Supplied By www.heating spares.co Tel. 0161 620 6677
Emberglow
COAL
Installation and Maintenance Instructions
Hand these instructions to the user
Model No’s FEBC00MN is for use on Natural Gas (G20) at a
supply pressure of 20 mbar in G.B. / I.E.
EFFECT BALANCED FLUE GAS FIRE
Page 2
Supplied By www.heating spares.co Tel. 0161 620 6677
CONTENTS
Section 1Information and Requirements
1.0Appliance Information3
1.1Conditions of Installation4
1.2Fireplace surround & suitability4
1.3Flue Terminal Position5
1.4Shelf position6
1.5Hearths6
Section 2Installation of Fire
2.1Unpacking the fire6
2.2Preparation of the wall7
2.3Preparation of the flue hole8
2.4Preparation of the flue pipes9
2.5Installation of the gas supply10-11
2.6Securing of the combustion chamber to the wall11-12
2.7Fitting the terminal guard12
2.8
Section 3Assembling Fuel Bed and Commissioning
3.1Fitting the fuel bed14
3.2Lighting the appliance15-16
3.3Fitting the fender17
3.4Fitting the canopy17
Removal & refitting of the glass frame
PAGE
13
Section 4Maintenance
4.1Removal of the Burner Assembly18
4.2Removal of the Control Valve18-19
4.3Removal of the Battery Pack19
4.4Removal of the Pilot Assembly19
4.5Removal of the Touch Control Switch
The model no. of this appliance is on the rating plate, which is affixed to the
battery pack retaining bracket on the front right hand side of the fire. The product
is manufactured by:-
CFM Europe Ltd, Trentham Lakes, Stoke-on-Trent, Staffordshire, ST4 4TJ
2
19-20
Page 3
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 1
INFORMATION AND REQUIREMENTS
1.0APPLIANCE INFORMATION
Main injector : (1 off)
Bray Injector Elbow – size 360
Pilot Type :S.I.T.140 Series NG – size 27
Max. Gross Heat Input :5.25 kW
Min. Gross Heat Input :2.05 kW
Gas Rate : 0.470 m3/hr (High)
0.190 m3/hr (Low)
Cold Pressure :20.0+/-1.0 mbar (8.0 +/- 0.4 in w.g.)
Ignition :Integral to gas valve
Electrode Spark Gap :4.0mm
Weight (Product & Fender) :33 kg
Weight (Canopy) :23 kg
Fig 1 -
445mm
Product
Dimensions
290mm
645mm
716mm
198mm
673mm
3
Page 4
Supplied By www.heating spares.co Tel. 0161 620 6677
INSTALLATION REQUIREMENTS
1.1CONDITIONS OF INSTALLATION
In Great Britain :-
It is the law that all gas appliances are installed only by a CORGI Registered
Installer
(Installation and Use) Regulations 1998 as amended. Failure to install appliances
correctly could lead to prosecution. It is in your own interest and that of safety to
comply with the law.
The installation must also be in accordance with all relevant parts of the Local and
National Building Regulations where appropriate, the Building Regulations
(Scotland Consolidation) issued by the Scottish Development Department, and all
applicable requirements of the following British Standard Code of Practice.
1. B.S. 5871 Part 3 Installation of Decorative Fuel Effect Gas Fires
2. B.S. 6891 Installation of Gas Pipework
3. B.S. 5440 Parts 1 & 2 Installation of Flues and V
4. I.S. 813 : 1996 Domestic Gas Installation (Republic of Ireland)
If installing this product into a timber framed building, please consult document
IGE / UP 7, issued by the Institute of Gas Engineers.
In Republic of Ireland :No purpose made additional ventilation is normally required for this
appliance, when installed in G.B. When Installing in I.E. please consult
document I.S. 813 : 1996 Domestic Gas Installation, which is issued by the
National Standards Authority of Ireland. If installing in Northern Ireland,
please consult local building regulations. Any purpose made ventilation
must be checked periodically to ensure that it is free from obstruction.
, in accordance with these installation instructions and the Gas Safety
entilation
1.2FIREPLACE / SURROUND SUITABILITY
The fire must only be installed on a hearth it must not be installed directly onto
carpet or other combustible floor materials.
The fire is suitable for fitting to non-combustible fire place surrounds and propri
etary fire place surrounds with a temperature rating of at least 150oc.
If a heating appliance is fitted directly against a wall without the use of a fire
surround or fire place all combustible material must be removed from behind
the trim. Soft wall coverings such as blown vinyl, wall paper etc. could be
affected by the rising hot air and scorching and/or discoloration may result.
Due consideration should be made to this when installing or decorating.
4
-
Page 5
Supplied By www.heating spares.co Tel. 0161 620 6677
1.3FLUE TERMINAL POSITION
The minimum acceptable dimensions from the flue terminal to obstructions
and ventilation openings are shown below and listed in the table
It is important that the position of the flue allows the free passage of air
across it at all times. The minimum acceptable space from the flue terminal
to obstructions and ventilation openings are specified below (Fig. 2)
Fig. 2
DIMENSION TERMINAL POSITION MINIMUM DIMENSION
ADirectly below an opening, air brick, 300mm (12in)
opening window
BAbove an opening, air brick, 300mm (12in)
opening window
CHorizontally to an opening, air brick,
opening window etc.
DBelow gutters, soil pipes or drain pipes 300mm (12in)
EBelow eaves 300mm (12in)
FBelow balconies or car port roof600mm (12in)
GFrom a vertical drain pipe or soil pipe 300mm (12in)
HFrom an internal or external corner 600mm (24in)
IAbove ground roof or balcony level 300mm (12in)
JFrom a surface facing the terminal 600mm (24in)
KFrom a terminal facing the terminal 600mm (24in)
LFrom an opening in the car port 1200m (48in)
MVertically from a terminal on the same wall 1500mm(59in)
NHorizontally from a terminal on the 300mm (12in)
Supplied By www.heating spares.co Tel. 0161 620 6677
1.4SHELF POSITION
The fire may be fitted below a combustible shelf providing there is a minimum dis
tance of 200mm above the top of the fire and the shelf does not project more than
150mm. If the shelf overhangs more than 150mm the distance between the fire
and the shelf must be increased by 15mm for every 25mm of additional overhang
over 150mm.
1.5HEARTHS
This appliance must only be installed on to a level concrete or non-combustible
hearth.
hearth material must be a minimum thickness of 13 mm with the outer perimeter of
the hearth panel at least 50 mm above the floor level, to discourage the placing of
carpet or other floor coverings over it. The hearth must be fitted symmetrically
about the fire opening and have a minimum width of 760 mm and a minimum
projection of 350 mm forwards from the fire opening.
The feet must not be removed when installing directly onto a hearth.The
SECTION 2
INSTALLATION OF FIRE
2.1UNPACKING THE FIRE
Carefully lift the fire out of the carton. Remove the loose item packaging carefully
from the the pack. Check the contents as listed :-
DO NOT UNDER ANY CIRCUMSTANCES USE THIS APPLIANCE IF THE
GLASS PANEL IS BROKEN OR NOT SECURELY FIXED TO THE FIREBOX.
-
Packing Check List
Pack 1 of 1
1offCombustion chamber / burner assembly
1off2 piece fuel-bed set (packed in seperate carton)
1off
1offInstallation & Maintenance Instruction Book
1offUser Instruction Book
1off
1offCooler plate
2off
2offDecorative side trims & 4 off side trim fixing screws
Pack 2 of 2
1offCast iron canopy assembly
Flue pipe and flue terminal unit
Loose items pack
Brass finials - to be screwed into casting upon commisioning
6
Page 7
Supplied By www.heating spares.co Tel. 0161 620 6677
2.2PREPARATION OF THE WALL
The appliance and flue pipes must be installed at right angles to the mounting
wall.
The appliance itself should be installed vertically against a flat wall. Where
an uneven wall surface is found, appropriate action should be taken to ensure that
the appliance is not stressed or does not distort when installed.
Ensure that the floor surface onto which the appliance is mounted onto is flat, and
the hearth size conforms to the requirements of section 1.5 on page 6.
The minimum height from the floor to the centre of the flue is shown on fig. 3
below.
Fig. 3
153mm
420mm to centre
line of flue from
hearth level
Hearth
A
min / max sized opening with a flat rear face between the fire opening and flue
outlet terminal is shown below. (fig 4).
Fig. 4
Outer Wall
Minimum Cavity Depth
Flue Terminal
Combustion Chamber
150mm. Maximum Flue
Length 680mm
7
Page 8
Supplied By www.heating spares.co Tel. 0161 620 6677
2.3PREPARATION OF THE FLUE HOLE
a)
Mark the position of the centre of the flue on the inner wall.
b)Cut hole for outer flue pipe. There are two possible methods to achieve
this, either core drill or via hammer and chisel.
c)To core drill, proceed as follows :-
Drill a pilot hole through the wall, in position as specified in figure 4.
Using a 6” core drill, drill the flue hole.
To Hammer and chisel, proceed as follows :Mark the position of the centre of the flue pipe as specified in figure 4.
Mark the position of the hole around this point.
Chisel out the area as marked on the wall.
We then recommend that a cardboard cylinder is placed around the flue pipe and
inserted in the chiselled out hole whilst making good.
NOTE :- If the appliance is to be installed into a building under
construction, it is recommended that a non-corrosive metal tube of 6”
diameter be inserted into the position of the hole as specified on page 7.
Prior to installing the combustion chamber and flue pipe assembly
, ensure the
decorative side trims are secured with the screws as shown below in Fig. 5 a
Fig. 5a
Decorative Side
Trims screw to side
panel of fire with
screws provided
8
Page 9
Supplied By www.heating spares.co Tel. 0161 620 6677
2.4PREPARATION OF THE FLUE PIPES
a)Measure the wall thickness and add on 110mm, to give the correct
length of the flue.
b)Mark this dimension onto the flue pipe, measuring from the end at
which the terminal is located.
c)Cut of f surplus flue length that is not required, and remove any burrs
from the edges with a burr knife or file.
d)Push the flue pipe / terminal assembly firmly into the rear of the
combustion chamber as shown below in Fig. 5
e)Drill 3 off holes, through outer flue pipe and into the mounting spigot,
and screw flue pipe and terminal assembly into place, as shown below
in Fig. 5b
Fig. 5b
3 off holes to be drilled
into spigot ring and 3 off
screws to be used to
secure flue pipe to
spigot ring.
Seal around flange with foil
tape supplied
IMPORTANT : DO NOT CUT FLANGED ENDS OF FLUE PIPE & ENSURE THE
PIPES ARE CUT SQUARELY.
f)Using mortar or sealing compound, seal the outer flue pipe to the out
side surface of the wall, (See Fig. 6 for position of mortar).
9
Page 10
Supplied By www.heating spares.co Tel. 0161 620 6677
Fig. 6
2.5INSTALLATION OF THE GAS SUPPLY
Position of
Mortar or Fire
Cement Seal
around Flue
terminal
a)
Fig. 7
Left hand
gas supply
route
An 8mm restrictor elbow is supplied fitted to the product for the
connection of the gas supply. This elbow is situated on the right hand
side of the product when viewed from the front. It is therefore suitable
for rear or right hand side gas supply. See Fig. 7 below.
Flue terminal
Combustion
Chamber
viewed from top
Rear gas
supply route
Right hand
gas supply
route
Pressure Test Point and
Restrictor elbow
connection point located
at the bottom R/H side
of the appliance
10
Page 11
Supplied By www.heating spares.co Tel. 0161 620 6677
Note : Before breaking into the gas supply a pressure drop test should be
carried out to establish that the existing pipework is sound.
b)
Before making the final gas connection, thoroughly purge the gas
supply pipework to remove all foreign matter, otherwise serious
damage may be caused to the gas control valve on the fire.
Failure to purge the gas supply will invalidate the guarantee.
c)
The gas connection should be made to the appliance inlet elbow to
using 8mm rigid tubing.
d)
Remove the pressure test point screw from the inlet elbow and fit a
manometer.
e)T
urn on the main gas supply and carry out a gas tightness test.
f)To light the appliance, refer to section 3.2 on pages 15 to 17.
NOTE : Please ensure that the battery that has been disconnected at the factory prior
to packing is re-connected. The battery is located at the bottom L/H/S of the
combustion chamber, attach the flying lead to it
g)Check that the gas pressure is 20.0 mbar (+/- 1.0mbar) 8.0 in w.g.(+/-
0.4 in w.g.)
h)Turn off the fire, remove the manometer and refit the pressure test point
screw
. Check the pressure test point screw for gas tightness with the
appliance turned on using a suitable leak detection fluid or detector.
2.6 SECURING OF THE COMBUSTION CHAMBER T O THE WALL
a)
Fig. 8
The combustion chamber should be secured to the wall using the
4 off screws and rawlplugs provided. Drill 4 off 6.0mm diameter holes
into the wall behind the product as shown below in Fig. 8
495mm
6 inch / 150mm core
drilled hole to suit
the flue pipes at
420mm height
75mm
463mm
Dimensions from top
face of the hearth
panel to centre of
mounting holes
11
Page 12
Supplied By www.heating spares.co Tel. 0161 620 6677
b)Fit the rawlplugs into the 6mm holes.
c)Clip the cooler plate into the bottom central fixing and into the left hand
and right hand mouning brackets (the same brackets used in section d)
below)
d)The mounting brackets are attached to the rear of the combustion
chamber
long philips screwdriver, secure the 2 off screws into the wall behind the
product.
NOTE :In England & Wales, the building regulations require that a terminal
guard should be fitted if the terminal could come into contact with people
near the building or be subject to damage. CFM Europe also recommend the
fitting of a flue terminal guard where regulations do not demand that it be
fitted. A suitable flue terminal guard can be obtained from CFM Europe Ltd.
quoting part no. 70-46560
2.7FITTING THE OPTIONAL EXTRA TERMINAL GUARD
With the flue terminal in position, place the terminal guard over the top of the flue
terminal and mark the position of the holes on the outer wall. Remove the terminal
guard and drill the 4 off 6 mm holes. Insert the rawl plugs into the drilled holes,
replace the terminal guard over the top of the flue terminal and attach to the wall
using the No.12 x 40mm screws provided with the terminal guard. See Fig. 9
below.
, position the product against the mounting wall and using a
Fig. 9
12
Page 13
Supplied By www.heating spares.co Tel. 0161 620 6677
2.8REMOVING / RE-FITTING THE GLASS FRAME ASSEMBLY
a)
The glass frame is held in position by hooking the top flange over the
combustion chamber opening at the top as shown in Fig. 10 below
Fig. 10
Glass Frame Assembly
locates over lip on top of
combustion chamber lid, and
drops onto flange as shown.
To remove, unclip base clips
as shown in Fig. 11 and lift
clear.
b)
The assembly is then secured to the bottom of the combustion chamber
by the two hinge clamp brackets as shown below in Fig. 11. These are
clamped together to form the seal between the glass frame assembly
and the combustion chamber.
.
Combustion
Chamber
denotes correct
final position of
glass frame.
NOTE :Always ensure that a consistent seal between the combustion
chamber and the glass frame is achieved.
Fig. 11
13
Page 14
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 3
ASSEMBLING FUEL BED AND COMMISSIONING
3.1FITTING THE FUELBED
a)Place the fuel-bed rear section centrally in the combustion chamber as
shown below in Fig. 12
Fig. 12
Retaining brackets
for front coal form
Retaining brackets for rear coal form
b)Fit the front ceramic coal form in front of the burner, as shown below in
Fig 13. Ensure that the front ceramic coal form is correctly located
behind the retaining brackets at the L/H & R/H ends.
Fig. 13
14
Page 15
Supplied By www.heating spares.co Tel. 0161 620 6677
Refit the glass frame as detailed in section 2.8, then light the appliance as detailed
in section 3.2 below.
3.2LIGHTING THE APPLIANCE
IMPORTANT : IF THE BURNER IS EXTINGUISHED FOR ANY REASON YOU MUST ENSURE THAT
YOU WAIT A FULL FIVE MINUTES BEFORE ATTEMPTING TO RE-LIGHT THE FIRE.
Fig. 14
X
Pilot
Control
Knob
a)Locate the control valve on the appliance, it is situated below the
combustion chamber in the centre. There are two control knobs on the
appliance, the left control knob controls the pilot ignition, the right hand
control knob controls the main burner. This appliance is designed to
run with the pilot permantly running, and the touch control can then be
used to light the main burner, and control the gas rate between high and
low. See Fig. 14 above for layout of controls.
b)
c)Turn the left hand control anticlockwise to the large flame position and
d) To adjust the heat input manually :-
Depress the left control knob and rotate it anti-clockwise to the position
marked pilot. (a click will be heard). Hold in the control knob for a few
seconds whilst the air is purged from the supply pipe. Bring the knob
back to its start position and turn it several times to the pilot position.
The pilot should light. Hold in the control knob for at least 10 seconds
to allow the thermocouple to heat up. Release the control knob. If the
pilot fails to light, repeat the procedure as detailed above.
this allows the gas flow to enter the main burner section of the control
valve. The main burner can then be controlled either manually on the
valve or by the touch control switch, located at the bottom of the right
hand side panel.
With the pilot lit as detailed in section c) turn the right hand control knob
anticlockwise to the X position (see Fig. 14 above).
enter the main burner and be ignited by the pilot flame. Once the main
burner has been lit, the right hand control knob can be adjusted to any
position between the large flame (5.45kW heat input) position and the
small flame (2.05kW heat input) position.
Main Burner
Control
Knob
This allows gas to
15
Page 16
Supplied By www.heating spares.co Tel. 0161 620 6677
e)To adjust the heat input via the touch control :-
Press the “up” button to light the main burner and adjust the heat input
to the maximum setting. (5.45kW heat input). Press the “down”
button to reduce the heat input to the minimum setting (2.05kW heat
input). If the low button is pressed and held continuously, the fire
will go pass the minimum setting and extinguish the flames
completely. See Fig. 15 below.
Fig. 15
“Up” button to increase heat
input
“Down” button to decrease
heat input or turn off main
burner
NOTE :The touch control does not light the pilot, it only lights
the main burner when the pilot flame is established and regulates
the heat input between high and low.
f)Check that the gas pressure is 20.0 mbar (+/- 1.0mbar) 8.0 in w.g.(+/-
0.4 in w
.g.) with the main burner operating on “high”.
To turn off the main burner :-
g)Turn right hand control knob clockwise to the position marked
or press the down button on the remote handset until the flame
extinguishes, at this point a clicking noise will be heard from the motor
To turn off the pilot flame :-
h)Turn left hand control knob clockwise to the position marked
and the pilot flame will extinguish.
i)After ensuring that the fire is safe to use it should be left on high
position to fully warm up. During this time a slight odour may be
noticed, this is due to the “newness” of the fire and will soon disappear
16
.
.
Page 17
Supplied By www.heating spares.co Tel. 0161 620 6677
AFTER THE PILOT FLAME HAS BEEN EXTINGUISHED, IF
RE-LIGHT THE APPLIANCE YOU MUST WAIT AT LEAST FIVE MINUTES
BEFORE TRYING TO RE-LIGHT THE APPLIANCE.
Finally
, hand the Installation and Maintenance Instructions and the Users
Instructions over to the customer and explain the operation of the fire.
YOU WISH TO
NOTE : THIS APPLIANCE IS DESIGNED TO WORK SAFELY AND
EFFECTIVELY DURING ADVERSE WEATHER CONDITIONS.
HOWEVER, DURING SUCH TIMES FLAME DISTURBANCE MAY BE
NOTICED. THIS IS NORMAL AND DOES NOT EFFECT OR IMPAIR
THE SAFETY OF THE APPLIANCE.
3.3FITTING OF THE FENDER
Warning : Please take care whilst handling the fender as it’s cast iron
construction means it is a heavy item that can be difficult to manoeuvere
a)Fit the fender by locating the two retaining brackets on the fender into
the slotted channel on the front of the combustion chamber
3.4FITTING OF THE CANOPY
W
arning : Please take care whilst handling the canopy as it’
construction means it is a heavy item that can be difficult to manoeuvere
s cast iron
a)The canopy is held in position by two off retaining screws at each side.
b)Fig. 16 below shows the position of the retaining screws for the canopy
Fig. 16
17
Page 18
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 4
MAINTENANCE
Servicing Notes
Servicing should be carried out annually by a competent person such as a
CORGI registered engineer. It is a condition of Flavel Fires 2 year guarantee
scheme that this is carried out by a competent person i.e a CORGI
registered Engineer in accordance with these servicing notes.
The condition of the ceramic coal forms should be checked and if necessary
the whole set should be replaced with a genuine replacement set.
After any servicing work a gas tightness check must always be
carried out.
4.1Removing the Burner Assembly from the fire.
4.1.1Isolate the gas supply.
4.1.2Remove fender from the front of the fire, as described in section 3.3 on
page 17
4.1.3Remove the glass frame assembly from the fire, as shown in section
2.8 on page 13.
4.1.4
4.1.5
4.1.6Slide the burner of
4.2Removing the Control Valve from the fire.
4.2.1Isolate the gas supply.
4.2.1Remove the fender as described in section 3.3, on page 17
4.2.2Disconnect the pipe to the bulkhead fitting on the valve and disconnect
4.2.3Loosen the pilot pipe, disconnect the ignition lead from the electrode
4.2.5Remove the 2 off fixing screws which hold the valve mounting plate to
Remove the ceramic coal forms from the combustion chamber
taking care not to damage them.
Remove the two M4 burner retaining screws, located at the front of
each end of the burner.
f the rear injector and remove from the product.
the pipe on the valve which runs to the inlet elbow
and disconnect the thermocouple from the pilot assembly
its mounting bracket and lift the valve and its mounting plate away from
the combustion chamber.
18
.
.
Page 19
Supplied By www.heating spares.co Tel. 0161 620 6677
4.2.6
4.2.7Re-assemble with new valve in reverse order.
4.3Removing the Battery Pack
4.3.1Disconnect the wire from the battery pack, located at the bottom
4.3.2Lift the battery pack out of its mounting cradle.
4.3.3Re-fit the new battery pack in its cradle and re-fit the wire.
4.4Removing the Pilot Assembly
Swap the valve mounting plate onto the new valve by unscrewing the
two M5 nuts and bolts holding it in position .
L/H/S of the combustion chamber.
4.4.1
4.4.2Remove the fender as described in section 3.3, on page 17
4.4.3Remove the glass frame assembly from the fire, as shown in section
4.4.4
4.4.5Loosen the pilot pipe, disconnect the ignition lead from the electrode,
4.4.6Remove the two fixing screws which secure the pilot assembly to the
4.4.7Remove the pilot assembly.
4.4.8Re-assemble with an new pilot assembly, and gasket, ensuring that an
4.5Replacing the Touch Control Switch
4.5.1Remove the right hand side panel from the fire. Remove the touch
Isolate the gas supply
2.8 on page 13.
Remove the ceramic coal forms from the combustion chamber
taking care not to damage them.
and remove the thermocouple from the pilot body.
pilot mounting panel in the base of the combustion chamber
even seal around the pilot assembly is obtained. Carry out a gas
tightness test after re-assembly.
control switch by releasing the nuts that hold it in position on the inside
face.
.
4.5.2Remove the connecting wires from the top left hand side of the
control valve.
19
Page 20
Supplied By www.heating spares.co Tel. 0161 620 6677
4.5.2Fit new switch and re-assemble in reverse order
PARTS SHORTLIST
Replacement of any other parts must be carried out by a competent person such
as a CORGI registered gas installer. The part numbers of the main replaceable
parts are as follows, these are available from your local Flavel Stockist, whose
details can be found on the CFM Europe website, in the “stockist” section.
Control ValveB-82290Pilot Body70-36250
Thermocouple
Ignition Electrode70-36290Ceramic / Coal SetFC-P086110
Due to our policy of continual improvement and development the exact
accuracy of illustrations and descriptions contained in this book cannot be
guaranteed
70-36270Pilot Gasket70-35220
Part No. B-86710
Issue 2
CFM Europe Ltd.
Trentham Lakes
Stoke-on-Trent
Staffordshire
ST4 4TJ
www.cfm-europe.com
Telephone - Service :(08700) 101187
Page 21
Supplied By www.heating spares.co Tel. 0161 620 6677
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.