flakt woods PM Installation And Maintenance Instructions Manual

AIR COMFORT
AIR TREATMENT
9191 GB 2015.09.29
FLÄKT WOODS PM-MOTOR
WITH SUPPLIED FC 102 FREQUENCY CONVERTER
» INSTALLATION AND MAINTENANCE INSTRUCTIONS
Warning!
The motor is designed exclusively for operation with the supplied speed control (frequency converter). Direct on-line connection to the mains is not possible for PM-motors.
GENERAL
• Admissible environmental temperature: from -15 °C up to +40 °C, with altitudes 1000 m above sea level
• Mounting: IM B3, B5
• Drive operating voltage: 400 VAC
• Insulation class: "F"; temperature rise to class B
(TEFC execution)
• IP55 degree of protection for the whole range
• Reduced dimensions
• Rare earth permanent magnets
Speed controller and motor shall be installed by a qualified electrician with adequate knowledge how to install speed­controlled drive systems (frequency inverters) and EMC safety. All cabling must comply with national and local regulations on cable cross-sections and ambient temperature.
Warning!
Risk of electric shock: Motor terminals may still be live if the impeller is rotating, even when the main incoming supplied has been isolated. Ensure the impeller is kept stationary before opening and whilst the terminal box is open.
Fläkt Woods 9191 GB 2015.09.24 Specifications are subject to alteration without notice
Installation and maintenance instructions
Fläkt Woods PM-Motor With suPPlied FC 102 FrequenCy Converter
2
SUPPLY CABLE
Mount mains supply to terminals L1, L2 and L3 and ground
wires to earth terminal and tighten.
Short circuit protection:
The speed controller must be protected against shortcircuit to avoid electrical or fire hazard. The fuses mentioned below are recommended to use to protect service personnel and equip­ment in case of an internal failure in the speed controller. Speed controller provides full short circuit protection in case of a short circuit on the motor output.
Over current protection:
Provide overload protection to avoid fire hazard due to over­heating of the cables in the installation. The speed controller is equipped with an internal over-current protection that can be used for upstream overload protection (UL-applications excluded). See par. 4-18 Current Limit. Moreover, fuses or circuit breakers can be used to provide the over-current protection in the installation. Over­current protection must always be carried out according to national regulations.
Leakage Current (>3,5mA)
EN/IEC61800-5-1 (Power Drive System Product Standard) requires special care if the leakage current exceeds 3,5 mA.
Earth grounding must be reinforced in one of the following ways:
• Earth ground wire of at least 10 mm
2
• Two separate earth ground wires both complying with the
dimensioning rules
Isolation switch
All speed controllers may be used with an isolated input sour­ce as well as with ground reference power lines.
RECOMMENDED PRE-FUSES
Power 0,75 1,5 2,2 3 4 5,5 7,5 11 15
3x380-
400V
UL (A) 10 10 15 15 15 25 25 50 50
IEC (A)
type gG
10 10 16 16 16 25 25 50 50
MOTOR CABLE
Motor and speed controller is delivered with 3,5 m long motor
cable. If it should be replaced with longer one or disconnected at the other end.
Following rules should be meet and considered:
• Motor cable should be shielded type.
• Shield should be grounded 360° at both ends of cable.
• Motor cable should be no longer than 20 meters.
• Motor is connected to star inside the motor.
• Phase wires are connected to terminals U1, V1, W1.
• Terminal connectors are not needed.
CONTROL CABLE
Control cable should be shielded. Keep control cable distance min 200 mm from mains and motor cable.
CONTROL SIGNALS
Fan is started with potential free switch connected between terminals 12 and 18. The circuit voltage is 24 VDC. AUTO-mode should be selected from operation panel. Speed reference can be given from with 0…10 V signal
connected in terminals 53(+) and 55(-). Alarm signal is availa­ble in relay1 (terminals 01, 02 and 03).
Running indication is available in relay 2 (terminals 04,
05 and 06).
Single speed operation:
Set constant speed reference (rpm) in parameter 411. Only external start signal is needed.
Two speed operation:
Lower speed reference (rpm) is set in parameter 411 and
higher speed reference (rpm) in parameter 319. Lower speed
is activated with start signal (terminals 12-18). Higher speed is
activated by closing terminals 12-29. Speed controller can be controlled via Modbus RTU. RS-485 cable is connected to the terminals 68 (P), 69 (N) and 61 (COM). If speed controller is last
unit in line, it should be terminated by setting switch S801 in ON position. Modbus operation is described in speed controller operation instructions.
START UP AND FUNCTIONAL TESTING
After power up test check motor rotation:
Set speed controller to Hand on mode from operation panel. Motor will start to the minimum or speed set in operation panel.
To change the direction of rotation:
• Remove power to the speed controller and wait for power to
discharge.
• Reverse the connection of any two of the three motor cables
on the motor or frequency converter side of the connection. When direction of rotation is right set speed controller to Auto on mode. Then speed controller will follow control signals.
PARAMETERS
Speed controller parameters are set at the factory providing for optimal performance of fan and motor. This includes motor parameters, ramp times, starting and stopping methods and speed limitations. Changing of these parameters may result in unstable operation or motor won’t start. Original parameter values can be downloaded from operation panel in case of losing them.
Fläkt Woods 9191 GB 2015.09.24 Specifications are subject to alteration without notice
Loading...
+ 4 hidden pages