flakt woods STRA-04 Installation & Maintenance Manual

STRA-04 Room controller. Installation and maintenance manual.
Fläkt Woods
8790 GB 2016.03
1
Specifications are subject of alteration without further notice.
Contents STRA-04 for Optivent
Installation instructions........................................................................2
Display handling...................................................................................3
Technical data........................................................................................4
Configuration........................................................................................4
Operating modes..................................................................................6
Control...................................................................................................7
Condensation detector/Window contact/Frost protection.............8
Parameter settings................................................................................9
Function key........................................................................................11
STRA-04 Room controller. Installation and maintenance manual.
Fläkt Woods 2
Specifications are subject of alteration without further notice.
STRA-04 for Optivent
Installation instructions
Follow local safety regulations when installing the product. For information on putting the product into operation, see the manual "STRA Manual", which can be downloaded from www.flaktwoods.com.
1. 2.
3.
or
4.
5. Dimensions
Dimensions given in mm
8790 GB 2016.03
STRA-04 Room controller. Installation and maintenance manual.
STRA-04 for Optivent
Fläkt Woods 3
Specifications are subject of alteration without further notice.
Connection diagram for STRZ-05, STRZ-18, STRZ-09, STRZ-70, EMSS and window contact STRZ-38
Connection diagram for STRZ-05, STRZ-18, STRZ-09, STRZ-70, EMSS and condensation sensor STRZ-16
Setpoint adjustment
In Occupied mode, the controller operates from a heating setpoint (FS = 22°C), or a cooling setpoint FS = 24°C) that can be changed using the INCREASE and DECREASE buttons.
When the INCREASE button is pressed, the current setpoint is raised by 0.5°C per press up to the maximum limit (FS = +3°C). When the DECREASE button is pressed, the current setpoint is reduced by 0.5°C per press down to the minimum limit (FS = -3?).
Switching between heating and cooling setpoints is done automatically in the controller depending on the heating and cooling requirement.
Function button
If the Function button is pressed briefly (less than 5 seconds) when the controller STRA-04 is in the Preset operating mode (Parameter 45, FS = 3 = Occupied), the controller switches to the Bypass operating mode. If the button is pressed briefly when the controller is in Bypass mode, it will switch to Preset mode.
If the Function button is pressed and held for more than 5 seconds, the controller switches to Unoccupied mode, regardless of the current operating mode. If the button is pressed briefly in Unoccupied mode, the controller will return to Bypass (for 60 minutes – this is a preset time that can be changed via setting of parameter 12).
Display handling
The display on the controller STRA-04 has the following indications:
8790 GB 2016.03
STRA-04 Room controller. Installation and maintenance manual.
STRA-04 for Optivent
Fläkt Woods 4
Specifications are subject of alteration without further notice.
Different parameter values can easily be set in a parameter menu shown on the display, using the buttons on the controller. The parameter value is changed using the INCREASE and DECREASE buttons, and the change is confirmed with the Function button.
Technical data
Supply voltage 18...30 V AC, 50...60 Hz Internal consumption 2.5 VA Ambient temperature 0...50°C Storage temperature -20..+70? Ambient humidity Max 90% RH Protection class IP20 Communication RS485 (EXOline or Modbus) with
automatic detection/change-over
Modbus - Bacnet 8-bit, 1 or 2 stop bits. Odd, even (FS) or
no parity. Communication speed 9600 bps (not changeable) Built-in temperature sensor NTC type, measuring range, 0...50°C,
measurement accuracy +/-0.5°C at
15...30°C Material casing Polycarbonate, PC Weight 110 g
The product meets requirements for prevailing European EMC standards CENELEC EN 61000-6-1 and EN 61000-6-3 and prevailing European LVD standard IEC 60 730-1. The product is CE marked.
Inputs
External room sensor PT1000 sensor, 0…50°C. A suitable
sensor is Fläkt Woods STRZ-05.
Occupancy detector Closing potential-free contact. A
suitable occupancy detector is Fläkt Woods STRZ-09.
CO 2 sensor STRZ-18-1-1 CO 2 sensor (0-10V).
Outputs
Forced ventilation 24 V AC actuator, max. 0.5 A Valve actuator, thermal actuator or Optivent 2 outputs Valve actuator 0…10 V DC, max. 5 mA Thermal actuator 24 V AC, max. 2.0 A Control Heating or cooling
Exercise FS = 23 hour intervals Terminal block Lift-type for max. cable cr oss-section
2.1 mm
2
Connection
To keep the unit as compact as possible, the communication input on the STRA-04 is not galvanically separated from the supply voltage. This means that it is vital to be able to distinguish clearly between G and G0, as well as the communication input's A and B.
All STRA regulators that share a transformer and communication loop must use the same transformer pole for G (terminal 10) and G0 (terminal 11), respectively. On the communication loop, the A terminal (terminal 42) may only be connected to another A terminal, and the B terminal (terminal 43) to another B terminal. Otherwise there is a high risk of short circuiting, which would ruin the components.
Configuration
Use the parameter menu in the display to configure the electronic unit. See the Parameter Settings section.
8790 GB 2016.03
Loading...
+ 8 hidden pages