at the bottom R/H/S rear of the fire,
unscrew the cap, fit the AA battery supplied in the loose items pack and re-fit the cap. See fig. 6 overpage.
12
Page 13
Fig. 6 FITTING THE BATTERY (CONT.)
Spark Generator
Battery Cap
AA Battery
3.1 LIGHTING THE APPLIANCE
a) Light the pilot by depressing the control knob at the “off” position and
turn anti-clockwise (with the control depressed) to the second position marked *.
b) When the pilot lights, (pilot can be seen through the right hand side of
the fuelbed) hold the control knob down for 10 seconds.
c) If the pilot fails to light, repeat the ignition sequence and hold in the
control knob for slightly longer.
d) When the pilot has lit, release the control knob from the depress
position, depress slightly again and turn the control anti-clockwise to the high position and check for clearance of combustion products as detailed overleaf.
13
Page 14
3.2 CHECKING FOR CLEARANCE OF COMBUSTION PRODUCTS
a) Close all doors and windows in the room. Remove the dress guard.
b) Light the fire and turn to the maximum position.
After 5 minutes hold the smoke match as shown in fig. 7. Whilst hold ing the smoke match in the correct position, approximately 5mm below and inside the lower edge of the centre of the canopy. Ensure that most of the smoke is drawn into the flue aperture. If in doubt repeat the exercise after a further 5/10 minutes.
Note:- It is recommended that the smoke match is fitted into an approved
smoke match holder, when checking for clearance of combustion products.
Fig. 7
Smoke match position approx. 5mm below and inside the front edge of the combustion chamber lid.
e) If the smoke is not drawn into the flue aperture, remove the efficeincy
baffle from the spigot, then repeat the procedure as detailed in section a) & b) above. If the spillage test is still not successful, then carry out procedure as detailed overpage.
If there is an extractor fan fitted in a joining room, then the spillage test must be repeated with the fan switched on and running at maximum speed. All interconnecting doors must be opened in accordance with the latest issue of BS
5440.
14
Page 15
IF SPILLAGE IS DETECTED
The cause must be discovered and the fault corrected. If the fault cannot be corrected disconnect the appliance from the gas supply and seek expert advice. Possible causes of spillage from the appliance (if the efficiency baffle has been removed) are :- chimney restriction, down draught or insufficient air supply to the room.
g) After ensuring that the fire is safe to use it should be left on “High”
position to fully warm up. During this time a slight odour may be noticed, this is due to the “newness” of the fire and will soon disappear.
3.3 FINAL CHECK
a) Refit the dress-guard if it has not already been re-fitted. b) Recheck the operation of the fire on all settings. c) Make sure that the user knows how to operate the fire and refer them
to the user book.
d) Inform the user that the model number for ordering parts is shown on
the rating plate. The rating plate can be viewed at the bottom left hand side of the rear panel.
e) Inform the user the fire should be serviced annually for continued safe
operation.
f) Hand this instruction booklet to the customer.
IF A REPLACEMENT FUELBED IS REQUIRED :-
When replacing the fuelbed remove the old fuelbed and discard it. Fit a complete fuelbed of the correct type.
To ensure that the release of fibres from these R.C.F (Refractory Ceramic Fibre) articles is kept to a minimum, during installation and servicing we recommend that you use a HEPA filtered vacuum to remove any dust accumulated in and around the appliance before and after working on the appliance. When replacing these articles we recommend that the replaced items are not broken up, but are sealed within heavy duty polythene bags, clearly labelled as “RCF waste”. RCF waste is classed as a “stable”, non reactive hazardous waste and may be disposed of at a landfill licensed to accept such waste Protective clothing is not required when handling these articles, but we recommend you follow the normal hygiene rules of not smoking, eating or drinking in the work area, and always wash your hands before eating or drinking.
15
Page 16
MAINTENANCE INSTRUCTIONS
Servicing Notes
Servicing should be carried out annually by a competent person such as a GAS SAFE registered engineer. The service should include visually checking the chimney and fire opening for accumulations of debris and a smoke test to check for positive up-draught in the chimney. The condition of the fuelbed should be checked and if necessary the whole set should be replaced with a genuine replacement set. After any servicing work a gas tightness test must always be carried out.
4.1 GENERAL ACCESS FOR SERVICING
4.1.1 TO REMOVE THE UPPER CANOPY
a) Prepare work area (lay down dustsheets etc.), Disconnect the appliance
from the gas supply.
b) Remove the four canopy rear fixing screws, and the two fixing screws
that are located on the underside of the canopy (see fig. 8 & 9 respec tively)
c) Remove the fuelbed and move to a safe place, then lift away the
canopy
d) Re-assemble in the reverse order.
Fig. 8 Removing the four canopy rear fixing screws
16
Fixing Screws
Page 17
Fig. 9 Removing the Upper Outer Case Fixing Screws
Fixing Screws
4.2 REMOVING THE BURNER ASSEMBLY FROM THE FIRE
a) Disconnect the appliance from the gas supply. Remove the front panel
by unscrewing the retaining nuts below the front panel as shown in fig. 10 below.
Fig. 10
Front panel retaining bolts
b) Remove the front bezel by unscrewing the 2 retaining screws, as shown
in fig. 11 overpage.
17
Page 18
Fig. 11
Front bezel retaining screws (1 off each side)
c) Unhook the burner heat shield from the L/H & R/H retaining holes and
lift forward to remove, as shown below in fig. 12
Fig. 12
Burner retaining screws (2 off at each end of burner)
Burner Heat Shield is removed by unhooking from the holes as shown
d) Remove the four burner retaining screws, disconnect the pilot assy. and
lift the burner clear
18
Page 19
4.3 REMOVING THE GAS VALVE FROM THE FIRE
a) Disconnect the appliance from the gas supply.
b) Remove the upper canopy as shown in section 4.1
c) Remove the left hand side panel, by unscrewing the rear panel fixing
screws, then the base panel retaining screw, as shown below in fig. 13
Fig. 13
Rear side panel retaining screws
Front retaining screw on the underside of the leg support bracket
c) Disconnect the pipes to the control valve, ignition wires and the control
valve locknut as shown below in fig. 14
Fig. 14
Gas Inlet Pipe
Main Supply Pipe
Pilot Pipe
Control Valve Locknut
19
Page 20
d) Remove the thermocouple, which is a push fit into the rear of the control
valve.
4.4 REMOVING THE ODS- PILOT ASSEMBLY
Note : Because this appliance is fitted with an atmosphere sensing ODS-pilot it is not possible to replace the thermocouple separately, because the thermocouple position is factory set to a tight tolerance. Any replacement of parts on the pilot requires a complete new pilot assembly.
a) Remove the front panel and front bezel as described in section 4.2
b) Unscrew the pilot fixing screws. These can be accessed from the front
of the appliance with the front panel and bezel removed.
c) Remove the thermocouple as described in section 4.3. (d)
20
Page 21
PARTS SHORTLIST
Replacement of any other parts must be carried out by a competent person such as a GAS SAFE registered gas installer. The part numbers of the user replaceable parts are as follows, these are available from specialist spares stockists whose details can be found on our web site, www.bfm-europe.com, in the ‘stockist’ section.
Fuelbed Set B-66010 Gas valve B-135670 ODS Pilot Assy. (NG) B-66500 Control Knob B-137500 Injector B-66390
Due to our policy of continual improvement and development the exact accuracy of illustrations and descriptions contained in this book cannot be guaranteed.
21
Page 22
REGENT L.F.E.
BATTERY IGNITION LIVE FUEL EFFECT CONVECTOR
GAS FIRE
User Instructions
This section of the instructions should be read by the user before operating the appliance and retained for future reference
Model No’s FRLCP0EN & FRLCN0EN are for use on Natural Gas (G20) at a supply pressure of 20 mbar in G.B. / I.E.
Page 23
INSTALLATION INFORMATION
CONDITIONS OF INSTALLATION
It is the law that all gas appliances are installed only by a competent (e.g. GAS SAFE Registered) Installer, in G.B. in accordance with the installation instructions and the Gas Safety (Installation and Use) Regulations 1998. Failure to install appliances correctly could lead to prosecution. It is in your own interest and that of safety to comply with the law.
The fire may be fitted below a combustible shelf provided that the shelf is at least 200mm above the top of the appliance and the depth of the shelf does not exceed 150mm.
The fire may be installed below combustible shelves which exceed 150mm deep providing that the clearance above the fire is increased by 15mm for each 25mm of additional overhang in excess of 150mm.
No purpose made additional ventilation is normally required for this appliance when installed in G.B. When installed I.E. please consult document I.S. 813 : 1996 Domestic Gas Installation which is issued by the National Standards Authority of Ireland. Any purpose made ventilation should be checked periodically to ensure that it is free from obstruction.
If the chimney or flue has been previously used by appliances burning fuels other than gas they must be swept prior to the installation of this fire.
If this appliance is fitted directly on to a wall without the use of a fireplace or surround, soft wall coverings such as wallpaper, blown vinyl etc. could be affected by the heat and hot air and may discolour or scorch. This should be considered when installing or decorating.
The Model number of this appliance is as stated on the rating plate affixed to the inner rear panel of the fire and the appliance is manufactured by:-
BFM Europe Ltd Trentham Lakes Stoke on Trent ST4 4TJ
2
Page 24
ABOUT YOUR NEW FLAVEL REGENT LFE GAS FIRE
The Flavel Regent LFE gas fire incorporates a unique and highly developed fuelbed which gives good flame aeshetics whilst maintaining reasonable running costs.
Please take the time to fully read these instructions as you will then be able to obtain the most effective and safe operation of your fire.
IMPORTANT SAFETY INFORMATION
WARNING
This appliance has a naked flame and as with all heating appliances a fireguard should be used for the protection of children, the elderly and infirm. Fireguards should conform to B.S. 8423 : 2002 should be fitted.
(Fireguards for use with gas heating appliances).
It is important that this appliance is serviced at least once a year by a GAS SAFE registered gas installer and that during the service the fire is removed from the fire opening and the chimney or flue visually checked for fallen debris or blockages which must be removed. The chimney should also be checked to ensure clearance of flue products. We recommend that during the annual service, replacement of the Oxypilot is carried out. After installation or during servicing
a spillage test must always be carried out.
Rubbish of any type must NEVER be thrown onto the ceramics, this could affect safe operation and damage the fire. Any debris or deposits should be removed from the fuel-bed from time to time. This may be carried out by referring to the cleaning section as described later in this book. Only the correct type of fuelbed ceramics must be used and only complete and genuine replacement sets must be sourced from BFM Europe Ltd.
Always keep furniture and combustible materials well clear of the fire and never dry clothing or items either on or near to the fire. Never use aerosols or flammable cleaning products near to the fire when it is in use.
The ceramic fuel-bed remains hot for a considerable period after use and sufficient time should be allowed for the fire to cool before cleaning etc. The fire must only be operated with the dress guard supplied with the fire
3
Page 25
OPERATING THE FIRE
a) Light the pilot by depressing the control knob at the “off” position and
turn anti-clockwise (with the control depressed) to the second position marked *.
b) When the pilot lights, (pilot can be seen through the right hand side of
the fuelbed) hold the control knob down for 10 seconds.
c) If the pilot fails to light, repeat the ignition sequence and hold in the
control knob for slightly longer.
d) When the pilot has lit, release the control knob from the depress
position, depress slightly again and turn the control anti-clockwise to the HIGH position.
WARNING
If the fire goes out for any reason or is turned off and it is necessary to relight the fire it is important to allow the fire to cool for 3 minutes before attempting to re-light it.
SPILLAGE MONITORING SYSTEM
This appliance is fitted with a spillage monitoring system which shuts down the fire if the evacuation of combustion products from the fire is affected by a partially or fully blocked flue. If this system operates the fire will go out. If this occurs, leave the fire for at least three minutes then follow the lighting procedure as described in the previous section. In the event of repeated operation a GAS SAFE registered gas
installer must be called to investigate and rectify the cause.
CLEANING - WARNING
Before attempting any cleaning operation ensure that the fire has been allowed to fully cool.
CLEANING THE FUELBED CERAMICS
We do not recommend regular cleaning of the fuelbed ceramics as these are fragile and damage may result. None of these parts must be washed or exposed to any cleaning agents or water. Any damaged parts must be replaced by contacting your dealer or telephoning BFM Europe Ltd. on the number stated on the rear cover of this book. The fuelbed ceramics must only be replaced with a complete and genuine replacement set and the fire must never be run with the wrong number or damaged fuelbed ceramics. The ceramic fuelbed must be carefully re-assembled as stated in the following section.
4
Page 26
LIGHTING WITH A SPILL
Important do not light with a wax taper
In the unlikely event of the piezo ignition unit failing to light the fire, turn the control knob to the OFF position, and wait a minute or so for the gas to disperse. The fire can then be lit by using a spill.
a) Apply a lighted spill through bottom window of the central radiants.
Light the pilot by depressing the control knob at the “off” position and turn anti-clockwise (with the control depressed) to the second position marked *.
b) When the pilot lights, remove the spill and continue to hold the control
knob down for 10 seconds.
c) If the pilot fails to light, repeat the ignition sequence and hold in the
control knob for slightly longer.
d) When the pilot has lit, release the control knob from the depressed
position, depress slightly again and turn the control anti-clockwise to the high position.
WARNING : Before attempting any cleaning operation ensure that the fire has been allowed to fully cool.
CLEANING THE DRESSGUARD OR REFLECTOR.
Remove the dress-guard by pulling the location wire out at the top, and lifting away. See fig. 2 overpage. Clean the dress-guard or reflector by wiping with a damp cloth, and polish with a dry duster. DO NOT USE ABRASIVE CLEANERS
CLEANING THE CASE.
Dusting is normally all that is required. But where extra cleaning is necessary, use a damp cloth.
5
Page 27
Fig. 2
REMOVAL / REFITTING OF THE FUELBED CERAMICS
a) Fit the rear fuelbed section to the combustion chamber, locating behind
the support bracket as indicated below in fig. 3
Fig. 3
Fit rear section of fuelbed behind support bracket as shown
b) Fit the front section of the fuelbed to the combustion chamber, locating
behind the front casting as shown overpage in fig. 4
6
Page 28
Fig. 4
c) Refit the dress guard.
Fuelbed front section fits behind the front casting as shown
7
Page 29
REPLACING THE BATTERY IN THE IGNITION GENERATOR
The battery holder is located at the bottom R/H/S of the fire, unscrew the cap, fit a new AA battery and re-fit the cap. See fig. 5 below.
Fig. 5
Spark Generator
Battery Cap
AA Battery
IN THE EVENT OF THE FIRE FAILING TO LIGHT, PLEASE VISUALLY CHECK FOR SPARKING AT THE IGNITION ELECTRODE ON THE PILOT. IF NO SPARK IS PRESENT PLEASE REPLACE THE BATTERY AS DETAILED IN ABOVE. SERVICE CALLS THAT ARE A DIRECT RESULT OF FLAT BATTERIES WILL BE CHARGED FOR BY THE MANUFACTURER AS THE BATTERY IN THE FIRE IS A CONSUMABLE ITEM THAT WILL REQUIRE ROUTINE REPLACEMENT.
8
Page 30
Due to our policy of continual improvement and development the exact accuracy of descriptions and illustrations cannot be guaranteed
Part No. B-147300
Issue 1
BFM Europe Ltd Trentham Lakes
Stoke-on-Trent
Staffordshire
ST4 4TJ
www.bfm-europe.com
Telephone - General Enquiries : (01782) 339000 Telephone - Service : (0844) 7700169
Loading...