Installation Guide
D102031X014
English - November 2016
Type Y692
Introduction
This installation guide provides instructions for installation, startup,
and adjustment. To receive a copy of the instruction manual,
contact your local Sales Ofce or view a copy at www.sher.com.
For further information refer to: Type Y692 Instruction Manual,
form 5347, D102031X012.
P.E.D. Categories
This product may be used as a safety accessory with pressure
equipment in the following Pressure Equipment Directive categories.
It may also be used out- side of the Pressure Equipment Directive
using sound engineering practice (SEP) per table below. For
information on the current PED revision see Bulletin: D103053X012.
PRODUCT SIZE CATEGORY FLUID TYPE
DN 40 and 50 / 1-1/2 and 2 in. I 1
Specications
Maximum Allowable Inlet Pressure
10.3 bar / 150 psig or body rating limit
Maximum Control (Casing) Pressure
1.0 bar / 15 psig
Proof Test Pressure
All Pressure Retaining Components have been proof
tested per PED
Outlet Pressure Ranges
Light Spring Assembly: 2 to 7 mbar / 1 to 3 in. w.c.,
7 to 26 mbar / 3 to 11 in. w.c., 16 to 86 mbar /
6.5 in. w.c. to 1.2 psig, 0.05 to 0.14 bar / 0.7 to 2 psig and
0.07 to 0.22 bar / 1 to 3.2 psig
Heavy Spring Assembly: 0.14 to 0.38 bar / 2 to 5.5 psig and
0.28 to 0.48 bar / 4 to 7 psig
Maximum Operating Outlet Pressure to Avoid Internal
Part Damage
0.21 bar / 3 psig above outlet pressure setting
Temperature Capabilities
Nitrile (NBR): -29 to 82°C / -20 to 180°F
Fluorocarbon (FKM): -18 to 149°C / 0 to 300°F
Ethylenepropylene (EPDM): -29 to 135°C / -20 to 275°F
Peruoroelastomer (FFKM): -29 to 149°C / -20 to 300°F
(1)
(1)
(1)
(1)
(1)
Installation
WARNING
!
Only qualied personnel should install or service a
regulator. Regulators should be installed, operated
and maintained in accordance with international
and applicable codes and regulations and Emerson
Process Management Regulator Technologies Inc.
(Emerson) instructions.
If the regulator vents uid or a leak develops in the
system, it indicates that service is required. Failure
to take the regulator out of service immediately may
create a hazardous condition.
Personal injury, equipment damage or leakage due
to escaping uid or bursting of pressure-containing
parts may result if this regulator is overpressured or
is installed where service conditions could exceed
the limits given in the Specications section or
where conditions exceed any ratings of the adjacent
piping or piping connections.
To avoid such injury or damage, provide pressurerelieving or pressure-limiting devices (as required
by the appropriate code, regulation or standard) to
prevent service conditions from exceeding limits.
Additionally, physical damage to the regulator could
result in personal injury and property damage due
to escaping uid. To avoid such injury and damage,
install the regulator in a safe location.
Clean out all pipelines before installation of the regulator and
check to be sure the regulator has not been damaged or has
collected foreign material during shipping. For NPT bodies, apply
pipe compound to the male pipe threads. For anged bodies, use
suitable line gaskets and approved piping and bolting practices.
Install the regulator in any position desired, unless otherwise
specied, but be sure ow through the body is in the direction
indicated by the arrow on the body.
For proper operation, the regulator must be installed with the spring
case barrel pointed down.
Note
It is important that the regulator be installed so that
the vent hole in the spring case is unobstructed at all
times. For outdoor installations, the regulator should
be located away from vehicular trafc and positioned
so that water, ice and other foreign materials cannot
enter the spring case through the vent. Avoid placing
the regulator beneath eaves or downspouts and be
sure it is above the probable snow level.
Overpressure Protection
The recommended pressure limitations are stamped on the regulator
nameplate. Some type of overpressure protection is needed if the
actual inlet pressure exceeds the maximum operating outlet pressure
rating. Overpressure protection should also be provided if the
regulator inlet pressure is greater than the safe working pressure of
the downstream equipment.
Regulator operation below the maximum pressure limitations does
not preclude the possibility of damage from external sources or debris
in the line. The regulator should be inspected for damage after any
overpressure condition.
Startup
The regulator is factory set at approximately the midpoint of the spring
range or the pressure requested, so an initial adjustment may be
required to give the desired results. With proper installation completed
and relief valves properly adjusted, slowly open the upstream and
downstream shutoff valves.
Adjustment
To change the outlet pressure, remove the closing cap or loosen the
locknut and turn the adjusting screw clockwise to increase outlet pressure
or counterclockwise to decrease pressure. Monitor the outlet pressure with
a test gauge during the adjustment. Replace the closing cap or tighten the
locknut to maintain the desired setting.
1. The pressure/temperature limits in this installation guide and any applicable standard or
code limitation should not be exceeded.

Type Y692
Taking Out of Service (Shutdown)
WARNING
!
To avoid personal injury resulting from sudden
release of pressure, isolate the regulator from all
pressure before attempting disassembly.
Parts List
Key Description
1 Control Spring
2 Adjusting Screw
3 Closing Cap
4 Lower Spring Seat
5 Diaphragm and Plate Assembly
6 Lower Diaphragm Plate
7 Diaphragm Plate Gasket
8 Pusher Post
9 Lever Assembly
11 Machine Screw
12 Stem Bushing
13 Stem
14 Cotter Pin
15 Stem Seal (O-ring)
16 Body Gasket
17 Split Ring
19 Union Nut
20 Lower Casing
21 Diaphragm Case Cap Screw
22 Hex Nut (12 required)
23 Spring Case
25 Disk Assembly
27 Orice
28 Body
29 Pipe Plug
30 Diaphragm Cap Screw
35 Closing Cap Gasket
44 Upper Spring Seat
46 Valve Disk Washer
Key Description
47 Machine Screw
50 Nameplate
51 Drive Screws (4 required)
56 Vent Assembly
71 Bushing
74 Pitot Tube
93 Hex Nut
3
35
2
1
4
34B4832-B
21
22
6
7
8
9
20
13
11
19
17
16
28
14
25
27
46
43B0674-B
5
4
3
FISHER CONTROLS CO.
TYPE
DATE MFGD
MARSHALLTOWN IOWA, USA
ORIFICE
RANGE
2
35
1
30
23
15
47
SPRING
29
50
51
56
71
Figure 2. Type Y692 Regulator Assembly
93
4
23
30
5
34B4869-A
3
2
44
1
4
35
23
30
5
Webadmin.Regulators@emerson.com
Fisher.com
Emerson Automation Solutions
Regulator Technologies
Americas
McKinney, Texas 75070 USA
T +1 800 558 5853
+1 972 548 3574
Europe
Bologna 40013, Italy
T +39 051 419 0611
For further information on the current
PED revision see Bulletin: D103053X012
or scan the QR code.
Figure 1. Type Y692 with a
Heavy Control Spring Assembly
Facebook.com/EmersonAutomationSolutions
LinkedIn.com/company/emerson-automation-solutions
Twitter.com/emr_automation
Asia Pacic
Singapore 128461, Singapore
T +65 6770 8337
Middle East and Africa
Dubai, United Arab Emirates
T +971 4 811 8100
Figure 3. Type Y692 with a
Light Control Spring Assembly
D102031X014 © 2001, 2017 Emerson Process Management Regulator
Technologies, Inc. All rights reserved. 01/17.
The Emerson logo is a trademark and service mark of Emerson
Electric Co. All other marks are the property of their prospective owners.
Fisher™ is a mark owned by Fisher Controls International LLC, a
business of Emerson Automation Solutions.
The contents of this publication are presented for information purposes
only, and while effort has been made to ensure their accuracy, they are
not to be construed as warranties or guarantees, express or implied,
regarding the products or services described herein or their use or
applicability. All sales are governed by our terms and conditions, which
are available on request. We reserve the right to modify or improve the
designs or specications of our products at any time without notice.
Emerson Process Management Regulator Technologies, Inc does not
assume responsibility for the selection, use or maintenance of any
product. Responsibility for proper selection, use and maintenance of any
Emerson Process Management Regulator Technologies, Inc. product
remains solely with the purchaser.