Flavel Emberglow FEBC00MN Installation And Maintenance Instructions Manual

Page 1
Supplied By www.heating spares.co Tel. 0161 620 6677
Emberglow
COAL
Installation and Maintenance Instructions
Hand these instructions to the user
Model No’s FEBC00MN is for use on Natural Gas (G20) at a supply pressure of 20 mbar in G.B. / I.E.
EFFECT BALANCED FLUE GAS FIRE
Page 2
Supplied By www.heating spares.co Tel. 0161 620 6677
CONTENTS
Section 1 Information and Requirements
1.0 Appliance Information 3
1.1 Conditions of Installation 4
1.2 Fireplace surround & suitability 4
1.3 Flue Terminal Position 5
1.4 Shelf position 6
1.5 Hearths 6
Section 2 Installation of Fire
2.1 Unpacking the fire 6
2.2 Preparation of the wall 7
2.3 Preparation of the flue hole 8
2.4 Preparation of the flue pipes 9
2.5 Installation of the gas supply 10-11
2.6 Securing of the combustion chamber to the wall 11-12
2.7 Fitting the terminal guard 12
2.8
Section 3 Assembling Fuel Bed and Commissioning
3.1 Fitting the fuel bed 14
3.2 Lighting the appliance 15-16
3.3 Fitting the fender 17
3.4 Fitting the canopy 17
Removal & refitting of the glass frame
PAGE
13
Section 4 Maintenance
4.1 Removal of the Burner Assembly 18
4.2 Removal of the Control Valve 18-19
4.3 Removal of the Battery Pack 19
4.4 Removal of the Pilot Assembly 19
4.5 Removal of the Touch Control Switch
The model no. of this appliance is on the rating plate, which is affixed to the battery pack retaining bracket on the front right hand side of the fire. The product is manufactured by:-
CFM Europe Ltd, Trentham Lakes, Stoke-on-Trent, Staffordshire, ST4 4TJ
2
19-20
Page 3
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 1
INFORMATION AND REQUIREMENTS
1.0 APPLIANCE INFORMATION
Main injector : (1 off)
Bray Injector Elbow – size 360 Pilot Type : S.I.T.140 Series NG – size 27 Max. Gross Heat Input : 5.25 kW
Min. Gross Heat Input : 2.05 kW Gas Rate : 0.470 m3/hr (High)
0.190 m3/hr (Low) Cold Pressure : 20.0+/-1.0 mbar (8.0 +/- 0.4 in w.g.) Ignition : Integral to gas valve Electrode Spark Gap : 4.0mm Weight (Product & Fender) : 33 kg
Weight (Canopy) : 23 kg
Fig 1 -
445mm
Product Dimensions
290mm
645mm
716mm
198mm
673mm
3
Page 4
Supplied By www.heating spares.co Tel. 0161 620 6677
INSTALLATION REQUIREMENTS
1.1 CONDITIONS OF INSTALLATION
In Great Britain :-
It is the law that all gas appliances are installed only by a CORGI Registered Installer (Installation and Use) Regulations 1998 as amended. Failure to install appliances correctly could lead to prosecution. It is in your own interest and that of safety to comply with the law.
The installation must also be in accordance with all relevant parts of the Local and National Building Regulations where appropriate, the Building Regulations (Scotland Consolidation) issued by the Scottish Development Department, and all applicable requirements of the following British Standard Code of Practice.
1. B.S. 5871 Part 3 Installation of Decorative Fuel Effect Gas Fires
2. B.S. 6891 Installation of Gas Pipework
3. B.S. 5440 Parts 1 & 2 Installation of Flues and V
4. I.S. 813 : 1996 Domestic Gas Installation (Republic of Ireland) If installing this product into a timber framed building, please consult document
IGE / UP 7, issued by the Institute of Gas Engineers.
In Republic of Ireland :­No purpose made additional ventilation is normally required for this
appliance, when installed in G.B. When Installing in I.E. please consult document I.S. 813 : 1996 Domestic Gas Installation, which is issued by the National Standards Authority of Ireland. If installing in Northern Ireland, please consult local building regulations. Any purpose made ventilation must be checked periodically to ensure that it is free from obstruction.
, in accordance with these installation instructions and the Gas Safety
entilation
1.2 FIREPLACE / SURROUND SUITABILITY The fire must only be installed on a hearth it must not be installed directly onto
carpet or other combustible floor materials.
The fire is suitable for fitting to non-combustible fire place surrounds and propri etary fire place surrounds with a temperature rating of at least 150oc.
If a heating appliance is fitted directly against a wall without the use of a fire surround or fire place all combustible material must be removed from behind the trim. Soft wall coverings such as blown vinyl, wall paper etc. could be affected by the rising hot air and scorching and/or discoloration may result. Due consideration should be made to this when installing or decorating.
4
-
Page 5
Supplied By www.heating spares.co Tel. 0161 620 6677
1.3 FLUE TERMINAL POSITION
The minimum acceptable dimensions from the flue terminal to obstructions and ventilation openings are shown below and listed in the table It is important that the position of the flue allows the free passage of air across it at all times. The minimum acceptable space from the flue terminal to obstructions and ventilation openings are specified below (Fig. 2)
Fig. 2
DIMENSION TERMINAL POSITION MINIMUM DIMENSION
A Directly below an opening, air brick, 300mm (12in)
opening window
B Above an opening, air brick, 300mm (12in)
opening window
C Horizontally to an opening, air brick,
opening window etc. D Below gutters, soil pipes or drain pipes 300mm (12in) E Below eaves 300mm (12in) F Below balconies or car port roof 600mm (12in) G From a vertical drain pipe or soil pipe 300mm (12in) H From an internal or external corner 600mm (24in) I Above ground roof or balcony level 300mm (12in) J From a surface facing the terminal 600mm (24in) K From a terminal facing the terminal 600mm (24in) L From an opening in the car port 1200m (48in) M Vertically from a terminal on the same wall 1500mm(59in) N Horizontally from a terminal on the 300mm (12in)
same Wall O NOT APPLICABLE N/A P NOT APPLICABLE N/A Q NOT APPLICABLE N/A
5
Page 6
Supplied By www.heating spares.co Tel. 0161 620 6677
1.4 SHELF POSITION
The fire may be fitted below a combustible shelf providing there is a minimum dis tance of 200mm above the top of the fire and the shelf does not project more than 150mm. If the shelf overhangs more than 150mm the distance between the fire and the shelf must be increased by 15mm for every 25mm of additional overhang over 150mm.
1.5 HEARTHS
This appliance must only be installed on to a level concrete or non-combustible hearth. hearth material must be a minimum thickness of 13 mm with the outer perimeter of the hearth panel at least 50 mm above the floor level, to discourage the placing of carpet or other floor coverings over it. The hearth must be fitted symmetrically about the fire opening and have a minimum width of 760 mm and a minimum projection of 350 mm forwards from the fire opening.
The feet must not be removed when installing directly onto a hearth.The
SECTION 2
INSTALLATION OF FIRE
2.1 UNPACKING THE FIRE
Carefully lift the fire out of the carton. Remove the loose item packaging carefully from the the pack. Check the contents as listed :-
DO NOT UNDER ANY CIRCUMSTANCES USE THIS APPLIANCE IF THE GLASS PANEL IS BROKEN OR NOT SECURELY FIXED TO THE FIREBOX.
-
Packing Check List Pack 1 of 1 1off Combustion chamber / burner assembly
1off 2 piece fuel-bed set (packed in seperate carton) 1off 1off Installation & Maintenance Instruction Book 1off User Instruction Book 1off 1off Cooler plate 2off 2off Decorative side trims & 4 off side trim fixing screws
Pack 2 of 2 1off Cast iron canopy assembly
Flue pipe and flue terminal unit
Loose items pack
Brass finials - to be screwed into casting upon commisioning
6
Page 7
Supplied By www.heating spares.co Tel. 0161 620 6677
2.2 PREPARATION OF THE WALL
The appliance and flue pipes must be installed at right angles to the mounting wall.
The appliance itself should be installed vertically against a flat wall. Where an uneven wall surface is found, appropriate action should be taken to ensure that the appliance is not stressed or does not distort when installed. Ensure that the floor surface onto which the appliance is mounted onto is flat, and the hearth size conforms to the requirements of section 1.5 on page 6. The minimum height from the floor to the centre of the flue is shown on fig. 3 below.
Fig. 3
153mm
420mm to centre line of flue from hearth level
Hearth
A
min / max sized opening with a flat rear face between the fire opening and flue
outlet terminal is shown below. (fig 4).
Fig. 4
Outer Wall
Minimum Cavity Depth
Flue Terminal
Combustion Chamber
150mm. Maximum Flue Length 680mm
7
Page 8
Supplied By www.heating spares.co Tel. 0161 620 6677
2.3 PREPARATION OF THE FLUE HOLE
a)
Mark the position of the centre of the flue on the inner wall.
b) Cut hole for outer flue pipe. There are two possible methods to achieve
this, either core drill or via hammer and chisel.
c) To core drill, proceed as follows :-
Drill a pilot hole through the wall, in position as specified in figure 4. Using a 6” core drill, drill the flue hole. To Hammer and chisel, proceed as follows :­Mark the position of the centre of the flue pipe as specified in figure 4. Mark the position of the hole around this point. Chisel out the area as marked on the wall.
We then recommend that a cardboard cylinder is placed around the flue pipe and inserted in the chiselled out hole whilst making good.
NOTE :- If the appliance is to be installed into a building under construction, it is recommended that a non-corrosive metal tube of 6” diameter be inserted into the position of the hole as specified on page 7.
Prior to installing the combustion chamber and flue pipe assembly
, ensure the
decorative side trims are secured with the screws as shown below in Fig. 5 a
Fig. 5a
Decorative Side Trims screw to side panel of fire with screws provided
8
Page 9
Supplied By www.heating spares.co Tel. 0161 620 6677
2.4 PREPARATION OF THE FLUE PIPES
a) Measure the wall thickness and add on 110mm, to give the correct
length of the flue.
b) Mark this dimension onto the flue pipe, measuring from the end at
which the terminal is located.
c) Cut of f surplus flue length that is not required, and remove any burrs
from the edges with a burr knife or file.
d) Push the flue pipe / terminal assembly firmly into the rear of the
combustion chamber as shown below in Fig. 5
e) Drill 3 off holes, through outer flue pipe and into the mounting spigot,
and screw flue pipe and terminal assembly into place, as shown below in Fig. 5b
Fig. 5b
3 off holes to be drilled into spigot ring and 3 off screws to be used to secure flue pipe to spigot ring.
Seal around flange with foil tape supplied
IMPORTANT : DO NOT CUT FLANGED ENDS OF FLUE PIPE & ENSURE THE PIPES ARE CUT SQUARELY.
f) Using mortar or sealing compound, seal the outer flue pipe to the out
side surface of the wall, (See Fig. 6 for position of mortar).
9
Page 10
Supplied By www.heating spares.co Tel. 0161 620 6677
Fig. 6
2.5 INSTALLATION OF THE GAS SUPPLY
Position of Mortar or Fire Cement Seal around Flue terminal
a)
Fig. 7
Left hand gas supply route
An 8mm restrictor elbow is supplied fitted to the product for the connection of the gas supply. This elbow is situated on the right hand side of the product when viewed from the front. It is therefore suitable for rear or right hand side gas supply. See Fig. 7 below.
Flue terminal
Combustion Chamber viewed from top
Rear gas supply route
Right hand gas supply route
Pressure Test Point and Restrictor elbow connection point located at the bottom R/H side of the appliance
10
Page 11
Supplied By www.heating spares.co Tel. 0161 620 6677
Note : Before breaking into the gas supply a pressure drop test should be carried out to establish that the existing pipework is sound.
b)
Before making the final gas connection, thoroughly purge the gas supply pipework to remove all foreign matter, otherwise serious damage may be caused to the gas control valve on the fire. Failure to purge the gas supply will invalidate the guarantee.
c)
The gas connection should be made to the appliance inlet elbow to using 8mm rigid tubing.
d)
Remove the pressure test point screw from the inlet elbow and fit a manometer.
e) T
urn on the main gas supply and carry out a gas tightness test.
f) To light the appliance, refer to section 3.2 on pages 15 to 17.
NOTE : Please ensure that the battery that has been disconnected at the factory prior to packing is re-connected. The battery is located at the bottom L/H/S of the
combustion chamber, attach the flying lead to it
g) Check that the gas pressure is 20.0 mbar (+/- 1.0mbar) 8.0 in w.g.(+/-
0.4 in w.g.)
h) Turn off the fire, remove the manometer and refit the pressure test point
screw
. Check the pressure test point screw for gas tightness with the
appliance turned on using a suitable leak detection fluid or detector.
2.6 SECURING OF THE COMBUSTION CHAMBER T O THE WALL
a)
Fig. 8
The combustion chamber should be secured to the wall using the 4 off screws and rawlplugs provided. Drill 4 off 6.0mm diameter holes into the wall behind the product as shown below in Fig. 8
495mm
6 inch / 150mm core drilled hole to suit the flue pipes at 420mm height
75mm
463mm
Dimensions from top face of the hearth panel to centre of mounting holes
11
Page 12
Supplied By www.heating spares.co Tel. 0161 620 6677
b) Fit the rawlplugs into the 6mm holes. c) Clip the cooler plate into the bottom central fixing and into the left hand
and right hand mouning brackets (the same brackets used in section d) below)
d) The mounting brackets are attached to the rear of the combustion
chamber long philips screwdriver, secure the 2 off screws into the wall behind the product.
NOTE : In England & Wales, the building regulations require that a terminal guard should be fitted if the terminal could come into contact with people near the building or be subject to damage. CFM Europe also recommend the fitting of a flue terminal guard where regulations do not demand that it be fitted. A suitable flue terminal guard can be obtained from CFM Europe Ltd. quoting part no. 70-46560
2.7 FITTING THE OPTIONAL EXTRA TERMINAL GUARD
With the flue terminal in position, place the terminal guard over the top of the flue terminal and mark the position of the holes on the outer wall. Remove the terminal guard and drill the 4 off 6 mm holes. Insert the rawl plugs into the drilled holes, replace the terminal guard over the top of the flue terminal and attach to the wall using the No.12 x 40mm screws provided with the terminal guard. See Fig. 9 below.
, position the product against the mounting wall and using a
Fig. 9
12
Page 13
Supplied By www.heating spares.co Tel. 0161 620 6677
2.8 REMOVING / RE-FITTING THE GLASS FRAME ASSEMBLY
a)
The glass frame is held in position by hooking the top flange over the combustion chamber opening at the top as shown in Fig. 10 below
Fig. 10
Glass Frame Assembly locates over lip on top of combustion chamber lid, and drops onto flange as shown. To remove, unclip base clips as shown in Fig. 11 and lift clear.
b)
The assembly is then secured to the bottom of the combustion chamber by the two hinge clamp brackets as shown below in Fig. 11. These are clamped together to form the seal between the glass frame assembly and the combustion chamber.
.
Combustion Chamber
denotes correct final position of glass frame.
NOTE : Always ensure that a consistent seal between the combustion
chamber and the glass frame is achieved.
Fig. 11
13
Page 14
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 3
ASSEMBLING FUEL BED AND COMMISSIONING
3.1 FITTING THE FUELBED
a) Place the fuel-bed rear section centrally in the combustion chamber as
shown below in Fig. 12
Fig. 12
Retaining brackets for front coal form
Retaining brackets for rear coal form
b) Fit the front ceramic coal form in front of the burner, as shown below in
Fig 13. Ensure that the front ceramic coal form is correctly located behind the retaining brackets at the L/H & R/H ends.
Fig. 13
14
Page 15
Supplied By www.heating spares.co Tel. 0161 620 6677
Refit the glass frame as detailed in section 2.8, then light the appliance as detailed in section 3.2 below.
3.2 LIGHTING THE APPLIANCE
IMPORTANT : IF THE BURNER IS EXTINGUISHED FOR ANY REASON YOU MUST ENSURE THAT YOU WAIT A FULL FIVE MINUTES BEFORE ATTEMPTING TO RE-LIGHT THE FIRE.
Fig. 14
X
Pilot Control Knob
a) Locate the control valve on the appliance, it is situated below the
combustion chamber in the centre. There are two control knobs on the appliance, the left control knob controls the pilot ignition, the right hand control knob controls the main burner. This appliance is designed to run with the pilot permantly running, and the touch control can then be used to light the main burner, and control the gas rate between high and low. See Fig. 14 above for layout of controls.
b)
c) Turn the left hand control anticlockwise to the large flame position and
d) To adjust the heat input manually :-
Depress the left control knob and rotate it anti-clockwise to the position marked pilot. (a click will be heard). Hold in the control knob for a few seconds whilst the air is purged from the supply pipe. Bring the knob back to its start position and turn it several times to the pilot position. The pilot should light. Hold in the control knob for at least 10 seconds to allow the thermocouple to heat up. Release the control knob. If the pilot fails to light, repeat the procedure as detailed above.
this allows the gas flow to enter the main burner section of the control valve. The main burner can then be controlled either manually on the valve or by the touch control switch, located at the bottom of the right hand side panel.
With the pilot lit as detailed in section c) turn the right hand control knob anticlockwise to the X position (see Fig. 14 above). enter the main burner and be ignited by the pilot flame. Once the main burner has been lit, the right hand control knob can be adjusted to any position between the large flame (5.45kW heat input) position and the small flame (2.05kW heat input) position.
Main Burner Control Knob
This allows gas to
15
Page 16
Supplied By www.heating spares.co Tel. 0161 620 6677
e) To adjust the heat input via the touch control :-
Press the “up” button to light the main burner and adjust the heat input to the maximum setting. (5.45kW heat input). Press the “down” button to reduce the heat input to the minimum setting (2.05kW heat input). If the low button is pressed and held continuously, the fire
will go pass the minimum setting and extinguish the flames completely. See Fig. 15 below.
Fig. 15
“Up” button to increase heat input
“Down” button to decrease heat input or turn off main burner
NOTE : The touch control does not light the pilot, it only lights
the main burner when the pilot flame is established and regulates the heat input between high and low.
f) Check that the gas pressure is 20.0 mbar (+/- 1.0mbar) 8.0 in w.g.(+/-
0.4 in w
.g.) with the main burner operating on “high”.
To turn off the main burner :-
g) Turn right hand control knob clockwise to the position marked
or press the down button on the remote handset until the flame extinguishes, at this point a clicking noise will be heard from the motor
To turn off the pilot flame :-
h) Turn left hand control knob clockwise to the position marked
and the pilot flame will extinguish.
i) After ensuring that the fire is safe to use it should be left on high
position to fully warm up. During this time a slight odour may be noticed, this is due to the “newness” of the fire and will soon disappear
16
.
.
Page 17
Supplied By www.heating spares.co Tel. 0161 620 6677
AFTER THE PILOT FLAME HAS BEEN EXTINGUISHED, IF RE-LIGHT THE APPLIANCE YOU MUST WAIT AT LEAST FIVE MINUTES BEFORE TRYING TO RE-LIGHT THE APPLIANCE.
Finally
, hand the Installation and Maintenance Instructions and the Users
Instructions over to the customer and explain the operation of the fire.
YOU WISH TO
NOTE : THIS APPLIANCE IS DESIGNED TO WORK SAFELY AND EFFECTIVELY DURING ADVERSE WEATHER CONDITIONS. HOWEVER, DURING SUCH TIMES FLAME DISTURBANCE MAY BE NOTICED. THIS IS NORMAL AND DOES NOT EFFECT OR IMPAIR THE SAFETY OF THE APPLIANCE.
3.3 FITTING OF THE FENDER
Warning : Please take care whilst handling the fender as it’s cast iron construction means it is a heavy item that can be difficult to manoeuvere
a) Fit the fender by locating the two retaining brackets on the fender into
the slotted channel on the front of the combustion chamber
3.4 FITTING OF THE CANOPY
W
arning : Please take care whilst handling the canopy as it’
construction means it is a heavy item that can be difficult to manoeuvere
s cast iron
a) The canopy is held in position by two off retaining screws at each side. b) Fig. 16 below shows the position of the retaining screws for the canopy
Fig. 16
17
Page 18
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION 4
MAINTENANCE
Servicing Notes
Servicing should be carried out annually by a competent person such as a CORGI registered engineer. It is a condition of Flavel Fires 2 year guarantee scheme that this is carried out by a competent person i.e a CORGI registered Engineer in accordance with these servicing notes. The condition of the ceramic coal forms should be checked and if necessary the whole set should be replaced with a genuine replacement set. After any servicing work a gas tightness check must always be carried out.
4.1 Removing the Burner Assembly from the fire.
4.1.1 Isolate the gas supply.
4.1.2 Remove fender from the front of the fire, as described in section 3.3 on
page 17
4.1.3 Remove the glass frame assembly from the fire, as shown in section
2.8 on page 13.
4.1.4
4.1.5
4.1.6 Slide the burner of
4.2 Removing the Control Valve from the fire.
4.2.1 Isolate the gas supply.
4.2.1 Remove the fender as described in section 3.3, on page 17
4.2.2 Disconnect the pipe to the bulkhead fitting on the valve and disconnect
4.2.3 Loosen the pilot pipe, disconnect the ignition lead from the electrode
4.2.5 Remove the 2 off fixing screws which hold the valve mounting plate to
Remove the ceramic coal forms from the combustion chamber taking care not to damage them.
Remove the two M4 burner retaining screws, located at the front of each end of the burner.
f the rear injector and remove from the product.
the pipe on the valve which runs to the inlet elbow
and disconnect the thermocouple from the pilot assembly
its mounting bracket and lift the valve and its mounting plate away from the combustion chamber.
18
.
.
Page 19
Supplied By www.heating spares.co Tel. 0161 620 6677
4.2.6
4.2.7 Re-assemble with new valve in reverse order.
4.3 Removing the Battery Pack
4.3.1 Disconnect the wire from the battery pack, located at the bottom
4.3.2 Lift the battery pack out of its mounting cradle.
4.3.3 Re-fit the new battery pack in its cradle and re-fit the wire.
4.4 Removing the Pilot Assembly
Swap the valve mounting plate onto the new valve by unscrewing the two M5 nuts and bolts holding it in position .
L/H/S of the combustion chamber.
4.4.1
4.4.2 Remove the fender as described in section 3.3, on page 17
4.4.3 Remove the glass frame assembly from the fire, as shown in section
4.4.4
4.4.5 Loosen the pilot pipe, disconnect the ignition lead from the electrode,
4.4.6 Remove the two fixing screws which secure the pilot assembly to the
4.4.7 Remove the pilot assembly.
4.4.8 Re-assemble with an new pilot assembly, and gasket, ensuring that an
4.5 Replacing the Touch Control Switch
4.5.1 Remove the right hand side panel from the fire. Remove the touch
Isolate the gas supply
2.8 on page 13. Remove the ceramic coal forms from the combustion chamber
taking care not to damage them.
and remove the thermocouple from the pilot body.
pilot mounting panel in the base of the combustion chamber
even seal around the pilot assembly is obtained. Carry out a gas tightness test after re-assembly.
control switch by releasing the nuts that hold it in position on the inside face.
.
4.5.2 Remove the connecting wires from the top left hand side of the
control valve.
19
Page 20
Supplied By www.heating spares.co Tel. 0161 620 6677
4.5.2 Fit new switch and re-assemble in reverse order
PARTS SHORTLIST
Replacement of any other parts must be carried out by a competent person such as a CORGI registered gas installer. The part numbers of the main replaceable parts are as follows, these are available from your local Flavel Stockist, whose details can be found on the CFM Europe website, in the “stockist” section.
Control Valve B-82290 Pilot Body 70-36250 Thermocouple Ignition Electrode 70-36290 Ceramic / Coal Set FC-P086110
Due to our policy of continual improvement and development the exact accuracy of illustrations and descriptions contained in this book cannot be guaranteed
70-36270 Pilot Gasket 70-35220
Part No. B-86710
Issue 2
CFM Europe Ltd.
Trentham Lakes
Stoke-on-Trent
Staffordshire
ST4 4TJ
www.cfm-europe.com
Telephone - Service : (08700) 101187
Page 21
Supplied By www.heating spares.co Tel. 0161 620 6677
Loading...