C-3 and C-4 Side Access HEPA/ULPA Filter Housings
are designed for use with nominal 12 inch deep
HEPA/ULPA filters. They are factory-assembled
flanged units suitable for gel sealed or gasket sealed
HEPA filters. Both the prefilters and the primary
HEPA/ULPA filters are serviceable through the same
gasketed side access door.
Versatility
C-3 and C-4 housings may be used with Alpha 95 filters (95% DOP efficiency) and with Alpha Cell and
Alpha 2000 filters (99.97% and 99.99% DOP efficiency). Standard housings accept nominal 12 inch deep
filters and 16” and 18” carbon adsorbers in a variety
of face sizes. They can be arranged from one filter
high and one filter wide to four filters high and eight filters wide. If large housings are not practical to rig into
place, smaller units may be stacked in the field.
Options
• Choce of frame construction materials
• Insulation
• Lifting lugs
• Transitions
• Static pressure ports
• DOP test ports
• High temperature modifications
• Weathercap
• Magnahelic gauges (mounted)
• PrefilterTrack
Crank Lock HEPA Filter Housing
Bulletin PB1604-0107
Construction
Housings are 24 inches deep in the direction of air
flow, (26 inches deep if it has a 4” prefilter section.)
and are constructed in your choce of frame materials.
Flanges are furnished for duct connections on the air
entering and air leaving sides. All joints are intermittently welded and finished to remove all burrs and
sharp edges. The joints are then sealed with silicone
enabling the housing to withstand an internal pressure
of +/- 3.0 in. w.g.
The filter locking mechanism for the fluid gel sealmodel housing is a 300 Series stainless steel handoperated arm that moves the filter s gel-filled channel
on to the internal housing knife edge sealing flange.
The same mechanism also pulls the filter away from
the sealing flange when changing filters. The filter
locking mechanism for gasket seal-model housing is a
300 Series stainless steel and brass device. The
mechanism presses the gasketed filter against the
housing s sealing surface by means of a mechanical
bolt and thrust assembly that is manually operated
using a standard 3/4 inch socket or wrench.
Standard 2 inch or 4 inch prefilter tracks will accommodate pleated panel filters with efficiency ranges up
to 50% per the ASHRAE Standard 52.2 dust spot test
methods. Access doors have 0.5 in. thick closed cell
neoprene gaskets around the inside perimeter.
Double pin door hinges which pivot, allow the door to
make level contact with the gasket when closed.
Stainless steel wing nuts secure the doors.
Important Features
• Choice of frame construction materials
• Stainless steel filter locking mechanism for
strength, durability and long-term integrity
• Access for up to four filters and prefilters wide
per door for quick filter changeout
• Double pin hinges enable the doors to make
level contact with the door gasket for a uniformly tight seal
Flanders Filters - Foremost in Air Filtration
Toll Free: 1-800-637-2803
Cfm Capacities and Dimensions
Using Standard Alpha 95 and Alpha Cell and High Capacity Alpha 2000 HEPA Filters
1. Height and Width code: the first numeral represents the number of 24 in. x 24 in. filters high and wide. See also
Model Number Development on page 3.
2. Standard housing depth is 23-1/4 inches with or without an optional prefilter track.
3. Housings greater than four wide must have filter removal from both sides.
4. Capacities shown are based on nominal 12 inch deep filters.
Gasket Seal
Gasket
A spring-loaded filter clamping
mechanism is used to maintain sealing pressure for gasketed filters. The
gasket seal is suitable for many
applications.
C-4C-3
Gel Seal
Housing
Knife Edge
Sealing Flange
A flange in the housing mates into a
gel-filled channel on the filter. The
gel seal guarantees filter-to-frame
sealing and is recommended for
critical applications.
Flanders Filters - Foremost in Air Filtration
Toll Free: 1-800-637-2803
Model Number Development
C3G - 1H1W - GGF - GLV - D1
Filter type:
C3G - Gasket Seal
C4F - Fluid Seal
Housing Size:
Filters High x Wide
(See Chart)
Filter Size:
CCF - 12”x12”x11-1/2” HEPA Filter
2CCF -12”x12”x11-1/2” HEPA filter with a 2” prefilter
4CCF -12”x12”x11-1/2” HEPA filter with a 4” prefiler
CGF - 12”x24”x11-1/2” HEPA Filter
2CGF- 12”x24”x11-1/2” HEPA Filter with 2” prefilter
4CGF- 12”x24”x11-1/2” HEPA filter with a 4” prefilter
GCF- 24”x12”x11-1/2” HEPA filter
2GCF- 24”x12”x11-1/2” HEPA filter with 2” prefilter
4GCF- 24”x12”x11-1/2” HEPA filter with 4” prefilter
GGF- 24”x24”x11-1/2” HEPA filter
2GGF- 24”x24”x11-1/2” HEPA filter with 2” prefilter
4GGF- 24”x24”x11-1/2” HEPA filter with 4” prefilter
CC12- 12”x12”x11-1/2” carbon adsorber
CG12- 12”x24”x11-1/2” carbon adsorber
GC12- 24”x12”x11-1/2” carbon adsorber
GG12- 24”x24”x11-1/2” carbon adsorber
CG16- 12”x24”x16” carbon adsorber
GC16- 24”x12”x16” carbon adsorber
GG16- 24”x24”x16” carbon adsorber
GG18- 24”x24”x18” carbon adsorber.
Housing Material:
GLV: Galvanized steel
304: Type 304 S/S
304L: Type 304 L S/S
316: Type 316 S/S
316L: Type 316L S/S
ALZ - 14 gauge aluminized
(non-standard)
Door Locations
D1- Filter access and housing on
one side only
D1A - Doors on both sides, but filter
access from one side only.
D2 - Doors on both sides and filter
access from both sides.
The filter size arrangements listed at left are the only standard
arrangements. 6” prefilters are available but non-standard.
Any prefilter with a carbon housing is available but not standard.
Multi-wide CC, CG and GC units are available but non-standard.
CC16, CC18, CG18 & GC18 units are not available.
Filter Usage and Housing Weight
HeightFilters/Width Code
CodeWeight
1W2W3W4W5W6W7W8W
1HFilters12345678
Weight105190270380460540
2HFilters246810121416
Weight200305460610765920
3HFilters3691215182124
Weight2554055908109951180
4HFilters48121620242832
Weight345520710104012301420
(1) Filters/Weight: Top number indicates the number of filters required to fill the unit. Bottom number indicates the
approximate weight in pounds of the housing EMPTY. Add 32 pounds for each HEPA/ULPA filter and 2 pounds per each
prefilter to determine approximate weight when loaded with filters.
Add 10% to calculate the approximate rigging weight of housings
Flanders Filters - Foremost in Air Filtration
Toll Free: 1-800-637-2803
Construction Details
Notes:
1. Standard construction is 14 ga. galvanized steel housing and doors leak tight to +/- 3.0 in. w.g.
2. Maximum operating temperature for standard C-3 and C-4 Housings is 250°F. High temperature C-3 and C-4 Housings
are available for 400°F continuous and 500 °F intermittent duty.
Guide Specifications
1.0 HEPA/ULPA Filter Housings
1.1 Side access HEPA filter housings shall be C-3 and
C-4 as manufactured by Flanders.
1.2 Units shall be factory-assembled housings with
flanges for duct connections on the air entering
and air leaving sides.
1.3 Housings shall be suitable for operation at +/- 3.0
in. w.g. internal pressure.
2.0 Construction
2.1 Housings shall be made of galvanized or stainless
steel with 11 ga. corner posts. Joints shall be intermittently welded and sealed with silicone.
2.2 Tracks for prefilters shall be fabricated from the
same material as the housing.
2.3 The filter locking mechanism for the gel seal
model shall be a 300 Series stainless steel
®
Flanders Filters, Inc.
531 Flanders Filter Road
Washington, NC 27889
hand-operated arm that moves the filter so its gelfilled channel mates with the internal housing knife
edge sealing flange. The same mechanism shall
also pull the filter away from the sealing flange
when changing filters.
2.4 The filter locking mechanism for the gasket seal
model housing shall be a 300 Series stainless
steel and brass device. The mechanism shall
press the gasketed filter against the housing’s
sealing surface by means of a mechanical bolt and
thrust assembly that is manually operated using a
standard 3/4 inch socket or wrench.
3.0 Features
3.1 Model numbers and capacities shall be as specified and/or shown on the drawings.
3.2 Provide options as specified.
REPRESENTED BY: