Fisher Site Considerations for Equip. Installation, Grounding, Wiring Manuals & Guides

Site Considerations for Equipment Installation, Grounding, and Wiring Manual
D301452X012
October 2019
Remote Automation Solutions
Site Considerations for Equipment Installation, Grounding, and Wiring Manual
FB3000 Remote Terminal Unit (RTU)
FB1100/1200 Flow Computer FB2100/2200 Flow Computer
ROC800, FloBoss™107, ControlWave™ Family of Flow Computers and RTUs
Site Considerations for Equipment Installation, Grounding, and Wiring Manual D301452X012 October 2019
ii

Device Safety Considerations

Reading these Instructions
Before operating the device, read these instructions carefully and understand their safety implications. In some situations, improperly using this device may result in damage or injury. Keep this manual in a convenient location for future reference. Note that these instructions may not cover all details or variations in equipment or cover every possible situation regarding installation, operation, or maintenance. Should problems arise that are not covered sufficiently in the text, immediately contact Customer Support for further information.
Protecting Operating Processes
A failure of this device – for whatever reason -- may leave an operating process without appropriate protection and could result in possible damage to property or injury to persons. To protect against this, you should review the need for additional backup equipment or provide alternate means of protection (such as alarm devices, output limiting, fail-safe valves, relief valves, emergency shutoffs, emergency switches, etc.). Contact Remote Automation Solutions for additional information.
Returning Equipment
If you need to return any equipment to Remote Automation Solutions, it is your responsibility to ensure that the equipment has been cleaned to safe levels, as defined and/or determined by applicable federal, state and/or local law regulations or codes. You also agree to indemnify Remote Automation Solutions and hold Remote Automation Solutions harmless from any liability or damage which Remote Automation Solutions may incur or suffer due to your failure to ensure device cleanliness.
Grounding Equipment
Ground metal enclosures and exposed metal parts of electrical instruments in accordance with OSHA rules and regulations as specified in Design Safety Standards for Electrical Systems, 29 CFR, Part 1910, Subpart S, dated: April 16, 1981 (OSHA rulings are in agreement with the National Electrical Code). You must also ground mechanical or pneumatic instruments that include electrically operated devices such as lights, switches, relays, alarms, or chart drives. Important: Complying with the codes and regulations of authorities having jurisdiction is essential to ensuring personnel safety. The guidelines and recommendations in this manual are intended to meet or exceed applicable codes and regulations. If differences occur between this manual and the codes and regulations of authorities having jurisdiction, those codes and regulations must take precedence.
Protecting from Electrostatic Discharge (ESD)
This device contains sensitive electronic components which can be damaged by exposure to an ESD voltage. Depending on the magnitude and duration of the ESD, it can result in erratic operation or complete failure of the equipment. Ensure that you correctly care for and handle ESD-sensitive components.

System Training

A well-trained workforce is critical to the success of your operation. Knowing how to correctly install, configure, program, calibrate, and trouble-shoot your Emerson equipment provides your engineers and technicians with the skills and confidence to optimize your investment. Remote Automation Solutions offers a variety of ways for your personnel to acquire essential system expertise. Our full-time professional instructors can conduct classroom training at several of our corporate offices, at your site, or even at your regional Emerson office. You can also receive the same quality training via our live, interactive Emerson Virtual Classroom and save on travel costs. For our complete schedule and further information, contact the Remote Automation Solutions Training Department at 800-338-8158 or email us at
education@emerson.com.
Site Considerations for Equipment Installation, Grounding, and Wiring Manual
D301452X012
October 2019
iii

Contents

Section 1: Overview 1
1.1 Safety Labels ......................................................................................................................... 1
1.2 Major Topics ......................................................................................................................... 2
Section 2: Protection 3
2.1 Protecting Equipment Systems ............................................................................................. 3
2.1.1 Quality is Conformance to Requirements ................................................................... 3
2.2 Protecting Equipment and Personnel .................................................................................... 3
2.2.1 Considerations for Protecting Personnel .................................................................... 4
2.2.2 Considerations for Protecting Equipment .................................................................. 4
2.3 Other Site Safety Considerations ........................................................................................... 5
Section 3: Grounding and Isolation 7
3.1 Power and Ground Systems .................................................................................................. 7
3.2 Importance of Good Grounds ................................................................................................ 7
3.3 Earth Ground Connections .................................................................................................... 7
3.3.1 Establishing a Good Earth Ground .............................................................................. 8
3.3.2 Ground Wire Considerations .................................................................................... 11
3.3.3 Other Grounding Considerations ............................................................................. 12
3.4 Isolating Equipment from the Pipeline ................................................................................ 13
3.4.1 Meter Runs without Cathodic Protection ................................................................. 13
3.4.2 Meter Runs with Cathodic Protection ....................................................................... 14
Section 4: Lightning Arresters and Surge Protectors 17
4.1 Strike .................................................................................................................................. 17
4.1.1 Chance of Being Struck by Lightning ........................................................................ 17
4.1.2 Antenna Caution ..................................................................................................... 20
4.1.3 Ground Propagation ................................................................................................ 22
4.1.4 Tying it all Together ................................................................................................. 22
4.1.5 Impulse Protection Summary .................................................................................. 22
4.2 Use of Lightning Arresters and Surge Protectors .................................................................. 23
4.2.1 Installing Lightning Arresters and Surge Protectors .................................................. 23
Section 5: Wiring Techniques 27
5.1 Overview ............................................................................................................................ 27
5.2 Device Wiring ..................................................................................................................... 27
5.2.1 Avoid Common Returns ........................................................................................... 27
5.2.2 Use Twisted Shielded Pair Wiring (with Overall Insulation) ....................................... 28
5.2.3 Ground Cable Shields ............................................................................................... 28
5.2.4 Use Known Good Earth Grounds .............................................................................. 29
5.2.5 Earth-ground Wires ................................................................................................. 29
5.2.6 Work Neatly and Professionally ................................................................................ 29
Site Considerations for Equipment Installation, Grounding, and Wiring Manual D301452X012
October 2019
iv
5.2.7 Observe High Power Conductors and Signal Warning .............................................. 29
5.2.8 Use Proper Wire Size ................................................................................................ 29
5.2.9 Use Lightning Arresters & Surge Protectors .............................................................. 30
5.2.10 Secure Wiring Connections .................................................................................... 30
Section 6: Grounding and Bonding a Solar PV Array 33
6.1 Code Requirements ............................................................................................................ 33
6.2 Ground Attachment ............................................................................................................ 33
6.3 Non-Conductive Components ............................................................................................ 34
6.4 Non-Conductive Coatings ................................................................................................... 34
6.5 Grounding Method ............................................................................................................. 35
6.6 Corrosion Protection ........................................................................................................... 36
6.7 Lightning Protection Considerations ................................................................................... 36
Site Considerations for Equipment Installation, Grounding, and Wiring Manual
D301452X012
October 2019
Overview 1

Section 1: Overview

This section covers the following topics:
Safety Labels
Major Topics
This document provides information pertaining to the installation of RTUs, controllers, and flow computers from Emerson Remote Automation Solutions, including the ROC, FloBoss devices, FB1000 and FB2000 Series of flow computers and the FB3000 RTUs. More specifically, this document provides information covering reasons, theory, and techniques for protecting your personnel and equipment from electrical damage. Your system equipment affects both the quality of service your company provides and many aspects of its operational safety. Loss of equipment means lost production and profits as well as increased expenses.
Note
Information contained in this document is for educational purposes. Emerson Remote Automation Solutions offers no warranties or guarantees on the effectiveness of the safety of techniques described herein. Where the safety of installations and personnel is concerned, refer to the National Electrical Code Rules and rules of local regulatory agencies.

1.1 Safety Labels

This product may display safety label(s) to identify potential hazards. The same types of notices appear within the documentation. Whenever you see an exclamation point (!) enclosed within a triangle (shown to the left), consult the documentation for additional safety information about the hazard and how to avoid it. The labels used are:
DANGER
MAY CAUSE DEATH
Observe all precautionary signs posted on the equipment.
Failure to do so may result in death or serious injury to personnel.
WARNING
DANGER TO PERSONNEL AND EQUIPMENT
Observed all precautionary signs posted on the equipment.
Failure to do so may result in injury to personnel or cause damage to the equipment.
Site Considerations for Equipment Installation, Grounding, and Wiring Manual D301452X012 October 2019
2 Overview
CAUTION
DANGER TO PERSONNEL AND EQUIPMENT
Observed all precautionary signs posted on the equipment.
Failure to do so may result in injury to personnel or cause damage to the equipment.
SAFETY FIRST
General instructions and safety reminders.

1.2 Major Topics

Topics are covered in five sections which are designed to pinpoint major areas of concern for the protection of personnel and site equipment:
Section 2 – Protection
This section provides the reasons for protecting equipment systems. It presents an overview of the definition of quality, what we are trying to accomplish in the protection of site installations, how to satisfy the defined requirements, and considerations for the protection of personnel and equipment.
Section 3 – Grounding & Isolation
This section provides information as to what constitutes a good earth ground, how to test and establish such grounds, as well as when and how to connect equipment to earth grounds.
Section 4 – Lightning Arresters & Surge Protectors
This section presents technical and statistical information about lightning strikes, details how to determine the likelihood of a lightning strike, discusses protecting equipment and personnel during the installation of radios and antennas, and reviews the dangers to personnel and equipment when working with antennas. Included is a discussion on using lightning arresters and surge protectors along with overviews of how each device protects site equipment.
Section 5 – Wiring Techniques
This section covers installing power and “measurement & control” wiring; includes information on unique situations, circulating ground and power loops, bad relays, and good wire preparation and connection techniques. In addition to presenting problems to avoid, this section lists ten rules of instrument wiring.
Section 6 – Grounding and Bonding of Solar Photovoltaic (PV) Arrays
This section discusses grounding and bonding of solar PV arrays, and covers code requirements, ground attachment, and grounding methods.
Site Considerations for Equipment Installation, Grounding, and Wiring Manual
D301452X012
October 2019
Installation 3

Section 2: Protection

This section covers the following topics:
Protecting Equipment Systems
Protecting Equipment and Personnel
Other Site Safety Considerations

2.1 Protecting Equipment Systems

Electrical equipment is susceptible to damage from a variety of natural and man-made phenomena. In addition to wind, rain and fire, the most common types of system and equipment­damaging phenomena are lightning, power faults, communication surges, noise and other electrical interference caused by devices such as radios, welders, switching gear, automobiles, etc. Additionally, there are problems induced by geophysical electrical potential and noise plus things that are often beyond our wildest imagination.

Quality is Conformance to Requirements

A quality equipment system is one that works reliably, safely and as purported by its manufacturer (and in some cases by the system integrator) as a result of good equipment design and well defined and followed installation practices. If we accept the general definition of quality as “conformance to requirements,” we must also accept the premise that a condition of “quality” cannot exist where requirements for such an end have not been evolved. In other words, you cannot have quality unless you have requirements that have been followed. By understanding the requirements for a safe, sound, and reliable equipment system, and by following good installation practices (as associated with the personnel and equipment in question), you enhance the operational integrity of the equipment and system.
Understanding the requirements for properly and safely installing equipment in various environments in accordance with good grounding, isolating, and equipment protection practices is fundamental for maintaining a system which is healthy for both the owner and customer.
Properly installed equipment is easier to maintain and operate and is more efficient and more profitable to our customers. Following good installation practices minimizes injury, equipment failure, and customer frustration that accompanies failing and poorly operating equipment (of even the finest design).
Additionally, personnel who install a piece of equipment add to or subtract from a system’s reliability based on their level of technical ability. Their understanding of the equipment, site conditions, and the requirements for a quality installation are essential to safety and success.

2.2 Protecting Equipment and Personnel

Installations must be performed in accordance with National Electrical Code Rules, electrical rules set by local regulatory agencies, and – depending on the customer environment (gas, water, and so on) – other national, state and local agencies. Additionally, installation at various customer sites
may be performed in conjunction with a “safety manager” or utility personnel with hazardous
Site Considerations for Equipment Installation, Grounding, and Wiring Manual D301452X012 October 2019
4 Installation
materials (HAZMAT) training on materials present (or potentially present) as required by OSHA, the customer, and other regulatory agencies.

Considerations for Protecting Personnel

Always evaluate the site environment as though your life depends on it. Make sure that you understand the physical nature of the location where you will be working. Table 2-1 provides a general guideline for evaluating an installation site.
Table 2-1: Considerations for Protecting Personnel
#
Guide
1
Indoor or outdoor: dress appropriately
2
If outdoor, what kind of environment, terrain, etc. Watch out for local insects and rodents (bees, spiders, snakes, etc.)
3
If indoor or outdoor: determine if there are any pieces of dangerous equipment or any processes which might be a risk to your safety
4
If in a tunnel, bunker, etc. watch out for a build-up of toxic or flammable gases. Make sure the air is good. Watch out for local insects and rodents (bees, spiders, snakes, etc.)
5
Hazardous or Non-Hazardous Environment: wear appropriate safety equipment and perform all necessary safety measures.
6
Before installing any equipment or power or ground wiring, make sure that there are no lethal (life-threatening) voltages between the site where the instrument is to be installed and other equipment (such as pipes or cabinets) or to earth itself.
7
Never assume that adjacent or peripheral equipment has been properly installed and grounded. Determine if this equipment and the RTU or flow computer can be touched simultaneously without hazard to personnel and/or equipment?
8
Be prepared. Before going to remote locations where there are few or no human inhabitants ask a few simple questions like, should I bring water, food, hygienic materials, first aid kit, etc?
9
Observe the work habits of those around you – for your own safety!
Some of the items that a service person should consider before ever going onsite can be determined by simply asking questions of the appropriate individual. Obviously other safety considerations can only be established at the installation site.

Considerations for Protecting Equipment

Always carefully evaluate the site installation/service environment and equipment. Understand the various physical interfaces you will be dealing with such as equipment mounting and supporting, RTU/flow computer analog and digital circuits, power circuits, communication circuits and various electrical grounds. Table 2-2 provides a general guideline for evaluating the equipment protection requirements of an installation site.
Site Considerations for Equipment Installation, Grounding, and Wiring Manual
D301452X012
October 2019
Installation 5
Table 2-2: Considerations for Protecting Equipment
#
Guide
Reference
1
Environment: Class I, Division 2 – Nonincendive Environment: Class I, Division 1 - Intrinsically Safe Other: Safe or unrated area
See appendices in hardware instruction manual.
2
Earth Ground - Established by mechanical/electrical or both or not at all
See Section 3
3
Is the area prone to lightning strikes?
See Section 4
4
Are there surge suppressors installed or to be installed?
See Section 4
5
Are there overhead or underground power or communication cables in the immediate area?
See Section 2.3
6
Is there an antenna in the immediate area?
See Section 4.1.2
7
How close is other equipment? Can someone safely touch this equipment and the RTU/flow computer simultaneously?
See Section 2.3
8
Determine equipment ground requirements. How will the RTU/flow computer and its related wiring be grounded? Consider earth ground, circuit ground, conduit ground, and site grounds.
See Section 3
9
Are there any obviously faulty or questionable power or ground circuits?
See Section 2.3

2.3 Other Site Safety Considerations

Identify overhead or underground power or communication cables prior to installing a new unit. Accidentally cutting, shorting or simply just contacting power, ground, communication or process control I/O wiring can have potentially devastating effects on site equipment, the process system, and or personnel.
Do not assume that it is safe to touch adjacent equipment, machinery, pipes, cabinets or even the earth itself. Adjacent equipment may not have been properly wired or grounded, may be defective, or may have one or more loose system grounds. Measure for voltage between the case of a questionable piece of equipment and its earth ground. If a voltage is present, something is wrong.
Site Considerations for Equipment Installation, Grounding, and Wiring Manual D301452X012 October 2019
6 Installation
AC-powered equipment with a conductive case should have the case grounded. If you do not see a chassis ground wire, do not assume that it is safe to touch this equipment. If you notice that equipment has been grounded to pipes, conduit, structural steel, etc., you should be cautious.
Note
The policy of the American Water Works Association (AWWA) on the grounding of electric circuits on water pipes states: The American Water Works Association (AWWA) opposes the grounding of electrical systems to pipe systems conveying water to the customer’s premises…”
Be sure that the voltage between any two points in the system is less than the stand-off voltage. Exceeding the stand-off voltage may damage the equipment and cause the equipment to fail.
Site Considerations for Equipment Installation, Grounding, and Wiring Manual
D301452X012
October 2019
Grounding and Isolation 7

Section 3: Grounding and Isolation

This section covers the following topics:
Power and Ground Systems
Importance of Good Grounds
Earth Ground Connections
Isolating Equipment from the Pipeline

3.1 Power and Ground Systems

Controllers and flow computers from Emerson Remote Automation Solutions support DC power systems. AC power supplies are not provided. Our devices typically include a ground lug that accommodates up to a #4 AWG size stranded copper wire for establishing a connection to Earth ground.

3.2 Importance of Good Grounds

Controllers and flow computers are used in control systems that must operate continually and within their stated accuracy over long periods of time with minimum attention. Failures resulting from an improperly grounded system can become costly in terms of lost time and disrupted processes. A properly grounded system helps prevent electrical shock hazards resulting from contact with live metal surfaces, provides additional protection of equipment from lightning strikes and power surges, minimizes the effects of electrical noise and power transients, and reduces signal errors caused by ground wiring loops. Conversely, an improperly grounded system may exhibit a host of problems that appear to have no relationship to grounding. It is essential that the service technician have a good understanding of this subject to prevent needless troubleshooting procedures.
WARNING
Devices must be installed in accordance with the National Electrical Code (NEC) ANSI/NEPA-70. Installation in hazardous locations must also comply with Article 500 of the code. For information on the usage of these devices in a hazardous location, see the appropriate sections of the device­applicable hardware manuals. For information on units in Class 1, Device 1, Groups C & D hazardous locations, refer to the instruction manual for the respective devices.

3.3 Earth Ground Connections

To properly ground the device, the unit’s chassis ground must ultimately be connected to a known
good earth ground. Refer to Establishing a Good Earth Ground and Ground Wire Considerations in this section.
Site Considerations for Equipment Installation, Grounding, and Wiring Manual D301452X012 October 2019
8 Grounding and Isolation

3.3.1 Establishing a Good Earth Ground

A common misconception of a ground is that it consists of nothing more than a metal pipe driven into the soil. While such a ground may function for some applications, it is not suitable for a complex system of sophisticated electronic equipment. Conditions such as soil type, composition, and moisture all have a bearing on ground reliability.
A basic ground consists of a 3/4-inch diameter rod with a minimum length of 8 feet driven into conductive earth to a depth of about 7-feet as shown in Figure 3-1. Use braided copper wire for the ground wire. The end of the wire should be clean, free of any coating, and fastened to the rod with a clamp. Cover or coat this ground connection to protect it from the weather and the environment.
Figure 3-1: Basic Ground Rod Installation
3.3.1.1 Soil Conditions
Before installing a ground rod, analyze the soil type and moisture content. Ideally, the soil should be moist and moderately packed throughout to the depth of the ground rod. However, some soils may exhibit less-than-ideal conditions and may require extra attention.
With respect to establishing and maintaining a good earth ground, soil types fall into either of two general categories: “good” soil and “poor” soil.
To be a good conductor, soil must contain some moisture and free ions (from salts in the soil). In rainy areas, the salts may be washed out of the soil. In sandy or arid areas the soil may be too dry and/or salt-free to a good conductor. If salt is lacking, add rock salt (NaCl); if the soil is dry, add calcium chloride (CaCl2).
Site Considerations for Equipment Installation, Grounding, and Wiring Manual
D301452X012
September 2019
Grounding and Isolation 9
3.3.1.2 Soil Types
Table 3-1 details good and poor soil types.
Table 3-1: Soil Types
Good
Poor
Damp Loam
Back Fill
Salty Soil or Sand
Dry Soil
Farm Land
Sand Washed by a Lot of Rain Dry Sand (Desert) Rocky Soil
Always test ground beds for conductivity prior to placing any equipment in service. This section provides a brief description of ground bed testing in both “good soil” and “poor soil. Details on this test are described in the National Electrical Code Handbook. Once you establish a reliable ground, test it routinely to preserve system integrity.
Figure 3-2 shows the test setup for “good soil” conditions.
Figure 3-2: Basic Ground Bed Soil Test Setup
If the ground resistance testing unit (GRTU, such as a Meggar® High-Performance Ground Resistance Tester or an Associated Research Vibroground) reads less than 5 ohms, consider the ground “good”: the lower the resistance, the better the earth ground. If the GRTU reads more than 10 ohms, the ground is “poor.” If a poor ground is indicated, drive one or more additional ground rods connected 10 feet from the main ground rod into the soil and interconnect them via bare AWG 0000 copper wire and 1” x ¼-20 cable clamps (as shown in Figure 3-3).
Loading...
+ 29 hidden pages